AWS C2.20/C2.20M:2016 An American National Standard for Specification Thermal Spraying Zinc Anodes on Steel Reinforced Concrete Nations, Or n AWS St AWS C2.20/C2.20M:2016 An American National Standard Approved by the American National Standards Institute May 19, 2016 for Specification Thermal Spraying Zinc Anodes on Steel Reinforced Concrete 2nd Edition Supersedes AWS C2.20/C2.20M:2002 Prepared by the American Welding Society (AWS) C2 Committee on Thermal Spraying Under the Direction of the AWS Technical Activities Committee Approved by the AWS Board of Directors Abstract This AWS standard is a specification for thermal spraying zinc anodes on steel reinforced concrete. This standard is formatted as an industrial process instruction. The scope includes: job description, safety, pass/fail job reference standards, feedstock materials, equipment, a step-by-step process instruction for surface preparation, thermal spraying, and quality control. There are five annexes, including job control record and portable adhesion testing. AWS American Welding Society® AWS C2.20/C2.20M:2016 ISBN: 978-0-87 17 1-888-4 © 2016 by American Welding Society All rights reserved Printed in the United States of America Photocopy Rights. No portion of this standard may be reproduced, stored in a retrieval system, or transmitted in any form, including mechanical, photocopying, recording, or otherwise, without the prior written permission of the copyright owner. Authorization to photocopy items for internal, personal, or educational classroom use only or the internal, personal, or educational classroom use only of specific clients is granted by the American Welding Society provided that the appropriate fee is paid to the Copyright Clearance Center, 222 Rosewood Drive, Danvers, MA 01923, tel: (978) 750-8400; Internet: <www.copyright.com>. ii AWS C2.20/C2.20M:2016 Statement on the Use of American Welding Society Standards All standards (codes, specifications, recommended practices, methods, classifications, and guides) of the American Welding Society (AWS) are voluntary consensus standards that have been developed in accordance with the rules of the American National Standards Institute (ANSI). When AWS American National Standards are either incorporated in, or made part of, documents that are included in federal or state laws and regulations, or the regulations of other governmental bodies, their provisions carry the full legal authority of the statute. In such cases, any changes in those AWS standards must be approved by the governmental body having statutory jurisdiction before they can become a part of those laws and regulations. In all cases, these standards carry the full legal authority of the contract or other document that invokes the AWS standards. Where this contractual relationship exists, changes in or deviations from requirements of an AWS standard must be by agreement between the contracting parties. AWS American National Standards are developed through a consensus standards development process that brings together volunteers representing varied viewpoints and interests to achieve consensus. While AWS administers the process and establishes rules to promote fairness in the development of consensus, it docs not independently test, evaluate, or verify the accuracy of any information or the soundness of any judgments contained in its standards. AWS disclaims liability for any injury to persons or to property, or other damages of any nature whatsoever, whether special, indirect, consequential, or compensatory, directly or indirectly resulting from the publication, use of, or reliance on this standard. AWS also makes no guarantee or warranty as to the accuracy or completeness of any information published herein. In issuing and making this standard available, AWS is neither undertaking to render professional or other services for or on behalf of any person or entity, nor is AWS undertaking to perform any duty owed by any person or entity to someone else. Anyone using these documents should rely on his or her own independent judgment or, as appropriate, seek the advice of a competent professional in determining the exercise of reasonable care in any given circumstances. It is assumed that the use of this standard and its provisions is entrusted to appropriately qualified and competent personnel. This standard may be superseded by new editions. This standard may also be corrected through publication of amendments or errata, or supplemented by publication of addenda. Information on the latest editions of AWS standards including amendments, errata, and addenda is posted on the AWS web page (www.aws.org). Users should ensure that they have the latest edition, amendments, errata, and addenda. Publication of this standard does not authorize infringement of any patent or trade name. Users of this standard accept any and all liabilities for infringement of any patent or trade name items. AWS disclaims liability for the infringement of any patent or product trade name resulting from the use of this standard. AWS does not monitor, police, or enforce compliance with this standard, nor does it have the power to do so. Official interpretations of any of the technical requirements of this standard may only be obtained by sending a request, in writing, to the appropriate technical committee. Such requests should be addressed to the American Welding Society, Attention: Managing Director, Technical Services Division, 8669 NW 36 St, # 130, Miami, FL 33166 (see Annex C). With regard to technical inquiries made concerning AWS standards, oral opinions on AWS standards may be rendered. These opinions are offered solely as a convenience to users of this standard, and they do not constitute professional advice. Such opinions represent only the personal opinions of the particular individuals giving them. These individuals do not speak on behalf of AWS, nor do these oral opinions constitute official or unofficial opinions or interpretations of AWS. In addition, oral opinions are informal and should not be used as a substitute for an official interpretation. by the AWS C2 Committee on Thermal Spraying. It must be reviewed every five years, and if not revised, it must be either reaffirmed or withdrawn. Comments (recommendations, additions, or deletions) and any pertinent data that may be of use in improving this standard are requested and should be addressed to AWS Headquarters. Such comments will receive careful consideration by the AWS C2 Committee on Thermal Spraying and the author of the comments will be informed of the Committee's response to the comments. Guests are invited to attend all meetings of the AWS C2 Committee on Thermal Spraying to express their comments verbally. Procedures for appeal of an adverse decision concerning all such comments are provided in the Rules of Operation of the Technical Activities Committee. A copy of these Rules can be obtained from the American Welding Society, 8669 NW 36 St, # 130, Miami, FL 33166. This standard is subject to revision at any time iii AWS C2.20/C2.20M:2016 This page is intentionally blank. iv AWS C2.20/C2.20M:2016 Personnel AWS C2 Committee on Thermal Spraying K. L. Sender, Chair W. J. Arata, Vice Chair J. M. Rosario, Secretary D. M. Beneteau C. C. Berndt M. M. Blasingame T. J. Connelly A. Duminie M. Froning D. T. Haegele D. C. Hayden J. O. Hayden N. M. Karinchak I. R. Lasa D. A. Lee W. M. Medford D. R. Moody B. Mosier J. Ryan Oerlikon Metco (US), Incorporated Carpenter Powder Products American Welding Society CenterLine (Windsor) Ltd. Swinburne University of Technology Superior Shot Peening, Incorporated Green Belting Industries, Ltd. HC Starck North American Trading, LLC The Boeing Company Select Arc Hayden Corporation Hayden Corporation Platt Brothers Florida Department of Transportation Kennametal, Incorporated INSPEC, Incorporated Plasma Powders and Systems K. Sampath Polymet Corporation Carpenter Powder Products Chart Industries C. Sauer A. P. Yanski NAVAIR Praxair TAFA Advisors to the AWS C2 Committee on Thermal Spraying R. Ahmed Patronas Carigali Sdn Bhd. B. T. Costello NAVSEA M. R. Dorfman Oerlikon Metco (US), Incorporated L. F. Grimenstein Nation Coating Systems, Incorporated A. J. Grubowski DDL OMNI D. Guillen J. A. Kapur A. Roy S. Szapra C. Tudor T. H. Via M. Weinstein Idaho National Laboratory Bay State Surface Technologies Quality Calibration and Consulting Naval Surface Warfare Center International MetalFusion Corporation Via Technologies Wall Colmonoy Corporation AWS C2C Subcommittee on Thermal Sprayed Coatings for Reinforced Concrete I. R. Lasa, Chair J. M. Rosario, Secretary M. L. Berndt J. M. Brodar J. Costa Florida Department of Transportation American Welding Society Aurecon Australia Salt River Project Structural Technologies AWS C2.20/C2.20M:2016 AWS C2C Subcommittee on Thermal Sprayed Coatings for Reinforced Concrete (Continued) N. M. Karinchak D. A. Lee D. G. Tepke Platt Brothers Kennametal, Incorporated SKA Consulting Engineers, Incorporated Advisors to the AWS C2C Subcommittee on Thermal Sprayed Coatings for Reinforced Concrete J. O. Hayden FS. Rogers Hayden Corporation Thermion, Incorporated A. Praxair TAFA P. Yanski vi AWS C2.20/C2.20M:2016 Foreword This foreword is not part of this standard but is included for informational purposes only. Cathodic protection (CP) is a proven technique for corrosion protection of chloride contaminated concrete structures. Zinc thermal sprayed coatings are used as distributed anodes in both sacrificial cathodic protection (SCP) and impressed current cathodic protection (ICCP) systems. The California Department of Transportation pioneered zinc thermal sprayed coatings as anodes for ICCP systems on reinforced concrete structures on the Richmond-San Rafael Bridge in 1983,"-) and the Florida Department of Transportation (FDOT) pioneered its use as a SCP system in 1989.°-4) In 2012 it was estimated that the FDOT alone has used thermal sprayed zinc in over 30 bridges with a combined total of 700,000 square feet of metallized concrete. The Oregon Department of Transportation was the first to install the zinc thermal sprayed coatings as ICCP system anodes in the repairs of steel reinforced concrete on a bridge substructure in 1991. The use of thermal sprayed zinc anodes is recognized at this time as a standard practice for corrosion control on reinforced concrete members. This AWS process standard covers the application of zinc thermal spray coatings to concrete, with a connection to the reinforcement, using arc and flame spray equipment. This standard is formatted as an industrial process instruction (see flow chart) and the scope includes: job description, safety, pass/fail job reference standards, feedstock materials, equipment, and a step-by-step process instruction for surface preparation, thermal spraying, and quality control. Specifications and Requirements Job Reference Standard Equipment Setup and Operation Surface Preparation ~ - 2ZnTSC Application Inspection and Accept Acceptance Tests Fail There are five annexes, including safety information for thermal spraying and job control record. Further information on guidelines for CP of reinforced concrete is available in NACE Standard RP0290. A vertical line in the margin or underlined text in clauses, tables, or figures indicates an editorial or technical change from the 2002 edition. Comments and suggestions for the improvement of this standard are welcomed. They should be sent to the Secretary, AWS C2 Committee on Thermal Spraying, American Welding Society, 8669 NW 36 St, # 130, Miami, FL 33166. 'Carello, R. A., D. M. Parks, and J. A. Apostolos, 1989, Development, Testing and Field Application of Metallized Cathodic Protection Coatings on Reinforced Concrete Substructures, FHWA/CA/TL-89/04, Sacramento, CA: State of California Department of Transportation. 2 Apostolos, J. A., D. M. Parks, and R. A. Carello, Cathodic protection of reinforced concrete using metallized zinc, Materials Performance, V. 26, No. 12, pp. 22-28, December 1987. Available from NACE International, 1440 S. Creek Drive, Houston, TX 770844906. 3Sagues, A. A. and R. G. Powers, 1994, Sprayed Zinc Galvanic Anode for Corrosion Protection of Marine Substructure Reinforced Concrete, SHRP-S-405, Washington, DC: Strategic Highway Research Program. 4 Apostolos, J. A., D. M. Parks, and R. A. Carello, Cathodic protection of reinforced concrete using metallized zinc, Materials Performance, V. 26, No. 12, pp. 22-28, December 1987. Available from NACE International, 1440 S. Creek Drive, Houston, TX 770844906. vii AWS C2.20/C2.20M:2016 This page is intentionally blank. Vili AWS C2.20/C2.20M:2016 Table of Contents Page No. Personnel Vii Xi xi Foreword List of Tables List of Figures 1. General Requirements 1.1 1.2 Scope Units of Measure 1.3 Safety 1 1 2. Normative References 2 3. Terms and Definitions 3 4, Job and Contract Specification 4.1 Requirements 4.2 Job Reference Standard 4.3 Thermal Spray Boundary 4.4 Job Control Record 4.5 Thermal Spray Coating Inspector 4.6 Thermal Spray Operator Qualification 4.7 Pre-Contract Award Validation 3 5. 3 6 6 6 6 6 6 Materials 5.1 Zinc Thermal Spray Wire 7 Tensile Bond Strength Test Specimens 5.3. Bend Test Requirements 5.4 Gases 5.5 Abrasive Blasting Media and Air 7 7 5.2 7 7 7 6. Equipment for Thermal Spraying 6.1 Thermal Spray Equipment 6.2 Air Compressors 7. 8 8 8 Inspection and Quality Control Equipment 8 Surface Preparation Zinc Thermal Spray coating on Concrete 8 7.1 7.2 9 8. Application-Process Methods 8.1 Surface Preparation 8.2 Thermal Spraying 10 9. Repair of Zinc Thermal Spray Coating on Reinforced Concrete 13 10 11 10. Records 13 11. Debris Containment and Control 13 12. Utility Services 14 ix AWS C2.20/C2.20M:2016 Page No. Annex Annex Annex Annex Annex A (Normative)-Sample Job Control Record for Applying Zinc Thermal Spray Coating on Concrete B (Informative)-Safety Information for Thermal Spraying C (Informative)-Requesting an Official Interpretation on an AWS Standard D (Informative)-List of Informative References E (Informative)-Conversion Factors Used in this Publication List of AWS Documents on Thermal Spraying 15 19 27 29 31 33 x AWS C2.20/C2.20M:2016 List of Tables Table 1 2 3 4 B.1 B.2 B.3. Page No. Inspection and Acceptance Tests Thermal Spray Coating Inspection and Acceptance Tests-Laboratory Bend-Test Cracking Threshold: Mandrel Diameter vs. TSC Thickness Flame and Arc Spray Standoff Distances and Spray-Pass Widths (Nominal) 5 5 7 12 19 Graphic Symbols Noise Levels Produced by Spray Guns Recommended Shade Numbers for Helmets and Goggles 25 25 List of Figures Page No. Figure 1 2 TSC Bend Test Pass and Fail Samples Process Flow Chart for Repairing Zinc Thermal Spray Coatings xi 8 (TSC) on Reinforced Concrete 13 AWS C2.20/C2.20M:2016 This page is intentionally blank. xii AWS C2.20/C2.20M:2016 for Thermal Specification Spraying Zinc Anodes on Steel Reinforced Concrete 1. General Requirements This standard covers the application of zinc thermal spray coatings to steel reinforced concrete using arc and flame spray equipment. The application of the zinc on steel reinforced concrete requires an electrical connection to the steel reinforcement. Although other metals can also be applied with these methods and equipment, at this time the standard only covers zinc and zinc alloys. This standard is formatted as an industrial process instruction: job description, 1.1 Scope. safety, Pass/Fail JJob Reference Standard, feedstock materials, equipment, a step-by-step process instruction for surface preparation, thermal spraying, quality control (QC), and a Job Control Record. This standard is based on the literature, equipment, process developments, and industrial practices known at the time of publication. This standard does not cover the design standards or recommended practices for cathodic protection (CP) systems. The design of a CP system for reinforced concrete structures, including the connection of the zinc coating to the steel reinforcement, should be undertaken by an experienced and qualified Corrosion Engineer. Table inspection, test methods, and acceptance criteria that shall be employed. * 1 summarizes 1.2 Units of Measure. This standard makes use of both U.S. Customary Units and the International System of Units (SI). The latter are shown within brackets ({ ]) or in appropriate columns in tables and figures. The measurements may not be exact equivalents; therefore, each system must be used independently. For the purposes of determining conformance with this specification, an observed or calculated value shall be rounded to the nearest unit in the last right-hand place of figures used in expressing the limiting values in accordance with the rounding-off method given in ASTM E29, Standard Practice for Using Significant Digits in Test Data to Determine Conformance with Specifications. 1.3 Safety. Safety and health issues and concerns are beyond the scope of this standard; some safety and health information is provided in Annex B, but such issues are not fully addressed herein. Safety and health information is available from the following sources: American Welding Society: (1) ANSI 749.1, Safety in Welding, Cutting, and Allied Processes (2) AWS Safety and Health Fact Sheets (3) Other safety and health information on the AWS website Material or Equipment Manufacturers: (1) Safety Data Sheets supplied by materials manufacturers (2) Operating Manuals supplied by equipment manufacturers Applicable Regulatory Agencies (1) NFPA 51B, Standard for Fire Prevention During Welding, Cutting, and Other Hot Work. (2) U.S. Department of Labor Regulations, CFR-29, Part 1910.107, Spray finishing using flammable and combustible materials. Work performed in accordance with this standard may involve the use of materials that have been deemed hazardous, and may involve operations or equipment that may cause injury or death. This standard does not purport to address all safety and health risks that may be encountered. The user of this standard should establish an appropriate safety program to address such risks as well as to meet applicable regulatory requirements. ANSI Z49.1 should be considered when developing the safety program. 1 AWS C2.20/C2.20M:2016 2. Normative References The standards listed below contain provisions, which, through reference in this text, constitute mandatory provisions of this AWS standard. For undated references, the latest edition of the referenced standard shall apply. For dated references, subsequent amendments to, or revisions of, any of these publications do not apply. (1) ASTM E29, Standard Practice for Using Significant Digits in Test Data to Determine Conformance with Specifications.5 (2) ASTM B833, Standard Specification for Zinc and Zinc Alloy Wire for Thermal Spraying (Metallizing) for the Corrosion Protection of Steel. (3) ASTM D4258, Standard Practice for Surface Cleaning Concrete for Coating. (4) ASTM D4259, Standard Practice for Abrading Concrete. (5) ASTM D4285, Standard Test Method for Indicating Oil or Water in Compressed Air. (6) ASTM D4417, Standard Test Methods for Field Measurement of Surface Profile of Blast Cleaned Steel. (7) ASTM D4940, Standard Test Method for Conductimetric Analysis of Water Soluble lonic Contamination of Blasting Abrasives. (8) ASTM D7091, Standard Practice for Nondestructive Measurement of Dry Film Thickness of Nonmagnetic Coatings Applied to Ferrous Metals and Nonmagnetic, Nonconductive Coatings Applied to Non-Ferrous Metals. (9) ASTM D7234, Standard Test Method for Pull-Off Adhesion Strength of Coatings on Concrete Using Portable Pull-OffAdhesion Testers. (10) ASTM D7393, Standard Practice for Indicating Oil in Abrasives. (11) AWS Thermal Spraying: Practice, Theory, and Application.® (12) AWS C2.21, Specification for Thermal Spray Equipment Acceptance Inspection, in preparation. (13) AWS C2.25/C2.25M, Specification for Thermal Spray Feedstock-Wire and Rods. (14) CGA G-1.1, Commodity Specification for Acetylene.' (15) CGA G-4.3, Commodity Specification for Oxygen. (16) NACE No. 6/SSPC SP 13, Surface Preparation of Concrete® (17) NACE RP0287, Field Measurement of Surface Profile of Abrasive Blast Cleaned Steel Using a Replica Tape. (18) SSPC-PA 2, Procedurefor Determining Conformance to Dry Coating Thickness Requirements? (19) SSPC-SP 10/NACE No. 2, Near White Metal Blast Cleaning. U.S. Federal Specifications!° (1) BB-A-106, Acetylene, Technical, Dissolved. (2) BB-0-925, Oxygen, Technical, Gas and Liquid. 5 6 ASTM International AWS 7CGA standards are published by ASTM International, 100 Barr Harbor Drive, West Conshohocken, PA 19428-2959. standards are published by the American Welding Society, 8669 NW 36 St, # 130, Miami, FL 33166, standards are published by the Compressed Gas Association, Inc., Crystal Gateway 1, Suite 501, 1235 Jefferson Davis High- way, Arlington, VA 22202. 8 NACE standards are published by NACE International, 1440 Creek Drive, Houston, TX 77084-4906. ° SSPC standards are published by the Society of Protective Coatings (SSPC), 40 24th Street, Pittsburgh, PA 15222-4656. '0U.S. Federal standards are published by the Superintendent of Documents, U.S. Government Printing Office, Washington, DC 20402. 2 AWS C2.20/C2.20M:2016 3. Terms and Definitions AWS A3.0M/A3.0, Standard Welding Terms and Definitions, Including Terms for Adhesive Bonding, Brazing, Soldering, Thermal Cutting, and Thermal Spraying, provides the basis for terms and definitions used herein. However, the following terms and definitions are included to accommodate usage specific to this document. anode. The electrode of an electrochemical cell at which oxidation occurs. Electrons flow away from the anode in the external circuit. Corrosion usually occurs and metal ions enter the solution at the anode. cathode. The electrode of an electrochemical cell at which reduction is the principal reaction. Electrons flow toward the cathode in the external circuit. cathodic protection (CP). A technique to reduce the corrosion of a metal surface by making that surface the cathode of an electrochemical cell. Such protection can be provided using ICCP or SCP. electrolyte. A chemical substance containing ions that migrate in an electric field. feathering. Reducing the thickness of an edge of a coating, e.g., by masking or simultaneously increasing traverse speed of the thermal spray gun. flash coat. A thin metallic coating usually less than 0.002 in [0.05 mm] in thickness. holding period. The time between the start of final blasting for surface preparation and completion of thermal spraying. impressed current cathodic protection (ICCP) system. A system of components including a power source external to the electrode system that provides a direct current to reduce the corrosion of a metal surface. job reference standard. A job site pass/fail reference standard made from concrete and rebar, representative of the whole job or major sections of the job and the environmental conditions, with or without enclosure, and shall include areas showing blasting, metallizing, and connection to the reinforcement. overspray. The excess spray material that is not being deposited on the part or area designated to be sprayed. sacrificial anode. A metal that provides sacrificial protection to another metal that is more noble when electrically coupled through an electrolyte. This type of anode is the current source in SCP systems. sacrificial cathodic protection (SCP). A type of cathodic protection where an active metal acts as a sacrificial anode when it is connected by metallic conductors to a less active metal in the structure to be protected. This specification is limited to thermally sprayed zinc anodes; however, sacrificial cathodic protection using thermally sprayed aluminum, magnesium, and alloys of aluminum, magnesium, and zinc are also in use. thermal sprayed coating (TSC). A protective coating, as it pertains to this standard, applied to a surface using arc or flame spray coating processes. thermal spray coating inspector. A person who is knowledgeable in the concepts and principles of thermal spray coatings and skilled in observing and measuring conformance to this standard. 4. Job and Contract Specification 41 Requirements 4.1.1 Summary of Requirements. Briefly summarize the background and requirements for this thermal spray job, i.e., zinc thermal spray coating on reinforced concrete as (1) a distributed anode for an ICCP system, or (2) a sacrificial anode for a SCP system: ICCP system, the rebar is protected by a counter corrosion current applied by a power source through the thermal spray zinc anode. The zinc thermal spray anode must be electrically isolated from the rebar. When installing a thermally sprayed zinc anode for use in an ICCP system, a viable method to avoid any short circuits between the anode and the rebar should be specified. In an 3 AWS C2.20/C2.20M:2016 SCP system, the zinc anode and the rebar are connected to each other and the protective counter corrosion current is powered by the voltage differential between the zinc anode and the rebar. The more active zinc corrodes in preference to the steel rebar. In a Table 1 summarizes the major job elements of a contract specification for the installation of zinc thermal spray anodes for the protection of reinforced concrete. The criteria, sampling schedule, and test methods are given for the major job elements. The zinc thermal spray coating thickness and adhesion strength should be related to the required service. Additionally, the contract should specify job-site access, job permits, industrial safety, and environmental compliance requirements as appropriate. 4.1.2 Specific Requirements (1) Zine feedstock shall meet the alloy composition requirements of ASTM B833 or AWS C2.25, with the additional requirement that the iron content shall not exceed 14 ppm. (2) The minimum inspection and acceptance criteria for the zinc thermal spray coating includes: (a) Surface preparation and thermal spray process qualification to include materials, equipment, and method. (b) Production area and components to include specific inspection and measurement procedures, locations, and frequency. (3) Thermal spray coating work requirements including: industrial process, which areas are to be sprayed (and not sprayed), thermal sprayed coating thickness, tensile bond strength, quality control (QC) steps, and the Job Control record (per 4.4). (4) Pass/Fail Job Reference Standard for surface preparation finish (of the concrete or the concrete with exposed rebar, or both) and for the zinc thermal spray coatings. (5) Thermal spray coating inspector qualification, designation, and authority on behalf of the purchaser. (6) Thermal spray operator qualification and validation of operator qualification record. (7) Schedule (thermal spray job start, duration, key events, maximum holding period, submittals, test panel, and completion). (8) Concurrent work that may or will be ongoing during the thermal spray work on the job site that may cause (mutual) interference. Cite the procedural and remedial actions to be taken should interference occur. File Delay and Disruption reports as required. (9) Job site work permits; access permits; work regulations and procedures; safety requirements, equipment, and procedures; and Job Control Record. (10) Containment and disposal of waste generated by paint removal, surface preparation, and dust overspray. (11) Applicable federal, state, county, city, and union regulations. (12) Other information and requirements that are necessary for the planning and the completion of the thermal spray job or contract. (13) Documented Quality Control Plan to ensure compliance with the Contract Documents and proper testing of the redundant electrical connections to the reinforcement. summarizes the inspections, test methods, and acceptance criteria that shall be employed during shop and field application of thermal spray coatings. Table 2 lists the laboratory tests that may be used to further examine and qualify the surface preparation, feedstock material, and thermal spray process parameters. The purchaser shall specify the required test method and acceptance criteria if other than those specified in Table 1. The preparation and analysis of thermal spray-coating metallographic test specimens should be performed by a laboratory, acceptable to the purchaser, using qualified thermal spray procedures. Table 1 Page | of the Job Control Record (Annex A) summarizes the job requirements. Pages 3 and 4 summarize the eight QC checkpoints. Contractor's quality control program, Job Control Record, and QC check points equivalent to this standard may be used if agreed to by the purchaser and contractor. 4 AWS C2.20/C2.20M:2016 Table 1 Inspection and Acceptance Tests Job Element Criteria Schedule Test Method Surface Preparation Blasting Air At daily ally Clean dry air ASTM D4285 or therwise required Blasting Media Concrete Surface Finish Clean blasting media per the test for oil in the appropriate abrasive specification. No oil film or fines Each Section >30 minutes prior to Clean with no visible oil, grease, dirt, moisture per Each Section NACE6/SSPC-SP Exposed Rebar Surface Finish ASTM D4940 and ASTM D7393 thermal spraying Visual and 10x magnification >30 minutes prior to thermal spraying 13 Finish per SSPC-SP 10/NACE No. 2 (near-white) Each Section >30 minutes prior to Visual and 10x magnification thermal spraying Anchor-Tooth Profile As mutually agreed by As specified by the Purchaser and Contractor. The profile depth shall be that which is created when blasting to meet the concrete surfacefinish requirement contract ASTM D4417, Method C or NACE RP0287 Zinc Thermal Spraying Coating TSC Thickness On Concrete 0.015 in-0.020 in [0.38 mm0.51 mm] or as specified by the contract ASTM D7091 As specified by the or ultrasonic gage calibrated for concrete contract SSPC-PA On Rebar TSC Tensile Bond on Concrete TSC Surface Texture Texture and Porosity 100 psi [0.69 MPa] minimum or as specified by the contract As specified by Comparable to Job Reference Standard As specified by 2 ASTM D7234 using portable the adhesion tester specified in the contract contract Texture: Visual the contract Porosity: Metallographic examination of companion coupon Porosity Table 2 Thermal Spray Coating Inspection and Acceptance Tests-Laboratory Test Tensile bond strength on concrete (minimum values) Substrate-thermal spray coating interface contamination Ib/in? [ Metallographic: 5 MPa] X magnification and % contamination AWS C2.20/C2.20M:2016 4.2 Job Reference Standard. The actual field equipment and process parameters and procedures (surface preparation, thermal spraying, and quality control) for the contract work shall be used for making the Job Reference Standards. The preparation and the use of the Job Reference Standard for quality control should be agreed upon by the purchaser and contractor. The passing criteria shall be defined in the agreement between the purchaser and contractor. Table summarizes the major elements, acceptance criteria, and sampling schedule for the installation of zinc anodes by thermal spraying. Job Reference Standards shall be prepared, as required, for: 1 (1) Concrete surface finish (without exposed rebar). (2) Concrete with exposed rebar surface finish and rebar profile. (3) Zinc thermal spray coating on concrete without exposed rebar. (4) Zinc thermal spray coating on concrete with exposed rebar. (5) Bond strength of zinc anode to concrete substrate. Test the bond at the time period after application of the thermal coating specified by the purchaser. The Job Reference Standards may be temporarily preserved, when the production work extends over 30 days, by applying a 0.003 in-0.005 in [0.08 mm-0.13 mm] clear polyurethane coating or equivalent material and thickness to protect the Job Reference Standard during the contract period. The Job Reference Standard shall be retained and made available to the end user upon request. 4.3 Thermal Spray Boundary. The contract shall specify the area, structure, or workpiece to be thermal sprayed and the thermal spray boundary between the sprayed and non-sprayed areas. 4.4 Job Control Record. Annex A presents a Job Control Record that covers the essential job information and eight QC check points: Page of the Job Control Record lists information on the contractor, the purchaser, zinc thermal spray 1 coating requirements, safety precautions, surface preparation and abrasive blasting media requirements, flame and arc spray equipment and parameters, and the thermal spray operator qualification. Pages 3 and 4 of the Job Control Record list the eight production QC checkpoints. 4.5 Thermal Spray Coating Inspector. The contract shall specify the spray coatings inspector's role and frequency of inspection. 4.6 Thermal Spray Operator Qualification. The contractor shall ensure that the thermal spray operators possess the knowledge and skill requirements described on the Thermal Spray Operator Qualification Test A&FS-1, Arc and flame spraying zinc wire on reinforced concrete, only in the process being utilized. Alternatively, the operator shall have a current and valid certification from a recognized industry organization, acceptable to the purchaser. 4.7 Pre-Contract Award Validation. If required by the purchaser, the contractor shall submit, provide information, or demonstrate performance, for review and approval of the following: (1) Surface Preparation (a) Submit equipment, material, and process information on the abrasive blasting media and the surface preparation process, and the QC methad to be used. (b) Demonstrate the surface preparation and QC method with the equipment and personnel proposed for performing the entire project. (c) Provide a Job Control Record. (d) Provide any other information and demonstrations required by the purchasing contract. (2) Thermal Spraying (a) Submit equipment, material, and process information on the zinc wire feedstock, arc spray equipment, and thermal spraying, and the QC processes to be used. (b) Demonstrate the surface preparation and zinc thermal spray coating application and QC method with the equipment and personnel proposed for performing the entire project. (c) Provide a Job Control Record. (d) Provide any other information and demonstrations required by the purchasing contract. 6 AWS C2.20/C2.20M:2016 5. Materials The contractor shall indicate the consumable materials to be used for the job unless already specified by the purchaser or the purchasing contract; see 4.7(1) and 4.7(2). 5.1 Zine Thermal Spray Wire. The zinc thermal spray wire shall meet the requirements stated in 4.1.2. 5.2 Tensile Bond Strength Test Specimens. Use ASTM D7234 as a basis to measure the contract-specified tensile bond strength. Specific testing instruments shall be specified in the contract documents. 5.3 Bend Test Requirements. Use the bend test (180° bend on a mandrel) as a qualitative test for proper surface preparation, equipment setup, and spray parameters. The bend test puts the TSC in tension. The mandrel diameter for the threshold of cracking depends on substrate thickness, and coating thickness. 5.3.1 Mandrel Diameter. The mandrel diameters stated in Table 3 shall be used for bend-testing of arc-sprayed zinc TSC that have been sprayed to the specified thickness on 0.05 in [1.3 mm] thick steel coupons. 5.3.2 Bend-Test Procedure for TSC Thickness Range 7 mil to 12 mil [175 ym to 300 pm] (1) Five corrosion-control bend coupons shall be sprayed and shall pass the following bend test: (a) Carbon steel coupons of approximate dimensions 2 in x 4 in to 8 in x 0.050 in [50 mm x x 10 mm to 200 mm 1.3 mm] shall be used. (b) Surface shall be prepared according to contract specification. (c) The TSC shall be sprayed 7 mil tol2 mil [175 um to 300 pm] thick. The TSC should be sprayed in crossing 'passes laying down approximately 3 mil to 4 mil [75 um to 10 pm] in each pass. (d) Coupons shall be bent 180° around a 0.50 in [13 mm] diameter mandrel. (2) Bend test shall pass if, on the bend radius, there is (a) No cracking or spalling, or only minor cracking that cannot be lifted from the substrate with a knife blade. (b) See Figure |. (3) Bend test shall fail if the coating cracks with lifting from the substrate. 5.4 Gases 5.4.1 Oxygen. Oxygen shall conform to Federal Specification BB-O-925, Oxygen, Technical, Gas and Liquid, or CGA G-4.3, Commodity Specification for Oxygen for thermal spraying. §.4.2 Acetylene. Acetylene shall conform to Federal Specification BB-A-106, Acetylene, Technical, Dissolved, or CGA G-1.1, Commodity Specification for Acetylene for flame spraying. Other fuel gases as specified by the thermal spray equipment manufacturer (e.g., methylacetylenepropadiene stabilized [MPS]) gas or propane. 5.5 Abrasive Blasting Media and Air. The contractor shall identify and use abrasive blasting media and air quality (per ASTM D4285) that best provides the surface preparation for the specified tensile bond. Table 3 Bend-Test Cracking Threshold: Mandrel Diameter vs. TSC Thickness For Steel Coupons 0.05 in [1.3 mm] Thick TSC Thickness, mils [ym] 210 [250] 215 [380] Mandrel Diameter, in [mm] 0.50 [13] 0.63 [16] 7 225 [640] <1.0 [25] AWS C2.20/C2.20M:2016 ver esee rN PASS PASS UE NO CRACKS MINOR CRACKS with NO LIFTING or SPALLING Figure FAIL CRACKS with LIFTING or SPALLING 1-TSC Bend Test Pass and Fail Samples 6. Equipment for Thermal Spraying 6.1 Thermal Spray Equipment. The Thermal Spray Equipment shall be capable of operation under the specific environmental and operational conditions and shall be demonstrated by the contractor as capable of producing the specified coatings. Thermal spray equipment shall conform to the requirements of AWS C2.21. 6.2 Air Compressors. An air compressor shall be used with sufficient volume and pressure as necessary to operate the abrasive blasting equipment and thermal spray equipment. See 8.1.1(2) for the ASTM D4258 and D4259 surface preparation guidance. About 150 ft/min [4.3 m*/min] of air at 80 psi-100 psi [0.55 MPa-0.70 MPa] is required. 7. Inspection and Quality Control Equipment 7.1 Surface Preparation. The QC equipment for surface preparation should include the following: 7.1.1 For Blasting Media Contamination: (1) Small glass or plastic container (4 0z-6 oz vol. [120 ml-180 ml]) with tops for qualitative oil-contamination test of the blasting media and the abrasive blasting system. (2) Clean white cloth squares to collect and qualitatively detect moisture and contamination in the compressed air. 7.1.2 For Concrete Surface Finish and Exposed Aggregate (in ICCP systems): (1) The concrete surface shall be free of oil, grease, dirt, moisture, and loose material (2) The contractor shall establish a job specific Pass/Fail Job Reference Standard for concrete-cleanliness agreed to by the purchaser and contractor. The contractor shall use the approved blasting media and blasting equipment and blasting parameters for making the Pass/Fail Job Reference Standard. The Job Reference Standard shall meet the contract specifications and shall be established on a concrete surface of the job or representative of the job. Record the pertinent technical parameters to include the enclosure temperature and humidity and the blasting media, equipment and blasting parameters. The Job Reference Standard shall be representative of the allowable variations of the environmental, surface preparation, and thermal spraying conditions. 8 AWS C2.20/C2.20M:2016 7.1.3 For Rebar Surface Finish and Profile (in SCP systems): (1) The rebar shall have file. Use SSPC-VIS 1 a minimum near-white metal finish (refer to to evaluate the near-white SSPC SP 10 finish. SSPC-SP 10/NACE No.2) and an angular pro- (2) The angular profile depth shall be that which is created when blasting to meet the concrete surface preparation requirement. IMPORTANT NOTE: Steel rebar shall not be exposed to excessive blasting as this will remove "good" concrete unless the adjacent concrete is properly protected. (3) The contractor shall establish a job specific Pass/Fail Job Reference Standard for rebar cleanliness and profile agreed to by the purchaser and contractor. The contractor shall use approved blasting media, equipment, and blasting parameters. This reference standard shall meet the contract specifications and shall be established on a concrete rebar of the job or representative of the job. Record the pertinent technical parameters to include the enclosure temperature and humidity and the blasting media, equipment, and blasting parameters. This Job Reference Standard shall be representative of the allowable variations of the environmental, surface preparation, and thermal spraying conditions. 7.2 Zinc Thermal Spray Coating on Concrete. The QC equipment for thermal spraying shall include the following: 7.2.1 Substrate Temperature. Contact thermometer or infrared pyrometer to measure substrate temperature. 7.2.2 Air Temperature, Dew Point, and Relative Humidity. Psychrometer or equivalent digital humidity measurement instrument to measure air temperature, dew point, and relative humidity. 7.2.3 Zinc Thermal Spray Coating Thickness on Concrete. The thickness may be measured: (1) In-place directly on the concrete with portable eddy current instruments per schedule specified by the contract (see Table 1). The instrument shall be calibrated with thickness reference standards. Three reference standards should be prepared: (a) The contract specified thickness. (b) The contract specified thickness minus 0.004 in [100 jim). (c) The contract specified thickness plus 0.004 in [100 um]. (2) Duct tape or metal "companion coupons" attached to the concrete surface to be sprayed. (a) For duct tape thickness measurements: (i) Remove the duct tape with the sprayed zinc thermal spray coating. (ii) Remove the sprayed zinc (iii) Measure thermal spray coating from the duct tape. the zinc thermal spray coating with a caliper or micrometer having spherically shaped anvils. (iv) Assure that the duct tape does not leave residual contamination on the substrate from the heat of the ther- mal spray process. (v) The non-coated area under the duct tape should receive to maintain the cosmetic appearance of the overall zinc coating. a flash coat of zinc after removal of the duct tape (b) For metal coupon thickness measurements: (i) Measure thickness with calipers or micrometers. measurement instruments may be used for steel coupons. Routinely calibrate magnetic instruments with secondary thickness standards. (ii) Magnetic thickness area under the coupon should receive a flash coat of zinc after removal of the coupon to Maintain the cosmetic appearance of the overall zinc coating. (iii) The non-coated (iv) Zinc Thermal Spray Coating Thickness on Exposed Rebar (for SCP). Measure the zinc thermal spray coating thickness in accordance with SSPC-PA 2 using either a Type magnetic pull-off gage or a Type 2 electronic | fixed probe gage. Routinely calibrate instruments with thickness standards. g AWS C2.20/C2.20M:2016 (v) In-Place Zinc Thermal Spray Coating Tensile Bond Strength on Concrete. Measure the in-place zinc ther- mal spray coating tensile bond strength on concrete in accordance with ASTM D7234. The minimum tensile bond shall meet the requirements of the purchaser. The precision and bias of the portable adhesion tester, the test method, and the interpretation of results shall be as agreed by the purchaser and contractor. (vi) For Bend Coupon, Companion Coupon, and Sample Collection. Sealable plastic containers shall be used to encase bend coupons, companion coupons and other samples collected during the job. 8. Application-Process Method The general application process shall be as described in the following subclauses. An example of the in-process qualitycontrol checkpoints are shown in Annex A. 8.1 Surface Preparation. Surface preparation of the concrete and the exposed rebar is necessary for application of the zinc thermal spray coating. The surface of the concrete shall be cleaned as per ASTM D4258 practice for removing greasc, dirt, and loose material. Use the abrasive blast cleaning procedure of ASTM D4259 practice for abrading concrete. The essential elements of ASTM D4258 and D4259, expanded for the preparation of reinforced concrete for zinc thermal spray coating, follow in 8.1.1. 8.1.1 Concrete. Prepare the concrete surface by light abrasive blasting to remove all surface debris and contamination (oil, grease, dirt, and loose material), and other material that could degrade the bond of the zinc thermal spray coating to the prepared concrete. Note: Heavy oil or grease contamination may have to be removed by detergent cleaning, water rinsing and drying prior to abrasive blast cleaning. (1) Patched concrete areas shal] have a cure period specified by the purchaser. Allow for a cure period prior to abra- sive blasting for thermal spraying. (2) Blasting media and blasting equipment shall be capable of delivering clean dry air at pressures and flow rates necessary to meet the purchaser's surface preparation requirements and demonstrated in the pre-contract award validation (see 4.7). (3) All dust and loosely adherent material from the blasted concrete surface shall be removed by sweeping, air blowing, or vacuuming. (4) Inspection and Acceptance (a) The prepared surface shall be_visually inspected for the absence of (1) debris, oil, grease, dirt, loosely adherent concrete, and other contaminants, and (2) large areas of exposed aggregate. The prepared surface shall meet the visual inspection condition agreed by the purchaser and contractor. (b) For ICCP systems: (i) The thermal sprayed zinc coating must not contact any metal rebar, which will create a short circuit in the ICCP system. Any metal contacting the reinforcement must be electrically isolated or removed prior to spraying. In addition, any cracks or porous area that may provide an electrically conductive path between the sprayed zinc coating and the reinforcement shall either be patch repaired or masked prior to spraying. (ii) If specified by the contract, inspect for exposed tie wires, rebar or other metallic objects close to the surface or exposed using a cover meter or pachometer. Test for electrical contact between any detected surface or exposed metal and the reinforcement to be protected with an ohmmeter. Resistance less than approximately 3 ohm indicates elec- trical contact. use a short detection system that will alarm during spraying when a short is detected between the reinforcement and the zinc sprayed coating. The purchaser and contractor shall agree to (iii) The thermal spray contractor should this detection system. 8.1.2 Exposed Rebar. The surface preparation of concrete with exposed rebar for SCP systems, shall be the same as 8.1.1 (1)-(3) with the following additions: 10 AWS C2.20/C2.20M:2016 (1) Abrasive blast the steel rebar to remove oil, grease, rust, dirt, and loose material as necessary to achieve a near- white metal finish as defined by SSPC-SP 10. (2) The profile depth shall be that which is naturally created (a) when blasting to achieve the concrete surface cleanliness requirement, and (b) to meet the rebar near-white metal finish. 8.2 Thermal Spraying 8.2.1 Masking. Masking may be required for complex geometries where overspray may reduce the tensile bond strength below that specified by the contract. Masking is not required for overspray on surfaces already sprayed to the specified thickness. 8.2.2 Thermal Spray Equipment Setup (1) Set up, adjust, and operate the thermal spray equipment per the manufacturer's instructions and technical manuals or the contractor's validated thermal spray parameters. (2) Use the bend test to validate proper equipment setup and spraying parameters. Use the proper mandrel diameter for the purchaser's specified zinc thermal spray coating thickness. (3) Attach a copy of the spray parameters used to the Job Control Record. 8.2.3 Post-Blasting Substrate Condition and Thermal Spraying Period 8.2.3.1 Concrete Surface Temperature and Cleanliness (1) Measure the concrete surface temperature with temperature is at least 5°F [3°C] above the dew point. a pyrometer. Do not perform any spraying unless the concrete (2) Spraying shall not be conducted during periods of rain or high winds unless the operation is carried out in tected area or inside an enclosure. Do not spray on concrete surfaces that are moist or wet. a pro- (3) It may be necessary to dry the concrete surface by air blowdown or heating to achieve the bond strength requirements of the contract. The drying method should be validated with the Job Reference Standard per 4.2. Care shall be taken to prevent thermal damage to the concrete surface by any application of heat. The surface temperature shall not be permitted to exceed 212°F [100°C] during heating or drying processes. The concrete surface temperature shall be measured with a contact pyrometer to ensure that the maximum allowable surface temperature is not exceeded. (4) Maintain surface cleanliness: no oil, grease, dirt, moisture, or loose material on the concrete surface. 8.2.3.2 Holding Period. Thermal spray coatings should be applied as soon as possible after surface preparation to minimize oxidation of exposed steel and contamination of the prepared surfaces. The permissible holding period between start of final blasting for surface preparation and completion of the thermal spray process shall not exceed 2 * hours unless agreed upon by the purchaser and system designer. Longer periods may be agreed to by the purchaser and system designer for less aggressive environment. The holding period depends on the moisture content of the concrete, and the temperature-humidity conditions that prevent moisture on the concrete surface and rusting of the rebar. The tensile bond will be reduced by surface moisture, high humidity, and long exposure time prior to coating. In low-humidity environments or in enclosed spaces using dehumidification equipment, it will be possible to prevent or to retard surface moisture and extend the holding period on the concrete and before flash rusting of the exposed rebar. 8.2.3.3 Low Temperature Environments. Thermal spraying in low temperature environments (<40°F [4°C]) must be qualified with statistically valid in-place tensile bond strength tests. The average of the tests should be above the minimum acceptable tensile bond strength. The range of the test strength cannot exceed a 3 sigma variation from the mean (average). 8.2.4 Plan the Thermal Spray Operation 8.2.4.1 Spraying Time Interval. The Thermal Spray Process should start as soon as possible after the final blasting. Complete the thermal spray process on: (1) Concrete without exposed rebar within 16 hours after start of final blasting for surface preparation subject to the holding period established in 8.2.3.2. (2) On concrete with exposed rebar; within the holding period established in 8.2.3.2. 11 AWS C2.20/C2.20M:2016 8.2.4.2 Sequence of Thermal Spray Operation. Inspect the surface geometry of the item or area to be sprayed. Plan the Thermal Spray Process Plan or sequence to: (1) Maintain the gun as close to perpendicular as possible and within +45° of the perpendicular to the substrate. (2) Use the manufacturer's recommended standoff distance for the air cap installed or the contractor's revisions thereto. See Table 4 for nominal standoff and spray-pass width values obtained from equipment manufacturers. 8.2.5 Execute Thermal Spray Process Sequence (1) Start-up and adjustment of the spray gun should not be made on the workpiece (or surface to be thermal sprayed). Do not allow any non-validated spray coating on the prepared surface to be thermal sprayed. For mechanized spraying, programmed overlapping and crossing passes shall be used to eliminate the occurrence of thin spots and stay within the coating thickness specification. (2) Apply the specified coating thickness in several perpendicular and overlapping passes. NOTE . For manual spraying, use crossing passes to minimize the occurrence of thin spots in the coating. NOTE 2. For manual and mechanized spraying, validate the spraying procedure or the spraying program with thickness measurements, bend tests, or both. NOTE 3. Feather the edges of coating layers to be overlapped with additional coating layers of zinc so as to maintain the specified coating thickness. (3) Complete the spraying within the holding period of 8.2.3.2. (4) When spraying zinc for an ICCP system, continuously monitor for short circuits between the zinc thermal spray coating and the rebar. Shut down and eliminate the short circuit if a short circuit occurs. 8.2.6 Thickness and Tensile Bond Strength Measurements 8.2.6.1 Thickness Measurement. Measure the thermal spray coating thickness in locations and at a frequency specified by the purchaser. 7.2(3) details how thickness is measured. 8.2.6.2 Tensile Bond Strength Measurement. Measure the zinc thermal spray coating tensile bond strength to concrete in accordance with 7.2(5). Make tensile bond strength measurements in accordance with the purchaser's criteria and sampling schedule per Table 1. 8.2.7 Degraded Zinc Thermal Spray Coating. If dust, dirt or debris accumulates on the concrete or rust appears on the exposed rebar, proceed as follows: (1) Stop spraying. (2) Mark off the acceptable sprayed area. (3) Call the thermal spray coating inspector to observe and evaluate the cause and magnitude of the anomalous condition, notify the purchaser or his agent, and record the actions taken to resume the job in the Job Control Record. Distances Flame- and Arc-Spray Standoff Distances and Spray-Pass Widths (Nominal) Spray-Pass Width in [mm] Perpendicular Standoff in [mm] Air Cap Flame Wire Arc Wire 5-7 [130-180] 6-12 [50-300] 12 Regular Fan 0.75 [20] 1.5 [40] Not Available 3-6 [75-150] AWS C2.20/C2.20M:2016 REMOVE DEGRADED Zn TSC PREPARE CONCRETE AND REBAR PER 7.1 APPLY Zn TSC PER 8.2 END ITEM INSPECTION PER TABLE 1 THERMAL SPRAY EQUIPMENT SETUP PASS PRODUCTION THERMAL SPRAYING INSPECT FAIL Figure 2-Process Flow Chart for Repairing Zinc Thermal Spray Coatings (TSC) on Reinforced Concrete 9. Repair of Zinc Thermal Spray Coating on Reinforced Concrete Figure 2 illustrates the process flowchart for repairing degraded zinc thermal spray coating. The repair of degraded zinc thermal spray coating on concrete and concrete with exposed rebar, e.g., excessive oxidation, delamination, blistering, peeling, cuts through the coating, and loss of coating shall include the following: (1) Remove all degraded zinc thermal spray coating by scraping or strip blasting or both. Remove all degraded zinc thermal spray coating prior to the final surface preparation for thermal spraying see 8.1). (2) Prepare concrete and rebar for thermal spraying see 8.1). (3) Apply zinc thermal spray coating see 8.2). (4) Inspect zinc thermal spray coating thickness and bond of the repaired area for conformance to Table | or the pur- chaser's specifications. 10. Records The contractor should use a Job Control Record to record the production and QC information required by the purchaser or the purchasing contract. Additionally, the contractor should have its own Quality Control Program and a Job Control Record to record all pertinent information. Use the Annex A Job Control Record to record the major planning, production, and QC items and actions. The contractor shall keep records for a time period consistent with the contractor's quality control and records program and as required for regulatory compliance and the purchasing contract. 11. Debris Containment and Control The purchaser shall] specify the requirements, responsibilities, and actions for the containment, collection, and removal of the debris produced by the contractor and its subcontractors. 13 AWS C2.20/C2.20M:2016 12. Utility Services The contractor shall list the utility services and the period of time they are required for use for the thermal spray application. These may be provided by the purchaser but shall be confirmed by the contractor. 14 AWS C2.20/C2.20M:2016 Annex A (Normative) Job Control Record for Sample Applying Zinc Thermal Spray Coating on Concrete This annex is part of this standard and includes mandatory elements for use with this standard. JCR No. Date (la) Thermal Spray Contractor Name Tel. Fax Address (1b) Job Control or Identification No. (lc) Point of Contact Tel. (2a) Purchaser Name Fax Address (2c) Contact Person (2b) Completion Date (2d) Job Description (3) Zinc TSC Feedstock, Thickness, Tensile Bond Strength, and Measurement Requirements (3a) Feedstock Material Certification Wire Diameter U.S. Customary S.L. Heat/Control No. Manufacturer TSC Thickness/Pass Total TSC Thickness Tensile Bond Strength in in in Ib/in? mm mm mm kPa (Attach Safety Data Sheet [SDS] to the Job's first Job Control Record) (3b) Sampling Schedule (4) Safety Precautions (5) Surface Preparation Media and Parameters Mfg./Type/Model Pressure Pot Blasting Equipment Nozzle Diameter Media Size Range and Pressure Air Flow U.S. Customary mesh in Ib/in? ft/min S.1. mesh mm kPa m/min (Attach media certification and SDS to the Job's first Job Control Record) 15 AWS C2.20/C2.20M:2016 (6) Flame-Spray Equipment and Parameters Air Cap Mfg./Model Perpendicular Standoff* Atomizing Air U.S. Customary S.1. Gun Travel Speed Spray Pass Width Ib/in? in in/sec in MPa cm cm/sec cm *To substrate. (7) Arc-Spray Equipment and Parameters Power Source Mfg./Model Air Cap Type Perpendicular Standoff* Atomizing Air U.S. Customary S.1. Votage (V) Current(A) Gun Travel Speed Spray Pass Width Ib/in? in in/sec in MPa cm cm/sec cm *To substrate. (8) Thermal Spray Operator(s) Name Employee No. (ID) Qualification Standard Qualification Valid Until (Date) Job Qualification Results (9) Qualification Test Tensile Bond Strengths (Five qualification samples) Qualification Test Tensile Bond Strengths (Five qualification samples) Qualification Test Tensile Bond Strengths (Five qualification samples) Average Maximum Minimum Average Maximum Minimum Average Maximum Minimum Ib/in? Ib/in? Ib/in? Ib/in? Ib/in? Ib/in? Ib/in? Ib/in? Ib/in? [MPa] (MPa] [MPa] (MPa] (MPa] [MPa] (MPa] (MPa] (MPa] Notes/Remarks Conversion factors for S.I. 1 Ib/in? = 0.69 kPa; 1 in = 25.4 mm. 16 AWS C2.20/C2.20M:2016 (10) Quality Control Check Points Made During Production per Clause 7 Value QC CP No. Action Req'd Value Measured Pass Date Fail Time Surface Preparation 1 Clean Dry Air (per ASTM D4285) Vent air into dry container for | minute. aa None Vent air through clean white cloth for 1 minute. Any wetting or staining indicates contamination. Correct deficiency before going further. 2 Clean Blasting Media Visually inspect for absence of: (1) Fines and contamination. None (2) Oil contamination per test with distilled water (a) Fill a small clean bottle (4 0z-6 oz (120 ml-180 ml]) half full of abrasive particles. (b) Fill the remainder of the bottle with None distilled water. the bottle. Inspect water for oil sheen. If any oil sheen is observed, do not use the blasting media. (c) Cap and shake (d) Alternatively use ASTM D7393. (3) If contaminated, clean the blasting equipment, especially the pot and hoses, then replace with blasting media and retest. 3 Clean Concrete (1) Absence of dust, debris, oil, and grease. None (2) Pass the Pass/Fail Job Reference Standard of Pass 7 4 1(2)(b) Clean Concrete and Near-White Metal-Finish Rebar (1) Absence of rust, debris, and contamination. SSPCSP 10 (2) Pass the Pass/Fail Job Reference Standard of 7 1(3)(c) Pass Thermal Spray Operation 5 Thermal Spray Equipment Setup (1) Validate parameter settings and attach to Job Control Record. (2) Observe successful surface preparation and bend test at each shift or crew change Only minor cracks (3) Retain bend coupon with the Job Control Record file or as specified by the contract 17 TT Inspector Initials AWS C2.20/C2.20M:2016 Value QC CP No. Action Req'd Value Measured Pass Date Fail Time Inspector Initials Thermal Spray Operation (Cont'd) 6 Zinc Thermal Spray Coating Application Observe the surface preparation, spraying set-up, concrete preheating, and thermal spraying process for conformance to Clause 8. Measure and record*: Zine TSC thickness/pass Total thickness 7 Zinc TSC Thickness Measurement (1) Per purchaser's sampling schedule* (2) Check method used and value: Eddy current instrument Ean Companion duct tape Companion steel coupon 8 tty Tensile Bond Strength Measurement (1) Tensile bond strength per purchaser's sampling schedule.* (2) Make tensile bond measurements per 7.2(5) *Enter values specified in the contract. Notes/Remarks TSC Inspector Name (Stamp or Print) Date TSC Operator Name (Print) Date Note: The form may be modified as agreed by the metallizing contractor and the owner, as it applies to each particular work, such that all necessary records are maintained. AB. AWS C2.20/C2.20M:2016 Annex B (Informative) Information for Thermal Safety Spraying This annex is not part of this standard but is included for informational purposes only. B1. General Thermal spraying can be hazardous to health. Potential thermal spraying hazards include exposure to vapors, dust, fumes, gases, noise (from the spray gun) and arc ultraviolet (UV) radiation. Additionally, improperly used thermal spray equipment can create potential fire and explosion hazards from the fuel and carrier gases and a potential electrical shock hazard from the electrical and electronic equipment and charged wire spools. Follow proper safety precautions to minimize hazards. Operators should comply with the procedures in the safety references and the manufacturer's technical manuals and the Safety Data Sheets (SDSs). Thermal spraying can be a completely safe process when performed by an operator who follows the recommended precautionary measures, has a proper understanding of thermal spraying practices and has knowledge and skill and exercises care in using thermal spray equipment. B1.1 Graphic Symbol Definition. This safety annex uses graphic symbols to alert the user to the presence of important operating instructions, safety considerations, and special instructions. These symbols (along with their definitions) are shown in Table B.1. Table B.1 Graphic Symbols Definition Symbol A Symbol Definition Special instructions, safety instructions, etc. are being presented. Ear protection must be worn. Explosive material is present. Eye protection must be worn. kd Inflammable material or high temperature is Safety gloves must be worn. present. N Danger: risk of electrical shock. Safety overalls must be worn. Respiratory equipment must be worn. Magnetic fields from high currents can affect pacemaker operation. Persons wearing electronic life support equipment (Pacemaker) should consult with their doctor before going Near spray equipment. 19 AWS C2.20/C2.20M:2016 B2. Abrasive Blasting and Thermal Spraying: Common Elements Both abrasive blasting and thermal spraying operations generate dust and fumes that may pose a respiratory hazard.Treat airborne metal dusts, finely divided solids, or their accumulations, as explosives. Use adequate ventilation in the thermal spray work area and collect the over- spray to minimize the danger of dust explosions and fires. In shop environments, wet bag and filter-cartridge collectors may be used to collect the fine overspray particles thus minimizing the explosion and fire hazard and release of controlled and hazardous materials. Keep bag- and filter-cartridge-collector units at least 50 ft [15 m] away from the spraying area to preclude ignition from the flame or heat of thermal spray guns. Fieldwork may require partial or complete containment of the work site for surface preparation and thermal spraying and the collection and safe disposal of the used blasting media and thermal spray overspray. Ensure compliance with the purchaser's and government agency requirements for air-quality and hazardous-materials control. Wear appropriate personal respiratory protection during abrasive blasting, thermal spraying, and paint sealing operations. If operator discomfort such as dizziness or nausea develops, stop the operation. Determine the cause of the discomfort and correct before resuming operations. When abrasive blasting, use a NIOSH certified Type CE respirator and Type CE hood (air line supplied-air hod with faceplate and devices to protect the wearer's eyes, face, chin, neck, shoulders, and upper body from rebounding abrasive blasting media). Respirators selected from those currently approved and certified by NIOSH/MSHA Section 134, should be used. Personnel in or near blasting operations should wear helmets, hand shields, face shields, or goggles conforming to ANSI Z87.1, Occupational and Educational Eye Protection; eye protection conforming to ANSI Z89.1, Protective Headwear for Industrial Workers. Noise levels generated in blasting and thermal spray operations can cause temporary or permanent hearing damage and fatigue. Wear noise suppressing earmuffs and properly fitted earplugs when thermal spray operators and personnel are in the immediate vicinity of thermal spray operations to reduce exposure to the high intensity noise levels to acceptable conditions. B3. Thermal Spraying B3.1 Use of Equipment. Follow the safety measures outlined below: * Read, understand, and follow the safety and operation instructions provided in the instruction manuals. * Do not operate equipment above recommended pressures and flows. * Thermal spray equipment has been expressly designed for thermal spraying. Never use it for any other purpose (such as welding, soldering, or brazing). * Keep hands and other parts of the body away from hot surfaces and objects. Sprayed metal and surfaces are hot. * Use only spare parts recommended by the equipment manufacturer to preclude safety hazards. B3.1.1 Equipment Handling. Operate and maintain the thermal spray equipment in accordance with the manufacturer's instruction manual. The extremely hot conditions of thermal spray operations require additional precautions such as not pointing the thermal spray gun at any person, or at any combustible and explosive material. Remove paper, wood, oily rags, cleaning solvents, sealers, and paints away from the thermal spraying area. Be especially careful not to spray on the hoses, when operating the gun. Hoses will burn. Keep them out of the way. All air lines, compressors, regulators, etc., should be inspected regularly for leaks and loose connections. Do not light flame-wire and rod guns without wire or rod in the nozzle as flames may shoot back into the gun causing operator injury and equipment damage. Use a friction lighter to light the flame gun; never use matches. 20 AWS C2.20/C2.20M:2016 B4. Fine Particulates (Metal Dust) from Thermal Spraying All dust having considerable calorific value can be explosive. This dust includes: flour, starch, hard rubber dust, wood flour, aluminum dust, and dust of other metals. The basic safety rules for thermal spraying include: (1) Facility and Equipment Design and Installation (a) Use adequate ventilation in spray booths and other confined spaces to prevent the accumulation of fumes and metal dust. (b) All closed collectors should be provided with blowout holes or relief panels. All fans, pipes, dust arrestors, and motor should be external to the duct system. (c) Use explosion-proof electrical components in the metal-dust environment. (d) Minimize and dissipate the generation of static electricity to avoid spark discharge by bonding and grounding equipment as necessary. (2) Operations and Maintenance (a) Read, understand, and follow the (i) Equipment manufacturer's safety instructions for arc spraying aluminum and zinc. (ii) Precautions and instructions on the feedstock SDS. (b) Avoid any condition that may suspend or float particles in the air creating a dust cloud. (c) Inspect and clean regularly to ensure that there is no potentially dangerous accumulation of metal dust in exhaust vents, workspace and cabinets. Good housekeeping is essential. (d) Avoid any actions that generate sparks or flames, or otherwise result in reaching the ignition energy or temperature. This includes NO SMOKING. (e) Prior to cleaning the metal dust collection system, tum off the power and red-tag electrical boxes and cabinets. (f) Non-sparking tools should be used in cleaning and repair operations. (g) When making repairs on the ventilating or dust collecting equipment, no welding or cutting should be done before the equipment is washed down and all metal dust removed. Good housekeeping in the shop and field work areas should always be maintained to assure proper storage of hazardous materials and to avoid accumulation of combustible materials and metal dusts, with particular attention given to inspecting for dust on beams, rafters, booth tops, and in-floor cracks. B4,1 Zinc Powder Feedstock. Fine zinc dust dispersed in the air in sufficient concentrations, and in the presence of an ignition source, may be a dust explosion hazard. The dust may release zinc oxide fumes if involved in a fire. Consult the feedstock manufacturer for safe use and handling instructions. BS. Ventilation During Thermal Spraying (Consult Section 11.8 [Ventilation], AWS Thermal Spraying: Practice, Theory, and Application.) A number of factors determine the amount of contamination to which the workman is exposed when performing blast and thermal spray operations. These include the following: (1) Volume of space in which the thermal spraying operation is to be done. (2) Number of spray and grit blast operators. (3) The evolution of hazardous fumes, gases, or dusts according to the abrasive used or material being sprayed. (4) Heat generated by the spraying process. 21 AWS C2.20/C2.20M:2016 (5) Presence of volatile solvents. (6) All of the preceding factors should be considered in order to better protect the operators and to supply adequate ventilation to the spray area. Local extraction or general ventilation systems, or both, should be used to control and remove toxic fumes, gases, and particulates from the work area. Local extractor systems can remove gases and particulates at the source permitting concurrent work activities and reducing the performance requirements of the general ventilation system. Where thermal spray operations are incidental to general operations, it is good practice to apply local exhaust ventilation to the spray areas. This prevents contamination of the general work area. Individual respiratory protective devices should be well maintained. They should not be transferred from one employee to another without being cleaned and disinfected. Forced-air respiratory devices require Grade D or better air per Compressed Gas Association, Commodity Specification for Air (CGA No. G-7.1). Mechanical ventilation is required in spraying and blasting operations that are performed in any enclosed, or partially enclosed space. Dust generated may rapidly fill any large tank, building, or semi-enclosed space. The ventilation equipment for most field thermal spray and blast operations consists of engine or motor driven portable extractors with flexible piping or ducts. When removing dust with portable exhausters, it is necessary to attach a dust collector to trap the dust and prevent contamination of the surrounding areas. In shop environments, use wet (water wash), bag, or filter type collectors for gathering spray dust. Dust collectors should be replaced and ventilation duct kept clean before entrapped dust builds up to create an explosion hazard or seriously reduces the efficiency of the system. Spray cabinets used for spraying small and medium size parts should be equipped with extraction ventilation, with a minimum air velocity of 400 ft/min (2 m/s] entering the collector hood. The spray equipment should be operated within the face area of the hood and directed into it. The design of the cabinet should be such that turbulent eddy currents are eliminated. Industrial Ventilation, published by the American Conference of Governmental Industrial Hygienists, should be consulted. Blasting rooms should be designed to be well lighted and adequately ventilated. Ventilation should provide down draft and longitudinal airflow with a velocity of 80 ft/min-100 ft/min (0.4 m/s-0.5 m/s]. The blasting room should be equipped with a dust collecting system. Conform to local, state, and federal regulations for blast cleaning operations. Blasting waste should not be exhausted directly into the atmosphere. Use of the blasting room for spraying is not good practice and should be avoided whenever possible. Spray dust will quickly clog most cloth dust collectors used in the blasting rooms. Moreover, when spraying in a blasting room, the dust collector system will require more frequent maintenance to prevent fire or explosion due to accumulation of metallic dust. When ventilating confined spaces, all air replacing that withdrawn shall be clean, respirable, and exhausted. Filtered air shall meet governing regulations for air quality. Ventilation shall be sized and configured in accordance with the thermal spray system and exhaust system manufacturers' recommendations. If portable gasoline or diesel-engine driven ventilators or compressors are used, they should be located so that engine exhaust gases cannot be drawn into the ventilating system. This precaution will also prevent exhaust gases from entering the intake of the compressor. This is particularly critical if the air is to be used for respirators. If dust collectors are used, closed type collectors should be provided with blowout holes or relief panels. Blowout panels should also be provided in ventilation piping. All fans, pipes, dust arrestors, and motors should be grounded. Ground to piping that carries fuel gas or oxygen should not be used. Ventilating fans should be kept running when cleaning out booths, pipes, etc. This prevents the accumulation of dust or fumes in the system. Aluminum and magnesium dusts present an explosive hazard, which requires special attention. Adequate wet collector systems should be used on either of these metals. Care should be exercised, since these metallic dusts may generate hydrogen gas in water. These systems should be designed to prevent hydrogen accumulation. Frequent cleanout operations should be performed to reduce residues. 22 AWS C2.20/C2.20M:2016 When spraying on unusually large objects or in large confined spaces, such as encountered in boilers and tanks, it is imperative that fresh air helmets and protective clothing be worn. No welding or cutting should be done in the repair of any ventilation or dust collecting equipment unless the equipment has been thoroughly cleaned and accordingly inspected. If there is any question as to the effectiveness of the ventilation and exhaust system or as to the presence of airborne particles that the operator might inhale, consult a competent industrial hygienist. B6. Hazardous Materials All thermal spray feedstock materials are supplied with SDS. Never spray understanding, and following the precautions contained in the SDS. a a material without reading, Some materials (beryllium, tellurium and their oxides, for example) are very dangerous to the respiratory system and should not be used at all, except under the supervision of a competent industrial safety engineer. Blasting, spraying, and finishing all produce dust. Blasting, spraying, and finishing should be considered as hazardous as spraying these hazardous feedstock materials. The following materials are specifically listed because they are commonly sprayed. There are many other hazardous materials that are not listed because they are not commonly sprayed. Because standards change and new information becomes available from time to time, it is important to use and follow up-to-date SDSs. Current regulatory information should be obtained from national and local agencies and followed. B6.1 Zinc and Zinc Alloys (Zinc, Bronzes, and Brasses). Fumes of these metals are toxic. Consult an industrial hygienist for the proper protection. B6.2 Nickel and Nickel Components. Fumes of nickel components are potentially hazardous. Consult an industrial hygienist for the proper protection. One known highly toxic compound is nickel carbonyl. Under certain conditions, nickel carbonyl can be formed by the combination of nickel and carbon monoxide. B6.3 Solvents and Gases. Solvents used for cleaning or to apply sealers or topcoats (e.g., acetone, xylene, or alcohol) have vapors that are harmful and can be fatal. Use only with adequate ventilation or proper respiratory protection and other protective clothing as needed. Avoid breathing solvent vapors and skin contact with solvents. Most solvents are also flammable liquids. All solvent tanks should have lids and be covered when not in use. Take proper safety precautions. Keep all solvents and flammable materials at least 50 ft away from welding, oxyfuel cutting and heating, and thermal spraying operations. Before beginning work, and specifically before opening any gas valve, make sure that there is adequate ventilation in the work area. Adequate ventilation depends on the specific work activity but should be calculated and verified by a safety professional if there is any doubt. Examine all gas equipment regularly for leaks and loose connections. Replace defective parts as necessary. Always secure gas cylinders to keep them from falling. Keep gas cylinders in use away from the thermal spray operation so that molten spray or flame will not reach them. Alternatively, provide fire resistant shields. When not in use, shut off the gas, remove the regulators, and place valve caps on the cylinders. B7. Personal Protection B7.1 Respiratory Protection. Consult the Thermal Spray Equipment Instruction Manual, SDS, and applicable national and local jurisdiction safety and health regulations (or local standards), before using spray materials. 23 AWS C2.20/C2.20M:2016 During the spray process, a respirator approved by applicable national and local regulations should be worn at all times, to protect the operator from exposure to dust and fumes. Respirators should also be worn when product handling generates dust. Consult an industrial hygienist for the proper protection. Individual respiratory protective devices should be well maintained. They should not be transferred from one employee to another without being cleaned and disinfected. Forced air respiratory devices require Grade D or better air per Compressed Gas Association, Commodity Specification for Air (CGA No. G-7.1). Any finely divided material may damage the respiratory system in varying degrees. Whenever fume concentration is high enough to cause operator discomfort (dizziness, nausea, etc.), stop spraying. Check the ventilating and exhaust systems and related equipment. If this equipment is not adequate and not operating properly, respirator equipment must be provided. If operator discomfort continues, even with the added protection, stop spraying and recheck all equipment. Do not resume spraying until all possibilities of discomfort have been eliminated. In areas distant from spraying, where no respiratory protection seems needed, periodic air sampling is recommended. Air samples should also be taken in the spray area after spraying has been stopped. Respiratory protection is not required when spraying is stopped and area is known to be free of harmful dust and fumes. B7.2 Body Protection. Possible allergic reactions to dust, fumes and the like, or other unknown causes of health impairment due to contact with the body cannot usually be predicted. To avoid such reaction, never allow spray dust to enter eyes, mouth, cuts, scratches, or open wounds. After spraying, and especially before eating or handling food, wash hands thoroughly. Wear fireproof or flame-resistant protective clothing. Wear flame-resistant clothing and leather or rubber gauntlets during thermal spray operations to keep harmful flying particles and thermal spray materials from skin contact. Aluminized clothing may be used with precautions (1) that IR and UV radiation are not to be reflected on unprotected skin, and (2) against electrical shock. B7.3 Hearing Protection. The operator and other personnel close to the thermal spray operation must be NI protected from excessive noise. If possible, the thermal spray operation should be in an approved spray cabinet or room. Hearing protection (that meets local standards) should be used. Do not rely on wads of cotton for hearing protection. They are ineffective against high-intensity noise. Noise levels at any location depend on such factors as equipment operating parameters; background noise; room size; and wall, floor, and ceiling materials. To determine the exact noise level, it is necessary to measure the sound level. The various spray guns can produce the noise levels as shown in Table B.2. B7.4 Eye Protection. Always wear proper eye protection when operating or watching the spray operation. Inspect the lens and cover plates frequently. Lenses and cover plates scratched, pitted, or damaged can impair vision and seriously reduce protection. UV radiation from the various thermal spray processes can cause eye and skin damage. When spraying, thermal spray operators and personnel viewing the thermal spray work should wear suitable eye protection: goggles, face shield, or goggles plus a face shield when it is required to lift the face shield during spraying. The recommended shade number for helmets and goggles are shown in Table B.3. Infrared (IR), visible, and Use opaque or arc radiation protective screens suitable for attenuating the thermal spraying IR and UV radiation to protect personnel working outside the immediate thermal spray work area and personnel passing nearby. B8. Electric Power Protection Ensure that adequate power line capacity is provided to avoid electrical hazards. If a line cord with a ground lead is provided with the equipment for connection to a switchbox, connect the ground lead to the grounded switchbox. If a cable plug is added for connection to a grounded mating receptacle, the ground lead must be connected to a safety ground. If the line cord comes with a three-pole plug, connect to a grounded mating receptacle. Never remove the ground from a plug or use a plug with a broken off ground prong. 24 AWS C2.20/C2.20M:2016 Table B.2 Noise Levels Produced by Spray Guns Thermal-Spray Process Noise Level (dBA) Minimum Recommended Protection Plasma 134 Earplugs and Earmuffs High Velocity Oxygen Fuel (HVOF) 134 Earplugs and Earmuffs Flame Powder 110 Earplugs Flame Wire 125 Earplugs and Earmuffs Arc Wire 116 Earplugs and Earmuffs Table B.3 Shade Levels to Protect from UV Light Produced by Spray Guns Shade Numbers Procedure Wire flame spraying 24 Powder flame spraying 3-6 Arc spraying with gun shield 3-6 Arc spraying without gun shield -12 Plasma spraying 9-12 The heat for spraying with an arc spray gun is produced by an electric arc of extremely high intensity. This relatively large amount of electric power can be dangerous if handled carelessly. The feedstock wires of the arc spray gun are electrically energized when the gun is in operation. Anyone touching both energized wires at the same time could receive a harmful or fatal electric shock or burn. When the spray is shut off, electrical charge is removed from both feedstock wires. B8.1 Cables. Frequently inspect cables for wear, cracks, and damage. Immediately replace those with excessively worn or damaged insulation to avoid the possibility of lethal shock from bare cables. Cables with damaged areas must be replaced. Keep cables dry, free of oil and grease, and protected from hot metal and sparks. Do not walk on or drive vehicles over cables. Terminals, wire raceways, and other exposed parts of electrical units should have insulating covers secured before operation. B8.2 Safety Devices. Safety devices such as interlocks and circuit breakers should not be disconnected or disabled. Before installation, inspection, or service of equipment, shut off all power and remove line fuse (or lock or red-tag switches) to prevent accidental turning on of power. Do not open power circuit or change polarity while spraying. If, in an emergency, it must be disconnected, guard against shock burns or flash switch arcing. Before leaving equipment unattended, always shut off and disconnect all power from equipment. A power disconnect switch must be available near the power source as required by code. 25 AWS C2.20/C2.20M:2016 AN B8.3 Protection For Wearers of Electronic Life Support Devices (Pacemakers). Magnetic fields from high currents can affect Pacemaker operation. Persons wearing electronic life support equipment (Pacemaker) should consult with their doctor before going near thermal spray equipment. B9. Fluorocarbon Material (O-Rings) Precautions Thermal spray equipment manufacturers often specify the use of O-rings made of fluorocarbon synthetic rubber. This material provides a wide range of desirable properties, including high flame and heat resistance, resistance to compression-set, and broad chemical compatibility. At elevated temperatures above 600°F [316°C], fluorocarbon material may degrade, emitting hydrogen fluoride fumes that, in the presence of water, may react to form highly corrosive hydrofluoric acid. This can cause severe burns on bare skin with delayed symptoms. In normal operation of gas guns, gun O-ring temperatures are well below the 600°F [316°C] level at which fluorocarbon O-rings start to degrade. However, the excess heat that occurs in gas guns during prolonged backfire, and in plasma guns when nozzle burnout occurs may cause O-ring degradation. B9.1 Precautions. A heat-degraded fluorocarbon O-ring will look charred or gummy and sticky. To avoid corrosive skin burns, observe the precautions given below: (1) Put on neoprene or PVC gloves before handling any part contaminated with heat-degraded fluorocarbon O-ring residue. (2) Wash the part thoroughly with soap and water. Fluorocarbon rubber manufacturers advise further neutralizing the part with limewater (calcium hydroxide solution). (3) Discard the gloves when finished. B9.2 First Aid. If heat-degraded fluorocarbon rubber contacts bare skin, do the following immediately: (1) Wash skin thoroughly with soap and water. (2) Rub a 2.5% calcium gluconate gel into the skin until any existing irritation disappears. If irritation persists, consult a physician. B10. Disposal of Materials and Equipment Disposal of all equipment material and collected overspray shall be in accordance with local regulations. Some materials may be classified as hazardous. Follow local requirements and information on SDSs. Some guns may contain a small amount of oil. Drain oil and dispose of per local regulations. 26 AWS C2.20/C2.20M:2016 Annex C (Informative) an Official Requesting Interpretation on an AWS Standard This annex is not part of this standard but is included for informational purposes only. Cl. Introduction The following procedures are here to assist standard users in submitting successful requests for official interpretations to AWS standards. Requests from the general public submitted to AWS staff or committee members that do not follow these rules may be returned to the sender unanswered. AWS reserves the right to decline answering specific requests; if AWS declines a request, AWS will provide the reason to the individual why the request was declined. C2. Limitations The activities of AWS technical committees regarding interpretations are limited strictly to the interpretation of provisions of standards prepared by the committees. Neither AWS staff nor the committees are in a position to offer interpretive or consulting services on (1) specific engineering problems, (2) requirements of standards applied to fabrications outside the scope of the document, or (3) points not specifically covered by the standard. In such cases, the inquirer should seek assistance from a competent engineer experienced in the particular field of interest. C3. General Procedure for all Requests €3.1 Submission. All requests shall be sent to the Managing Director of AWS Technical Services Division. For efficient handling, it is preferred that all requests should be submitted electronically through technical @aws.org. Alternatively, requests may be mailed to: Managing Director Technical Services Division American Welding Society 8669 NW 36 St, # 130 Miami, FL 33166 C3.2 Contact Information. All inquiries shall contain the name, address, email, phone number, and employer of the inquirer. C3.3 Scope. Each inquiry shall address one single provision of the standard unless the issue in question involves two or more interrelated provisions. The provision(s) shall be identified in the scope of the request along with the edition of the standard (e.g., D1. 1:2006) that contains the provision(s) the inquirer is addressing. C3.4 Question(s). All requests shall be stated in the form of a question that can be answered 'yes' or 'no'. The request shall be concise, yet complete enough to enable the committee to understand the point of the issue in question. When the point is not clearly defined, the request will be returned for clarification. Sketches should be used whenever appropriate, and all paragraphs, figures, and tables (or annexes) that bear on the issue in question shall be cited. 27 AWS C2.20/C2.20M:2016 C3.5 Proposed Answer(s). The inquirer shall provide proposed answer(s) to their own question(s). C3.6 Background. Additional information on the topic may be provided but is not necessary. The question(s) and proposed answer(s) above shall stand on their own without the need for additional background information. C4. AWS Policy on Interpretations The American Welding Society (AWS) Board of Directors has adopted a policy whereby all official interpretations of AWS standards are handled in a formal manner. Under this policy, all official interpretations are approved by the technical committee that is responsible for the standard. Communication concerning an official interpretation is directed through the AWS staff member who works with that technical committee. The policy requires that all requests for an official interpretation be submitted in writing. Such requests will be handled as expeditiously as possible, but due to the procedures that must be followed, some requests for an official interpretation may take considerable time to complete. C5. AWS Response to Requests Upon approval by the committee, the interpretation is an official interpretation of the Society, and AWS shall transmit the response to the inquirer, publish it in the Welding Journal, and post it on the AWS website. C6. Telephone Inquiries Telephone inquiries to AWS Headquarters concerning AWS standards should be limited to questions of a general nature or to matters directly related to the use of the standard. The AWS Board Policy Manual requires that all AWS staff members respond to a telephone request for an official interpretation of any AWS standard with the information that such an interpretation can be obtained only through a written request. Headquarters staff cannot provide consulting services. However, the staff can refer a caller to any of those consultants whose names are on file at AWS Headquarters. 28 AWS C2.20/C2.20M:2016 Annex D (Informative) List of Informative References This annex is not part of this standard but is included for informational purposes only. ANSI/ISEA Standards ANSUISEA Z87.1, American National Standard for Occupational and Educational Personal Eye and Face Protection Devices ANSUISEA 789.1, American National Standard for Industrial Head Protection ASTM Standards ASTM C-633, Standard Test Method for Adhesion or Cohesion Strength of Thermal Spray Coatings CGA Standards CGA G-7.1, Commodity Specification for Air SSPC Standards SSPC-Vis 1, Visual Standard for Abrasive Blast Cleaning Steel. SSPC 2300 (I), Specification for the Application of Thermal Spray Coatings (Metallizing) of Aluminum, Zinc, and Their Alloys and Composites for the Corrosion Protection of Steel 29 AWS C2.20/C2.20M:2016 This page is intentionally blank. 30 AWS C2.20/C2.20M:2016 Annex E (Informative) Conversion Factors Used in this Publication This annex is not part of this standard but is included for informational purposes only. Length Metric U.S. Customary in Fraction in 0.001 0.03937 0.0625 0.09375 0.125 0.1562 0.1875 mm Nominal 25.4 x 103 [0.025 mm] 1 1.587 2.381 3.175 1/16 3/32 1/8 3.969 4.763 25.4 5/32 3/16 1.00 m] [1.6 mm] [2.4 mm] [3.2 mm] [4.0 mm] [4.8 mm] (25 mm] [1 Pressure U.S. Customary Metric Metric Nominal Ib/in? 100 Ib/in? 145 Ib/in? [6.9 kPa] [0.69 MPa] [7 kPa] 1 [1 [0.7 MPa] MPa] Thermal Spraying Parameter Spray Rate To Convert From To Multiply By Ib/hr Ib/ft?/0.001 in [kg/hr] [lb/hr] [kg/m?/m] 0.454 2.20 0.192 [kg/m7/m] Ib/ft?/0.001 in 5.202 ft?/hr/0.001 in (m?/hr/um] f?/hr/0.001 in 2.36 0.424 (kg/hr] Area Coverage > unit area [m?/hr/um] 31 AWS C2.20/C2.20M:2016 This page is intentionally blank. 32 AWS C2.20/C2.20M:2016 List of AWS Documents on Thermal Spraying Title Designation C2.16/C2.16M Guide for Thermal Spray Operator Qualification C2.18 Guide for the Protection of Steel with Thermal Sprayed Coatings of Aluminum and Zinc and Their Alloys and Composites C2.19/C2.19M Specification for the Application of Thermal Spray Coatings to Machine Elements for OEM and Repair C2.20/C2.20M Specification for Thermal Spraying Zinc Anodes on Steel Reinforced Concrete C2.21M/C2.21 Specification for Thermal Spray Equipment Performance Verification C2.23M/C2.23 Specification for the Application of Thermal Spray Coatings (Metallizing) ofA Aluminum, Zinc, and Their Alloys and Composites for the Corrosion Protection of Steel C2.25/C2.25M Specification for Thermal Spray Feedstock-Wire and Rods 33 AWS C2.20/C2.20M:2016 This page is intentionally blank. 34