1 A Brief Overview of Polarized MHO Characteristics in Steady-State By Luis G. Pérez (Draft. For educational purposes only.) TABLE I. INPUTS TO A CROSS-POLARIZED MHO RELAY BASIC IMPLEMENTATION OF A POLARIZED MHO DISTANCE RELAY SCHEME A polarized MHO relay with circular characteristic in the impedance plane can be implemented using an angle comparator (see Figure 1) whose phasor inputs are [1]: πΜ1 = πΌΜ ⋅ πΜπ − πΜ πΜ2 = πΜπππΏ (1) (2) COMP TRIP Comparator operates when: πΜ1 −90β ≤ πππππ ( ) ≤ 90β πΜ2 Figure 1. Circular, cosine-type phase comparator Input S1 is called “operating quantity”. Input S2 is the polarizing -or reference- quantity. In a typical distance relay scheme with six elements, voltage V and current I are chosen according to Table 1 [1,2]. Voltage VPOL is a special characteristic of the relay and its choice depends on a series of factors [2,3]. There are different types of designs. The design shown in Table 1 is known as “crosspolarized”. Complex number Zr is the relay impedance setting (ohmic reach), which for the first, instantaneous zone of the relay, is commonly adjusted to under-reach the protected line’s remote end. The apparent impedance is defined, for each element of Table I, as: Μ π πΜ = πΌΜ = π + ππ Luis Pérez Last review: April 26, 2014 πΜ Μππ − πΜπ πΜπ − πΜπ πΜπ − πΜπ πΜπ b-g πΜπ c-g πΜπ πΌΜ ΜπΌπ − πΌΜπ πΌΜπ − πΌΜπ πΌΜπ − πΌΜπ πΌΜπ + πΜ0 ⋅ πΌΜπππ πΌΜπ + πΜ0 ⋅ πΌΜπππ πΌΜπ + πΜ0 ⋅ πΌΜπππ πΜπππΏ Μππ ⋅ πΜπ πΜπ ⋅ πΜπ πΜπ ⋅ πΜπ πΜππ ⋅ (πΜπ − πΜπ ) πΜππ ⋅ (πΜπ − πΜπ ) πΜππ ⋅ (πΜπ − πΜπ ) Note: π0 is a relay setting called residual compensation factor. Ires is the residual current: πΌΜπππ = πΌΜπ + πΌΜπ + πΌΜπ . Values ka, kb, etc., are design constants. S1 S2 Element a-b b-c c-a a-g (3) For a given fault, quantities V and I take a value in steady state. The resulting apparent impedance for each element, defined as in Eq. (3), can be plotted in the complex Z-plane. The understanding of this definition of apparent impedance and the corresponding resulting impedance plane is fundamental for the understanding of distance relay analysis. For the sake of stating this concept as clear as possible, the apparent impedance defined for each element is shown in Table II. TABLE II. APPARENT IMPEDANCE DEFINED FOR EACH ELEMENT OF TABLE I. Element a-b b-c c-a a-g b-g c-g Apparent Impedance πΜ (πΜπ − πΜπ )/(πΌΜπ − πΌΜπ ) (πΜπ − πΜπ )/(πΌΜπ − πΌΜπ ) (πΜπ − πΜπ )/(πΌΜπ − πΌΜπ ) πΜπ /(πΌΜπ + πΜ0 ⋅ πΌΜπππ ) πΜπ /(πΌΜπ + πΜ0 ⋅ πΌΜπππ ) πΜπ /(πΌΜπ + πΜ0 ⋅ πΌΜπππ ) 2 It is important to recall that, in order to supply a voltage for close-in three-phase faults, many relays have a type of polarization voltage called memory-polarizing voltage. For a close-in fault (case for which voltages depress to near zero value), this memory polarizing voltage expires several cycles after the fault occurrence. In some relays, the memory polarizing voltage is applied in addition to the steady state polarizing voltage. This document is not intended to analyze the transient characteristic of memory-polarized relays, but the characteristics of the relays in the complex plane for steady state conditions without considering the transient effect of the memory polarizing voltage. THE CHARACTERISTIC IN THE COMPLEX PLANE It can be shown that, for a given relay setting Zr and for a given ZP, Eq. (9) represents a circle in the Z-complex plane, whose center, ZC, and radius, r, are given by the following expressions: 1 πΜπΆ = 2 (πΜπ + πΜπ ) 1 π = |πΜπ − πΜπ | πΌΜ⋅πΜ −πΜ πππΏ ) = ±90β (11) 2 The circle is shown in Figure 2. Point C is the circle’s center. In terms of Z, the inequality stated in Figure 1 becomes πΜ −πΜ ) π−πΜπ −90β ≤ πππππ ( Μ π ≤ 90β (12) This last equation represents the inside region of the circle shown in Figure 2, including its border. X As defined in Figure 1, the operation threshold for any of the six elements shown in Table I can be expressed by the following equation: πππππ ( πΜ π (10) Q Zr (4) C The polarizing voltage, VPOL can always be written in terms of V using the following expression: (5) VPOL = V −V P P ZP R Where V and Vp depend on the particular case being analyzed. With this, Eq. (4) becomes: πΌΜ⋅πΜ −πΜ π πππππ ( πΜ−π ) = ±90β Μ π (6) Figure 2. Resulting circular characteristic of a MHO polarized relay. R and X are defined in Equation (3) Taking I as common factor: Observe that, for a self-polarized relay: πΜ −πΜ/πΌΜ πππππ (πΜ/πΌπΜ−πΜ /πΌΜ) π = ±90β (7) Define a new complex number, with impedance units (ohms), as: πΜ πΜπ = π (8) πΜπππΏ = πΜ ⇒ πΜπ = 0 ⇒ πΜπ = 0 In this case, the circle passes through the origin and the complex number πΜπ − πΜπ is a diameter of the circle. πΌΜ Considering Eq. (3) and this last definition, Eq. (7) becomes: πΜ −πΜ π πππππ (πΜ−π ) = ±90β Μ π Luis Pérez Last review: April 26, 2014 (9) FAULT ANALYSIS In order to examine the relay performance, the behavior of the six elements for different kinds of 3 faults can be analyzed in the complex plane shown in Figure 2. The impedance represented in that plane is the one defined in Equation (3) and Table II. In other words, the apparent impedance is different for each element for a given fault. Let us study the behavior of element b-c for the case of a b-c fault. For this element, the comparator’s inputs are: πΜ1 = πΌΜππ ⋅ πΜπ − πΜππ πΜ2 = πΜπ ⋅ πΜπ (13) (14) Thus, πΜπ = πΜππ − πΜπ ⋅ πΜπ (15) and Μ Μ Μ π π ⋅π πΜπ = πΌΜ ππ − πΌπΜ π ππ ππ (17) πΉ1 (21) Luis Pérez Last review: April 26, 2014 (22) For this design, Eq. (21) becomes Μ Μ Μ π½ ⋅π⋅ππΏ1 +2π1 πΜπ = π ⋅ πΜπΏ1 − π½Μ+2πΆ Μ (23) or Μ Μ π½ 2π1 πΜπ = (1 − π½Μ+2πΆΜ ) ⋅ π ⋅ πΜπΏ1 − π½Μ+2πΆ Μ 1 1 (24) πΜπ = −πΜπ1 πΜπ ⋅ π π π½Μ + 2πΆΜ1 (−π√3)(π½Μ + 2πΆΜ1 ) πΜπ ⋅ (π½Μ ⋅ π ⋅ πΜπΏ1 + 2πΜ1 ) −− (−π√3)(π½Μ + 2πΆΜ1 ) − πΜπ = −π√3 (20) Substituting Eqs. (17)-(19) in Eq. (16): π π In order to suppress the dependency with the fault resistance, the relay can be designed with: (19) This is the ratio of the pre-fault current to the positive sequence fault current. It is an indicator of how significant the pre-fault line current is with respect to the severity of the fault. πΜπ = π ⋅ πΜπΏ1 + DETERMINATION OF THE DESIGN CONSTANT: THE FAULT-DEPENDENT CHARACTERISTIC The dependence with the load and the fault location is evident in this equation. In the extreme case of not having pre-fault load current (β=0), with the notation of the Appendix: In these expressions: πΌΜ π½Μ = πΌΜππΉ This means that the radius and the center of the circle shown in Figure 2 both change according to those factors. 1 πΜππ = −π√3 ⋅ [π ⋅ ππΏ1 ⋅ (π½Μ + 2 ⋅ πΆΜ1 ) + π π ] ⋅ πΌΜπΉ1 (18) πΜπ = (π½Μ ⋅ π ⋅ πΜπΏ1 + 2 ⋅ πΜ1 + π π ) ⋅ πΌΜπΉ1 a) The pre-fault load (ο‘) b) The fault location (m) c) The fault resistance Rf (16) For this fault, the voltages and currents can be found using the sequence network connection shown in the Appendix. The results of interest are: πΌΜππ = −π√3 ⋅ (π½Μ + 2 ⋅ πΆΜ1 ) ⋅ πΌΜπΉ1 Notice from Eq. (21) that ZP depends on: (25) NUMERICAL EXAMPLE The statements demonstrated in the previous paragraphs can be illustrated with some fault examples on the simple system shown in Figure 3. Table III shows the five simulations performed on the system. Figure 4 represents the b-c polarized MHO element characteristic (ZP as in Equation (24)) for two different fault locations and a certain fixed pre-fault condition. Figure 5 shows the characteristic of the same element for a fixed fault location and for two different pre-fault conditions. Figure 6 compares the characteristic for a forward fault and the characteristic obtained 4 for a reverse fault. Notice that point Q is fixed for all conditions, regardless of the ZP value. Cases 1 and 2 12 10 TABLE III. FAULT CASES. (ANGLE ο€SR) IS THE ACTUAL LOADFLOW ANGLE BETWEEN THE VOLTAGES VS AND VR AT BUSES S AND R, RESPECTIVELY. 1 2 3 4 5 ο€SR (deg.) m (p. u.) Ipf (A) Re{S} (MW) 8 8 0 10 0 0.67 0.10 0.67 0.67 (-0.3) 755 755 0 942.5 0 138.4 138.4 0 166.1 0 X in primary ohms Case Q 8 6 4 2 0 -2 -4 -10 Note: ο€SR is the angle that the voltage at bus S leads the voltage at bus R. πΜπΆ π 1 4.413 +7.439j 1.717 +1.085j 4.613 +7.887j 4.356 +7.339j -2.79 -1.193j -1.66 -5.51j -1.25 -5.76j -0.8 -6.0j -1.85 -5.38j 0.58 +5.67j 0.131 +2.042j 0.333 +1.92j 0.56 +1.8j 0.036 +2.108j 1.252 +7.633j 7.766 7.842 7.918 10 S I Line 1 Forward Fault 2.078 2 0 -4 -10 -5 Positive sequence impedances of the 115 kV Line and Equivalent System Data: πΜπΏ1 (Line 1) = 0.8 + 4π Ω πΜπΏ1 (Line 2) = 2.4 + 12 Ω πΜπ»1 = πΜπ»2 = 2π πΊ πΜπ 1 = πΜπ 2 = 3π πΊ ππ = 1.0π. π’. ; ππ = 0.99 π. π’. Figure 3. Example system 5 10 Cases 3 and 5 12 R Line 2 0 R in primary ohms Figure 5. Cases 3 and 4(---) 10 Relay Luis Pérez Last review: April 26, 2014 4 -2 Q 8 X in primary ohms Reverse Fault 6 7.724 Notes: a) πΜ is the apparent impedance as defined in Eq. (3) and Table II, using RF =2 ohms. It is represented with the symbol “*” in Figures 4 to 6. The point represented with a “o” indicates the corresponding πΜ for a bolted fault at the same location. b) All values are in primary ohms. H Q 8 X in primary ohms πΜπ 5 10 Cases 3 and 4 πΜ 4 5 12 Case 3 0 R in primary ohms Figure 4. Cases 1 and 2 (----) TABLE IV. RESULTS 2 -5 6 4 2 0 -2 -4 -10 -5 0 R in primary ohms 5 10 Figure 6. Cases 3 and 5(---) The fact that the characteristic depends on the fault conditions implies that engineers cannot plot a fixed characteristic for all faults, as in the case 5 of a self-polarized relay. Thus, when presenting the results of a test on a relay polarized MHO element, the fault and load conditions for which the presented characteristic is valid must be clearly stated. There are methods to represent a fixed characteristic of polarized relays. This can be achieved re-defining the apparent impedance (and the corresponding Z-plane) such that the resulting circle is fixed for all faults conditions [4]. the pre-fault load conditions. This dependency is observable even for those cases where the relay has been designed to suppress the dependency with the fault resistance. Engineers must be careful when the characteristic of a polarized MHO element is presented. The fault and load conditions must be clearly specified in each case. REFERENCES THE OTHER ELEMENTS IN TABLE I AND SOME COMMENTS ABOUT DIFFERENT POLARIZING SCHEMES The same classic procedure used to analyze the bc element can be used to analyze and choose the design constants for the other five elements shown in Table I [1-5]. This is left as an exercise to the reader. The analysis technique can also be applied to any type of voltage-polarized relay. The goal is to find ZP for the particular polarization voltage being used. In general: Μ Μ Μ π π−π πΜπ = πΌΜπ = πΌΜπππΏ (26) VPOL can be any of the known polarizing voltages used by different manufacturers. For example, for a b-c element, VPOL can be a combination of positive sequence voltage Va [5] and a sample of this voltage a half a cycle before (dual positivesequence and memory polarization scheme). In this case ZP changes in time because part of the polarizing voltage changes (expires). However, the steady-state characteristic would remain as defined by the steady-state value of the positive sequence voltage. CONCLUSION For a plot in an apparent impedance plane, as traditionally defined, the size and position of the steady-state circular characteristic of a polarized MHO element depends on the fault location and Luis Pérez Last review: April 26, 2014 [1] A. R. Van C. Warrington, Protective Relays: Their Theory and Practice. Vols. One and Two. John Wiley & Sons, N. Y., 1969. [2] Wedepohl, L. M. “Polarised Mho Distance Relay,” Proceedings of IEE, Vol. 112, No 3, March 1965, pp. 525-535. [3] Cook, V. Analysis of Distance Protection, R.S.P. and J.W.& Sons, Inc. Great Britain, 1985. [4] Martilla, R. J., "Directional Characteristics of Distance Relay Elements,” (Parts I and II), IEEE Transactions on Power Apparatus and Systems, Vol. PAS-100, No. 1, 1981, pp. 96-113. [5] Roberts, J.; Guzman, A., Schweitzer, E. O. “Z=V/I does not Make a Distance Relay,” Proceedings of WPRC, 1993. SEL paper 6022.pdf. 6 APPENDIX ANALYSIS OF A B-C FAULT Current divider factor: πΜπ¦1 π₯1 +πΜπ¦1 πΆΜ1 = πΜ Forward Fault (A4) Thevenin voltage at the fault point (open circuit voltage at the fault point before the fault occurs): πΈΜππ» = πΆΜ1 ⋅ πΈΜπ + (1 − πΆΜ1 ) ⋅ πΈΜπ Relay (A5) Positive sequence fault current: a) One-line diagram Μ πΈ πΌΜπΉ1 = 2πΜ ππ» +π 1 ES ER Z S1 Z R1 m ο Z L1 (A6) Pre-fault current through the line: Z S1 V1 I1 π I2 (1 − m) ο Z L1 m ο Z L1 I F1 Μ Μ πΈ −πΈ πΌΜππΉ = πΜ π +πΜπ = πΜ Z R1 π₯1 V2 π¦1 πΈΜπ −πΈΜπ π1 +πΜπΏ1 +πΜπ 1 (A7) Positive and negative sequence currents measured by the relay: (1 − m) ο Z L1 Rf πΌΜ1 = πΌΜππΉ + πΆΜ1 ⋅ πΌΜπΉ1 (A8) πΌΜ2 = −πΆΜ1 ⋅ πΌΜπΉ1 (A9) b) Sequence diagram Figure A1. Sequence network connection Positive and negative measured by the relay: sequence voltages V1 = m ο Z L1 ο I1 + ( Z1 + R f ) ο I F 1 The usual notation [1] is employed. = m ο Z L1 ο ( I PF / I F 1 + C1 ) ο I F 1 + ( Z1 + R f ) ο I F 1 Sending-side total impedance: πΜπ₯1 = π ⋅ πΜπΏ1 + πΜπ1 (A1) πΜ2 = [−π ⋅ ππΏ1 ⋅ πΆΜ1 + πΜ1 ] ⋅ πΌΜπΉ1 Receiving-side total impedance: πΜπ¦1 = (1 − π) ⋅ πΜπΏ1 + πΜπ 1 πΜ1 = [π ⋅ ππΏ1 ⋅ (π½Μ + πΆΜ1 ) + (πΜ1 + π π )] ⋅ πΌΜπΉ1 (A10) (A2) Where πΌΜ π½Μ = πΌΜππΉ Parallel equivalent impedance for positive (and negative) sequence: Μ Μ ππ₯1 ⋅ππ¦1 πΜ1 = πΜ +πΜ π₯1 Luis Pérez Last review: April 26, 2014 π¦1 (A3) (A11) πΉ1 Phase currents: (A12) 7 πΌΜππ = πΌΜπ − πΌΜπ = −π√3 ⋅ (πΌΜ1 − πΌΜ2 ) πΌΜππ = −π√3 ⋅ (π½Μ + 2πΆΜ1 ) ⋅ πΌΜπΉ1 (A13) Phase voltages: πΜπ = πΜ1 + πΜ2 = (π½Μ ⋅ π ⋅ πΜπΏ1 + 2πΜ1 + π π ) ⋅ πΌΜπΉ1 (A14) πΜππ = πΜπ − πΜπ = −π√3 ⋅ (πΜ1 − πΜ2 ) πΜππ = −π√3 ⋅ [π ⋅ πΜπΏ1 ⋅ (π½Μ + 2πΆΜ1 ) + π π ] ⋅ πΌΜπΉ1 (A15) Luis Pérez Last review: April 26, 2014