STUDENT KIT LAB MODULE Program: EE242/CEEE242/CEEE223 Semester: 7 Ownership: Discipline of Power Date March 2022 Issued: Course Name: ELECTRICAL ENGINEERING LABORATORY V Version: 2.0 Course Code: EPO662 Mode of Delivery: ! Face to Face Virtual HIGH VOLTAGE AC GENERATION AND BREAKDOWN Authors Prepared by: Dr. Ngah Ramzi Hamzah Dr. Dalina Johari Faranadia Abdul Haris Dr. Dalina Johari 2nd Revision : Faranadia Abdul Haris 1st Revision : Date : Dec 2010 Date : Feb 2019 Date : Mac 2022 ASSESSMENT DETAILS Field/Module: High Voltage / HV1 Experiment Title: HIGH VOLTAGE AC GENERATION AND BREAKDOWN At the end of the course, students should be able to: CLO1: Work in a team effectively to perform laboratory works (A3). CLO2: Display proficiency using laboratory tools in Course Learning conducting experiment (P4). Outcomes: CLO3: Determine a suitable technique in order to solve the Complex engineering problem (C4). CLO4: Present the findings observed from the experiment/case Study clearly and effectively through a lab/PBL report (A3). Upon completion of this experiment, students should have the: MO1: Ability to construct and setup high voltage AC test circuit with safety measures. Module Outcomes: MO2: Ability to apply the knowledge on AC breakdown knowledge studied in previous semester. MO3: Ability to perform analysis on the AC breakdown phenomenon. Instructions: 1. Perform the tasks as given/instructed in the lab module. 2. Submit the report in a group. 1. No food or drink is allowed in lab unless food or drinks are provided as a part of the lab. 2. Shoes must be worn in lab. Safety 3. Please ensure all the diagram connection is checked or Instructions: approved by instructor/assistance engineer before running the experiment. 4. Always bring test pen during laboratory session. 2 1. THEORETICAL BACKGROUND 1.1 Introduction In High Voltage Engineering applications, the dielectrics also known as electrical insulator can be categorized either gas/vacuum, liquid and solid insulations. High pressure gas also provides a flexible and reliable medium for high voltage insulation. The high-pressure gas suitable for insulation are Sulphur hexafluoride (SF6), Nitrogen (N2), Carbon dioxide (CO2) and Freon (CCl2F2). Vacuum is the best insulator with the dielectric strength up to 1012 V/cm limited by emission from the electrode surfaces. Under high vacuum conditions, the breakdown cannot occur due to collisional processes as in gases, and hence the breakdown strength is quite high. Vacuum insulation is used in particle accelerators, x-ray and field emission tubes, electron microscopes, capacitors, and circuit breakers. 5. PRE-LAB WORK 2.1. Explain the function of switchgears in electrical system. 2.2. Why it is important to quench the arc that occurs in the switchgears? 2.3. List and briefly explain the medium used to quench the arc in switchgears. 2.4. State the type of switchgear that uses vacuum as medium to quench the arc and explain the operation of this switchgear. 6. EXPERIMENTAL WORK 3.1 Preparing the Test Vessel DG100 Procedures 1. Turn the cap B1 to counter clockwise until the cap B1 is detached from the portion B. Refer Figure 1.1 2. Turn the locking screw A counter clockwise until the portion B is able to be lifted away from the test vessel assembly 3. Properly place the portion B on a flat surface that will not cause scratch to the electrode C1 or bending of the rod D as shown in Figure 1.2. 4. Wipe the interior wall of the test cell E and the electrode C2 using the designated jig ; to ensure no moisture and oil droplets inside the test cell E. Refer Figure 1.3 and Figure 1.4. 3 5. Wipe the portion B and the electronic rod C1 and D need to be clean and preventing it from moisture and oil as shown in Figure 1.5 and Figure 1.6 using the designated jig. 6. Carefully re-assemble all the detached parts of the test vessel DG100 as shown in Figure 1.7. 7. Adjust the portion F to ensure the electrode C1 is aligned with the electrode C2 as shown in Figure 1.8. 8. Measure the gap between the electrodes C1 and C2 as shown in Figure 1.8. The default setting is 1.0 cm, and the gap adjustment can ONLY be carried out by the Lab Instructor. 9. Wipe the exterior part of the Test Vessel as shown in Figure 1.10 10. By using three fingers, turn the valve G in clockwise direction. Do not close the valve G too tightly. 4 5 6 3.2 Using the Vacuum Pump (BO78R04) Procedures 1. The connection between Test Vessel and Vacuum Pump is shown in Figure 2.1. 2. Based on Figure 2.2, turn the valve G three rounds in counter clockwise direction to flush out air inside the Vacuum Pump. 3. Wait for 10 seconds and turn the valve G at the Test Valve clockwise until fingers tight. 4. Turn the lever I on the side of the vacuum pump to ON position (Figure 2.3) and lever I on top of the vacuum pump to ON position (Figure 2.4). 5. Wait for 3 second to “flush out” air in the vacuum pump. 6. Turn the lever I and the lever H in sequence to OFF position. 7. Connect the Portable Vacuum Pump BO78R04 to the Test Vessel DG100 via the hose J. Ensure a tight fitting at the hose ends. 8. Plug the electrical socket K to wall outlet. 9. Switch ON the power supply at the vacuum pump by pressing the toggle switch L. 10. Turn the lever I to OPEN position 11. From OFF position turn the lever H for 10 degrees only. At this moment, the pointer on the meter M will turn the counter clockwise. 12. By using three fingers, turn the valve G in counter clockwise direction. The pointer on the meter M will drop and stay at stable position for quite some time. 13. Adjust the lever H slowly so that the pointer on the vacuum meter M starts to increase slowly. 14. When the pointer reaches -0.1 bar (which is 50% of the desired pressure), turn the valve G 1 time in clockwise direction. 15. When the pointer reaches -0.15 bar (the desired pressure), turn the valve G1 time in clockwise direction. 16. When the pointer reaches -0.2 bar (the desired pressure), turn the valve G1 time in clockwise direction; to seal the valve G. 17. Turn OFF the Valve G at the Test Vessel in clockwise little by little as shown in Figure 2.6 and be alert to close it when the Pressure Meter shows the desired value. 18. Turn off the vacuum pump by pressing toggle switch L as shown in Figure 2.7. 19. Turn the lever I to OFF position. 20. Turn the lever I to OFF position. 21. Disconnect the hose J from the Test Vessel as shown in Figure 2.8. 22. Turn the lever H and lever I to ON position. 7 23. Unplug the electrical socket K out from the wall socket outlet as shown in Figure 2.9. 24. Keep back the Vacuum Pump in the right way as shown in Figure 2.10. 8 9 3.3. Discharging Using Discharge Rod Procedures 1. The discharge rod for AC system is shown in Figure 3. 2. The operator shall hold the rod at the end without the hook. 3. The operator shall apply a safety Personal Protective Equipment (PPE) as shown in Figure 3.1 and Figure 3.2. 4. The operator shall handle the discharging rod at the handle end. 5. Touch the hooked end to all live parts (surface by surface) of the test circuit for discharging process as shown in Figure 3.3. 10 6. After touching all the live parts, place the hook to attach to the component nearest to the test transformer T100 as shown in Figure 3.4. 7. Before conducting an experiment, make sure the hooked is removed from the hanging place and put it on the rubber mat. 11 3.4. Experiment High Alternating Voltage Generation Procedures 1. Setup the circuit as shown in Figure 4.1 The box indicated with A letter consists of measuring circuit and the construction of the circuit is shown in Figure 4.2 2. Place the MCP 100 at the correct position as shown in Figure 4.3. 3. Remove the shorting wire for this experiment as shown in Figure 4.4. When not in use, the MCP100 is shorted for maintaining its accuracy. 4. Use a metal rod as connector between MCP 100 and the capacitor as shown in Figure 4.4. 5. Ensure that the equipment and all metal parts in contact or slightly above the floor are properly earthed in Figure 4.4. 6. After setting up the circuits of Figure 4 and 5, consult the instructor and check the circuits for correct wiring of the testing circuit and earth circuit as shown in Figure 4.5. For safety precaution, ensure that the discharge rod is connected to the earth circuit. 7. Remove the discharge rod upon completing procedure 6 as shown in Figure 4.6. 8. All personnel should leave the testing area. 9. Close the fence gate properly as shown in Figure 4.8. 10. Switch on the system by turning on the key 1 once to the right (position 1) and return to vertical (position 0) as shown in Figure 5.3. Turn on the computer by pressing power switch 2 (see Figure 6). 11. Select “EPO660” User Account WGMSWIN. 12 13 14 15 12. Once the Microsoft Windows is displayed on the monitor 3 , press on the Mode PC button 4 and Display Test button 5 on the SIMATIC PANEL. 13. Switch on the ICM compact unit 6 . Observe and record the partial discharge reading (in pC) on the ICM compact unit 6 14. The toggle asked for save previous work, immediately click for “NO”. If click “SAVE”, it will corrupt the system. 15. Look for the WGMSWIN icon on the desktop and double click it. The monitor screen will display the main panel as shown in Figure 7. 16. Click on the “File” menu and then click on “Open” sub-menu. A dialog box as shown in Figure 8 will be displayed. You will be asked if you want to “Save changes to WgmsMan?”. Select “No” to prevent the system from collapsing. 17. A directory will then appear Then go to “Local C Harddisk > Program Files HIGHVOLT > Wgmswin > Templates > 02007 > V2.6 > Gradually Successive” as shown in Figure 9. 18. Double click on the “Gradually Successive” file and then at the bottom of the simulation have toggle button then press test result as shown in Figure 10 will be displayed. 19. Fill the Name of Operator, Date, Test Object, Number of experiment for reference and also Remarks to labeled as a name of experiment. 20. Before running the experiment, setting the simulation and set the parameter is mandatory refer table 1 for the value. 21. Click Test Setting tab at the bottom of the page and the page will come up as the Figure 11 22. Click the “Settings” button on the left-hand side of the panel. A sub-panel as shown in Figure 5.4 will be displayed. 23. Click on the “Limits” tab and the sub-panel will display as shown in Figure 5.5. Set the “voltage limit”, i.e. the maximum voltage to be tested. The current limit and current comparator limit are to be left as displayed 24. Click on the “WBG Settings” tab and the sub-panel will display as shown in Figure 5.6. Set the parameters as instructed in Table 1. 25. Click on the “Climate Conditions” tab. Select the “AC” option as shown in Figure 5.7. Keep the other data and parameters as displayed 26. Click on the “OK” button. The sub-panel will disappear, leaving only the main panel being displayed. Observe that the parameters on the top side of the panel are automatically set. Check that the “Switch on Ready” is displayed. 16 27. Click on the “Ready ON” button (bottom left-hand side of the main panel). “Ready ON” button and “Operate ON” button will illuminate. The warning beacons on the fence will be flashing with red light as shown in Figure 5.8. 28. Click on the “Operate ON” button (bottom left-hand side of the main panel). “Operate ON” button will illuminate 29. Observe and record the reading displayed on the ICM Compact unit 6 (Figure 6). 30. Give warning by sounding the horn (XXX) or call-out, “Attention! Switch on!”. Ensure that there are no personnel in the testing area (within the fence). 31. Click on the “START” button (bottom right-hand side of the main panel. 32. The main panel will display the progress of test voltage. Observe that the Actual Voltage may be slightly different from the Setting Voltage (on the top side of the panel). Record both values. 33. Observe and record the reading displayed on the ICM compact unit 6 from time to time. 34. This step No. 35 and 36 may be repeated for several values of test voltage. At each value of test voltage, record the Actual Voltage and Setting Voltage. Also, record the reading displayed on the ICM compact unit 6. 35. After the test has been completed, click on the “Operate OFF” button and then the “Ready OFF” button. 36. Open the gate of the fence as shown in Figure 5.9. 37. Contact the discharge rod to the circuit. Faithfully observe the method of discharging as taught by the instructor. Leave the discharge rod in contact with the testing circuit as shown in Figure 5.10. 38. After completing the experiment, remove the MCP100 from the circuit and re-attached the shorting wire for safe keeping. 17 18 19 Figure 5.6 20 21 3.5. Experiment One Minute Power Frequency Test Procedures 1. Setup the circuit as shown in Figure 12. The Test Vessel is to be placed as the Test Object. The setup must be made within the testing (fenced) area. 2. Ensure that the discharge rod is connected to the earth circuit. 3. The measuring circuit is shown as crossed box in Figure 12. For details of the circuit, refer to Figure 13. 4. Ensure that the equipment and all metal parts in contact and properly earthed. 5. After setting up the circuits of Figure 12 and 13, consult the instructor and together check the circuits for correct wiring of the testing circuit and earth circuit. 6. Once the correct wiring is confirmed, remove the discharge rod. 7. Leave the testing area and head for the Control Measuring and Automatization System (see Figure 14). 8. Ensure that there are no personnel in the testing area (within the fence). 9. Ensure that there is no discharge rod in contact (electrically or mechanically) with the test circuit. 10. Close the fence gate properly. 11. Switch on the system by turning on the key 1 once to the right (position 1) and return to vertical (position 0). Turn on the computer by pressing power switch 2 . (See Figure 14). 12. Once the Microsoft Windows is displayed on the monitor 3 ,press on the Mode PC button 4 and Display Test button 5 on the SIMATIC PANEL. 13. Look for the WGMSWIN icon on the desktop and double click it. The monitor screen will display the main panel as shown in Figure 15. 14. Click on the “File” menu and then click on “Open” sub-menu. A dialog box as shown in Figure 14 will be displayed. You will be asked if you want to “Save changes to WgmsMan?”. Select “No”. 15. Then go to “Local C Hard disk > Program Files > HIGHVOLT >Wgmswin > Templates > 02007 > V2.6 > Gradually Successive.xlsm”. 16. Double click on the “Gradually Successive.xlsm” file and the panel will be displayed as shown in Figure 16. 17. Move the cursor onto the cell with dark borders (below the Disruptive voltage at gradually successive voltage) and click the mouse’s left button. A sub-panel will appear as shown in Figure 17. 22 23 24 25 18. In this experiment, set the parameters according to the data in Table 3. After all the parameters have been confirmed, click on the “OK” button. Table 3: Parameters to be set. Voltage Limit voltage [kV]: Final voltage [kV]: Start voltage [kV]: Step voltage [kV]: Rate of voltage rise [kV/s]: Stress 40 30 5 1 3 Tolerance of step voltage [%]: No. of cycles: Duration of step: Break duration: 2 <5 00:01:00 00:00:05 19. Click on the “Test Results” tab of the Page menu (at the bottom of the panel). The panel will appear as shown in Figure18. 20. Enter the operator’s name, date of experiment conducted, name of test object, test number and remarks (if any) on the “Test Results” page. 21. Click on the “Ready ON” button (bottom left-hand side of the main panel). “Ready ON” button and “Operate OFF” button will illuminate. The warning beacons on the fence will be turning with red light. Check that the Indicator Bar displays “Switch on Operate”. 22. Click on the “Operate ON” button (bottom left-hand side of the main panel). “Operate ON” button will illuminate. Check that the Indicator Bar displays “Ready”. 26 23. Give warning by call-out, “Attention! Switch on!” Ensure that there is no personnel in the testing area (within the fence). 24. Click on the “START” button (bottom right-hand side of the main panel). 25. The operator should give warning by call-out/countdown the Actual Test Time once the main panel displayed the progress of test voltage. 26. Observe and record the Actual Voltage on the SIMATIC PANEL. 27. Observe and record the Partial Discharge on the ICM Compact unit. 28. Once the breakdown voltage is reached, the profile of the voltage will drop to zero. The main panel will display Actual Time Test (on the top side of the panel) as “00:00:XX”. 29. Click on the “Operate OFF” button and then the “Ready OFF” button. 30. Repeat step 24 through 32 to complete the no. of cycles set in Table 3. 31. Click “File” on the menu bar and then click “Save As”. Then go to “Desktop” icon, click on the “EPO660_TEST_RESULTS” folder. Name the fiIe as “Gradually Successive.xlsm where XX is the operator’s group number and YY is the test number. 32. Click “File” on the menu bar and then click “Close”. You will be asked if you want to “Save changes to “Gradually Successive?”. Select “No”. 33. Open the gate of the fence. 34. Perform discharging with the discharge rod and leave the discharge rod in contact with the component nearest to the test transformer T100. 35. Setup the Test Vessel for a vacuum pressure of -0.4 bar. 36. Repeat steps 14 through 37 until the vacuum pressure of the test vessel reach -1.0 bar. 37. Copy all results in a folder and download to a pen drive. 7. RESULTS Student should include the findings such as completed the tables and presented the graphs of Experiment 3.4 and 3.5 Experiment 3.4 1. Observe and record the Actual Voltage on the SIMATIC PANEL. 2. Observe and record the Partial Discharge on the ICM Compact unit. 27 Setting Voltage (kV) 10 11 12 13 14 15 16 17 18 19 20 Table 1.1 Actual Voltage (kV) Partial Discharge (Coulomb) Experiment 3.5 1. Observe and record the Actual Voltage on the SIMATIC PANEL. 2. Observe and record the Partial Discharge on the ICM Compact unit. 3. Observe and record item No.1 and 2 at different vacuum pressure (-0.2 bar, -0.4 bar, -0.6 bar, -0.8 bar and -1.0 bar) Setting Voltage (kV) 5 6 7 8 9 10 11 12 13 14 15 Table 1.2: (Pressure: -0.2 bar) Actual Voltage (kV) Partial Discharge (Coulomb) 4. Plot the graph of breakdown voltage versus vacuum pressure. 28 8. DISCUSSIONS 5.1 Based on Experiment 1, the maximum setting voltage has been set to 20kV with a test object of MCP100 (Standard Capacitor). Why is the breakdown occurred at a setting voltage of 20kV? 5.2 What types of ‘Law’ for breakdown in gases that involved in Experiment 2? 5.3 Explain the working principle of law stated in answer (4.2) with a necessary diagram and equation. 5.4 Explain two methods that can been used in this experiment to generate High AC Voltage. 5.5 Based on the experiment, the breakdown occurs in non-uniform electric field. Hence, explain the form of the discharge occurs between the two electrodes with a necessary diagram. 5.6 Explain the process of Electron Avalanche in gaseous insulator with a necessary diagram. 9. QUIZ 6.1. High voltage engineering is a requirement for electrical engineering students as it has many practical applications. Give three (3) modes of high voltage applications. (3 marks) 6.2. Differentiate between an insulator and a conductor by showing their energy band diagram. (4 marks) 6.3. Define the terms of dielectric strength and electric field stress. (3 marks) 29 10. CONCLUSION Conclude in detail the findings and the outcomes of this experiment. This should include the summary of knowledge gained, comments and discussion of the results, errors and their possible sources and how this experiment can be improved. 11. REFERENCES • • • Naidu M.S. and Kamaraju V., High Voltage Engineering 2nd ed, Tata McGraw-Hill Publ. Co., Ltd., New Delhi, 1996. J. R. Lucas, High Voltage Engineering, 2001 E. Kuffel, W.S. Zaengl and J. Kuffel, High Voltage Engineering: Fundamentals, 2nd, Newness, 2000, ISBN: 8181477367 END 30