PART - II (2nd DAY) EXECUTION OF BUILDINGS Each item of work shall be executed according to relevant standard specification number as described in the Andhra Pradesh Standard Specifications (APSS) and Indian Standard (IS) Specifications. Whenever these are silent in any aspect, the construction and completion of works shall confirm to sound engineering practice as approved by Engineer in charge. All works shall be done according to the detailed drawings and specifications. The works shall be set to the highest precision of dimensions, levels, grades and lines as per designs and drawings using precise scientific equipment and measuring instruments. All the materials shall be new and of the kinds and qualities described in contract. All materials used and work done shall be subject to approval of the Engineer-in-charge. MATERIALS Water: Water should be clean, fresh and free from all chemicals, oils, salts and deleterious materials and vegetable growth. Water has to meet requirements mentioned in Cl.5.4 of IS: 456-2000. Storage of water should be sufficient and adequate for the regular consumption of works for the use of labour onsite Earth: Soil used for filling shall be free from all garbage, organic and vegetable growth including roots, weeds etc. Expansive soils having high swelling index eg. Black cotton soils should not be used for basement filling. Sand (Fine Aggregate): Sand to be used shall be composed of hard siliceous material and shall be clean, sharp, hard, strong and angular type. Sand shall be clean river or pit sand of approved quality and free from salts, earth, dust, or other impurities. • Sand for Plain and Reinforced Cement Concrete shall confirm to IS: 383-970. • Sand for Mortar shall confirm to IS: 2116-1980 • Sand for Plastering shall confirm to IS:1542-1992 • For PCC & RCC Zone-I to III Sand shall be used. • For PCC & RCC quantity of sand passed through 600µ sieve should be less than 80%. Coarse Aggregate: The coarse aggregate shall be from hard granite crushed stone confirming to IS 383:1970. The pieces of aggregate shall be non porous, hard, strong, durable, clean and free from clay, rounded in shape and shall have granular or crystalline non powdery surfaces. The aggregate shall be well graded. Tests where required shall be carried out in accordance with IS:2386-1963. Cement: The following cements may be used with prior approval of the competent authority. • Ordinary Portland Cement 43 Grade • Ordinary Portland Cement 53 Grade • Portland Pozzolana Cement 53 Grade IS:8112 IS:12269 IS:1489 The quality of cement shall be in conformity to the performance characteristics given in IS:8112-1989. The cement should be delivered to the site in sound dry bags and shall be stored properly. The cement shall be procured in standard packing (50 kg per bag) from the authorized manufactures. Cement shall be got tested for all the tests as directed by the Engineer-in-charge atleast once in a month in advance before the use of cement bags bought and kept at site godown. Cement bags required for testing shall be supplied by the contractor at free of cost. Cement should not be placed directly on cement mortar or cement concrete flooring . A wooden platform or false floor a sheet of water proof paper should be provided. As a rule cement should not be stored longer than three months Bricks: Bricks for masonry shall be common burnt clay building bricks having a minimum crushing strength of 40 kg/sq.cm and shall confirm to the relevant specifications of IS:1077-1995. They shall be sound, hard and thoroughly well burnt, but not over burnt, with uniform size having rectangular faces with parallel sides and sharp straight right angled edges and be of uniform colour with fine compact uniform texture. Bricks shall be free from flaws, cracks and nodules of free lime. Water absorption after 24 hours immersion in cold water shall be not more that 20% by weight. They shall not absorb more than 10% by weight after immersion for six hours. They shall emit a clear metallic ringing sound when struck by a mallet and shall not break when dropped on their face, from a height of 60cm. Samples of bricks bought to the site shall be tested periodically for compression and other tests in accordance with IS:3495 STEEL Mild Steel shall conform to IS:432-1982, High Yield Steel Deformed bars shall conform to IS:1786-1985 and binding wire shall conform to IS:280. Mild Steel / HYSD Steel shall be procured only from the reputed units manufacturing the steel to the prescribed specifications of Bureau of Indian Standards or equivalent and licensed to affix ISI or other equivalent certifications, marks and acceptable to Engineer-in-charge. The diameter and weights of steel should be as per IS:1786-1985. 6Ø - 0.22 kg/m 8Ø - 0.39 kg/m 10Ø - 0.62 kg/m 12Ø - 0.89 kg/m 16Ø - 1.58 kg/m 20Ø - 2.47 kg/m 25Ø - 3.85 kg/m 32Ø - 6.31 kg/m The contractor shall furnish the samples for testing each batch and consignment along with the test certificates issued by the vendors to the Engineerin-charge immediately after receipt of the steel for verification and testing. No steel procured by the contractor shall be used in any work until the Engineer-in-charge has given notice that the test results are satisfactory. Reinforcement shall be free from pitting due to corrosion and free from loose rust, dirt, dust, mill scale, paint, oil, grease, adhering earth etc. Erected and secured reinforcement after fabrication shall be inspected and approved by the Enginer-inCharge prior to placement of concrete. WOOD The wood shall be well seasoned, uniformly colored and shall be free from knots, cracks, shakes, splits, cross grains etc. The wood shall be durable and reasonably straight grains Moisture content of wood used for frames of doors and windows in coastal area shall be 16% to 18%. Moisture content of wood used for frames of doors and windows inland area shall be 14% to 15%. Moisture content of wood used for shutters of doors and windows in coastal area shall be 15% to 16%. Moisture content of wood used for shutters of doors and windows in inland area shall be 12% to 14% WORK EXECUTION Marking • Clear Jungle, Garbage if any and Level the Surface • Study & Keep ready Architectural & Structural Drawings while giving marking for the Structure. • Use Precise Tap for Marking. • Prefer Total Station for marking Big Size Structures. • Mark out Peripheral Center Line of the Structure on four sides duly verifying both the diagonal measurements. • Mark out internal Center Lines and verify the all internal diagonal measurements in both the ways. • Mark All Column Center Points. • Provide Base Lines & Bench Marks on Four Sides. • Maintain Bench Marks throughout the period of Construction without causing any disturbance to them. Earth Work Excavation for Foundations Mark out the Dimensions of Footing / Pile Cap Verify whether the Centre of all Foundations Coincide with the Center of the Columns. Execute Earth Work Excavation as per APSS 308 Execute E/w manually or by mechanical means as per the directions of the Engineer-in-Charge. See that offset of the trench around the center of the column in four directions shall be uniform. All foundation works are to be carried out in dry and workable condition. Hence, dewatering arrangements are to be made if raised water table is observed in foundations. Shoring, Sheeting, Planking, Strutting etc. arrangements shall be made as per the directions of the Engineer-inCharge. Excavated earth shall not deposit at the edges of foundations. Min. clearance to provide walk way to workers shall be maintained. PILE FOUNDATION Pile foundations are normally used in Expansive Soils, Cohesive Soils with low bearing capacity. Pile foundations with Under Reamed Piles commonly used for normal buildings. Piles shall be installed as accurately as possible according design and drawings vertically. Angular Deviations should not exceed 1.50% Position Deviation should not exceed D/6 or 75mm whichever is less Under Reamed Pile Foundations shall be executed in accordance with IS:2911 Part-3) – 1980. Minimum Length of Pile should be 3.50m Reamer (Bulb) Diameter Du shall be 2.50 time Diameter of Stem (d). Up to 300 mm dia. Spacing Bulbs should not exceed 1.50 times Diameter of Bulb (1.50 Du). For Piles Diameter greater than 300mm Spacing Bulbs should not exceed 1.25 time Diameter of Bulb. The top most bulb should be at a distance of 1.75m from Natural Ground Level. The Minimum Clearance between bottom of Pile Cap embedded in soil and bulb should be 1.50 times diameter of bulb. Distance between two Under Reamed Piles should be less than 1.50 time Diameter of Bulb. CONCRETING Plain and Reinforced Cement Concrete items shall be executed in accordance with APSS 402 & 403 and IS 456:2000 No concrete shall be cast in the absence of the works in charge engineer. All the materials used should be of good quality and in accordance with respective APSS and IS Codes. All concrete works shall be built to the lines, grades and dimensions as per the designs and drawings. DESINGN MIX & NOMINAL MIX Design Mix is preferred to Nominal Mix. If the Design Mix Cannot be used for any reason on the work for Grades of M20 or lower, Nominal Mix may be used with the permission of the Engineer-in-Charge However, it is likely to involve a higher content of Cement in Nominal Mixes. Process of Mix Design takes a minimum period of 28 days. Hence, for getting Mix Design concrete ingredients shall be furnished well in advance. Mix Design done earlier not prior to one year may be considered adequate for later work provided there is no change in source and the quality of materials. The design mix shall be got approved by the Engineer-in-Charge before proceeding with the concreting. The mix shall be designed to produce the grade of concrete having required workability and Characteristic Strengths. Target mean strength of the concrete mix should be equal or more than fck + 1.65 times Standard Deviation. Standard Deviation for M20 & M25 Grades is 4 and for higher grades it is 5. Whenever the grade of concrete such as M20, M25, M30 etc. is specified, it shall be Contractor’s responsibility to ensure the minimum compressive strength (crushing strength) stipulated for the respective grade of concrete is obtained at works. The contractor shall maintain the test results on regular basis as indicated in IS 456:2000. In all cases, the 28 days compressive strength specified shall be the criterion for acceptance or rejection of the concrete. WATER - CEMENT RATIO Water is key ingredient of Concrete Excess Water result in Weak Concrete Less Water result in Unworkable Concrete Quantity of Water used shall be as specified in Mix Design. To obtain required Workability Plasticizers shall be used as per the Directions of the Engineer-in-Charge. CONCRETE SLUMP Recommended Slumps for PCC / RCC Plain Cement Concrete:50 to 75mm RCC Piles: 100 to 150mm RCC Footings: 10 to 25mm Columns & Beams: 25 to 40mm Roof Slabs (Thin sections): 40 to 50mm Sections with Congested Steel: 40 to 50mm MIXING CONCRETE For Design mix where site mixing is permitted shall be with concrete mixtures with weigh batching scale. Materials shall be weighed and batched in mechanical weigh batchers as per specified proportions of the approved design mix. Materials requiring Volumetric mixing, wherever permitted should be measured separately in boxes of appropriate size before being mixed in the specified proportions. The concrete shall be mixed in machine mixer until the mixture is of uniform color & consistency and in no case , for less than two minutes. Mixer should not be loaded beyond its rated capacity. Speed of the Mixer should be run at the manufactured rating. CONCRETE PLACING Concrete shall only be placed after the Engineer has inspected the shuttering and reinforcement. After mixing, the concrete shall be transported from the mixer to the position of placing as rapidly as possible by appropriate mean without causing separation and segregation of concrete, maintaining the required workability. Concrete shall be placed and compacted before initial setting of concrete commences and should not be subsequently disturbed. Concrete shall be deposited as nearly as practicable directly in its final position and shall not be re handled in a manner which will cause segregation and loss of materials, displacement of reinforcement, shuttering and embedded inserts or impair its strength. Concrete shall be placed in the shuttering by approved implements and shall not be dropped into place from a height exceeding 1 meter or handled in a manner which will cause segregation. Concrete shall be deposited in successive horizontal layers to a compacted thickness not more than 45 cm. These shall be placed as rapidly as practicable to prevent formation of cold joints or planes of weakness between each succeeding layer within the pour. When concrete is conveyed by Chutes, the plant shall be of such size and design as to ensure practically continuous flow. Slope of the chute shall be so adjusted that the concrete flows with the use of any excessive quantity of water and without segregation of its ingredients. The delivery end of the chute shall be as close as possible to the point of deposit. COMPACTION OF CONCRETE All concrete shall be compacted to produce a dense homogeneous mass. Prior to beginning of concrete placement the contractor shall make ready sufficient number of properly operating Vibrators and Operators. Concrete after depositing should be compacted thoroughly by means of mechanical vibration Vibrations shall conform to IS Specifications. Vibrators of Surface (Plate Vibrators), Immersion Type (Needle Vibrators) shall be used. Concrete shall be thoroughly surged around the reinforcement, around embedded fixtures and into corner of form work. The Hardened concrete shall be free from voids and cavities. Over Vibration result in Segregation of Ingredients of Concrete. Under Vibration result in Voids and Cavities in Concrete. Vibrators shall be operated by experienced ment. Immersion vibrators shall be inserted at points not more than 45 cm apart. Immersion vibrators shall be withdrawn slowly. Blending and melding of the concrete between successive layers shall be ensured. Vibrators contact with Reinforcement and Shutters. Finishing & Protection: The finished surface shall be uniform in texture and free from screed marks or other imperfections. The concrete surface shall be consolidated, smooth screeded and leveled to produce even surface. The fresh concrete shall be protected from defacements, damage due to construction operations, rain, sun and winds and from foot traffic until concrete has hardened. The prepared surface shall be approved by the Engineer-in-Charge. CURING Curing is the Maintenance of a satisfactory moisture content and temperature for complete hydration in concrete for a period of time immediately following placing and finishing so that desired properties may develop. Curing has a Strong Influence on the properties of the Concrete. Proper Curing increase Strength, Durability, Water Tightness, Abrasion Resistance, Volume Stability and Resistance to Freezing & Thawing. All exposed faces of concrete shall be kept continuously moist for a minimum period of 28 days by spraying water at regular intervals or by covering with gunny bags which shall be constantly sprinkled with water. For curing floors, flat roofs, concrete pavements and other level surfaces the ponding method of curing shall be adopted • • • • • • • • CENTERING Form work design, details and tolerances shall be confirmed to IS:14687 and IS 456:2000. Only Steel form centering shall be used. Steel Forms with Surface Dents, Bulges, Undulations or Holes shall not be used Form work shall be substantially and rigidly constructed of steel and shall be true to dimensions. Form work shall be constructed to confine and shape the concrete to the required shape, lines and dimensions described. Shuttering shall be erected true to line and securely braced, cross braced, strutted and supported with props at close intervals to prevent deformation under the weight of pressured wet concrete and constructional loads, wind pressure and other forces. The face of form work in contact with concrete shall be cleaned and treated with Release Agent. All Shuttering joints shall be sufficiently tight to prevent leakage of cement slurry. • All faulty joints of centering shall be adequately caulked (filling & sealing joints) • Shuttering joints shall be closed with • Standard Shuttering Oil, Engine Oil or Filtered Waste Oil free from Carbon particles and impurities shall be used as Release Agent. • Release agents should be applied so as to provide a thin uniform coating to the Forms without coating the reinforcement. • Stripping Time of Form Work as Per IS 456:2000 • Columns & Beams Vertical Forms 16 to 24 h • Soffit Form Work to Beams: 7 days • Props to Beams (up to 6.00m span) 14 days • Props to Beam (above 6.00m span) 21 days • Props to Slabs (up to 4.50m span) 7 days • Props to Slab (above 4.50m span) 14 days. REINFORCEMENT FOR RCC WORKS Reinforcement shall be of High Yield Strength Deformed (HYSD) bars of grade Fe 415 / Fe 500 confirming to IS 1786-1985. Reinforcement shall be steel and shall be free from corrosion, oil grease, paint and dirt at the time of fixing in position and subsequent concreting. Reinforcing steel bars shall conform accurately to the sizes, dimensions and shapes given as per designs and drawings. Bars shall be bent cold to the specified shape and dimensions and the bars shall be hooked or bent accurately and placed in exact position as per designs and drawings. Bars of full length shall be used. Reinforcement shall be lap jointed or spliced only in unavoidable. The overlaps shall be staggered for different bars and located at points along the span where neither shear or bending moment is maximum. Not more than 33% of the bars as specified in drawing shall be lapped at one section. The Reinforcement shall be securely held in position and bound together tight by annealed binding wire and b y using stays, blocks or metal chairs, spacers, hangers or other approved devices at sufficiently close intervals. Reinforcement shall not be allowed to sag between supports. Layers of bars shall be separated by spacer bars or other approved devices. Stirrups, Ties, Links should be securely wired to the main reinforcement. It shall be ensured that the bars are not displaced during concreting or any other operation over the work. All bars protruding from concrete and to which other bars are to be spliced and which are likely to be exposed for an indefinite period shall be protected by thick coat of neat cement grout to prevent from corrosions. Reinforcement chairs shall be used to separate bottom steel from the top steel and to maintain corrective effective depth. Reinforcement chairs shall be slightly lesser size so as to accommodate the chair underneath the top steel and after allowing the required covers to the top and bottom steel. The chair shall be minimum of 450mm long and should have legs bent in opposite directions to ensure stability. The chairs shall be placed on cover block so that the legs do not stick out once the shuttering is removed. COVER BLOCKS Before concreting, cover blocks shall be fixed in all RCC works to separate the reinforcement from the shuttering so that when the concrete is set the reinforcement is well within the concrete section at a distance from the outer face with specified cover to reinforcement. Cover blocks shall be reasonably good for using appropriate grade of RCC work. The mortar for preparing cover blocks shall be at least be of proportion 1:2. Cover blocks shall be prepared on clean and level platform by separating the mortar in moulds of required size and depth. When the mortar is still green strands of tying wire shall be inserted into each block. This wire is useful for tying the block to the reinforcement. After 24 hours the cover blocks shall be removed from the mould and cured for about seven days. A properly made cover block does not get crushed when the reinforcement is tied over it and during the concreting work. Clear Cover to Slab Reinforcement: 15mm Clear Cover to Beam Reinforcement: 25mm Clear Cover to Column Reinforcement: 40mm Clear Cover to Footing Reinforcement: 50mm RCC SLABS The RCC Slab laid should leak proof. After centering is removed and curing period is over the slabs shall be put to test by stagnating water of 15 cm depth for one week and watched carefully to test the leakages in any. If there are any leakages, the contractor shall immediately rectify the same at his own cost and again test the same to see that there are no leakages. No payments will be made to the contractor on this account either for testing or for rectification thus carried out. The officer observing the leakage test shall issue a certificate to this effect before final bill is made. After observing for two rainy seasons as defect liability period if the roof or floor is found to be perfectly leak proof and no moisture or dampness is seen underneath at ceiling the slab, the contractor can ask for refund of Deposits from the department. The variation thickness of RCC Roof slab due to varying spans or special covering materials should not affect the general roof surface which should be uniform. For all slabs to be laid to be laid MS hooks to be provided as directed by the department for fixing fans and lights etc. PVC pipes have to provided as directed by the department in slab at the specified places for running electrical wiring. BASEMENT FILLING Basement shall be filled with suitable materials. Cohesion less materials such as sand or stone dust are suitable materials for basement filling. Basement filling shall be done in layers not more than 15cm thickness. Consolidation shall be done by watering and ramming until maximum density is achieved. BRICK WORKS All bricks to be used in the work shall thoroughly soaked in water before use to prevent absorption of water from the mortar. The bricks shall be set in cement mortar (1:6) proportion for basement and (1:8) proportion for super structure by adopting a proper bond (preferably either English Bond or Flemish Bond) throughout the wall. The walls shall be taken up truly plumb. All courses shall be truly horizontal (level) and truly vertical. Vertical Joints of consecutive courses shall not come directly over one another. Vertical Joints in alternate course shall come direct over one another. Joints shall be fully filled with mortar and racked. Each brick shall be laid with full joints of cement mortar on it’s bed, ends and sides in one operation. No feeding of mortar by using excess water shall be allowed. Half Brick masonry shall be constructed only in stretcher bond Reinforcement for half brick walls shall be in the form of MS bars and shall be of specified quantities. Reinforcement for half brick walls shall be well embedded in cement mortar at every third course and half the joint thickness of mortar shall first be laid and the other half laid after the reinforcement is placed. The free ends of the reinforcement wherever possible shall be pegged in the mortar joints of main brick walls. Where the supports are not monolithic with beam or slab the bearing surface shall be plastered with Cement Mortar (1:3) with a craft paper laid over the plaster before laying the concrete. The Vertical face of the masonry rebate at bearings shall be plastered smooth with CM(1:3). For beams the craft paper shall be continued to the sides, folding the paper neatly to the plastered vertical face of the masonry opening. Lintel slabs shall allow resting on PCC Bed Blocks on either side of opening. PLASTERING The surface shall be prepared by roughening of the back ground and racking joints. The surface of the wall shall be kept wet for 2 hours before plastering Guides (patches of 15cmx15cm) of required thickness at not more than 2.00 meters intervals horizontally and vertically shall be applied over the entire surface truly in the plane and truly plumb to serve as guides. Plaster shall be started from the top and worked down towards plinth. The work shall be tested frequently with a plumb bob and straight edge. Mortar shall be dashed and pressed over the surface and then brought to smooth and uniform surface by means of float and trowel. The plaster shall be well pressed into the joints. All corners, junctions and arises shall be brought truly to a line and plumb. The finished surface shall be watered for a period of at least 10 days. WATER PROOF PLASTER OVER ROOF On the clean wet surface of the concrete slab, before it has set, a layer of cement plaster shall be laid to give an average depth of 20mm over the concrete. The mortar to be used shall be of CM(1:3) proportion mixed thoroughly with a standard water proofing material with water repelling properties to ensure non absorption. Gauges should be put on the floor about 3.00 metes apart to ensure even thickness. Plastering must be done in squares and thread lining at interval 45cm x 45cm shall be done to avoid cracks. After completing plastering it shall be covered with two inches of grass or saw dust and kept wet for three weeks. Recommended Window sizes & sill heights S.No. Sizes Sill heights 1 Bed Room 1000mm x 1300mm / 1200mm x 1300mm 510 mm 2 Living Room 1000mm x 1300mm / 1200mm x 1300mm 640 mm 3 Dining 1000mm x 1300mm / 1200mm x 1300mm 640 mm 4 Kitchen 1000mmx600mm / 1200mmx600mm 1000 mm 5 Bathroom 600mm x 600mm 1300 mm Recommended Door Sizes 1 External Doors : 1200MM X 2100 MM - with Double Shutters 2 Internal Doors in Living Rooms : 1000mm x 2100mm - with Single Shutter 3 Internal Doors in Bed Rooms : 900mm x 2100mm - with Single Shutter 4 Internal Doors in Kitchen : 800mm x 2100mm - with Single Shutter 5 Bath Room Doors : 800mm x 2100mm - with Single Shutter REQUIREMENT OF PARTS OF BUILDING Heights & Distances 1 Minimum Plinth Level above NGL 450 mm 2 Minimum Ceiling Height (Normal Buildings) 3000 mm 3 Minimum Ceiling Height (Educational Buildings) 3600 mm 4 Minimum Head Room under False Ceiling 2400 mm 5 Minium Ceiling Height (Bath Rooms) 2000 mm 6 Parapet Wall Minium Height 1050 mm 7 Top of Railing in Balcony 900 mm 8 Top of Staircase Railing 850 mm 9 Kitchen Platform Height 800 mm 10 Clearance Below Kitchen Platform Slab 680 mm 11 Height of Kitchen Sink Top Edge 740 mm 12 Front Top Edge of Wash Basin 850 mm 13 Lip of Urinal for Gentlemen 700 mm 14 Top of Urinal Partition 1300 mm 15 Bottom Edge of Mirror behind Wash Basin 1300 mm Heights & Distances 16 Bottom of Shower Rose 2000 mm 17 Stop Cock for Shoer Rose 1000 mm 18 Tap near Water Closet 220 mm 19 Tap in Bath Room 700 mm 20 Tap near Kitchen Sink 400 mm 21 Projection of Tap in Bath Room 200 mm 22 Projection of Shower in Bath Room 500 mm 23 Distance b/n Center of WC and Wall 450 mm 24 Minium Space in front of WC 600 mm 25 Minimum Space in front of Wash Basin 650 mm 26 Bottom of Switch Board 1350 mm 27 Bottom of AC Socket 1800 mm 28 Bottom of Distribution Board 1800 mm 29 Bottom of Ceiling Fan 2600 mm 30 Min. Clearance between Ceiling & Ceiling Fan 300 mm REQUIREMENT OF PARTS OF BUILDING STAIR CASES I) II) III) IV) Minium Width : For Residential Buildings : 1000 mm For Assembly Buildings : 1500 mm For Education Buildings : 1500 mm For Institutional Buildings ( Hosptial Etc.) : 2000 mm Minimum Tread Width : For Residential Buildings : 250 mm For Other Buildings : 300 mm Maximum Riser Height : For Residential Buildings : 190 mm For Other Buildings : 150 mm Maximum No. of Risers per 1 Flight : 15 No. SIZES OF RAIN WATER PIPES FOR ROOF DRAINAGE Average Rate of Rainfall in mm/h Diameter of Pipe Roof Area in sq.meters 50 sq.m 75 sq.m 100 sq.m 125 sq.m 150 sq.m 200 sq.m 50 13.40 8.70 6.60 5.30 4.40 3.30 65 24.10 16.00 12.00 9.60 8.00 6.00 75 40.80 27.00 20.40 16.30 13.60 10.20 100 85.40 57.00 42.70 34.20 28.50 21.30 125 - - 80.50 64.30 53.50 40.00 150 - - - - 83.60 62.70 i) Recommended Slop of Terrace Slab: 1 in 100 or Steeper ii) Recommended Spacing of Outlet Pipes: 6.00 meters c/c iii) Recommended Slab Projection Beyond Face of Wall: 300 mm SANITARY & WATER SUPPLY S.No. Description of Item APSS Specification No. IS Code 1 Glazed Stone Pipes (Sanitary Lines) 1301 & 1318 IS: 651 & IS: 4127 2 SWR Pipes (Sanitary Lines) 1307 & 1323 IS: 13592 & IS: 7634 3 CPVC (Water Lines) - IS: 15778 4 Sanitary Inspection Chambers 1325 IS: 1742 5 Glazed Fire Clay Sanitary Appliances 1326 IS:771 RECOMMENDED SLOPES FOR SELF CLEANING VELOCITY 1 For 100mm Dia. Pipes 1 in 40 2 For 150mm Dia. Pipes 1 in 60 3 For 250mm Dia. Pipes 1 in 90 IMPORTANT IS CODES - BUILDING ITEMS S.No. 1 2 3 4 5 6 7 8 9 10 11 12 Specification Cement - 43 Grade Cement - 53 Grade Coarse Aggregates Fine Aggregates Sand for Mortar Sand for Plastering Common Burnt Clay Bricks Fly Ash Bricks Aerated Autoclaved Cellular Concrete Blocks Mile Steel HYSD Steel Structural Steel IS Code IS 8112:1989 IS 12269:1989 IS 383:1970 IS 383:1970 IS 2116:1980 IS 1542:1992 IS 1077:1992 IS 12984:2002 IS 2185 (3): 1984 IS 432:1982 IS 1786:1985 IS 226:1975 S.No. Specification IS Code 13 Detailing Reinforcement IS 5525: 1969 14 Ceramic tiles IS 13712:2006 15 Water IS 3025:1986 16 Under Reamed Foundation IS 2911(3): 1980 17 Shallow Foundations IS 1904:1986 18 Plain & Reinforced Cement Concrete IS 456:2000 19 Concrete Mix Design IS 10262:1982 20 Concrete Admixtures IS 9103:1999 21 Brick Masonry with Clay Bricks IS 2212:1962 22 Methods of Measurements IS : 1200 23 Architectural Drawings IS 962:1989 STANDARD SPECIFICATION FOR BUILDING ITEMS S.No. Specification APSS Specification I MATERIALS 1 Common Burnt Clay Bricks 102 2 Sand 110 3 Cement 112 4 Tiles 121 5 Seel for Reinforcement 126 6 Steel for Structural Work 127 7 Water 129 8 Teak Wood 130 II WORKS 1 Excavation for Foundations 308 2 Filling Foundations 309 3 Filling Basement 310 4 Cast in situ Pile Foundations 313 STANDARD SPECIFICATION FOR BUILDING ITEMS APSS SL.No. Specification Specification 5 Plain Cement Concrete 402 6 403 501 & 504 8 Reinforced Cement Concrete Brick Masonry with Cement Mortar Reinforcement Half Brick Walls 9 Flooring with Polished Shahabad 701 & 703 10 Fooring with Glazed Tiles 701 & 707 11 Granolithic Concrete Flooring 701 &710 12 Plastering with CM Single Coat 901 & 903 13 Plastering with CM Two Coats 901 & 904 14 Water Proof Cement Paintings 912 15 Wood Doors &Windows 16 Painting with Enamel Paint 1212 17 Painting with Plastic Emulsion 1216 18 Aluminum Doors & Windows 1609 7 501 & 509 1001 & 1002