May 2021 CITY OF SURREY – ELECTRICAL SECTION Electrical Demand Load Calculation Single Family Dwelling & Detached Dwelling Unit This form will not be collected from site and must be submitted with a CAF at the time of a service connection request to e.inspections@surrey.ca. Current BC Electrical Code and BCSA Bulletin IB-EL 2014-01 Take Precedence Permit # : _____________ Address : ________________________________________________ Contractor : _______________________ FSR : _______________ FSR # : _____________ Date : _____________ Signature: _____________ ❖ 90m2 Basic load plus each of remainder or portion of x 1000w (House) 5000 + st 1 Range _______kw (up to 12 kw remainder @40%) (House) 6000+ Electric Heating (House) All Air Conditioning Loads (House) @ 100% Any Electric Vehicle Charging equipment (House) @ 100% Other loads (100% demand for tank-less water heaters, steamers, swimming pools, hot tubs and spas) House Feeder Conductor Type House Feeder Conductor Size House (minimum 24 000w or calculated) w w w w w (CU) (AL) (kcmil/AWG) w (House) ❖ Detached Dwelling Unit - Basic load plus each 90m2 of remainder or portion of x 1000w Range _______kw (up to 12 kw remainder @40%) Any Electric Heating Other loads (Suite) (Suite) Total Demand with Heating = st Amp (Electric Heating 1 10KW@100% remainder @75%) w w w (Suite) Suite Feeder Conductor Type Suite Feeder Conductor Size Detached Dwelling Unit (minimum 14 400w, Greater than 80 m2 24 000w or calculated) ❖ House (subtract heating load if used) = w Detached Dwelling Unit (subtract heating load if used) = w 5000 + 6000 + (CU) (AL) (kcmil/AWG) w (Suite) @ 100% @ 65 % Service Conductor Type (CU) Service Conductor Size w w (AL) (kcmil/AWG)