Uploaded by Juan Manuel Rodriguez

12x2x16 AWG 600V Individual and Overall Shielded Instrumentation and Control Cable 8LD3112109 v 2 r 10

advertisement
12x2x16 AWG 600V Individual and Overall Shielded Instrumentation
and Control Cable
Part Number:
8LD3112109
Applications:
Class 1 Division 2, Outdoor, Indoor, Hazardous areas, Process
control industry
12 pairs are individual polyester/aluminum tape shilded, cabled
together, overall polyester/aluminum tape shielded and PVC
jacketed.
The wires are 600 volts and 105°C rated per MIL-W-16878.
UV resistant FR-PVC
21.0 mm nom.
585 kg/km
General Construction:
Outer Jacket Material:
Outer Diameter:
Weight:
Design & Materials
Conductor Material:
Conductor Size:
Conductor Construction:
Insulation Material:
Insulation Thickness:
Insulation O.D.:
Conductor Color Code:
Lay Length:
Ind. Shield Material:
Ind. Shield Thickness:
Drain-wire 1 Material:
Drain-wire 1 Construction:
Drain-wire 1 size:
Overall Shield Design:
Overall Shield Material:
Overall Foil Thickness:
Overall Drain-wire Material:
Overall Drain-wire size:
Overall Drain-wire Construction:
Total number of conductor units:
Total number of elements:
Outer Jacket Thickness:
Outer Jacket Color:
Marking:
Annealed Tinned Copper
16 AWG
19x0.287 mm
FR-PVC -55°C to 105°C rating
0.43 mm
2.3 mm nom.
Black x White, numbered
60 mm
Aluminum/Polyester Foil
24 µ
Annealed Tinned Copper
Stranded
22 AWG
100% Coverage
Aluminum/Polyester Foil
24 µm
Annealed Tinned Copper
18 AWG
Stranded
24
12
1.6 mm nom.
Gray
Per request
Standards
Applicable Standards:
Flammability Rating:
P/N: 8LD3112109
RoHS-2 2011/65/EU
IEC 60332-3 , IEEE 383
1/2
Performance
Max. DC Resistance :
Capacitance:
Inductance:
Min. Insulation Resistance :
Min. Bend Radius:
Max. Operating Temperature:
Min. Operating Temperature:
UV resistance:
Prepared By
Dov Shaham
Revised By
Dov Shaham
15.2 Ω/km@20°C
200 pF/m
0.25 µH/m
200 MΩ•km
125 mm
+90 °C
-30 °C
Yes
Version Num
2.10
Modified on
23-01-2013
Teldor Cables & Systems Ltd. ("Teldor") reserves the right to make changes to the products described in this catalog without prior
notice. Teldor does not assume any liability which may occur due to the use of the products described herein. Drawings may not be to