Plant Client Contract Code Document ID Contract No. PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 66-6700 TECHNICAL SPECIFICATIONS – HIGH VOLTAGE SWITCHGEAR PANELS 00 Page 1 of 2 00 IFR ISSUED FOR APPROVAL 29.06.18 NSH 29.06.18 DAS 29.06.18 RPM - Rev. Status Description Date Prepared Date Checked Date Approved AC Based on: PIN-LES–ELT-1014, Rev.0, 12-2015 Barcode © Copyright 2018 : All rights reserved thyssenkrupp Industrial Solutions (India) Private Limited Category Code: -01 PIN-QMC-03-F101 03-2015 Rev Plant Client Contract Code Document ID Contract No. PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 66-6700 TECHNICAL SPECIFICATIONS – HIGH VOLTAGE SWITCHGEAR PANELS Rev 00 Page 2 INDEX SHEET The document Cover Sheet indicates revisions made in this document along with the purpose of issue of the revised document. The details of revisions made in the enclosures of this document are listed in the table of Contents below and the enclosures listed therein are an integral part of this document. CONTENTS PIN-QMC-03-F101 03-2015 Part Docu Size Description No. Of Rev. Pages No. Revised Clauses Part-I A4 Index sheet and status of revision A4 Site Conditions A4 General specifications 2 1 7 0 1 0 - Part-IIA A4 Design Data Sheet 7 0 - Part IIB A4 Design Data Sheet – Numerical Relay 2 0 - Part-IIIA A4 Notes on Method of Offer Submission 1 0 - Part-IIIB A4 Scope of Supply & Price Schedule 2 0 - Part-IV A4 Drawings & documents enclosed 1 0 - Part-V A4 Inspection Test Plan 1 0 - Part-VI A4 Compliance Declaration 2 0 - of 2 Plant Client Contract Code PA plant Coromandel International Limited Coromandel-PA Contract No. 66-6700 Site Conditions Rev Sr. No. Description Site Condition 1. Location Visakhapatnam, Andhra Pradesh 2. Altitude 5.1816 mtrs. above MSL 3. Ambient Temperature - Maximum 45 Deg C 4. Ambient Temperature – Minimum 15 Deg C 5. Design Ambient Temperature (For Electrical Equipment) 50 Deg C 6. Relative Air Humidity 80-85 % 7. Daily Maximum Rainfall 269 mm in 24 hours 8. Seismic Zone II 9. Soil Resistivity 9.57 Ohm-meter 10. Thermal Resistivity of Soil Later Deg.K.m/Watt 11. Presence of Corrosive atmosphere Yes 12. Tropicalizing required Yes 01 Page 1 of 1 Plant Client Contract Code Document ID PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 Contract No. 66-6700 HIGH VOLTAGE SWITCHGEAR PANELS Part-I - General Specifications Rev 1.0 00 Page 1 INTRODUCTION This specification covers the design, manufacturing, inspection and testing at manufacturer’s works, of High Voltage Switchgear panels. Equipment to be supplied shall comply with latest revision of applicable Indian Standards (IS), IEC Standards and specific codes and standards mentioned in clause ‘Codes and Standards’ of Part-II of this specification. Scope of supply and services covered under this specification shall be as per various parts of this specification. Offer shall be submitted as per Part-IIIA, Notes on Method of Offer Submission. Standard and descriptive requirement is covered in Part-I while specific requirement is covered in Part-II. Requirements for testing at manufacturer’s works are covered in Part-V. PIN-LES–ELT-1014, Rev.0, 12-2015 All equipment and components shall be new and shall have a design life of minimum 20 years. 2.0 GENERAL REQUIREMENTS 2.1 Construction a. The high voltage switchgear panels shall be metal clad, totally enclosed, vermin proof, dust tight CRCA sheet steel cubicles as specified in Part-II. b. Circuit breaker panels and busbars shall be of natural air cooled type. c. If necessary, louvers shall be provided for natural ventilation. These louvers shall be covered by brass wire mesh of opening less than 1 mm. d. Each panel shall essentially comprise two portions: Fixed portion housing busbars, CTs, relays, instruments, outgoing terminals and other accessories. Withdrawable portion comprising the circuit breaker (with or without PT)/ Bus PT/ line PT. e. Extension at either end of panels/ busbars shall be possible. f. Each cubicle shall be provided with a front access hinged door of suitable strength with handle and padlocking facility. g. Compartmentalization shall be such that fire in one compartment does not spread to another compartment and failure of one equipment does not affect the adjacent units. Suitable vents shall be provided to release gas pressure developed due to live arc at the bus or failure of components like CTs, PTs etc. Busbar compartments shall have a separate pressure relief arrangement. h. All control switches or devices requiring operation shall be located at a height which is convenient for operation. Meters shall be located at a height which is convenient for monitoring. i. Each LV compartment shall be provided with: Panel light (CFL type) with MCB. Switch Socket with ELCB. of 7 Plant Client Contract Code Document ID PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 Contract No. 66-6700 HIGH VOLTAGE SWITCHGEAR PANELS Part-I - General Specifications Rev 00 Page 2 j. In case of truck mounted circuit breakers, smooth rack-in and rack-out of circuit breaker on floor shall be possible. Vendor shall design suitable arrangement for the same. If required suitable ramp shall be supplied for this purpose. k. Circuit breaker cubicle shall be provided with automatically operated safety shutters with caution stickers to cover the stationary isolated contacts whenever the carriage/ truck is withdrawn. Safety shutters shall be provided with padlocking arrangement for shutter in covered position. l. A circuit breaker of given rating shall be prevented from engaging with the stationary element of a circuit breaker of higher rating. m. All circuit breakers of identical rating shall be physically and electrically interchangeable. n. No live parts shall be accessible on opening the panel door or cover. o. Specified continuous current rating of various equipment/ components of panels is the required in-panel rating at full load condition for design ambient temperature and at site conditions. Vendor shall suitably derate the nominal rating to suit above conditions. p. All opening, doors, covers shall be covered with suitable neoprene gaskets. q. All hardware shall be zinc-passivated or cadmium plated. r. In case of cassette type circuit breaker, separate circuit breaker handling trolley shall be supplied if specified in Part-IIIB, to facilitate removal and insertion of circuit breaker carriage. s. Earthing trolley for cable side and bus side earthing with voltage sensing circuit (1 ph PT) and alarm/ interlock facility shall be supplied if indicated in Part-IIIB. Earthing trolley shall be suitable for insertion in circuit breaker compartment after removal of circuit breaker carriage. t. Suitable lifting hooks/ arrangement shall be provided for each panel. PIN-LES–ELT-1014, Rev.0, 12-2015 2.2 Busbars and Bus Taps a. Busbars shall be of uniform cross section throughout the length. Continuous and short time current rating of busbars and busbar material shall be as indicated in Part-II. b. All busbars and busbar joints shall be easily accessible for periodic inspection without requirement of dismantling any components like CTs etc. c. All busbar joints and all tap-off connections from main horizontal busbars shall be shrouded. d. All busbar joints and connections shall be made through zinc passivated or cadmium plated high tensile strength nuts, bolts and washers. e. Sleeves for the busbars, if specified in the data sheet, shall withstand the rated line-to-line voltage and the maximum permissible temperature. Effect of provision of sleeves shall be considered in sizing of busbars. f. Continuous current rating of all busbar links within a circuit breaker / Contactor panel shall be at least equal to the in-panel rating of the installed circuit breaker/Contactor, irrespective of the CT ratio. of 7 Plant Client Contract Code Document ID PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 Contract No. 66-6700 HIGH VOLTAGE SWITCHGEAR PANELS Part-I - General Specifications Rev 2.3 00 Page 3 Earth Bus a. Earth bus as specified in Part-II shall be provided along the full length of each switchboard and each stationary unit shall be connected directly to this bus by two separate and distinct connections. b. Earthing terminal connectors shall be provided at the bottom of the panel at either end for connection to the Purchaser’s earth conductor. c. Hinged doors shall be earthed through flexible copper braids. All non-current carrying metal parts shall be effectively bonded to the earth bus. 2.4 Switchgear Components Note: Makes of switchgear components shall be as specified in Part-II. A. Circuit Breakers Each circuit breaker shall be provided with emergency manual trip device, mechanical ‘ONOFF’ indicators, spring ‘CHARGED-DISCHARGED’ indicators, manual spring charging facility with manual ‘CLOSE’ push button. Emergency mechanical ‘TRIP’ Push Button shall be accessible without opening the panel door. Each circuit breaker shall have three (3) positions - SERVICE, TEST and ISOLATED, with mechanical indication. The design of circuit breaker shall be such that it is possible to close the front access door even when the circuit breaker is pulled out to ISOLATED position. After failure of power supply to the spring charging motor, at least one OPEN-CLOSE-OPEN operation of the circuit breaker shall be possible. For safe operation, maintenance and testing of circuit breaker, interlocks shall be provided for the following: i. To prevent a closed circuit breaker from being isolated or inserted into the service position. ii. To prevent operation of circuit breaker in any intermediate position. PIN-LES–ELT-1014, Rev.0, 12-2015 iii. To ensure earthing of circuit breaker carriage before the main circuit breaker contacts are plugged into the stationary contacts. Positive earthing of the circuit breaker trolley/ carriage shall be maintained while plugging in/ out. iv. To prevent ‘Plugging In’ of circuit breaker when earth switch is closed. v. To prevent closing of earth switch when circuit breaker is ‘Plugged In’. vi. To prevent compartment door from being opened if the circuit breaker is in ‘SERVICE’ position. vii. To prevent insertion of earthing trolley when circuit breaker is in service position. Interlock shall be provided such that cable earthing trolley cannot be inserted in of 7 Plant Client Contract Code Document ID PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 Contract No. 66-6700 HIGH VOLTAGE SWITCHGEAR PANELS Part-I - General Specifications Rev 00 Page 4 Incomer/ bus-coupler panel. Interlocks shall be provided such that bus earthing trolley cannot be inserted in outgoing feeder panels. viii. To prevent insertion of bus earthing trolley or closing of bus earth switch unless all circuit breakers associated with that bus (i.e. Incomer/ outgoing/ bus-coupler) are racked out. ix. To prevent 'Plugging In’ of circuit breaker (in Incomer/ outgoing/ bus-coupler of associated bus) in service position if Bus earthing trolley is inserted. B. Power Contactor i. Contactor along with HRC fuses shall be provided for outgoing feeders as indicated in single line diagram enclosed in Part-IV. ii. Contactor shall be mounted on a trolley similar in construction to circuit breaker trolley. All safety and protection interlocks shall be similar to a circuit breaker defined elsewhere in this Specification. iii. HRC fuse shall have a very fast electrical cut-off characteristic and very low let-through energy. iv. Contactor should be able to break locked rotor current of motor. v. Contactor shall be electrically or mechanically latched type as mentioned in Part-II. Mechanically latched type Contactor shall be provided with closing solenoid and shunt trip coil. C. Current Transformer & Potential Transformer Accuracy class, VA burden, ratio and other technical particulars of instrument transformers shall be as specified in Part-II and in relevant single line diagram enclosed in Part-IV. VA burden of CT and PT indicated in SLD/ Part-II is minimum requirement and CT/ PT shall have VA burden to meet the connected load plus minimum 20% margin unless otherwise specified in Part-II. All CTs and PTs shall be subjected to partial discharge measurements during the course of manufacture including measurement of inception and extinction voltage values. CTs shall be bar primary window type. PIN-LES–ELT-1014, Rev.0, 12-2015 CT polarity shall be indelibly marked on each transformer and at the associated ferrules on the terminal block. PTs shall be fully insulated for the rated voltage. All CT/ PT terminals shall be brought to terminal block in LV compartment. Star point formation, earthing connections etc. shall be done at the terminal block using suitable links. CATD or equivalent terminals shall be used for CT terminals. D. Relays and Meters Make and type of protection relays and meters shall be as per Part-II, enclosed SLD/ schematic drawings. All relays shall be flush/ semi-flush mounted on the front of respective cubicle. of 7 Plant Client Contract Code Document ID PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 Contract No. 66-6700 HIGH VOLTAGE SWITCHGEAR PANELS Part-I - General Specifications Rev 00 Page 5 Ammeter for motor feeders shall be provided with suppressed end scale to indicate starting current (6 to 8 times full load current). Numerical/ microprocessor based relays and digital meters shall have facility for communication with SCADA if specified in Part-II. E. Control Wiring Control wiring shall be carried out with flexible heat resistant switchboard wires of minimum size 1.5 sq. mm for control circuits and 2.5 sq. mm for CT circuits. Wires connected to earth shall be of green colour only. Each wire shall be identified at both ends with wire designation in accordance with the wiring diagram developed from approved control schematics. Interlocking type plastic ferrules of yellow colour with black lettering shall be used for identification. All wire termination except for clip-on screw type terminal blocks shall be made with ring/ fork tongue compression type connectors. Wires shall not be tapped in between terminal points. Type of lug shall suit relevant application. The wiring inside the panel shall be properly laid and fixed in wiring ducts with removable covers. The wiring ducts shall be properly insulated and shielded from high voltage areas. Wires shall be accessible from the front without removing the component mounting plate. Routing of wires behind the component mounting plate is not acceptable. Wires forming part of tripping circuit of circuit breaker shall be provided with additional red ferrule marked `T’ or with some other acceptable identification mark as per manufacturer’s standard. Openings provided in sheet steel partitions for carrying out the interpanel wiring shall be provided with rubber grommets. Wiring between different shipping sections shall be carried out through separate set of terminal block. Sufficient length of jumper wires shall be provided with ferrule nos. at both ends. One end of these wires shall be connected to the terminal block. Full details of such wiring shall be furnished by the vendor. All spare contacts of relays, switches and other components shall be wired upto terminal blocks. Also, contacts of all components of spare circuit breaker/ contactor feeders shall be completely wired up to the terminal blocks. Wiring between fixed portion of cubicle and door mounted equipment shall be routed through flexible PVC conduits. PIN-LES–ELT-1014, Rev.0, 12-2015 Two wires shall not be terminated at one terminal. Additional terminations, if required, shall be done on adjacent terminals using suitable shorting links. F. Control Terminal Block Terminal blocks of different voltage classes shall be segregated. The terminal blocks shall be further grouped and segregated according to circuit functions and voltages. Minimum 20% spare terminals shall be provided in each block. Individual terminals in each block and in each group shall be serially numbered in accordance with the drawings. Such of 7 Plant Client Contract Code Document ID PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 Contract No. 66-6700 HIGH VOLTAGE SWITCHGEAR PANELS Part-I - General Specifications Rev 00 Page 6 numbering shall be legible, permanent and indelible by use of suitable transparent covering over ferrule. Terminal block for CTs shall be provided with drop out facility for testing purpose. 2.5 Name Plate Main name plate shall be provided at the top of the board, both on the front and rear side. Switchboard number/ designation shall also be indicated on a separate label on the front and rear side. Name plates of approved design shall be provided at the front and rear of each panel. Name plates shall also be provided for all components (i.e. for instrument, relay and auxiliary switch) mounted on the face. All internally mounted components shall be identified by painting the item nos. (as per approved scheme drawings) on or adjacent to the component. Identification by stickers is not acceptable. Material of name plates shall be 3 mm thick 3-ply lamicoid sheets, or approved equivalent. The letters shall be engraved in white on black background. Inscription details on name plate shall be as per Purchaser’s requirements which shall be provided during vendor drawing approval stage. 2.6 Control Supply Purchaser’s auxiliary supply (AC and DC) shall generally be made available at one point, preferably inside Bus PT panel or bus-coupler panel. Means shall be provided for distribution, isolation, segregation and protection of circuits. 2.7 Space heaters Each vertical panel shall be provided with space heater to prevent moisture condensation inside panel. Space heater shall be located at the bottom of the panel and shall be controlled through MCB and thermostat with adjustable setting. 2.8 Painting Vendor shall furnish complete details of painting procedure and painting facilities available along with the offer. Final paint shade shall be as indicated in Part-II. 3.0 FACTORY ACCEPTANCE TEST Purchaser shall have right to carry out stage inspection. PIN-LES–ELT-1014, Rev.0, 12-2015 All Type tests and Routine tests as specified in Part-V shall be carried out during final inspection. Minimum fifteen days advance notice shall be given for carrying out final inspection. Vendor shall ensure that all relays and meters are properly configured for the intended protection/ metering schemes. All relevant functions and operations shall be demonstrated during the final inspection. Vendor shall ensure that all meters associated with testing of the equipment are calibrated by a competent authority and the calibration certificates are valid at the time of carrying out the testing of equipment. of 7 Plant Client Contract Code Document ID PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 Contract No. 66-6700 HIGH VOLTAGE SWITCHGEAR PANELS Part-I - General Specifications Rev 4.0 00 Page 7 PACKING All panels and loose equipment shall be properly packed to protect the equipment during transportation and storage at site prior to installation. Type of packing shall take into account mode of transportation, weather conditions, distance to installation site etc. Vendor shall furnish packing details for Purchaser’s approval. 5.0 SUPERVISION OF INSTALLATION, TESTING AND COMMISSIONING Vendor shall depute his personnel to the site for supervision of installation of panels (for providing guidance to installation contractor and ensuring that necessary precautions are taken for proper alignment and assembly of the panels). In addition, vendor shall depute his specialists to the site during testing and commissioning phase, to check proper configuration of all relays and meters, assistance for carrying out relay testing and setting, demonstrating connectivity, boxing up etc. Vendor shall quote charges for Supervision of Installation, Testing and Commissioning as indicated in Part-IIIB. Spare parts required during testing and commissioning of the switchboards, shall be supplied by vendor as part of equipment supply cost. Vendor shall quote separately for Mandatory Spares as well as Spares for 2 years’ Operation and Maintenance, as indicated in Part-IIIB. 6.0 GUARANTEED PERFORMANCE The performance figures indicated in Part-II shall be guaranteed within the tolerance specified or as permitted by relevant standards. In case of failure of the equipment (including bought out items) to meet the guaranteed performance, Purchaser reserves the right to reject the equipment. However, Purchaser also reserves the right to use the rejected equipment until the new equipment meeting the guaranteed performance requirement is supplied by the Vendor. If any equipment supplied by the Vendor fails at site during erection, commissioning or service (within guarantee period), the Vendor shall repair and put back into successful operation the failed equipment within the time frame and procedure of repair agreed with the Purchaser depending on nature of failure, at no extra cost to the Purchaser. PIN-LES–ELT-1014, Rev.0, 12-2015 The period of guarantee of the equipment shall be as per the agreed commercial terms & conditions. of 7 We reserve all the rights relating to this technical document © ...2015...ThyssenKrupp Industrial Solutions (India) Private Limited QAD No.PIN-LES–ELT-1014, R0 HIGH VOLTAGE SWITCHGEAR PANELS PART - IIA GENERAL DESIGN DATA SHEET Code Coromandel-PA Contract no. 66-6700 Doc. 6700-ELT-0000-EC-0005 Rev. 0 Page 1 OF 7 * 001 Make : 002 Panel designation/ Tag no. : 2900-SW-11 (11kV) & 2900-SW-21 (6.6kV) 003 Nominal System Voltage and Voltage variation : 11 kV +/- 10% & 6.6kV +/- 10% 004 Supply Frequency and Frequency variation : 50 Hz +/- 5% 005 Combined Voltage and Frequency variation : 10 % (absolute) 006 System neutral grounding : Soildly Grounded (11kV) / Resistance Grounded (6.6kV) 007 Type of Circuit breaker : VCB/ SF6 008 Reference SLD No. : 6700-ELT-0000-FA-0002 009 Installation : Indoor CODES & STANDARDS 010 011 IS/ IEC 62271-1 :- High Voltage switchgear and controlgear - Common specification. 012 IS/ IEC 62271-200 :- AC Metal enclosed switchgear & control gear for rated voltages above 1 kV and up to & including 52 kV. 013 IEC 62271-106 :- High Voltage Alternating Current Contactors and Contactor-based Motor Starters. 014 IS 9385 :- High voltage fuses (all parts). 015 IS 11353 :- Guide for Uniform System of Marking & Identification of Conductors & Apparatus Terminals. 016 IS 5578 :- Guide for Marking of Insulated Conductors. 017 IS/ IEC 60529 :- Degrees of Protection Provided by Enclosures (IP Code). 018 IS 12729/IEC 62271-1 :- Common Specification for High-Voltage Switchgear and Controlgear Standards. 019 IS 5082 :- Wrought aluminium & aluminium alloy bars, rods, tubes & sections for electrical purposes. 020 IS 2705 :- Current Transformers (all parts). 021 IS 3156 :- Voltage Transformers (all parts). 022 IS 1248 :- Direct acting indicating analogue electrical measuring instruments and their accessories (all parts). 023 IS 9920/ IEC 62271-103 & 104 :- High Voltage Switches (Part 1). 024 IS 9921 :- AC disconnectors (isolators) and earthing switches for voltages above 1000V (all parts). 025 IS 2071 :- High Voltage test techniques (all parts). 026 IEC 60255-1 :- Measuring Relays & Protection Equipment - Common requirement. 027 Indian Electricity act and CEA Regulations (2010) 028 Fire Insurance Authority Regulations 029 030 SWITCH BOARD RATING/ DESIGN PARAMETERS 031 Rated Insulation Level a) Nominal System Voltage in kV : 6.6 11 b) Rated voltage in kV (Ur) (rms value) c) Rated short duration power-frequency withstand voltage in kV (Ud) (rms value) d) Rated lightning impulse withstand voltage in kV (Up) (Peak) : 7.2 12 : 20 28 : 60 75 032 Rated Normal current (Ir) for Main Busbar : As per single line diagram (Part-IV) 033 Rated short time withstand current (Ik) : As per single line diagram (Part-IV) 034 Rated duration of short circuit (tk) : 035 Rated peak withstand current (Ip) : 2.5 times of Ik (kA) 036 Internal Arc Testing (IAC) : Yes,40 kA for 0.1 s 1 s 037 Partition Class : PM 038 039 040 Loss of service continuity category Type of accessibility of switchgear Types of compartments a) Busbar (Main) compartment b) Busbar (Control & auxiliary circuit) compartment c) Switching compartment d) Incoming/ Outgoing HV & CT compartment e) LV control compartment : : LSC2B AFLR : : : : : Non-accessible compartment Tool-based accessible compartment Procedure-based accessible compartment Tool-based accessible compartment Tool-based accessible compartment 041 We reserve all the rights relating to this technical document © ...2015...ThyssenKrupp Industrial Solutions (India) Private Limited QAD No.PIN-LES–ELT-1014, R0 HIGH VOLTAGE SWITCHGEAR PANELS PART - IIA DESIGN DATA SHEET Coromandel-PA Contract no. 66-6700 Doc. 6700-ELT-0000-EC-0005 Rev. 0 Page 042 043 Type Degree of enclosure protection : Floor Mounted, Metal Clad, Drawout Type, Single Tier : IP 4X 044 Material of enclosure : CRCA SHEET STEEL/ Alu-Zinc 045 Sheet thickness : 046 CONSTRUCTION Code 047 a) Frame, Doors and Covers : min. 2.0 mm b) Panel Partitions : min. 2.0 mm Material of construction for cable gland plate * * * : a) 3 core cables : min. 3 mm CRCA sheet steel b) Single core cables : min. 4 mm Aluminium Entry 2 OF 7 * * : a) Power and Control Cables : Bottom b) Busduct : NA c) Minimum space required for cable termination (Reference :- Raychem heat shrinkable kit) Nominal system voltage in kV 6.6 11 Indoor straight connection (mm) 250 300 Indoor cross connection (mm) 450 450 Outdoor (mm) 450 650 048 Louvers provided : Yes/ No 049 Minimum distance from top of panel to ceiling : 050 Explosion vent/ duct provided : Yes/ No 051 Dimension of Explosion vent/ duct (W x D x H) : 053 Type of painting process : 7 tanks process for surface preparation 054 Primer : 2 coats of epoxy based primer, powder coating 055 Final paint : 2 coats of epoxy based finish paint, powder coating 056 Final paint shade : RAL-7032 057 058 Minimum thickness of paint : 60 Microns 059 Busbar Material : Electrolytic grade Aluminium 060 Minimum clearance in air mm mm * * * * * PAINTING 052 061 : a) Phase to phase : mm b) Phase to earth : mm * * Maximum temperature of bus bar joints a) Bare copper/ Bare aluminium alloy : 90 Deg C b) Tin-coated : 105 Deg C c) Silver/ nickel coated : 115 Deg C : 75 Deg C Maximum temperature of contacts BUS BARS a) Bare copper b) Tin-coated : 90 Deg C c) Silver/ nickel coated : 105 Deg C a) Expected to be touched in normal operation : 70 Deg C b) Not expected to be touched in normal operation : 80 Deg C a) Bare : 90 Deg C b) Silver/ nickel/ tin coated : 105 Deg C : 200 Deg C Accessible parts Terminals for connections to external conductors 062 Maximum allowable temperature of busbars terminals/ joints/ contacts during SC conditions 063 Busbar (Dimension & Sleeves) a) Shape of bus bar : b) Bus bar dimensions : mm * * We reserve all the rights relating to this technical document © ...2015...ThyssenKrupp Industrial Solutions (India) Private Limited QAD No.PIN-LES–ELT-1014, R0 HIGH VOLTAGE SWITCHGEAR PANELS PART - IIA DESIGN DATA SHEET BUS BARS (Cont.) 063 Code Coromandel-PA Contract no. 66-6700 Doc. 6700-ELT-0000-EC-0005 Rev. 0 3 OF 7 * f) Rated withstand temperature of sleeves * : °C 064 Joints shall be shrouded : Yes 065 Material of shrouds : Epoxy / FRP 066 Bus bar support insulator : 067 Page c) Silver coating for busbar joints/ breaker sliding contact : Yes d) Tin coating to be provided to terminals for external conductor : Yes connection e) Heat shrinkable type sleeve shall be provided : Yes. With phase identification a) Voltage class : kV b) Creepage distance : mm c) Material : Epoxy Earth Bus * * * * * : a) Short Circuit withstand current : 40 kA for 1 s b) Size : mm c) Material : Cu/ Al * * 068 CONTROL/ AUXILIARY SUPPLY 071 072 Protection, Control, Indication, Meters a) Voltage rating : 110V DC,+10% -15% b) Number of feeders : 2 Nos. c) Auto-change over required : YES d) Preferred point of supply connection : Bus PT Space heater, Panel illumination aux. supply and Spring charging a) Voltage rating : 240V +/- 10%, 1-ph, 50 Hz b) Number of feeders : 1 No. c) Auto-change over required : No d) Preferred point of supply connection : Bus PT 073 Make 075 Type and Model No. : VCB and 076 077 Numbar of Poles Mounting : 3 : Draw out (truck/ trolley mounted or cassette type) 078 Rated short time withstand current (Ik) 079 CIRCUIT BREAKER * 074 a) 1 s : b) 3 s : : kA (rms) b) DC time constant : 45 ms : kA, 2.5 times of Ik 081 Total interrupting time measured from trip coil energisation : 082 Opening time at no load (interval of time between the instant of energising the opening release and the instant when the arcing contacts have separated in all poles) 087 * * a) Symmetrical Rated short circuit making current (Ip) 084 085 086 * Rated short circuit breaking current (Isc) 080 083 * 60 ms (maximum) : ms Closing time at no load (interval of time between energising of the closing circuit and the instant when the contacts : ms touch in all poles) Rated operating sequence : O-0.3s -CO-3min-CO Circuit Breaker class : S1- M2-E2 ( Capacitor duty as per application requirement Permissible no. of interruptions without changing the quenching medium at a) Rated current : nos. b) 50% rated breaking current : nos. c) Rated breaking current : nos. * * * * * * * Maximum overvoltage factor of the circuit breaker when switching OFF a) Unloaded transformer of rating as per SLD : b) Unloaded long cable : c) Shunt capacitor : * * * We reserve all the rights relating to this technical document © ...2015...ThyssenKrupp Industrial Solutions (India) Private Limited HIGH VOLTAGE SWITCHGEAR PANELS PART - IIA DESIGN DATA SHEET 088 QAD No.PIN-LES–ELT-1014, R0 Code Coromandel-PA Contract no. 66-6700 Doc. 6700-ELT-0000-EC-0005 Rev. 0 Page 4 OF 7 Operating mechanism a) Type : Stored Energy Spring Charged b) Trip free mechanism to be provided : Yes c) Anti pumping to be provided : Yes, Electrical d) Shunt Trip coil required : No e) No Volt trip required : No f) Duty : OPEN-CLOSE-OPEN operation after failure of power supply 089 Spring charging motor a) Type : Universal b) Rating : W : s , max 50 s 090 Spring charging time 091 Allowable range of control voltage variation 092 Power required for Closing / Tripping 093 Closing / Tripping Number of spare auxiliary contacts (in addition to actual requirement as per scheme) CIRCUIT BREAKER (Cont.) : -15%, +10% / -30%, +10% : / * : min. 2 NO + 2 NC Aux. contact make & continuous current rating at 095 Contact wear monitoring provided : Yes / No 096 Operation counter shall be provided : Yes : / / 097 Mechanical ON/ OFF indicator provided : Yes 098 Mechanical TEST/ SERVICE/ ISOLATED indicator provided : Yes 099 Mechanical emergency trip PB operation shall be possible without opening panel door 100 Interlock shall be provided to prevent opening of CB front door when CB is in service position : Yes 101 In-panel rating for breaker with following name plate rating - 102 : 2500A : 1250A : 3150A : 1600 A : 4000A : 2000A : Specific particular for SF6 CBs : bar b) SF6 quantity per pole : kg 104 105 106 107 Yes d) Maximum leakage allowed : e) Alarm for low SF6 pressure provided : * * : bar * * Yes f) Breaker lockout pressure switch for very low pressure provided 103 : : a) Rated SF6 pressure g) SF6 pressure gauge provided Specific particulars for VCBs a) Vacuum monitoring provided * * A * 630A c) Minimum pressure for safe interruption of rated breaking current HIGH VOLTAGE CONTACTOR * W 094 240V AC / 24V DC / 110V DC * * : Yes * : Yes/ No : : Yes / No * b) Vacuum pressure inside interrupter : * c) Target life of vacuum bottle : d) Envelope material : * e) Surge diverter mounted inside the panel : Yes (For Motor Feeders) ** * f) Type of surge diverter : Gapless Metal Oxide g) Max. permissible value of surge voltage : 2.25 PU Make Type/ Model No. Rated voltage * torr : : : kV * * * A * 108 Rated current (in panel rating at site conditions) : 109 Category of utilization : AC3 (For Motor duty application) & AC6b for Capacitor Duty 110 111 Number of spare auxiliary contacts (in addition to actual requirement as per scheme) Current rating of auxillary contacts at 110V DC : min. 2 NO + 2 NC : : A * We reserve all the rights relating to this technical document © ...2015...ThyssenKrupp Industrial Solutions (India) Private Limited QAD No.PIN-LES–ELT-1014, R0 HIGH VOLTAGE SWITCHGEAR PANELS PART - IIA DESIGN DATA SHEET HIGH VOLTAGE CONTACTOR (Cont.) 112 113 Operating coil Code Coromandel-PA Contract no. 66-6700 Doc. 6700-ELT-0000-EC-0005 Rev. Page 0 : a) Rated voltage : V DC b) Burden while closing / tripping : / VA d) Burden when closed : e) Pick up voltage / Drop out voltage : / % rated voltage Specific particulars for vacuum contactor 5 OF 7 * * VA * * : a) Level of vacuum inside interrupter : * b) Vacuum monitoring device provided : * c) Envelope material : * d) Life of vacuum bottle : * e) Surge diveter mounted insise the panel : * f) Type of Surge Diverter : Gapless Metal Oxide (Motor feeder) g) Type of operating mechanism : Mechanically latched type * * 115 Make : 116 Type/ Model no. : 117 Continuous current rating at site conditions : 118 Rated rupturing capacity 119 Voltage class 121 Type 122 123 124 Potential transformer * Based on Feeder rating * : kA * : kV * : Epoxy resin cast * Class of insulation : Class 'E' or better * Rated insulation level : As per Clause No 31 ; same as switchboard 120 a) Continuous overvoltage factor CTs & PTs HIGH VOLTAGE FUSES 114 b) Short time overvoltage factor : 1.2 1.9 for 30 s (non effectively grounded system) : c) Mounting of line PT : In Incomer CB panel d) Mounting of bus PT : In bus PT panel : As per SLD enclosed in Part-IV 125 Current transformers a) Type : Epoxy resin cast, Bar primary b) Mounting : In stationary part of panel, cable compmt. c) Accuracy class & Burden : As per SLD enclosed in Part-IV d) Rated short time withstand current (Ik) & time (tk) : As per SLD enclosed in Part-IV e) Rated peak withstand current (Ip) : As per SLD enclosed in Part-IV * 126 NOTE : Wherever CBCT is required as per SLD for ground fault protection same shall be supplied by Vendor and installed inside the Panel. 127 Protection relays a) Type : Main Protection Relay : Numerical Trip Ckt Supervision & Tripping Relay : Electromechanical b) Connectivity to SCADA required : Not Envisaged now, in Future: Yes c) Min. no. of binary inputs and outputs : Incomer/ Buscoupler - RELAYS (For numerical relays) d) Loading of software and configuration of relay Outgoing Feeder - 12/8 8/4 : By vendor at factory 128 Tripping Relay : Separate high speed lock-out type with Hand reset 129 Timers : In-built in numerical relay 130 Auxiliary relays : Electromechanical 131 132 Note : CBCT operated Earth leakage protection relay shall have minimum sensitivity of 100 mA ( line side) * * We reserve all the rights relating to this technical document © ...2015...ThyssenKrupp Industrial Solutions (India) Private Limited QAD No.PIN-LES–ELT-1014, R0 Code HIGH VOLTAGE SWITCHGEAR PANELS METERS PART - IIA DESIGN DATA SHEET Coromandel-PA Contract no. 66-6700 Doc. 6700-ELT-0000-EC-0005 Rev. 0 Page 133 Mounting : Flush on panel metering chamber front 134 Accuracy class : As per SLD enclosed in Part-IV 135 Type of meters for a) Incomer : As per SLD enclosed in Part-IV b) Outgoing feeder : As per SLD enclosed in Part-IV 136 Scale (for analogue meters) : 270° taut band 137 Size (for analogue meters) : 96 x 96 138 Connectivity to SCADA required : 6 OF 7 mm No MAKE OF COMPONENTS SWITCHES INDICATING LAMPS, ANNUNCIATOR REMOTE COMMUNICATION 139 140 Communication protocol : MODBUS TCP/IP 141 Communication Port : RS 485 142 Real Time clock : Yes 143 Time stamping resolution : 1 ms 144 Parameters to be transmitted to SCADA/EMS 145 Dual redundant ports : Yes Indicating Lamp Type : Clustered LED : NA 146 147 148 Indicating Lamp Colour : As per SLD 149 Alarm annunciator : As per SLD enclosed in Part-IV 150 Temperature scanner for Trafo/ Motor fdr. : As per SLD enclosed in Part-IV 151 152 Auto- Off - Manual : Rotary cam operated, stay put 153 Remote - Off - Local : Rotary cam operated, stay put 154 Breaker Trip - neutral - close (T-N-C) switch : Pistol grip, spring return to neutral 155 156 Electro mechanical relays : Areva (Schneider) / ABB / Easun Reyrolle 157 Numerical/ Microprocessor based relays : ABB/ Areva (Schneider) / Siemens / GE Multilin 158 Auxiliary relays : 159 Timer Relay : Schneider/ ABB/ Easun Reyrolle ABB/ Easun Reyrolle/ Schneider 160 PT fuse (HV) : Alstom/ Siemens/ S&S/ Eswari/ GE Power 161 HRC LV fuse : L&T / ABB / Siemens 162 Instrument transformers (HV) : Prayog/Pragati/ AE/ CGL/ Schneider 163 Digital Composite Multi function meter : Conserv/ Secure/ Siemens/ L&T/ Satec 164 Analog meters : Automatic Electric(AE)/SIMCO/IMP/ Rishabh/MECO 165 Motor run hour meter : AE/ SIMCO/ IMP/ Rishabh/ MECO 166 Transducers : Minilec/ ABB/ Pepperl+Fuchs/ Rishabh 167 Annunciator 168 Miniature circuit breaker 169 Breaker control switch 170 Control/ Selector switch 171 Terminal block : Minilec/ IIC/ Piri/ AE L&T/ Siemens/ ABB/ Legrand/ GE Power/ Havells/ : Schneider/ Indo Asian : Kaycee/ Areva (Schneider) / Recom/ Vaishno Siemens/ L&T/ Kaycee/ Gem Telergon/ Vaishno/ : Recom/ Switron : Elmex/ Connectwell/ Allen Bradley 172 Internal wiring : BIS compliant 173 Lugs 174 Push Buttons 175 Indication lamps : Dowells/ Jainson/ Comet Siemens/ L&T/ Teknik/ GE Power/ Vaishno/ : Schneider : Teknik/ L&T/ Siemens * * * * * * * * * * * * * * * * * * * * LOADING & DIMENSIONS 176 177 Description a) Circuit breaker with carriage (each type & rating) b) Complete Circuit Breaker Panel c) Complete Vacuum contactor motor feeder panel d) Cable pan/ Adaptor box required below Panel Static Wt.(kg) Dynamic Wt.(kg) * * * * * * Yes/ No Dimensions (mm) (WxDxH) ____ x ____ x ____ ____ x ____ x ____ ____ x ____ x ____ ____ x ____ x ____ We reserve all the rights relating to this technical document © ...2015...ThyssenKrupp Industrial Solutions (India) Private Limited QAD No.PIN-LES–ELT-1014, R0 HIGH VOLTAGE SWITCHGEAR PANELS PART - IIA DESIGN DATA SHEET Code 66-6700 Doc. 6700-ELT-0000-EC-0005 Rev. DESCRIPTION 178 Coromandel-PA Contract no. Page 0 7 OF 7 For review Prints with offer & Approval GA & Foundation drawings indicating Final Documents (Refer Note 194.c,d below) 2 4 6 6 a) Dimensioned outline of panel, (front/ top/ side views), space required in front and rear b) Foundation details incl. pockets for foundation bolts,cutouts and DRAWING & DOCUMENTS requirement of inserts, base frame details, Static/ Dynamic loading c) Cross section view of each type of panel incl. main busbar arrangement d) Panel door front view with layout of equipment 179 List of parts & complete bill of material with makes of components 2 4 180 Detailed SLD showing protection, metering etc. 2 4 6 181 a) Control schematic diagrams of all feeder types b) Control logic diagram for all feeder types - 4 4 6 6 182 Label list - 4 6 183 Wiring diagram with terminal block disposition, ferrule nos. etc. - 4 6 184 Interpanel wiring diagram - 4 6 185 Relay setting document for individual feeder - 4 6 186 Catalogue of all equipment & components 2 4 6 187 Installation, operation & maintenance manual - 4 6 188 Type test certificates 2 4 6 189 Routine Test Certificates - 4 6 190 List of spares 2 4 6 191 Manufacturing bar chart 2 4 6 192 Quality Assurance Plan and Inspection Test Procedure - 4 6 193 194 Notes : a) For items marked " * " thus, data to be furnished / confirmed by vendor. b) For items marked "**" thus, data will be furnished / confirmed by TKIS - India. c) Markup on Final documents from site shall be furnished to Vendor. Same shall be incorporated by Vendor and submitted as As built documents in required number of sets. d) Soft copies of all As-Built/ Final drawings/ documents shall be provided on 2 nos. CDs. We reserve all the rights relating to this technical document © ...2015...ThyssenKrupp Industrial Solutions (India) Private Limited QAD No.PIN-LES–ELT-1014, R0 NUMERICAL RELAY PART - IIB GENERAL DESIGN DATA SHEET Code Coromandel-PA Contract no. 66-6700 Doc. 6700-ELT-0000-EC-0005 Rev. 001 Relay make : 002 Relay model no. : 003 Relay family : 004 Ordering code no. : Page 0 1 OF 2 * * * * 005 Typical application : Feeder protection 006 Region specific default setting : 50Hz, IEC Standard, English language 007 Protection functions : 008 Protection characteristics (Standard) : 009 Number of user defined characteristics : 010 Reset characteristics : 011 Command to control Circuit breaker : * IEC * * * ENCLOSURE & HARDWARE DESIGN 012 013 Housing : Flush mounting 014 Connection terminals : Screw type / plug-in type 015 Dimensions : 016 Weight : 017 IP rating for housing : 018 Human Machine Interface (HMI) 019 a. Type of display : Alphanumeric display b. Mimic required : No c. HMI Language : English (with backlit) LED Indications a. No. of LEDs 020 * * * * * : b. Programmable LEDs required : c. No. of programmable LEDs available : Yes Conformal coating required : Yes System frequency for measuring inputs : 50 HZ * 021 022 023 024 025 Current inputs a. No. of CT inputs : b. Rating of CT inputs : INPUT / OUTPUT 1A Voltage inputs a. No. of VT inputs 026 * * : b. Rating of VT inputs : 110V AC c. Auxiliary supply voltage : 110V DC Binary inputs/outputs a. No. of binary inputs required : As per Control Schematic & spare b. No. of binary inputs available : c. Voltage threshold for binary inputs : d. No. of binary outputs required : As per Control Schematic & spare e. No. of binary outputs available : f. Expandability of binary input/output : g. Spare DI/DO per relay : 2 DI / 2 DO (min.) 027 Analogue input to relay : 4 - 20 mA 028 Analogue output from relay : 4 - 20 mA 029 RTD input to relay * * * * a. Type of RTD : PT-100 b. No. of RTD inputs : 8 nos. We reserve all the rights relating to this technical document © ...2015...ThyssenKrupp Industrial Solutions (India) Private Limited QAD No.PIN-LES–ELT-1014, R0 NUMERICAL RELAY PART - IIB DESIGN DATA SHEET DATA STORAGE, EVENT RECORDING USER PROGRAMMABLE LOGIC 031 032 033 034 Max. number of logical equations programmable Max. number of standard logic functions (AND/OR/NOT gates & timers) in each logic equation Allows user to implement own functions for switchgear See Note-1 automation Language for logic programming Code Coromandel-PA Contract no. 66-6700 Doc. 6700-ELT-0000-EC-0005 Rev. 0 Page 2 OF 2 : * : * : Yes * * : 035 036 037 038 039 Note-1 : User shall be able to map the binary inputs, protection elements, LEDs and binary outputs together in a logical scheme 040 Fault recording / event recording 041 a. Number of faults recorded : b. Number of event recorded : c. User settable event for recording value exceeding specified value Oscillographic fault recording : * * Yes a. Number of oscillographic fault records available : b. Number of cycles of pre-trigger data : c. Number of cycles of post-trigger data : d. Sampling rate : samples per cycle e. Buffer battery provided : Yes a. Real time clock provided : Yes b. Resolution for event log : msec 045 Time synchronizing interface : SNTP 046 Service interface port (Front) : USB serial interface 047 Communication interface port (Rear) : RJ45 048 Communication protocol : MODBUS-TCP/IP 049 Communication port redundancy : Yes 050 Network redundancy protocol : Parallel Redundancy Protocol (PRP) 051 Number of communication ports : 042 * * * * * * Time stamping * * 043 COMMUNICATION INTERFACES 044 052 053 * * Fiber Optic ports a. Mode : Multi mode b. Optical wavelength : 850nm c. Type of FO connectors : ST Parameters to be transmitted to/from SCADA/PMS/EMS PROGRAMMING SOFTWARE 054 055 Software version for logic programming : 056 Software version for relay parameterization : 057 Software version for IEC 61850 configuration : 058 Software version for fault record analysis : 059 Software for graphic visualization : 060 Note:a) For items marked " * " thus, data to be furnished / confirmed by vendor. b) For items marked "**" thus, data will be furnished / confirmed by TKIS - India. c) Data sheet shall be submitted by vendor for each Numerical Relay model type. * * * * * Plant Client Contract Code Document ID PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 Contract No. 66-6700 HIGH VOLTAGE SWITCHGEAR PANELS Part-IIIA - Notes on Method of Offer Submission Rev 00 Page 1. Offer shall be submitted in two parts viz. Technical part and Price part. 2. Technical part shall consist of following: a. Copy of “General Specifications” of this specification with acceptance of all clauses to be indicated by letter 'A’ on right side of the specification sheet with seal of the company and initial of authorised person. Deviations, if any, should be indicated by letter ‘D’. b. Copy of “Design Data Sheet” of this specification duly filled in clearly and legibly in the assigned space against items marked thus '', along with all documents requested with the offer. c. Copy of “Scope of Supply & Schedule of Prices” of this specification marked ‘quoted’ against each item, to confirm that the vendor is making an offer as per break up requested therein. d. “Inspection Test Plan” of this specification with acceptance of all clauses to be indicated by letter 'A’ and duly signed. e. Covering letter enclosing above document. f. Filled up “Compliance Declaration” of this specification with seal of the company and initial of the authorized person. 3. Price part shall consist of following: a. Copy of “Scope of Supply & Schedule of Prices” of this specification with unit rate of each item and total price of each section, with total price of the tender, including supplies and various services as specified or as recommended by the vendor. b. Covering letter enclosing above price part and deviation on commercial terms if any. 4. Both the parts of offer shall be submitted in separate sealed envelope indicating details of offer such as Technical or Price part, enquiry no. and date of submission. PIN-LES–ELT-1014, Rev.0, 12-2015 5. Offer will be evaluated based on above documents only and any other document enclosed with the offer shall not be considered for evaluation of offer. 1 of 1 Plant Client Contract Code Document ID Contract No. PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 66-6700 HIGH VOLTAGE SWITCHGEAR PANELS Part-IIIB - Scope of Supply & Schedule of Prices Rev 00 Page 1 of EQUIPMENT & SERVICES TO BE FURNISHED UNDER THIS SPECIFICATION Sr No Description 1. 11kV Switchboard (2900-SW-11) with following feeders complete with all accessories in accordance with this specification : Sr No 2. Feeder Description a. Incomer feeder type with Line PT 2 b. Transformer feeder 4 c. Bus PT feeder type 1 d. Licensed copy of the relay operating software 1 Lot 6.6kV Switchboard (2900-SW-12) with following feeders complete with all accessories in accordance with this specification : Sr No Feeder Description a. Incomer feeder type with Line PT 1 b. Motor feeder 4 c. Bus PT feeder 1 d. Capacitor Feeder 1 e. Licensed copy of the relay operating software 3. SPARES 3.1 Mandatory spares: Minimum quantity of spares to be supplied along with the switchgear: Sr No PIN-LES–ELT-1014, Rev.0, 12-2015 Quantity 1 Lot Description a. Circuit Breaker Closing coil-11kV 1 No. b. Circuit Breaker Tripping coil-11kV 1 No. c. Circuit Breaker Spring charging motor-11kV 1 No. d. Circuit Breaker Closing coil-6.6kV 1 No. e. Circuit Breaker Tripping coil-6.6kV 1 No. f. Circuit Breaker Spring charging motor-6.6kV 1 No. g. Vacuum contactor HT fuse 6.6kV 3 No. h. PT HT fuse 11kV 3 Nos. i. PT HT fuse 6.6 kV 3 Nos. j. Bus support insulator 11kV 4 Nos. k. Micro switch (1 NO + 1 NC) 4 Nos. l. Aux. contact block (4 NO + 4 NC) 4 Nos. Unit Rate Total 2 Plant Client Contract Code Document ID Contract No. PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 66-6700 HIGH VOLTAGE SWITCHGEAR PANELS Part-IIIB - Scope of Supply & Schedule of Prices Rev Sr No Quantity m. Control fuses 6 Nos. n. Indication lamps 10 Nos. o. Glasses for indicating meters 4 Nos. p. Control terminal blocks 10 Nos. q. Vacuum Contactor Closing coil 1 No. r. Vacuum Contactor Tripping coil 1 No. 3.2 Commissioning spares as required to be included in Sr. no. 1 above and supplied by vendor as required. Note: Vendor shall furnish separately a complete list. 3.3 Recommended spares for two years trouble-free operation. Note: Vendor shall furnish separately a complete list of recommended spares with their unit rate indicated alongside. 4. TOOLS & TACKLE 4.1 a. Circuit breaker racking handle 2 b. Manual spring charging handle 2 c. Earthing trolley (for cable earthing) 2 d. Earthing trolley (for bus earthing) 2 e. Circuit breaker handling trolley 2 4.2 Note: Vendor shall furnish separately a complete list of recommended tools & tackle with their unit rate indicated alongside. 5. Services of a competent engineer to supervise the installation, testing and commissioning of all equipment supplied by the vendor (including numerical relay programming) for 2 no. visits and 10 no. of total working days. 6. PIN-LES–ELT-1014, Rev.0, 12-2015 Description As required 00 Page Unit Rate 2 of Total Included in Sr. No.1 & 2 above Lumpsum Unit rate for extra visit UR Unit rate for extra working days UR TESTING & INSPECTION Tests as specified in Part-V of this specification shall be performed in presence of Purchaser’s representative, if so desired by the Purchaser. i. Routine tests ii. Type test All panels Included in 1 & 2 UR TOTAL PRICE OF THIS TENDER INCLUDING ALL ABOVE ITEMS. Rs. 2 Plant Client Contract Code Document ID PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 Contract No. 66-6700 HIGH VOLTAGE SWITCHGEAR PANELS Part-IV - Drawings & Documents Enclosed Rev 00 Page 1 Following drawing(s)/document(s) is/are enclosed: Sr. No. 1. PIN-LES–ELT-1014, Rev.0, 12-2015 2. Dwg. No./ Doc. No. Description Size No. of Sheets 6700-ELT-0000-FA-0002 Detailed HV Single Line Diagram A0 1 ANNEXURE -I 6700-ELT-0000-FS-0001 Power & control schematic : HV A4 22 23 of 1 We reserve all the rights relating to this technical document © ...2015...ThyssenKrupp Industrial Solutions (India) Private Limited HIGH VOLTAGE SWITCHGEAR PANELS PART - V INSPECTION TEST PLAN A Type Tests i Dielectric tests a) 1 min. power freq. voltage withstand test Code Coromandel-PA Contract no. 66-6700 Doc. 6700-ELT-0000-EC-0005 0 Page Scope of Inspection Rev. Reference Documents Tests QAD No.PIN-LES–ELT-1014, R0 Sample size IS 3427, IS 12729 IEC 62271 Vendor Client / TKIS India/ Third Party PPROTO R b) Lightning Impulse voltage withstand test -do- PPROTO R Temperature Rise Test Measurement of the resistance of the main circuit and auxiliary circuits Short time withstand and peak withstand current test -do- PPROTO R -do- PPROTO R PPROTO R v Verification of breaking and making capacity -do- PPROTO R ii iii iv -do- For each rating vi Mechanical Operation Test IS 3427, IEC 62271 PPROTO R vii viii Verification of IP protection Internal Arc Test -do-do- PPROTO PPROTO R R ix Millivolt drop test across breaker contacs and between terminals when housed in cubicle -do- PPROTO R B Routine Tests (All Panels) i Visual Check of Tag nos., paint shade and finish, busbar marking/ sleeving, shrouding, identification/ location of components GA drawings P W ii Dimensional check incl. operating height, busbar dimensions, clearances, space for cable termination, flange and busbar dimensions for connection to busduct etc. Checking of sample busbar assembly GA drawings P W iii Verification of busbar dimensions and support arrangement with respect to type tested panel drawings GA drawings P W iv Bill of material including make of component Check GA drawings P W v Interchangeability of circuit breakers & outgoing feeder modules of similar rating and type. - P W - P W - P W - P W Vendor documents P R - P R vi vii viii ix x Pressure switch operation of SF6 breakers Mechanical operation of circuit breakers, outgoing feeder modules, auxiliary switches, manual devices, etc. Operation of circuit breakers, vacuum contactors, relays under normal and minimum allowable voltage. Closing and opening time of breaker at normal and minimum allowable voltage CT polarity tests 100% xi Operation checks for all control functions and safety interlocks Schematics P W xii Relay operation check through secondary injection Vendor documents P W xiii Checking of meters through secondary injection Vendor documents P W xiv High Voltage Test IS 3427, IS 12729, IEC 62271 P W -do- P W - P W P W P W xv xvi xvii xviii Insulation Resistance Test of main, control and auxiliary circuit before and after HV test Verification of relay software loading and programming Verification of loose components, accessories, spares as per PO Verification of test certificates for bought out items/ components - Min. 10% and one of each type 1 OF 1 Remark See note 2 100% 100% - Notes: 1) W = Witness, R = Review, P = Perform on project equipment, PPROTO = Perform on prototype. 2) Temperature rise test shall be performed at rated current with diversity factor = 1. One breaker panel (preferably buscoupler) shall be included in the test and the breaker shall carry the full test current. Plant Client Contract Code Document ID Contract No. PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 66-6700 HIGH VOLTAGE SWITCHGEAR PANELS Part-VI - Compliance Declaration Rev 00 Page 1 Compliance Declaration Please note that vendor shall indicate his replies to the following points without which the offer shall be liable for rejection. Deviations if any from this specification shall be listed in the enclosed format (List of Deviations) indicating the applicable specification clause. The vendor will be made liable for full compliance with the specification requirements, if deviations are not listed in “List of Deviations” as it will be deemed as “No deviation”. S.NO DESCRIPTION 1. Confirm that all deviations against this specifications are consolidated under “List of Deviations”. Deviations mentioned elsewhere will not be taken into consideration. Confirm that there is no discrepancy in the technical details outlined in the specification and the technical bid data. Relevant Catalogues/ literature giving specifications for all models offered including sizing data is enclosed with the offer. Relevant Catalogues/ specifications of all bought out items are enclosed with the offer. Quoted for “Spare parts recommended for 2 years continuous trouble-free operation” along with listing Quoted and offered recommended Commissioning spares along with listing Quoted for “Mandatory spares” 2. 3. 4. 5. 6. PIN-LES–ELT-1014, Rev.0, 12-2015 7. (Signature of Vendor) Name : Designation : Date : EXPECTED REPLY No Deviation CONFIRMATION BY VENDOR REMARKS No Discrepancy Yes Yes Quoted Quoted Quoted (Company Seal) of 2 Plant Client Contract Code Document ID Contract No. PA plant Coromandel International Limited Coromandel-PA 6700-ELT-0000-EC-0005 66-6700 HIGH VOLTAGE SWITCHGEAR PANELS Part-VI - Compliance Declaration Rev 00 Page LIST OF DEVIATIONS Doc. No: Sr. Clause No. No Page No PIN-LES–ELT-1014, Rev.0, 12-2015 (Signature of Vendor) Name : Designation : Date : Subject / Deviation Description (Company Seal) 2 of 2 ANNEXURE - I 11kV Board INCOMER LINE PT BUS PT AUX SUPPLY PAGE 1 /9 11kV Board INCOMER LINE PT BUS PT AUX SUPPLY PAGE 2 /9 11kV Board INCOMER LINE PT BUS PT AUX SUPPLY PAGE 3 /9 11kV Board INCOMER LINE PT BUS PT AUX SUPPLY PAGE 4 /9 11kV Board INCOMER LINE PT BUS PT AUX SUPPLY PAGE 5 /9 11kV Board INCOMER LINE PT BUS PT AUX SUPPLY PAGE 6/9 11kV Board INCOMER LINE PT BUS PT AUX SUPPLY PAGE 7 /9 11kV Board INCOMER LINE PT BUS PT AUX SUPPLY PAGE 8 /9 11kV Board INCOMER LINE PT BUS PT AUX SUPPLY PAGE 9 /9 11kV Board TRAFO OUTGOING PAGE 1/3 11kV Board TRAFO OUTGOING PAGE 2/3 11kV Board TRAFO OUTGOING PAGE 3/3 6.6kVBoard Incomer Line LT BUs PT Aux Supply PAGE 1/5 6.6kVBoard Incomer Line LT BUs PT Aux Supply PAGE 2/5 6.6kVBoard Incomer Line LT BUs PT Aux Supply PAGE 3/5 6.6kVBoard Incomer Line LT BUs PT Aux Supply PAGE 4/5 6.6kVBoard Incomer Line LT BUs PT Aux Supply PAGE 5/5 6.6kVBoard MOTOR PAGE 1/2 6.6kVBoard MOTOR PAGE 2/2 6.6kVBoard CAPACITOR FEEDER PAGE 1/3 6.6kVBoard CAPACITOR FEEDER PAGE 2/3 6.6kVBoard CAPACITOR FEEDER PAGE 3/3