Protection and control Sepam range Sepam 2000 S25, S26 and S35, S36 Installation Use Commissioning General characteristics Contents chapter / page Installation - Use - General characteristics - Testing installation 1/1 use - commissioning 2/1 general characteristics 3/1 testing - setting record sheets 4/1 1 2 Installation - Use - General characteristics - Testing Installation Contents chapter / page Installation - Use - General characteristics - Testing installation 1/2 use conditions installation of Sepam 2000 handling, transport and storage environment of the installed Sepam 2000 1/2 1/2 1/2 1/2 equipment identification identification of Sepam 2000 accessories supplied with Sepam 2000 optional accessories 1/3 1/3 1/4 1/5 assembly and wiring dimensions and drilling assembly Sepam 2000 components connections principle 1/6 1/6 1/6 1/7 1/7 use and connection of current inputs to CTs connection of 1 A or 5 A CTs selection of operating modes CCA 660 or CCA 650 connector 1/8 1/8 1/8 1/9 use and connection of current inputs to CSPs CSP current sensors connection of CSPs accessories for CSP current sensors selection of operating modes (microswitches) 1/10 1/10 1/10 1/11 1/14 use and connection of split core balance CTs PO, GO split core balance CTs assembly of core balance CTs connection of split core balance CTs selection of operating mode (microswitches) 1/15 1/15 1/15 1/15 1/15 use and connection of CSH 120 and CSH 200 core balance CTs CSH 120 and CSH 200 core balance CTs selection of operating mode (microswitches) connection of CSH 120 and CSH 200 core balance CTs assembly wiring parallel cables 1/16 1/16 1/16 1/17 1/17 1/17 1/17 use and connection of CSH 30 interposing ring CT CSH 30 interposing ring CT assembly wiring connection to CT with 1 A secondary connection to CT with 5 A secondary connection to neutral of 3 CTs selection of operating mode (microswitches) 1/18 1/18 1/18 1/18 1/19 1/19 1/19 1/19 use and connection of ACE 990 interface connection characteristics dimensions selection of operating mode (microswitches) assembly wiring 1/20 1/20 1/21 1/21 1/21 1/21 1/21 connection of voltage inputs connection of 3 VTs connection of 3 VTs (residual voltage measurement) connection of 2 VTs connection of 1 VT connection of residual voltage input connection of 2 phase-to-phase voltages (synchro-check function) connection of 2 phase-to-neutral voltages (synchro-check function) connection of 3 VTs or 2 VTs in V arrangement (synchro-check function) 1/22 1/22 1/22 1/23 1/23 1/23 1/24 1/24 1/24 connection of Pt100 temperature sensors connection of sensors in 3-wire mode connection of sensors in 2-wire mode wiring 1/25 1/25 1/25 1/25 1/1 Installation Use conditions Installation of Sepam 2000 Each Sepam 2000 comes in a single package which contains: c Sepam 2000, c mounting accessories, c connection accessories (connectors). The other optional accessories come in a separate package. We recommend that you follow the instructions given in this document for quick, correct installation of your Sepam 2000: c equipment identification, c assembly, c connection of current and voltage inputs, probes, c microswitch setting, c connection of power supply and earth, c checking prior to commissioning. Environment of the installed Sepam 2000 Operation in a damp environment The temperature/relative humidity factors must compatible with the unit’s environmental withstand characteristics. If the use conditions are outside the normal zone, commissioning arrangements should be made, such as air conditioning of the premises. T (°C) 55 40 normal use zone Handling, transport and storage 35 65 93 95 humidity (%) Sepam 2000 in its original packaging Transport: Sepam 2000 may be shipped to any destination without taking any additional precautions by all usual means of transport. Handling: Sepam 2000 may be handled without any particular care and can even withstand being dropped by a person handling it (person standing on floor). Operation in a polluted atmosphere Sepam 2000 is designed to be used in a clean industrial environment as defined by IEC 60654-4 class 1. A contaminated industrial atmosphere components (such as the presence of chlorine, hydrofluoric acid, sulfur, solvents…) may cause corrosion of the electronic components, in which case environmental control arrangements should be made (such as closed, pressurized premises with filtered air,…) for commissioning. Storage: Sepam 2000 may be stored in closed premises for several years. Periodic, yearly checking of the environment and the packaging condition is recommended. Sepam 2000 installed in a cubicle Transport: Sepam 2000 may be transported by all usual means of transport in the customary conditions used for cubicles. Storage conditions should be taken into consideration for a long period of transport. Handling: Should the Sepam 2000 fall out of a cubicle, check its condition by visual inspection and energizing. If there is any doubt, return the Sepam 2000 for checking in the factory. Storage: Keep the cubicle protection packing for as long as possible. Sepam 2000, like all electronic units, should not be stored in a damp environment for more than a month. Sepam 2000 should be energized as quickly as possible. If this is not possible, the cubicle reheating system should be activated. 1/2 Installation - Use - General characteristics - Testing Installation Equipment identification Identification of Sepam 2000 Each Sepam is identified by a 14-character reference which describes its hardware and functional composition in accordance with the chart below. series model type variant communication number operating of ESTOR language boards current sensor auxiliary supply operating temperature S26 LX B = Busbars 1 to 99 S36 LT C = Capacitor X = none 0=0 F = French C = CS A = 24/30Vdc N = -5/55°C J = Jbus 1=1 A = English T = CT B = 48/125Vdc LS G = Generator F = FIP ISIS 2=2 I = Italian XT M = Motor O = FIP I/O 3=3 E = Spanish KR S = Substation KZ T = Transformer ZR R = RTU C = 220/250Vdc YR XR LR SR SS TS TR CR CC There are five labels for identifying Sepam 2000: c two labels on the right side panel which give the product’s hardware features (1), c a label on the front of the cartridge which gives the functional features (2), c a label on the left side of the cartridge which includes its references (3), c a label on the right side of the cartridge which may be used to note the references of a non-standard program logic scheme (4). Example of Sepam references: 2 2 ESTOR boards S36 Sepam 2036 A English XR type T TC S substation A 24V 03 03 N -5/+55°C X no communication MERLIN GERIN MERLIN GERIN S36 SEPAM 2036 model S36 XR *** X2* TAN equipment reference (Sepam, model and application) 9641087 serial n° (1) origin : FRANCE XR S03 2 A TAN 9641087 spaces reserved for equipment changes e.g. addition of an ESTOR board spaces reserved for after-sales servicing operations e.g. replacement of an ECM board Example of labels on the right side panel. board name S36 XR S03 Sepam model 6 XR S03 AA 161 SF B type of application (2) X equipment upgrading label program logic diagram reference servicing dates S36 : standard Sepam XR : model S03 : type 6 : Sepam S36 XR : model S03 : type A : English A : rev. level Sepam réf. : Date Version Identification of a non-standard program logic scheme Proj réf. : Drwg n° : Cubicle ID : example of a label on the front side of the cartridge. (4) label on the right side of the cartridge. 03143764FA-B0-01-9740208 (3) example of a label on the left side of the cartridge. Installation - Use - General characteristics - Testing 1/3 Installation Equipment identification (cont’d) Accessories supplied with Sepam 2000 Each Sepam 2000 comes with the following accessories. CCA 660 or CCA 650 connector for connection of 1 A or 5 A CTs: c for 4 mm eye lugs, c for max. 6 mm2 cable (awg 10), or CCA 601 BNC/BNC cable, length 5.5 m for connection to the CSP sensors. CCA 604 connector 4-pin connector. Connection of power supply: c screw terminals, c 0.6 to 2.5 mm2 cable (awg 20 to awg 14). CCA 606 connector 6-pin connector. Connection of a core balance CT: c screw terminals, c 0.6 to 2.5 mm2 cable (awg 20 to awg 14). CCA 608 connector (according to type of Sepam) 8-pin connector. Connection of VTs: c screw terminals, c 0.6 to 2.5 mm2 cable (awg 20 to awg 14). CCA 621 connector 21-pin connector. Connection of logic inputs/outputs, and RTDs: c screw terminals, c 0.6 to 2.5 mm2 cable (awg 20 to awg 14). 2 Sepam mounting lugs CCA 602 cable 3 m long cable with connectors supplied with Sepam2000 equiped with the Jbus communication functions. 1/4 Installation - Use - General characteristics - Testing Optional accessories TSM 2001 pocket terminal Used to make Sepam 2000 settings. It does not have a battery since it is supplied with power by the Sepam 2000. SFT 2801 / SFT 2821 kit The SFT 2801 software tool installed on a PC microcomputer may be used instead of the TSM 2001 pocket terminal. c The SFT 2821 software tool installed on a PC may be used to: v prepare a protection setting file and transfer it to Sepam 2000 via the pocket terminal connection, v transfer to a PC, via the pocket terminal connection, all the Sepam 2000 protection settings and store them in a file. These software tools are delivered together. They comprise: c three 3"1/2 diskettes, c an instruction manual, c a connection kit (ACE 900 interface + cord). ACE 900 adapter to be connected to the pocket terminal inlet. In the rest of the document, the term «pocket terminal» refers to both the TSM 2001 pocket terminal and the SFT 2801 kit. AMT 819 plate Used to mount Sepam 2000 on a 19" rack. 11,5 459 265,5 190,5 202 37,5 31,5 26,5 429 482 AMT 820 shield Used to block off the space between Sepam 2000 and the edge of the AMT 819 plate. 87 Communication accessories Refer to the “RS485 communication network connection guide”. Installation - Use - General characteristics - Testing 1/5 Installation Assembly and wiring Drilling diagram Dimensions and drilling Sepam 2000 is flush-mounted in a rectangular cut-out. Maximum thickness of mounting plate: 3 mm. Sepam A (mm) B (mm) C (mm) S26 * 244 250 264 S36 * 332 338 352 mounting lugs (x 2) 222 201 202 * S25, S35 for earlier versions. 20 B 300 C A (2) Assembly (2) c Insert Sepam 2000 through the front of the cut-out. Slide it into the cut-out until the front of Sepam 2000 is in contact with the mounting plate. The 2 notches (1) at the base of the Sepam 2000 case allow it to hold by its own weight. c Position the 2 lugs (2) in the holes on the top of Sepam. Tighten the threaded studs of the lug. c Make sure not to block the ventilation openings on the top and bottom of Sepam 2000. Leave a space of at least 5 cm above and below Sepam 2000. (1) 1/6 Installation - Use - General characteristics - Testing Sepam 2000 components slot 6 ESTOR2 (1) 5 ESTOR1 4 ESB 3 ESTOR ESTOR ESB 2 ECM(2) 1 CE40 S26 model* XT ESTOR (4) ESB ESTOR (4) ESB 3U/Vo ECM CE40 ESTOR ESB SONDE ECM CE40 6 ESTOR1 5 ESB 4 3U/Vo 3 2 ECM (2) 1 CE40 LX ESTOR (4) LT ESTOR (4) LS ESTOR slot _ 3U/Vo _ ECM CE40 CE40 8 7 ESTOR2 XR ESTOR ESTOR ESTOR ESB 3U/Vo ECM CE40 LR ESTOR ESTOR ESTOR ESB 3U/Vo ECM ECM CE40 LS SONDE ESTOR ESTOR ESB 3U/Vo ECM ECM CE40 SS SONDE ESTOR ESTOR ESB 3U/Vo SONDE ECM CE40 SR ESTOR ESTOR ESTOR ESB SONDE ECM CE40 KR ESTOR ESTOR ESTOR ESB 3U/Vo _ ECM ECM CE40 KZ SONDE ESTOR ESTOR ESB _ ECM CE40 YR ESTOR ESTOR ESTOR ESB _ ECM _ ECM CE40 ZR ESTOR ESTOR ESTOR ESB _ SONDE ECM CE40 TR ESTOR ESTOR ESTOR ESB 3U/Vo 3U/Vo ECM CE40 TS SONDE ESTOR ESTOR ESB 3U/Vo ECM CE40 CR ESTOR (5) ESTOR (5) ESTOR ESB 3U/Vo _ ECMD ECMD CE40 CC ESTOR ESTOR ESTOR ESB ECMD ECMD CE40 (1) (3) S36 model* ECMD _ (1) the ESTOR board may be installed, depending on the application, or ECA for CSP sensors option for ESTOR board (4) for SX1 and SX2 applications ESTOR boards are not installed. (5) except for S35 CR. (2) (3) The Sepam 2000 connections are made on the removable connectors located on the rear of the device. All the connectors are screw-lockable. Connection principle Wiring of screw connectors: c recommended wire fitting: v Telemecanique DZ5CE0155 for 1.5 mm2, v DZ5CE0253 for 2.5 mm2. Stripped length with fitting: 17 mm. Without fitting: c stripped length: 10 to 12 mm, c maximum 2 wires per terminal. The 21-pin connectors must be connected correctly by hand before being locked by the 2 screws (top/bottom). 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A A A A 8 7 PROBES INPUTS AND OUTPUTS ESB 6 3U/V0 8 7 6 5 4 3 2 1 A 5 SW1 SONDE 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 ECM (communication option) B 4 B SW2 SW1 B 6 5 4 3 2 1 A INPUTS AND INPUTS AND VOLTAGE INPUT OUTPUTS OUTPUTS CE40 4 3 2 1 A 3 2 PROBES CURRENT INPUT + V-DC 24-30 48-125 220-250 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 V-DC 24-30 48-125 220-250 ESTOR 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 V-DC 24-30 48-125 220-250 ESTOR 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 V-DC 24-30 48-125 220-250 SONDE A 1 POWER SUPPLY * S25, S35 for earlier versions. Installation - Use - General characteristics - Testing All the Sepam 2000 connection terminals are located on the rear of the device. The Sepam 2000 boards are fitted into numbered slots on the back; Sepam S26*: 1 to 6, Sepam S36*: 1 to 8. The connections are identified by adding different markings: c slots 1 to 8, c connectors A or B, c terminals 1 to 21. Example: 5 A16 slot n° 5, connector A, terminal 16. Each connector is used for a specific functional unit identified in the top right-hand corner according to the function: c CE40: auxiliary supply and communication option, c ECM: current sensor (CT) interface, c ECA: current sensor (CSP) interface, c 3U/Vo: voltage sensor interface, c ESB: circuit breaker control interface, c ESTOR: auxiliary control circuit interface, c SONDE: Pt100 temperature sensor interface. The relative position of the units depends on the Sepam 2000 model. 1/7 Installation Use and connection of current inputs to CTs 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 The current transformer (1 A or 5 A) secondary circuits are connected to the CCA 660 or CCA 650(1) connector ECM module. This connector contains 3 core balance CT primary-through adapters to ensure impedance matching and isolation between the 1 A or 5 A circuits and the Sepam 2000. This connector may be disconnected with the power on since disconnection does not open the CT secondary circuits. A A 8 7 PROBES INPUTS AND OUTPUTS ESB 3U/V0 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A SONDE 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A SW1 A 6 5 ECM (communication option) B INPUTS AND INPUTS AND VOLTAGE INPUT OUTPUTS OUTPUTS B SW2 SW1 B 6 5 4 3 2 1 A 4 CE40 4 3 2 1 A 3 2 PROBES CURRENT INPUT + V-DC 24-30 48-125 220-250 ESTOR V-DC 24-30 48-125 220-250 ESTOR V-DC 24-30 48-125 220-250 SONDE V-DC 24-30 48-125 220-250 Connection of 1 A or 5 A CTs A 1 POWER SUPPLY ECM DPC B4 B1 P1 L1 B5 B2 P2 L2 L3 B6 B3 CCA 660 or CCA 650 Sepam current inputs 1 2 3 Selection of operating modes (microswitches) Sepam 2000 has several possible operating modes. The operating mode is selected via microswitches on the rear of the device. They must be set before Sepam 2000 is put into service. The microswitches must be switched while the Sepam 2000 is de-energized. The microswitches are hidden by the CCA 660 or CCA 650(1) connector once it has been installed. N.B. Sepam S36 and S35 models LR, LS, KR, KZ, CR and CC have 2 or 3 inputs for connecting CTs. Remember to set the microswitches for the 2 or 3 inputs. (1) do not use for S26, S36 or S35 CR. Microswitch setting SW2 for use on the 5 A secondary circuit. SW1 1/8 for measuring residual current by the sum of the currents. SW1 SW1 SW2 SW2 for use on the 1 A secondary circuit. SW2 SW1 for measuring residual current: c by a CSH core balance CT, c by CT + CSH 30, c by core balance CT + ACE 990, c by CSH 30 via phase CT return Installation - Use - General characteristics - Testing CCA 660 or CCA 650 connector c Open the 2 side shields for access to the connection terminals. The shields may be removed, if necessary, to facilitate wiring. If removed, replace them after wiring. c Remove the bridging strap if necessary. The strap links terminals 1, 2 and 3. c Connect the wires using 4 mm eye lugs. The connector accommodates wires with cross sections of 1.5 to 6 mm2 (awg 16 to awg 10). c Close the side shields. c Plug the connector into the 9-point inlet on the rear of the device. Item B of the ECM module. c Tighten the CT connector fastening screws on the rear of Sepam 2000. Installation - Use - General characteristics - Testing 1/9 Installation Use and connection of current inputs to CSPs CSP current sensors CSP type current sensors operate according to the Rogowski coil principle. They deliver to the secondary circuit a voltage that is proportional to the derivative of the primary current. The CSP sensor – Sepam 2000 assembly forms a consistent protection and metering system. The CSP’s special coiling principle and the absence of a magnetic core gives the sensors the following properties: - no saturation: linearity of the curve, - no hysteresis or remanence: transient phenomena are accurately restituted, without undergoing any deformation. This simplifies current sensor specification and provides a wide dynamic operating range. Connection of CSPs The CSP sensors are connected by prefabricated coaxial cables, part no. CCA 601, supplied with Sepam 2000. The cables are plugged into: c Sepam 2000, in the BNC inlets on the rear of the device, identified L1, L2 and L3 of the ECA modules, c the CSP sensors, in the BNC outlet on each sensor, c the 3 BNC outlets are not equipped with the plugged detector detection system. CCA 601 cable ECA L1 P1 L2 P2 L3 1 The CCA 601 cable shielding is earthed naturally by the connection to Sepam 2000's BNC inlets. Do not earth by another means. The CSP sensors should be earthed via the earthing screw on the side of the device. 2 3 ECA L1 P1 P2 CCA 601 cable CSP sensor Detailed view of a connection 1/10 Installation - Use - General characteristics - Testing Accessories for CSP current sensors Accessory connection principle phase The use of specific CSP sensors requires the use of suitable accessories for injecting current and recording the current signals from the sensor secondary circuits. 1 CSP Input 4 Output C 7 1 Amp injection box ACE 907 3 CCA 603 CCA 601 B ou 5 A 6 Output E D recorder ACE 908 Input 2 SEPAM 1 – CSP phase sensor connected to Sepam by 5.5 m cable (CCA 601), the ends of which are fitted with BNC type connectors (supplied with Sepam). 2 – Sepam phase current input with BNC type connection with a T-shaped connector (delivered with CCA 603 box). 3 – optional CCA 603 connection box installed on front of cubicle and connected to Sepam by 5.5 m cable A (supplied with CCA 603 box). 4 – ACE 907 injection interface connected to CCA 603 box by 1 m cable B (supplied with ACE 907 interface). 5 – ACE 908 recording interface connected to CCA 603 box by cable D and to a recorder 6 by 1 m cable E with BNC end (cables supplied with ACE 908 interface). 7 – standard injection box delivering a 1 A current connected to ACE 907 interface by wires with ø 4 mm fittings not supplied. N.B. Do not use the ACE 907 interface with 100 A RCAF 1B sensors. CCA 603 connection box (3-phase) Box delivered with: three BNC T-connectors, three 1.5 m BNC cables, weight: 200 g 42.5 23.6 44 46 67.5 67.5 69 mounting lug Installation - Use - General characteristics - Testing 1/11 Installation Use and connection of current inputs to CSPs (cont’d) Common characteristics of ACE 907 and ACE 908 interfaces Voltage input c Rated voltage: 40 mV. c Input impedance u 100 kΩ. c Response in 47 to 63 Hz frequency band (25 to 100 Hz for ACE 908). c Phase shift between input and output +90° ±1% for ACE 907 (-90° +1% for ACE 908). c Module between input and output +6 dB/octave ±2% for ACE 907 (- 6 dB/octave ±2% for ACE 908). c Supply voltage: 127 or 230 volts ±15% (250 mA time-delayed fuse). c Operating frequency: 47 to 63 Hz. c Operation: -10°C to + 55 °C. c Storage: -25°C to +70 °C. c No-load consumption: 2 watts. c Weight: 1.5 kg. c Dimensions : v height 70 mm, v width 170 mm, v depth 260 mm. Current inputs c Rated current: 1 A. c Impedance i 1 Ω. c Thermal withstand: 80 A 1 s. Voltage outputs c Impedance i 1 Ω. c Load impedance u 30 kΩ. c Short-circuits tolerated. ACE 907 interface (3-phase) Interface delivered in a case containing: c ACE 907 interface, c one 2 m mains supply cable, c three 1 m BNC cables. 70 170 260 Connection input output L1 current injection L1 4 3 2 L2 5 6 7 8 9 10 11 1 L3 L2 L3 115/230 VAC ACE 908 interface (3-phase) Interface delivered in a case containing: c ACE 908 interface, c one 2 m mains supply cable, c six 1 m BNC cables. Connection input output L1 L1 L2 4 3 2 5 6 7 1 8 9 10 11 L2 L3 L3 115/230 VAC 1/12 Installation - Use - General characteristics - Testing Use of ACE 907 and AC 908 c Connect the interface as indicated in the connection diagram. c Set the “current sensor” selector switch to the position that corresponds to the CSP sensor rating. Correspondence between sensor rating, Sepam 2000 SW2 microswitch setting and the position of the “current sensor” selector switch. CSP network rated current In (in Amps) sensor current range 30-300 A 30 36 60 75 90 120 150 180 225 160-1600 A 160 192 240 320 400 480 640 800 960 1200 1600 500-2500 A 500 600 750 1000 1250 1500 2000 2500 SW2 setting 01 01 01 01 01 01 01 01 01 01 01 2 3 4 5 6 7 8 5 10 11 selector 1 switch setting 45 300 Example c CSP 3110 sensor, 30-300 A rating. c Rated current 90 A. Set the selector switch to position 6. ACE 907 or ACE 908 interface conversion characteristics “current sensor” selector switch position 1 2 3 4 5 6 7 8 9 10 11 1 1 1 1 1 1 1 1 ACE 907 current input (A) 1 1 1 maximum permissible current (A) 24 24 24 24 24 24 24 24 24 22 16 80 100 120 160 200 240 300 400 80 100 120 160 200 240 300 400 output voltage (mV) 40 48 60 ACE 908 input voltage (mV) 40 48 60 maximum permissible voltage (V) 3,6 4,3 5,4 7,2 9 10,8 14,4 18 21,6 27 36 100 100 100 100 100 100 100 100 output voltage (mV) 100 100 100 Example (“current sensor” = 6) A 1 A current injected into the ACE 907 interface will be interpreted by Sepam as a 90 A primary current. For a 90 A primary current, the ACE 908 interface will deliver a 120 mV voltage signal to the recorder. Precaution To eliminate possible measurement errors, due to ground currents (interface or analyzer supply network ground different from Sepam ground), it may be necessary to supply the ACE 908 interface and the measuring instrument via an isolating transformer. Installation - Use - General characteristics - Testing 1/13 Installation Use and connection of current inputs to CSPs (cont’d) Selection of operating modes (microswitches) The operating mode is selected by setting microswitches on the rear of the device. They must be set prior before Sepam 2000 is switched on, while it is de-energized. Set microswitches SW1 and SW2 in accordance with the chart opposite. They are to be set according to: c the CSP model used (30 A-300 A, 160 A-1600 A, 500 A-2500 A), c the rated current of the protected installation, c the earth fault current measurement method (sum or core balance CT). Microswitch setting chart Correspondence between sensor rating and SW1 and SW2 microswitch settings 30-300 A 30 36 60 75 90 120 150 180 225 N.B.: when the rated current of the electrical installation to be protected does not appear in the chart, choose the column that corresponds to the current rating immediately above. 160-1600 A 160 192 240 320 400 480 640 800 960 1200 1600 500-2500 A 500 600 750 1000 1250 1500 2000 2500 01 01 CSP network rated current In (in Amps) sensor current range 45 300 SW2: phase current 01 01 01 01 01 01 01 01 01 Example of microswitch setting This example indicates the microswitch setting in the following case: c network rated current: 160 A. c CSP sensor used: model 160-1600 A. c residual current measured by the sum of the 3 phase currents. 01 SW1: residual current measured by the sum of the 3 phase currents 1 SOM1 phase 1 01 6 01 01 01 01 SOM2 01 01 01 01 01 01 01 01 01 01 7 phase 2 SW2 12 SW1: residual current measured by core balance CT 01 13 01 01 01 01 01 01 phase 3 18 1 SW1 2 1/14 SOM 1 and SOM 2 are parameters to be set in the pocket terminal status menu. In is a parameter to be in the pocket terminal status menu. Installation - Use - General characteristics - Testing Installation Use and connection of split core balance CTs PO, GO split core balance CTs Dimensions ø5 These core balance CTs are used when it is impossible to dismantle the cables. They are connected to the Sepam 2 A or 30 A rating input. Ø c Transformation ratio 1/470. B L H dimensions (mm) Ø H PO 46 72 GO 110 78 weight (kg) L B 148 57 1.3 224 76 3.2 Assembly of core balance CTs c Install the core balance CT with the cables grouped in the middle. c If unwanted tripping occurs due to occasional current surges or motor starts: a) core balance CT ø = 2 x cable ø b) magnetic sleeve - L = core balance CT ø. L (a) Connection of split core balance CTs To measure residual current up to 20A, connect the core balance CT to the “2A rating” input. To measure residual current up to 300 A, connect the core balance CT to the “30 A rating” input. (b) ECA/ECM A DPC REF 30 A rating 2 A rating core bal. CT A6 A5 A4 A3 A2 A1 P1 P1 S2 S2 core balance CT S1 P2 S1 P2 1 2 earthed metallic cable shielding 3 1 Selection of operating mode (microswitches) c Set the corresponding Sepam 2000 switches SW1. The switches concerned are found on the input module. They must be set while Sepam 2000 is de-energized. The microswitches may be hidden by the CCA660 or CCA650 connector when it is installed. 3 SW2 SW1 Installation - Use - General characteristics - Testing 2 Cable shield earthing. for measuring residual current by split core balance CTs 1/15 Installation Use and connection of CSH 120 and CSH 200 core balance CTs CSH 120 and CSH 200 core balance CTs The specific CSH 120 and CSH 200 core balance CTs are used for direct measurement of earth fault current. The only difference between them is their inner diameter and they operate with 2 input ratings: c 2 A input rating: settings from 0.1 A to 20 A, c 30 A input rating: settings from 1.5 to 300 A. Due to the CSHs’ low voltage isolation, they may only be used on cables. Characteristics: c inner diameter: v CSH 120 : ø 120 mm, v CSH 200 : ø 200 mm. c accuracy: ±5%, c transformer ratio: 1/470, c maximum permissible current: 20kA-1 second, c operating temperature: - 25 °C to +70 °C, c storage temperature: - 40 °C to +85 °C, c maximum metering current Imm . This is a current value beyond which the Sepam CSH core balance assembly saturates. The user must therefore be careful not to set the tripping threshold higher than Imm. The maximum metering current depends on: v chosen rating (2 A or 30 A core balance CT), v core balance CT used (CSH 120 or CSH 200), v wiring resistance Rw back and forth between the core balance CT and Sepam 2000. Imm 300 A CSH 200 30 A core balance CSH 120 CT rating 100 A 80 A 50 A CSH 120 2 A core CSH 200 balance CT rating 20 A 1Ω 0.1 Ω 2Ω 10 Ω RW The graph above gives the value of Imm for Rw < 10 Ω. This graph is used to choose the required core balance CT and wiring. Example: the high setting of the earth fault protection is 80 A. Therefore, the 30 A rating of Sepam 2000 is chosen (wiring to terminals 3 and 4 of the earth fault connector). From the graph, it may be deduced that the CSH 120 and CSH 200 are suitable regardless of the wiring resistance, within the limit of 10 Ω. D C ø 5 mounting F øA H Selection of operating mode (microswitches) K G B J L E c Set the SW1 microswitches on the Sepam 2000. The microswitches concerned are found on the input module. They should be switched while the Sepam 2000 is de-energized. dimensions (mm) The microswitches are hidden by the CCA 660 or CCA 650 connector once it has been installed. CSH 120 A 120 B 164 C weight (kg) D E F G H J K L 26,5 44 190 76 52 40 166 62 35 0.6 28 274 120 90 60 257 104 37 1.4 CSH 200 200 256 46 SW2 SW1 1/16 for measuring residual current by a CSH core balance CT. Installation - Use - General characteristics - Testing Connection of CSH 120 and CSH 200 core balance CTs ECA/ECM To measure residual current up to 20 A, connect the core balance CT to the “2 A rating” input. REF 30 A rating 2 A rating core bal. CT To measure residual current up to 300 A, connect the core balance CT to the “30 A rating” input. DPC A A6 A5 A4 A3 A2 A1 P1 S2 S1 P1 P2 S2 1 2 core bal. 3 S1 P2 earthed metallic cable shielding 1 2 3 Cable shielding earthing. Assembly It is essential to mount the core balance C in the right direction in order for the protections to operate correctly. The assembly direction should be such that the silk-screen printed side of the core balance CT (P2 side) is at the cable end and the unmarked side (P1 side) at the busbar end. The core balance CT S2 terminal is always connected to the A4 terminal of the 6-pin connector. Mounting directly on cable. Mounting on plate or rail. In both cases, group the cables in the middle of the core balance CT. Non-conductive binding to hold the cable. Remember to insert the 3 medium voltage cable-shielding earthing cable through the core balance CT. Wiring Parallel cables The CSH 120 or CSH 200 core balance CT is connected to the CCA 606 6-point connector (item B) of the current input module. If it is impossible to insert the cables into a CSH 200 core balance CT, they may be connected in parallel. c Install one core balance CT per set of cables (max. 5). c Comply with the energy flow direction. c Loss of accuracy: 2 core balance CTs = - 10% 5 core balance CTs = - 25%. Recommended cable: c sheathed, shielded cable, c min.cable cross-section 0.93 mm2 (awg 18), c resistance per unit length < 100 milli ohms/m, c min. dielectric strenght: 1000 V. Connect the connection cable shielding in the shortest manner possible to the Sepam2000 6-point connector. Flatten the connection cable shielding against the metal frames of the cubicle. The cable shielding is grounded in Sepam 2000. Do not ground the cable by any other means. Installation - Use - General characteristics - Testing Ph1 Ph2 Ph3 Ph1 Ph2 Ph3 1/17 Installation Use and connection of CSH 30 interposing ring CT C CSH interposing ring CT 29 B 8 The CSH 30 interposing ring CT is used as adaptor when residual current is measured by a current transformer with a secondary circuit (1 A or 5 A). It acts as an adaptor between the CT and the Sepam 2000 residual current input. It should be connected to the CT input of the Sepam 2000 and installed near the corresponding Sepam input (max. 2 m). 4 F øA E 21 16 5 2 ø 4.5 D 2 ø 4.5 Characteristics c inner diameter: 30 mm, c accuracy: ± 5%, c transformer ratio: 1/470, c maximum permissible current: 20 kA-1 second, c operating temperature: - 25°C to + 70°C, c storage temperature: - 40°C to + 85°C, c maximum metering current: 10 Ino. dimensions (mm) A B C 30 31 60 weight (kg) D 53 E 82 F 50 0.12 Assembly The CSH 30 interposing ring CT is mounted on a symmetrical DIN rail. It may also be mounted on a plate through the mounting holes provided on its base. Wiring The cable must be inserted into the CSH 30 interposing ring CT in the right direction in order for the directional earth fault protection to operate correctly: the cable coming from S2 of the CT must be inserted through the P2 side of the CSH 30 core balance CT. Horizontal mounting on DIN rail. The secondary winding of the CSH 30 is connected to the CCA 606 6-pin connector. Cable to be used: c sheathed, shielded cable, c min. cable cross-section 0.93 mm2 (awg 18) (max. 2.5 mm2), c resistance per unit length < 100 mΩ/m, c min. dielectric strength: 1000 V. Connect the CSH 30 interposing ring CT connection cable shield in the shortest manner possible (2 m maximum) to the Sepam 2000 6-pin connector. Flatten the cable against the metal frames of the cubicle. The connection cable shielding is grounded in Sepam 2000. Do not ground the cable by any other means. Vertical mounting on DIN rail. 1/18 Installation - Use - General characteristics - Testing Connection to CT with 1 A secondary ECA/ECM c plug into the CCA 606 connector, c wind the transformer secondary wire around the CSH 30 interposing ring CT 5 times. DPC REF 30 A rating 2 A rating core bal. CT 5 turns A6 A5 A4 A3 A2 A1 S2 P1 S1 P1 S1 P2 S2 P2 CSH 30 core balance CT 1 A TC 1 Connection to CT with 5 A secondary ECA/ECM c plug into the CCA 606 connector, c wind the transformer secondary wire around the CSH 30 interposing ring CT once. DPC REF 30 A rating 2 A rating core bal. CT 2 1 turn A6 A5 A4 A3 A2 A1 S2 P1 S1 P1 S1 P2 S2 P2 CSH 30 core balance CT 5 A TC 1 c plug into the CCA 606 connector. c wind the current transformer secondary neutral wire around the CSH 30 interposing ring CT once (CT with 5 A secondary) or 5 times (CT with 1 A secondary). 2 B4 B1 P1 L1 B5 B2 P2 L2 L3 B6 B3 DPC REF 30 A rating 2 A rating core bal. CT 3 CCA 660 or CCA 650 ECA/ECM DPC Connection to neutral of 3 CTs 3 A6 A5 A4 A3 A2 A1 S2 CSH 30 core bal. CT S1 1 or 5 turns 1 2 3 Sepam current inputs Selection of operating mode (microswitches) c Set the SW1 microswitches on the Sepam 2000. The microswitches concerned are found on the input module. They should be switched while the Sepam 2000 is de-energized. SW2 The microswitches are hidden by the CCA 660 or CCA 650 connector once it has been installed. SW1 Installation - Use - General characteristics - Testing for measuring residual current by a CSH core balance CT. 1/19 Installation Use and connection of ACE 990 interface The ACE 990 is used to match the measurement of a MV core balance CT with ratio 1/n (50 ≤ n ≤ 1500), with that of the residual current input of Sepam 2000. ECA/ECM E5 So as not to downgrade measurement accuracy, the MV core balance CT must be able to supply sufficient power. The value is given in the chart opposite. A6 A5 E4 E3 E2 S2 E1 S1 Connection ACE 990 To wire the ACE 990 interface correctly, the following must be known: c ratio of the core balance CT (1/n) c core balance CT power, c close approximation of Ino (1) rating, essential for Sepam 2000 protection setting. The chart opposite may be used to determine the possible choices for the connection of the ACE 990 interface primary circuit to the Sepam 2000 earth current input, as well as the Ino(1) setting. A4 REF A3 A2 A1 Example of wiring. The exact value of the rated Ino (1) to be set is given by the following formula: value of k ACE 990 input Sepam 2000 input Min. power delivered by MV core balance CT Ino = k x number of core balance turns 0.00578 E1 – E5 A2 - A4 0.1 VA 0.00676 E2 – E5 A2 - A4 0.1 VA 0.00885 E1 – E4 A2 - A4 0.1 VA 0.00909 E3 – E5 A2 - A4 0.1 VA 0.01136 E2 – E4 A2 - A4 0.1 VA 0.01445 E1 – E5 A1 - A4 0.4 VA 0.01587 E1 – E3 A2 - A4 0.1 VA 0.01667 E4 – E5 A2 - A4 0.1 VA 0.01689 E2 – E5 A1 - A4 0.4 VA 0.02000 E3 – E4 A2 - A4 0.1 VA 0.02212 E1 – E4 A1 - A4 0.4 VA 0.02273 E3 – E5 A1 - A4 0.4 VA 0.02632 E2 – E3 A2 - A4 0.1 VA 0.02841 E2 – E4 A1 - A4 0.4 VA 0.03968 E1 – E3 A1 - A4 0.4 VA 0.04000 E1 – E2 A2 - A4 0.1 VA 0.04167 E4 – E5 A1 - A4 0.4 VA 0.05000 E3 – E4 A1 - A4 0.4 VA 0.06579 E2 – E3 A1 - A4 0.4 VA 0.08671 E1 – E5 A3 - A4 2 VA c In the chart opposite, find the wiring that corresponds to the value of k. 0.10000 E1 – E2 A1 - A4 0.4 VA 0.10135 E2 – E5 A3 - A4 2 VA The secondary circuit of the MV core balance CT is wired to terminals E2 and E3 of the ACE 990. 0.13274 E1 – E4 A3 - A4 2 VA 0.13636 E3 – E5 A3 - A4 2 VA The terminals S1 an S2 of the ACE990 should be wired to terminals A2 and A4 of Sepam 2000 respectively. 0.17045 E2 – E4 A3 - A4 3 VA 0.23810 E1 – E3 A3 - A4 4 VA 0.25000 E4 – E5 A3 - A4 4 VA c Calculate the value of Ino to be set: Ino = 0.02632 x 400 = 10.5 A 0.30000 E3 – E4 A3 - A4 4 VA 0.39474 E2 – E3 A3 - A4 6 VA 0.60000 E1 – E2 A3 - A4 10 VA where k is the factor defined in the chart opposite. Example: The core balance CT used has a ratio of 1/400 and power rating of 2 VA. If the earth fault protection settings are between 0.5 A and 85 A, the rated Ino(1) used may be 10 A. This value makes it possible to accurately measure from 0.5 A to 100 A. c Calculate the following ratio: close approximation of Ino number of turns i.e. 10/400 = 0.025 c In the chart opposite, find the closest value of k. A close value is k=0.02632. It corresponds to core balance CTs that are supposed to deliver at least 0.1 VA of power. This value of Ino may be used to monitor a current between 0.5 A and 105 A. (1) : this is the current value for which the earth fault protection setting rage extends to between 5% and 1000% of this value, at the most. 1/20 Installation - Use - General characteristics - Testing Characteristics Selection of operating mode (microswitches) c Accuracy: v amplitude: ± 1 %, v phase: < 2°. c Maximum permissible current: 20 kA, 1 s (on primary of MV core balance CT with ratio 1/50 which does not saturate). c Operating temperature: - 5 °C to + 55 °C. c Storage temperature: - 25 °C to + 70 °C. c Set the SW1 microswitches on the Sepam 2000. The microswitches concerned are found on the input module. They should be switched while the Sepam 2000 is de-energized. The microswitches are hidden by the CCA 660 or CCA 650 connector once it has been installed. SW2 SW1 for measuring residual current with core balance CT connected to ACE 990 interface. c In the E/F sensor headings of the Status menu: v Set the E/F sensor to “Core bal. CT+ACE990”. v Set the Ino parameter as a multiple of 0.1 A according to the calculation rule described earlier. Dimensions Assembly The ACE 990 interface is mounted on a symmetrical DIN rail. 50 72 25 E1 E2 E3 E4 E5 Wiring 11 46 99 MERLIN GERIN S1 S2 Only one core balance CT may be connected to the ACE 990 interface. The secondary of the MV core balance CT is connected to 2 of the 5 inputs of the ACE 990 interface. ACE 990 The output terminals of the ACE 990 are connected to the 6-pin connector, CCA 606. 20 77 11 Weight: 640 gr The core balance must be connected to the interface in the right direction in order for the directional earth fault and restricted earth fault protections to operate correctly. The cable coming from the core balance terminal marked S1 should be connected to the terminal with the lowest index. Cables to be used: Cables to be used: c cable between core balance CT and ACE 990: v wiring resistance less than 200mΩ/m, v cross-section between 1.5 mm2 (awg 15) and 2.5 mm2 (awg 13) c cable between ACE 990 and Sepam 2000: v shielded and encased (max. length = 2 meters), v cable cross-section between 0.93 mm2 (awg 18) and 2.5 mm2 (awg 13), v resistance per unit of length less than 100 mΩ / m, v minimum dielectric strength: 100 V. Connect the ACE 990 connection cable shielding in the shortest manner possible (max. 2 cm) to the 6-pin connector on the Sepam 2000. Flatten the cable against the metallic frames of the cubicle. The connection cable earthing is grounded in Sepam 2000. Do not ground the cable by any other means. Installation - Use - General characteristics - Testing 1/21 Installation Connection of voltage inputs 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A A 7 6 PROBES INPUTS AND OUTPUTS 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A 8 3U/V0 A SW1 SONDE 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A ECM (communication option) B INPUTS AND INPUTS AND VOLTAGE INPUT OUTPUTS OUTPUTS B SW2 SW1 B 6 5 4 3 2 1 A 4 5 CE40 4 3 2 1 A 3 2 PROBES CURRENT INPUT + 24-30 48-125 220-250 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 ESB V-DC ESTOR V-DC 24-30 48-125 220-250 ESTOR V-DC 24-30 48-125 220-250 SONDE V-DC 24-30 48-125 220-250 This concerns the types of Sepam 2000s that have voltage inputs. Type S26* LT, XT. S36* XR, LR, LS, SS, SR, TR, TS. The phase and residual voltage transformers (VTs) are connected to the CCA 608 8-pin connector on the 3U/Vo module. Sepam 2000 can function with 1, 2 or 3 VTs. The residual voltage can be measured by two methods: c calculated by Sepam 2000 based on the phase voltages, c wired directly to Sepam 2000 from a transformer with broken delta-star windings. SW1 microswitch setting: The microswitches must be set before the Sepam 2000 is energized, according to the chosen connection diagram. N.B. Sepam 2000 S36 ou S35 TR and TS models have two VT connection inputs. Remember to set the microswitches for both inputs. A 1 POWER SUPPLY * S25, S35 for earlier versions. Connection of 3 VTs 1 This arrangement does not allow residual voltage to be measured by the sum of the 3 phase voltages. 3 2 Use the pocket terminal to set the Number parameter of the phase VT ratio heading in the Status menu to 3U. P1 P2 S1 S2 A8 A7 A6 A5 A4 A3 A2 A1 3U/V0 DPC U21 U32 U13 V2 or SW1 microswitch setting voltage inputs Connection of 3 VTs (residual voltage measurement) This arrangement enables Sepam 2000 to measure system voltages and calculate the residual voltage based on the VT secondary voltages. It requires the use of 3 VTs with the primary between phase and earth. Terminals 1 and 6 must be strapped in order for Sepam to calculate the residual voltage. Use the pocket terminal to set the Number parameter to 3U and the Vnso parameter of the phase VT ratio heading in the Status men to 3V. 1 2 3 3U/V0 DPC U21 U32 U13 P1 P2 S1 S2 A8 A7 A6 A5 A4 A3 A2 A1 V2 SW1 microswitch setting voltage inputs 1/22 Installation - Use - General characteristics - Testing Connection of 2 VTs 1 This arrangement does not allow residual voltage to be measured by the sum method. 3 2 Use the pocket terminal to set the Number parameter of the phase VT ratio heading in the Status menu to 3U. P1 P2 S1 S2 A8 A7 A6 A5 A4 A3 A2 A1 3U/V0 DPC U21 U32 U13 V2 or SW1 microswitch setting voltage inputs Number = 3U Connection of 1 VT 1 2 1 2 This arrangement does not allow residual voltage to be measured by the sum method. 3 3 Use the pocket terminal to set the Number parameter of the phase VT ratio heading in the Status menu to the value indicated in the diagram opposite. P1 P2 S1 S2 A8 A7 A6 A5 A4 A3 A2 A1 3U/Vo DPC U21 U32 U13 3U/Vo DPC U21 U32 U13 Vo microswitch setting o voltage inputs Number = 1U Connection of residual voltage input This arrangement is used to connect the residual voltage measured outside Sepam 2000 via a transformer with broken delta-star windings. The connection is made on terminals A1 and A2 of the 8-pin connector. P2 S1 S2 A8 A7 A6 A5 A4 A3 A2 A1 Vo SW1 o P1 SW1 microswitch setting voltage inputs Number = V 1 2 3 3U/V0 DPC Use the pocket terminal to set the Vnso parameter to Uns/e or Uns/3 according to the type of VT used. U21 U32 U13 P1 P2 S1 S2 A8 A7 A6 A5 A4 A3 A2 A1 V2 SW1 microswitch setting voltage inputs Installation - Use - General characteristics - Testing 1/23 Installation Connection of voltage inputs (cont’d) 1 Connection of 2 phase-to-phase voltages (synchro-check function) The connections are made so that the voltages applied to inputs 5 and 4 (U sync 1) and 2 and 1 (U sync 2) correspond to the same phases. 2 3 A8 A7 A6 A5 A4 A3 A2 A1 3U/V0 example : U21 DPC U21’ This arrangement allows Sepam 2000 to measure voltage and power. Use the pocket terminal to set the Number parameter to 1U. U21 U32 U13 U sync 2 SW1 microswitch setting voltage inputs Connection of 2 phase-to-neutral voltages (synchro-check function) A8 A7 A6 A5 A4 A3 A2 A1 3U/V0 DPC The connections are made so that the voltages applied to inputs 5 and 4 (U sync 1) and 2 and 1 (U sync 2) correspond to the same phases. example : V1 U21 U32 U13 V1’ Use the pocket terminal to set the Number parameter to V. U sync 2 SW1 microswitch setting voltage inputs 1 Connection of 3 VTs or 2 VTs in V arrangement (synchro-check function) The connections are made so that the voltages applied to inputs 5 and 4 (U sync 1) and 2 and 1 (U sync 2) correspond to the same phases. 2 3 3U/V0 V1, V2, V3 or U21, U13 and U21. This arrangement allows Sepam 2000 to measure voltage and power. Use the pocket terminal to set the Number parameter to 3U. DPC U21 U32 U13 A8 A7 A6 A5 A4 A3 A2 A1 U sync 2 SW1 microswitch setting voltage inputs 1/24 Installation - Use - General characteristics - Testing Installation Connection of Pt100 termperature sensors 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 The Pt100 sensors are connected to the CCA 621 21-pin connector on the SONDE module. A Connection of sensors in 3-wire mode The following wiring should be done when one of the measurement channels is not being used. sensors DPC A21 A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1 A 8 7 PROBES INPUTS AND OUTPUTS ESB 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A 6 3U/V0 A SW1 SONDE 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A INPUTS AND INPUTS AND VOLTAGE INPUT OUTPUTS OUTPUTS CE40 (communication option) B B SW2 SW1 B 6 5 4 3 2 1 A 4 5 ECM 4 3 2 1 A 3 2 PROBES CURRENT INPUT + V-DC 24-30 48-125 220-250 ESTOR V-DC 24-30 48-125 220-250 ESTOR V-DC 24-30 48-125 220-250 SONDE V-DC 24-30 48-125 220-250 This concerns the types of Sepam 2000 that have inputs for Pt100 type temperature sensors. A 1 POWER SUPPLY Connection of sensors in 2-wire mode This connection mode should only be used when it is impossible to use the 3-wire mode (e.g. existing cable) since it introduces a substantial measurement error. The following wiring should be done when one of the measurement channels is not being used. Example: channel 6 not used. sensors DPC Pt100 n°5 Pt100 n°4 Pt100 n°3 Pt100 n°2 Pt100 n°1 A21 A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1 Pt100 n°5 Pt100 n°4 Pt100 n°3 Pt100 n°2 Pt100 n°1 A18 A17 A16 A18 A17 A16 Wiring e.g. channel 6 not used. It is preferable to use shielded cables. The use of unshielded cables may cause measurement errors, the size of which depends on the degree of electrical and magnetic disturbance in the cable surroundings. Only connect the shielding at the Sepam 2000 end: connect the connection cable shielding in the shortest manner possible to the corresponding terminals of the 21pin connector. Do not connect the shielding at the temperature sensor end. Recommended cross-sections according to distance : c up to 100 m > 1 mm2, awg 16, c up to 300 m > 1.5 mm2, awg 14, c up to 1 km > 2.5 mm2, awg 12. Installation - Use - General characteristics - Testing 1/25 Installation Connection of power supply and logic inputs and outputs 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A A A The Sepam 2000 chassis must be earthed via the grounding screw situated on the right side panel (rear view). Connection of logic inputs and outputs A 8 ESTOR 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 l18 l17 l16 l15 l14 l13 O14 O13 O12 O11 l12 l11 A A21 A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1 ESB A DPC CDG O2 O1 l2 l1 A21 A20 A19 A18 A17 A16 A15 A14 A13 A12 A11 A10 A9 A8 A7 A6 A5 A4 A3 A2 A1 A 8 PROBES A 7 ESB 3U/V0 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A 6 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A SW1 SW2 SW1 B 6 5 4 3 2 1 INPUTS AND INPUTS AND INPUTS AND VOLTAGE INPUTS OUTPUTS OUTPUTS OUTPUTS 4 3 2 1 A 2 CURRENT INPUTS SONDE + A 1 POWER SUPPLY ECM CE40 (communication option) B B SW2 SW1 B 6 5 4 3 2 1 A 4 B 3 A 5 B PROBES 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 CE40 (communication option) A 4 5 ESTOR Cabling should be done in accordance with the diagram for your application. DPC 6 SW1 INPUTS AND INPUTS AND INPUTS AND VOLTAGE INPUTS OUTPUTS OUTPUTS OUTPUTS SONDE The logical data are connected to the CCA 621 connector on the ESB and ESTOR modules. Check that the voltage applied to the inputs is compatible with the voltage indicated by a dot on the sub-assembly. ESTOR 7 PROBES V-DC 24-30 48-125 220-250 Use a braid or cable fitted with a 4 mm eye lug. The eye lug fastening screw is already mounted on Sepam when it is delivered. (Should the screw be lost, never replace it by a screw longer than 8 mm) A V-DC 24-30 48-125 220-250 Safety: 8 7 6 5 4 3 2 1 ECM 24-30 48-125 220-250 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 SONDE V-DC 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 3U/V0 4 3 2 1 A 3 2 PROBES CURRENT INPUTS + V-DC 24-30 48-125 220-250 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 The Sepam 2000 power supply is connected to the CCA 604 4-pin connector on the CE40 module situated on the rear of the device. The power supply input is protected against accidental polarity inversion. ESB V-DC 24-30 48-125 220-250 ESTOR V-DC 24-30 48-125 220-250 ESTOR V-DC 24-30 48-125 220-250 SONDE V-DC 24-30 48-125 220-250 Connection of power supply and earth A 1 POWER SUPPLY Example : ESTOR 1 and ESB. 1/26 Installation - Use - General characteristics - Testing Installation Connection of the Jbus/Modbus communication coupler 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A A A A 8 PROBES Installation - Use - General characteristics - Testing 7 ESB 6 3U/V0 8 7 6 5 4 3 2 1 A 5 SW1 SONDE 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 ECM (communication option) B 4 B SW2 SW1 B 6 5 4 3 2 1 A INPUTS AND INPUTS AND INPUTS AND VOLTAGE INPUTS OUTPUTS OUTPUTS OUTPUTS CE40 4 3 2 1 A 3 2 PROBES CURRENT INPUTS + V-DC 24-30 48-125 220-250 ESTOR V-DC 24-30 48-125 220-250 ESTOR V-DC 24-30 48-125 220-250 SONDE V-DC 24-30 48-125 220-250 Sepam 2000 can be equiped, as an option, with a communication coupler situated on the CE40 module. Please refer to the “RS 485 network connection guide” and “Sepam 2000, Jbus/Modbus communication” documents for commissioning instructions and the choice of accessories. A 1 POWER SUPPLY 1/27 Use - commissioning Contents chapter / page Installation - Use - General characteristics - Testing use - commissioning 2/1 description / use front face TSM 2001 pocket terminal 2/2 2/2 2/4 use (current operation) energizing operation via the front face or the TSM 2001 pocket terminal operation via the TSM 2001 pocket terminal alone clearing measurements annunciation list of messages 2/6 2/6 2/6 2/7 2/8 2/8 2/8 commissioning checking prior to commissioning commissioning using the pocket terminal parameter and setting errors status menu parameters chart microswitch SW1 and SW2 settings protection protection function setting ranges program logic and annunciation resource and program logic chart connection of logic inputs connection of logic outputs time delay settings disturbance recording 2/10 2/10 2/10 2/11 2/11 2/12 2/12 2/14 2/18 2/18 2/18 2/18 2/22 2/40 maintenance list of Sepam 2000 self-tests indicators lamps and display messages communication indicator lamps unwanted tripping, no tripping tests Sepam replacement 2/41 2/41 2/42 2/43 2/43 2/43 2/43 Sepam 2000 identification Sepam identification using the pocket terminal compatibility of types and models 2/44 2/44 2/45 Sepam 2000 documentation 2/47 password 2/48 use of the password 2/48 modification of the password 2/48 loss of the password 2/48 2/1 Use - commissioning Description/use Your Sepam 2000 is a multifunction, microprocessor-based device which includes in the same case: c control and monitoring of the associated circuit breaker or contactor, c measurement of electrical variables, c display of operating messages, c protection of the network and the drives it supplies. Sepam 2000 may be equiped (as an option) with a communication link with the remote monitoring station. There are two models of Sepam. Front face 1 2 3 4 5 Standard model: Sepam 2000 S36 or S35 (for all types). status indicators display keys for access to measurement and alarm processing cartridge pocket terminal socket Status indicators 1 : c green on indicator lamp shows that Sepam 2000 is energized, c red trip indicator lamp: Sepam has tripped the circuit breaker after detecting a fault. A related alarm message indicates the cause of tripping, c red indicator lamp shows internal Sepam faults. All the output relays are dropped out (fail-safe position). (Refer to the chapter on maintenance), c yellow I on indicator lamp and green O off indicator lamp show the position of the circuit breaker: v I = circuit breaker closed, v O = circuit breaker open. Compact model: Sepam 2000 S26 or S25 (for certain types). 2/2 Installation - Use - General characteristics - Testing v reset key: Display 2 The display unit indicates: c measurements, c operating messages. Keys for access to measurements and alarm processing 3 c metering key The measurements may be accessed by pressing the A, V/Hz, W/ϕ, Wh/°C metering keys. Each key provides access to a set of measurements according to the ring method. The protections trigger circuit breaker tripping and display of the related messages. The red trip indicator lights up. After the fault has been cleared, the user presses the reset key to acknowledge. The trip indicator is extinguished, the list of alarms is erased and the device can be closed. The reset key is disabled until the fault has been cleared. key -AI1 TRIP0 I2 TRIP3 I3 TRIP2 IM1 TRIP1 IM2 IM3 Example: current measurement When a measurement is not available in a type of Sepam, ----------- is displayed, c clear key: this key erases the stored value being displayed (reset): - max. current demand IM1, IM2, IM3, - tripping currents TRIP1, TRIP2, TRIP3, TRIP0, - peak demand power PM, QM, c alarm processing key v alarm key: each time tripping or another event occurs, an alarm message stored in a list of alarms is displayed. The most recent message appears on the display. This key provides access to step by step reading of the list of stored alarm messages. The previous message may be displayed by pressing this key. Display of: ----------- indicates the end of the list of alarm messages. Installation - Use - General characteristics - Testing Cartridge 4 The cartridge contains the information required for Sepam operation, such as: c settings, c stored data, c program and annunciation logic Pocket terminal socket 5 This socket is used to connect the TSM 2001 pocket terminal or the ACE 900 interface to the SFT 2801 / SFT 2821 software (PC link). 2/3 Use - commissioning Description/use (cont'd) TSM 2001 pocket terminal / SFT 2801 1 4-line display 2 data entry keypad P/Select: Metering Protection Program logic P/Select: Add. reading Status About Sepam 2/4 The TSM 2001 pocket terminal and the SFT 2801 software for PC operate in the same way. The pocket terminal provides access to all the Sepam 2000 information, such as: c current measurements, c operating assistance messages, c protection settings. The pocket terminal is supplied with power by Sepam 2000 and does not require any batteries; it can be connected with the power on. The pocket terminal beeps when it is connected. The main menu appears (if nothing is displayed, check the brightness adjustment using the key). The user may access the various items of information from three menu levels. A menu may comprise several pages. To access a menu, simply position the blinking cursor on the desired line and press the enter key. The first line of the menu contains the name of the current menu or function. Indication of P/ at the head of the menu indicates that the user has entered the password. Role of the keys: c the pocket terminal beeps when the user presses a key that is disabled. c the menu key is used to display the previous menu, c the ▲ and ▼ keys are used to move the c cursor one line up or down in a menu. To move to the next screen of a menu, the user simply positions the cursor on the last line and presses the ▼key. To move to the previous screen of a menu, the user simply positions the cursor on the second line and presses the ▲ key, c the code key is used to enter and exit the parameter setting mode, c the numeric and . keys are used to enter settings and the password, c the units key is used to change setting unit multiplying factors (e.g. A, kA,...), c the data+ and data- keys are used to select values from preset data lists. These lists are used when only a limited number of values may be used for a parameter, e.g. network frequency value, c the clear key is used: v to clear error messages, v to call back a previous setting value during data input, v to reset tripping currents and maximum demand readings to zero, c the enter key is used to confirm a menu selection or to confirm all the settings for a function. N.B. The first line always contains the name of the current menu or function. Installation - Use - General characteristics - Testing Menu Enter P/Select: Metering Protection Program logic Enter P/Select: Add. reading Status About Sepam Menu P/ABOUT... SFT 2800 Program logic Communication Menu Menu P/ADD. READING Residual I Residual V I and V start P/STATUS Rated frequency Phase CT ratio E/F Sensor Menu P/PROGRAM LOGIC Logic input Logic output Monostable relay Menu P/PROTECTION F011 50-51 F081 50N-51N F431 49 Menu P/METERING Phase current System voltage Power & pwr factor Enter Enter Enter Enter Enter Enter Menu Menu Menu Menu Menu Menu P/PROGRAM LOGIC M01PA001 CAT H NOL APPLICATION MOTOR P/PHASE CT = In = Ib Number = RATIO 500 A 450 A I1-I2-I3 P/I RESIDUAL CURRENT I0 = 12.3 A P/LOGIC OUTPUT = 10 01-02 011-014 = 0000 021-024 = 1010 P/50-51 Curve Is T F011 = Definite = 1,2 kA = 300 ms P/I PHASE I1 I2 I3 CURRENT = 453 A = 452 A = 453 A Example of use of the SFT 2801 software with Sepam 2000. Installation - Use - General characteristics - Testing 2/5 Use - commissioning Use (current operation) Energizing Sepam is energized when operating normally. In the event of re-energizing after a break in the auxiliary power supply, Sepam 2000 automatically restarts according to the following sequence, which lasts about 5 s: c green on and red indicators light up, c beep (if the pocket terminal is connected), c extinction of the red indicator, c resetting of watchdog contact, c testing of display: c breaker position indicator lights up, c display of the first message. Sepam is then in operation. If the pocket terminal is connected, it displays: Press Menu key to get the main menu 0,0,0,0,0,0,0,0,0,0,0 then ***********, then I1 = 0.0 A Sepam 2000 performs the functions of a precision measurement and alarm processing unit. The values are displayed directed with the related uit A, kA, etc. The messages clearly worded. There are two ways of operating the device: c via the front face (metering, annunication keys), c via theTSM2001 pocket terminals (using menus). Whenever a measurement is not available in the user's type of Sepam, -----------is displayed. Operation via the front face or pocket terminal functions key TSM menu desig. description range accuracy comments phase current A metering I1 I2 I3 measurement of each phase current 0 to 24In ±0.5% value depends on associated CT maximum current demand A metering IM1 IM2 IM3 measurement of the average current in the 3 phases 0 to 24In ±0.5% the value is periodically recalculated. Value set in Status menu to 5, 10, 15, 30 or 60 mn RESET: clear key tripping current A metering TRIP1 TRIP2 TRIP3 TRIP0 measurement of phase and earth currents at the time of the tripping order 0 to 24In ±5% RESET: clear key voltage V/Hz metering V1,V2,V3 measurement of phase-neutral and phase-phase voltages 0 to 1.5Un ±0.5% Value depends on associated VT frequency V/Hz metering F measurement of frequency 45 to 65 Hz ±0.02 Hz measured on input U21 real power W/ϕ metering P measurement of real power 0 to 999 MW ±1% positive or negative reactive power W/ϕ metering Q measurement of reactive power 0 to 999 MVAr ±1% positive or negative power factor W/ϕ metering PF measurement of power factor -1 to +1 0.01 P sign inductive or capacitive maximum real and reactive power demand W/ϕ metering PM 0 to 999 MW ±1% W/ϕ metering QM measurement of the greatest average power value U21,U32,U13 real and reactive energy temperatures Wh/°C metering +MWH measurement of real energy consumed Wh/°C metering +MVRH measurement of reactive energy consumed Wh/°C metering -MWH measurement of real power supplied Wh/°C metering -MVRH measurement of reactive power supplied Wh/°C metering T1, T2 T3, T4 T5, T6 measurement of temperatures 0 to 999 MVAr ±1% same remarks as for maximum current demand 0 to 99999.99 ±1% for the display 0 to 280x106 ±1% for the pocket terminal values are stored in the event of a power failure -50° to 250°C ±1°C operates with Pt100 sensors N.B. No values are displayed when the measurement is less than 1.5% of the rated value. 2/6 Installation - Use - General characteristics - Testing Operation via the pocket terminal alone function pocket terminal menu name description range accuracy earth fault add. reading residual current Io measurement of residual current 0 to 10Ino ±5% residual voltage add. reading residual voltage Vo measurement of residual voltage 0 to 1.5Un ±5% start current add-reading Tstart start time 0 to 999 s ±5% and time start current & time Imax maximum start current 0 to 24In ±5% Istart instantaneous current if > 1.2Ib 0 to 24In ±5% number of breaking operation cumulative value of (kA)2 5% In at 24 In ±10% cumulative breaking current add. reading Nb of operation in (kA)2 differentiel current and through current add. reading Idiff & Ithrough Idiff I measuremnt of Ithrough differential and through currents 0 to 24 In ±5% true rms current add. reading Irms Irms measurement of true rms current up to harmonic 21 0 to 4 In +1% phase rotation protection pos. seq. U/V1 Vd measurement of positive seq. voltage indication of "inverse" if the network is rotating backwards 0 to 100% Vn ±5% number of starts protection Tblock blocked start time 0.5 to 655 s nb. starts Nrest number of starts allowed 1 to 60/hour thermal overload protection thermal E % heat rise 0 to 999% unbalance ratio protection unbalance Ii negative current 0 to 1Ib ±5% directional protection Phi 1 phase shift between I1 and U32 0° to 360° ±3° at In,Un overcurrent directional O/C Phi 2 phase shift between I2 and U13 0° to 360° ±3° at In,Un Phi 3 phase shift between I3 and U21 0° to 360° ±3° at In,Un Phi 0 phase shift between Io and Vo 0° to 360° ±3° directional earth fault protection directional E/F name description ±2% zero reset (1) general counters for all types of application C1 number of closing operations performed by the breaking device Kp19 C2 number of phase-to-phase short-circuit fault trips Kp20 counters for the motor - generator applications C3 number of hours of motor running C4 number of minutes associated with running hours counter C3 Kp21 counters for the capacitor application with capacitor control C4 capacitor 1 running hours counter Kp21 C5 capacitor 2 running hours counter Kp21 C6 capacitor 3 running hours counter Kp21 counters for the substation application with recloser function C3 number of earth fault trips Kp20 C4 number of successful reclosing operations Kp22 C5 number of cycle 1s performed Kp22 C6 number of cycle 2s performed Kp22 C7 number of cycle 3s performed Kp22 C8 number of cycle 4s performed Kp22 (1) requires use of the password Installation - Use - General characteristics - Testing 2/7 Use - commissioning Use (current operation) (cont’d) Clearing measurements c maximum phase current demand. To reset to zero: v press clear on the pocket terminal if the maximum current demand readings are displayed, v press clear on the display if at least one maximum demand is displayed, c tripping current (phase or earth). To reset to zero: v press clear on the pocket terminal if all the tripping currents are displayed, v press clear on the display if at least one tripping current is displayed, c maximum real and reactive power demands. To reset to zero: v press clear on the pocket terminal if all the maximum demands are displayed, v press clear on the display if at least one maximum power demand is displayed, List of messages (according to the type of Sepam). message (1) type meaning ? CONTROL ? A tripping order discrepancy ? CONTROLX ? P capac capacitor x switch control supervision RECEIVE BI A blocking input EXT. TRIP A tripping by external protection PRESSURE A breaking pole pressure fault INST O/C A reclose instantaneous overcurrent INST E/F A reclose instaneous earth fault CYCLE 1 A reclose cycle 1 in progress CYCLE 2 A reclose cycle 2 in progress CYCLE 3 A reclose cycle 3 in progress CYCLE 4 A reclose cycle 4 in progress SUCCESSFUL A reclose successful reclosing (fault cleared) DEFINITIVE A reclose definitive tripping (fault not cleared) TR.GAS A gas detector (alarm or tripping) DISCHARGE A time-delayed energizing OPG INHIB A inhibition of disturbance recording RESTART A staggering of restarts TX AL/TRIP A transformer fault (alarm or tripping) START INHIB A motor restart inhibited CARTRIDGE M cartridge and Sepam not compatible CONNECTOR M unplugged connector MAINTENANCE M internal Sepam fault M.CARTRIDGE M internal cartridge fault RTD FAULT M PTC or PT100 sensor fault LOCK. ROTOR P locked rotor BUCHHOLZ P buchholz, alarm or tripping When an event is detected by Sepam 2000, an operating message appears on the display. The messages are stored in a list of alarms and may be reviewed in chronological order of appearance, starting with the most recent, by pressing the alarm key. LOAD SHED. P positive sequence undervoltage (or I12) LONG START P excessive starting time UNBALANCE P negative sequence / unbalance UNBAL.ALARM P capac neutral to neutral unbalance, alarm UNBAL.TRIP P capac neutral to neutral unbalance, tripping Beware: pressing the reset key will erase the contents of any list of alarms. UNBAL. ALARM 1 P neutral to neutral unbalance capacitor 1, alarm UNBAL. ALARM 2 P neutral to neutral unbalance capacitor 2, alarm UNBAL. ALARM 3 P neutral to neutral unbalance capacitor 3, alarm UNBAL. TRIP 1 P neutral to neutral unbalance capacitor 1, tripping UNBAL. TRIP 2 P neutral to neutral unbalance capacitor 2, tripping UNBAL. TRIP 3 P neutral to neutral unbalance capacitor 3, tripping LOM 1 P rate of change of frequency, setting 1 LOM 2 P rate of change of frequency, setting 2 GEN. DIFF. P generator differential MOTOR DIFF. P motor differential FIELD LOSS P reactive overpower (de-energizing) FRAME LEAK P frame leak OVERFREQ.1 P frequency too high, setting 1 OVERFREQ.2 P frequency too high, setting 2 OVERCURRENT P phase overcurrent LOW O/C P phase overcurrent, settings 1 and 3 O/C V REST P voltage restrained overcurrent DIR. O/C P directional phase overcurrent N.B. Zero resetting of the maximum demand readings allows calculations to be started for a new integration interval. c motor heat rise. To reset to zero, press the clear key on the pocket terminal if the heat rise measurement is displayed and if the user is in parameter setting mode, c number of starts. To reset, press the clear key on the pocket terminal if the blocked time is displayed and if the user is in parameter setting mode. The resetting of these functions alters the normal operation of the protections (changes their prior status). Annunciation type A = automation (program logic) P = protection M = maintenance (1) If your Sepam 2000 has been customzied, other messages may appear. Please refer to the information package provided by your OEM. 2/8 Installation - Use - General characteristics - Testing message (1) type FAULT SSL meaning default SSL reception HIGH O/C P phase overcurrent, settings 2 and 4 NEUTR. O/C1 P neutral overcurrent, setting 1 NEUTR. O/C2 P neutral overcurrent, setting 2 EARTH FAULT P earth fault DIR. E/F P directional earth fault OVERVOLT. 1 P overvoltage, setting 1 OVERVOLT. 2 P overvoltage, setting 2 O/VOLT.X By P overvoltage setting x busbar y N VOLT DISP P neutral voltage displacement EXT. STOP. A gen emergency generator shutdown EXT. LOCK A gen coupling inhibited E/F P earth fault current Io’ FIELD STOP A gen generator de-energizing order FREQ. GAP A gen frequency variance greater than set point, synchro-check protection ANGLE GAP A gen angle variance greater than set point, synchro-check protection VOLTAGE GAP A gen voltage variance greater than set point, synchro-check protection SYNCHRO. A search for synchronism STOP SYNC. A stopping of search for synchronism U.SYN1 FAIL A VT circuit 1 open U.SYN2 FAIL A VT circuit 2 open UNDERFREQ.1 P frequency too low, setting 1 UNDERFREQ.2 P frequency too low, setting 2 UNDERFREQ.3 P frequency too low, setting 3 UNDERFREQ.4 P frequency too low, setting 4 U/CURRENT P phase undercurrent UNDERVOLT. P undervoltage UNDERVOLT.1 P undervoltage, setting 1 UNDERVOLT.2 P undervoltage, setting 2 UNDERVOLT’1 P undervoltage, setting 1 UNDERVOLT’2 P undervoltage, setting 2 U/VOLT.X By P undervoltage setting x busbar y STARTS/HOUR P number of allowed starts reached TR PRESSURE P transformer pressure fault REF P restricted earth fault REF’ P restricted earth fault REVERSE P. P reverse real power ROTATION P phase rotation direction fault RTD XX P temperature fault (alarm or tripping) on RTD n°XX THERMAL P thermal overload (alarm or tripping) LATCH. CTRL P&T latching contactor IMP. CTRL P&T contactor with impulse orders PERM. CTRL P&T contactor with latched orders U/V RELEASE P&T circuit breaker with undervoltage release coil SHUNT-TRIP P&T circuit breaker with shunt-trip coil ! ERROR ! P&T error in command parameter setting type A = automation (program logic) P = protection P&T = control function parameter setting test (1) If your Sepam 2000 has been customzied, other messages may appear. Please refer to the information package provided by your OEM. Installation - Use - General characteristics - Testing 2/9 Use - commissioning Commissioning These operations must be carried out before Sepam 2000 is energized. Checks: c supply voltage Ensure that the cubicle auxiliary supply voltage matches Sepam 2000's operating voltage. It is indicated on the rear of the device, beside the power supply connector, by a dot in the voltage box, Example S26L X on the cartridge label should match S26LX on the Sepam label. c connectors Check that all the connectors are correctly connected to the rear of the device and screwlocked. MERLIN GERIN S26 LX S01 4LXS01FA 161SFA MERLIN GERIN SEPAM 2026 S26 LX J2 TBN *** * 4 3 2 1 + V-DC 24-30 48-125 220-250 Setting of microswitches on the rear of the device. Check that the microswitches which define operating modes and Sepam 2000 calibration operations were correctly set at the time of installation (1). A c earthing Check that the Sepam 2000 chassis is earthed by the ground nut situated on the Sepam side panel, on the power supply side. Check that the screw is tightened. c cartridge v Check that the cartridge is in its slot behind the front wicket door. To do so, open the wicket door by pulling on the notch situated on the left side panel. The Sepam S36 or S35 has a shield on the right, which resembles the memory cartridge wicket door. This shield is not another wicket door. Do not try to open it. Check that the cartridge has been inserted correctly. Check the tightening of the 2 threaded screws by hand. Above all do not insert or remove the cartridge when Sepam 2000 is energized, v the cartridge has an identification label on the front. The first 5 characters in the first line indicate the Sepam 2000 model. Ensure that the type of cartridge matches the Sepam model indicated on the side of Sepam. The microswitches must be set with Sepam de-energized. If the microswitches are incorrectly set, the measurements given by Sepam 2000 will be erroneous and the protections will fail to trip at the desired set points. 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 A B B SW2 SW1 B 6 5 4 3 2 1 4 3 2 1 A + V-DC 24-30 48-125 220-250 Checking prior to commissioning A Default parameter setting Factory-set parameter status: c microswitches: v they are set for a 5A secondary current transformer power supply, v residual current measurement by the core balance CT, v residual voltage measurement by the sum of the 3 voltages, c protection: v settings: 999 kA or kV v time delays: 655 s c program logic time delay: v t = 200 ms, v number of starts (motor protection): v N = 999, v time between starts = 0.5 s Commissioning using the pocket terminal Switch on the Sepam After the Sepam 2000 has started up, check that no messages are present by pressing the “alarm” key. Checking mode All the data may be accessed for checking purposes without the risk of changing parameters or settings. Parameter setting mode (2) This mode is reserved for commissioning and maintenance. The entry of a password is required. P\ appears at the top left of the screen (3) . (1) Refer to “Installation” chapter. All parameters and settings must be based on a network discrimination study that is to be carried out prior to commissioning. (3) This mode is automatically cancelled if no keys are pressed for about 1 minute. It may be cancelled manually by pressing the Code key. (2) 2/10 Installation - Use - General characteristics - Testing Parameter and setting errors Status menu parameter chart Changing a status parameter may put a protection setting outside the tolerance range. Sepam detects this problem and displays the following message: heading frequency name Fn function network frequency phase CT ratio phase CT' ratio for CT In CT rating P\CT ratio protection setting out of range press clear key basis current of equip. being protected number number of current sensors phase CT In CT rating (standard ratio for CSP values see table on the next page) Ib basis current of the equipment being protected number number of current sensors capteur Io sensor type of earth capteur Io’ fault current The user should then check and, if necessary, change the protection settings. The PROTECTION line blinks until the settings have been corrected. Settings out of range. A protection value may be out of range when it is set.. Sepam detects this and indicates the permissible range of settings. P\50N-51N F081 Iso out of range 0.05Ino < Iso < Ino Press clear key Example: 50N, 51N earth protection. All the parameters and settings are accessible in 3 menus: v general parameters: status menu, v protection : protection menu, v operating parameters: program logic menu, General parameters The general parameters are accessible in the status menu; they are to be set at the time of commissioning, using the setting sheet (see corresponding chapter) and must not be modified during current operation. max. interval phase VT phase VT’ direction of energy disturbance recording (4) communication (2) time tagging (2) password Ib command selection data + and - 50 or 60 Hz keys numeric adjustable from keys 10 A to 6250 A numeric 0.4 to 1.3In keys in amps data + and - 2 or 3 sensors keys data + and - 30 values between keys 30 A and 2500 A numeric 0.4In to 1.3In keys in amperes data + and - 2 or 3 sensors keys data + and - c sum of 3I keys c 2 A core bal. CT c tore 30 A c 30 A core bal. CT c core bal. CT + ACE 990 Ino CT rating with CT S26, S36 adjustable from + CSH 30 option numeric 1.0 A and 6250 A keys core bal. CT rating with S25, S35 56 values from core bal. CT + data + and - 1 A to 6250 A ACE 990 option keys period max. demand integration data + and - adjustable from period keys 5, 10, 15, 30, 60 mn number number of VTs wirred data + and - S26-S36 S25-S35 keys V U21 1U U21-U32 3U 3U Unp rated VT primary numeric adjustable from voltage keys 220 V to 250 kV Uns rated VT secondary data + and - 100, 110, 115, voltage keys 120 V Vnso type of residual data + and - c sum of 3Vs voltage measurement keys c Uns / e c Uns / 3 incomer reverses the signs data + and - incomer: feeder of power and energy keys cable --> busbars (1) measurements feeder: busbars --> cable (1) pretrig number of periods numeric adjustable from before triggering keys 1 and 85 periods event speed transmission speed data + and - 300, 600, 1200, keys 2400, 4800, 9600, 19200, 38400 bds station Sepam station number numeric 1 to 255 in the network keys parity transmission format data + and - even, odd, keys without parity synchro type of synchronization data + and - via: used keys - network - inputs I11 or I21 (3) events I1 I2 numeric I11 to I18 keys I21 to I28 I31 to I38 KTS1 to KTS32 by 8-bit words KTS33 to KTS64 for S26, S36 only see corresponding page (1) incomer + , feeder + for commissioning, refer to “communication” document. (3) 0 = not time-tagged 1 = time-tagged. All events are set to zero by default. (4) available as of version 9940 of SFT 2800. (2) Installation - Use - General characteristics - Testing 2/11 Use - commissioning Commissioning (cont’d) Microswitch SW1 and SW2 settings Protection The microswitch settings must be coherent with the choices made in the status, phase CT ratio and VT ratio menus: Locked rotor / excessive starting time (48/51 LR) Protection of motors that are liable to start with overloads or insufficient supply voltage and/or drive loads that are liable to become locked (e.g. crusher). It is an overcurrent protection that is only confirmed after a time delay which corresponds to the normal start time. Recommendation: use short, definite time. According to the type of Sepam 2000, the following functions are available: c current input for 1 A / 5 A CT 1 A secondary 5 A secondary SW2 Negative sequence / unablance (46) Protection of equipment against overheating caused by an unbalanced power supply, phase inversion or phase break, and against low levels of overcurrent between 2 phases. Recommendation: use IDMT curves. SW2 v residual current measurement by sum of 3 currents SW1 SW1 Rate of change of frequency (81R) Protection which calculates the rate of frequency variation and compares it to a set point (used with uncoupling and load shedding). v residual current measurement by core balance CT SW1 SW1 Machine differential (87M-87G) Fast, sensitive protection of motors and generators against internal faults due to damaged insulation. The protection is based on the principle of percentage differentials, i.e. starting current restraint to sustain stability in spite of its high level of sensitivity. c current input for CSP sensor current sensor range CSP 30-300 A rated current of network 30 36 45 60 75 90 120 150 180 160-1600 A 160 192 240 320 400 500-2500 A 500 600 750 1000 1250 1500 2000 2500 01 01 01 01 01 225 300 480 640 800 960 1200 1600 01 01 01 01 01 01 SW2 v residual current measurement by sum of 3 currents SW1 01 01 01 01 01 01 Som1 01 01 01 01 01 Som2 v residual current measurement by core balance CT SW1 01 01 01 01 01 01 01 Neutral unbalance (50/51) Detection of unbalance current between the neutral points of double star-connected capacitor banks; unbalance current indicates that components of one of the capacitors are damaged. 01 01 01 01 c connection voltage input v residual voltage measurement by sum SW1 v no residual voltage measurement SW1 v residual voltage measurement by broken delta-star transformer Thermal overload (49) Protetion of equipment against thermal damage caused by overloads. Thermal overload is calculated according to a mathematical model, with 2 time constants, taking into account the effect of negative sequence current by means of an adjustable weighting coefficient: This function includes: v an adjustable setting to define equipment warm state (or alarm setting), v an adjustable tripping setting Starts per hour (66) Protection against overheating caused by too frequent starts. Checking of: v number of starts per hour, v number of consecutive warm starts (detected by the thermal overload protection), v number of consecutive cold starts. The protection inhibits energizing for a preset time period when the permissible limits are reached. Tank frame leakage (50/51) Quick, selective detection of earth leakage current in transformer primary and secondary windings. This overcurrent protection is associated with a current sensor installed on the frame earthing connection. It calls for isolation of the transformer tank. Phase overcurrent (50/51) Three-phase connection and equipment protection against phase-to-phase faults. The following types of time delay settings are available: definite, standard inverse, very inverse, extremely inverse and ultra inverse. Percentage type overcurrent (50/51 - 50N/51N) Detection of an unbalance current flowing between the two neutral points of double star mounted capacitor banks; this current indicates that the components of one of the banks are damaged. Directional overcurrent (67) Incomer protection, which provides quick, selective protection against upstream faults when there are several power supplies in parallel. SW1 2/12 Installation - Use - General characteristics - Testing Earth fault (50N/51N) Protection against earth faults. The following types of time delay settings are available: definite, standard inverse, very inverse, extremely inverse and ultra inverse. Earth fault current detection can be provided by: v three phase current transformers, v a current transformer (1 A, 5 A), combined with a CSH30 interposing ring CT, v a CSH120 or CSH200 core balance CT, according to the required diameter, this method being the most accurate one. The two ratings available (2 A and 30 A) provide a very wide setting range, Directional earth fault (67N) This protection has several uses: v highly sensitive earth fault protection of transformer feeders supplied by long cables characterized by high capacitive current, v quick, selective detection of upstream earth faults when there are several incomers in parallel. Overvoltage (59) Protection against abnormally high voltage and checking that there is sufficient voltage of power supply changeover. This protection monitors system voltage U21. Neutral voltage displacement (59N) Detection of insulation faults in ungrounded systems by measurement of neutral voltage displacement. This protection is generally used for transformer incomers or busbars. Undercurrent (37) Pump protection against the consequences of priming loss. This protection detects delayed undercurrent corresponding to motor no-load operation which is typical of a loss of pump priming. Underfrequency (81L) Detection of variances with respect to the rated frequency, in order to maintain high quality power supply. This protection can be used for overall tripping or for load shedding. Overfrequency (81H) Protection against abnormally high frequency. Undervoltage (27) Protection used either for automated functions (changeover, load shedding) or for the protection of several motors against undervoltage. This protection checks for undervoltage in each of the phase-to-phase voltages measured. Positive sequence undervoltage (27D) Protection of several motors against malfunctioning due to insufficient or unbalanced supply voltage. Remanent undervoltage (27R) Monitoring of the clearing of voltage sustained by rotating machines after the opening of the circuit. This protection is used with automatic changeover functions to prevent transient electrical and mechanical phenomena that are caused by fast resupply of power to motors. It monitors system voltage U21. Neutral (50N/51N) Overload protection of neutral earthing impedance and sensitive overall network protection against earth faults. This “earth fault” protection is associated with a current sensor installed on the neutral earthing connection. Reactive overpower (32Q/40) Protection of synchronous drives against field loss which causes overconsumption of reactive power and leads to the loss of synchronism. Reverse real power (32P) Protection of motors against operation as generators when driven by their loads or, in the case of double sources, to avoid the output of one source into the other. It is based on the real overpower function F531. Direction of rotation (47) Protection which prevents the changing of direction of motor rotation following a power supply modification. Temperature monitoring (38/49T) Protection which detects abnormal overheating of equipment fitted with Pt100 type platinum resistor type temperature sensors. v 1 alarm setting, v 1 tripping setting. The cabling of each sensor is continuously monitored. Voltage restrained overcurrent (51V) Three-phase protection against alternator phase faults. Its characteristics are suitable for the weak current suppied by the alternator when a short-circuit occurs. Synchro-check (25) Closing of the breaking device if the two circuits have voltage, frequency or phase variances within the planned limits. Restricted earth fault (64 REF) Detection of phase to earth faults in the winding of the transformer connected to the secondary end of the protection. This protection may be used when the secondary neutral is earthed inside the protected zone. Installation - Use - General characteristics - Testing 2/13 Use - commissioning Commissioning (cont’d) Protection function setting ranges display messages function LOCK. ROTOR LONG START locked rotor / 48/51LR excessive starting time UNBALANCE negative sequence / unbalance ANSI 46 LOAD SHED UNDERVOLT.1 UNDERVOLT.2 positive sequence undervoltage 27D ROTATION direction of rotation 47 LOM1 rate of change of frequency 81R LOM2 MOTOR DIFF. machine differential GEN. DIFF. FIELD LOSS FRAME LEAK OVERCURRENT or HIGH O/C LOW O/C O/C V REST 87M pocket terminal item parameters commands setting limits F441 Is setting numeric keys and units 0.5 to 5Ib ST long start time delay numeric keys and units 0.5 s to 655 s LT locked rotor time delay numeric keys and units 0.05 s to 655 s curve choice of tripping curve data + and - keys DT or IDMT Is setting numeric keys and units DT: 0.1 to 5Ib IDMT: 0.1 to 0.5Ib T time delay numeric keys and units DT: 0.1 to 655 s IDMT: 0.1 to 1s at 5Ib F381 Vsd setting numeric keys and units 0.3 Vnp to Vnp F382 T time delay numeric keys and units 0.05 s to 655 s Vd rotation direction fault metering (Vnp = Unp/V3) F581 dFs/dt setting numeric keys and units 0.1 to 10 Hz/s F582 T time delay numeric keys and units 0.1 to 655 s F621 Is setting numeric keys and units 0.05 In to 0.5 In (min.: 1A) F541 Qs setting numeric keys and units O.05 to 1.2 Sn T time delay numeric keys and units 0.1 s to 655 s curve choice of tripping curve data + and - keys DT, SIT, VIT, EIT, UIT Is setting numeric keys and units DT: 0.3 to 24 In SIT, VIT, EIT, UIT: 0.3 to 2.4 In T time delay numeric keys and units DT: 0.05 to 655 s SIT, VIT, EIT, UIT, LIT: 0.1 to 12.5 s at 10 Is curve choice of tripping curve data + and - keys DT, SIT, VIT, EIT, UIT Is setting numeric keys and units DT : 0,3 to 24 In SIT, VIT, EIT, UIT : 0.3 to 2.4 In T time delay numeric keys and units DT : 0.05 to 655 s SIT, VIT, EIT, UIT : 0.1 to 12.5 s at 10 Is curve choice of tripping curve data + and - keys DT, SIT, VIT, EIT, UIT Is setting numeric keys and units DT: 0.3 to 24 In SIT, VIT, EIT,UIT: 0.3 to 2.4 In T time delay numeric keys and units DT: 0.05 to 655 s SIT, VIT, EIT, UIT: 0.1 to 12.5 s at 10 Is F451 87G reactive overpower frame leak phase overcurrent 32Q/40 50/51 50/51 voltage restrained 50/51V overcurrent F021 F011 to F014 F191 DT: definite time SIT, VIT, EIT, UIT: IDMT (inverse) 2/14 Installation - Use - General characteristics - Testing display messages function ansi pocket terminal item parameters commands setting limits DIR. O/C directional overcurrent 67 F511* F521 curve choice of tripping curve data + and - keys DT, SIT, VIT, EIT,UIT Is setting numeric keys and units DT: 0.3 to 24In SIT, VIT, EIT, UIT: 0.3 to 2.4In T time delay numeric keys and units DT: 0.05 to 655 s SIT, VIT, EIT, UIT: 0.1 to 12.5 s at 10 Is angle characteristic angle data + and - keys 30°, 45° or 60° Phi1 Phi2 Phi3 phase shift metring between I1 and U32 between I2 and U13 between I3 and U21 curve choice of tripping curve data + and - keys DT, SIT, VIT, EIT, UIT Iso setting numeric keys and units DT with: Sum3I: 0.05 to 10In CT+CSH 30: 0.05 to 10Ino CSH 2A: 0.1 to 20 A CSH 30A: 1.5 A to 300 A Core bal. CT+ ACE 990: 0.05 to 10 Ino SIT, VIT, EIT, UIT with: Sum3I: 0.05 to In CSH 30: 0.05 to 10Ino CSH 2A: 0.1 to 2 A CSH 30A: 1.5 A to 300 A Core bal. CT + ACE 990: 0.05 to Ino T time delay numeric keys and units DT: 50 ms to 655 s SIT, VIT, EIT, UIT: 0.1 to 12.5 s at 10 Iso Iso setting numeric keys and units Sum3I: 0.05 to 10In CSH 30: 0.05 to 10Ino CSH 2A: 0.1 to 20 A CSH 30A: 1.5 A to 300 A Core bal. CT + ACE 990: 0.05 to 10 Ino T time delay numeric keys and units 0.05 to 655 s angle characteristic angle data + and - keys 0°, 15°, 30°, 45°, 60°, 90°, -45° EARTH FAULT DIR. E/F NEUTR. O/C1 NEUTR. O/C2 or E/F IO’ OVERFREQ. 1 OVERFREQ. 2 earth fault directional earth fault neutral unbalance overfrequency 50N/51N 50G/51G 67N 50N/51N 81H F061 to F064 F081 to F084 F501 Phi0 phase shift metering between Io and Vo F091 F092 curve choice of tripping curve data + and - keys DT, SIT, VIT, EIT, UIT F071 F072 Iso setting numeric keys and units DT with: Sum3I: 0.05 to 10In CT+CSH 30: 0.05 to 10 Ino CSH 2A : 0.1 to 20 A CSH 30A:1.5 A to 300 A Core bal. CT + ACE 990: 0.05 to 10 Ino SIT, VIT, EIT, UIT, with: Sum3I: 0.05 to In CT+CSH 30:1.5 A to 300 A Core bal. CT + ACE 990: 0.05 to Ino CSH 2A: 0.1 to 2 A CSH 30A: 1.5 to 30 A T time delay numeric keys and units RET** H2 restraint data + and - keys DT: 50 ms to 655 s SIT, VIT, EIT, UIT: 0.1 to 12.5 s at 10 Iso yes / no Fs setting numeric keys and units for 50 Hz: 50 to 55 Hz for 60 Hz: 60 to 65 Hz T time delay numeric keys and units 0.1 to 655 s F571 F572 * for Sepam 2000 S25 and S35. ** for F081 to F084 and F091, F092 only. Installation - Use - General characteristics - Testing 2/15 Use - commissioning Commissioning (cont’d) display messages function ANSI pocket terminal item parameters commands setting limits OVERVOLT. 1 OVERVOLT. 2 overvoltage 59 F301 F302 F311 Us setting numeric keys and units 0.5 to 1.5Un T time delay numeric keys and units 0.05 to 655 s Vso setting numeric keys and units 0,02 to 0.8Un (VT: Un/e/100/e) 0.05 to 0.8Un (VT: Un/e/100/3) T time delay numeric keys and units 0.05 to 655 s Is setting numeric keys and units 0.05Ib to Ib T time delay numeric keys and units 0.05 to 655 s Fs setting numeric keys and units for 50 Hz: 45 to 50 Hz for 60 Hz: 55 to 60 Hz T time delay numeric keys and units 0.1 to 655 s Us setting numeric keys and units 0.05 Unp to Unp T time delay numeric keys and units 0.05 to 655 s Us setting numeric keys and units 0.05 Un to Un T time delay numeric keys and units 0.05 to 655 s Nstart starts per hour numeric keys and units 1 to 60 H start number of warm starts per hour/Nstart numeric keys and units 1 to 60 C start number of cold starts per hour/Nstart numeric keys and units 1 to 60 T time delay numeric keys and units 0.5 s to 655 s N VOLT DISP U/CURRENT UNDERFREQ.1 UNDERFREQ.2 UNDERVOLT.1 UNDERVOLT.2 neutral voltage displacement undercurrent REVERSEP. RTD XX XX = 1 to 12 2/16 37 underfrequency 81 undervoltage remanent undervoltage STARTS/HOUR 59N checking of number of starts reverse real power temperature monitoring 27 27R 66 32P 38/49T F391, F392 F411, F412 F221 F561 F562 F241 F321, F331, F341, F361, F371, F322 F332 F342 F362 F372 F351, F352 F421 F531 F461 to F466 F471 to F476 N.rest nb. of possible or starts or T.block blocking time metering Ps setting numeric keys and units 1% to 120% of Sn T time delay numeric keys and units 0.1 to 655 s Ts1 to Ts2 temperature settings numeric keys and units 0°C to 180°C Installation - Use - General characteristics - Testing display messages function ANSI pocket terminal item parameters commands setting limits THERMAL thermal overload 49 F431 OL1 alarm setting (or hot state) numeric keys and units 50% to 200% OL2 tripping setting numeric keys and units 50% to 200% Adjust unbalance factor data + and - keys without = 0, low = 2.25 average = 4.5, high = 9 T1 heat rise time constant numeric keys and units 5 to 120 mn T2 cooling time constant numeric keys and units 5 to 600 mn SYN CHECK synchronism check 25 F171 F181 Heating heat rise metering dUs voltage variance setting numeric keys and units 0.03 to 0.3Un dFs frequency variancenumeric keys setting and units 0.05 to 0.5 Hz dPhi phase variance setting numeric keys and units 5 to 45 degrees Us high setting numeric keys and units 0.8 to 1.1 Un Us low setting numeric keys and units 0.1 to 0.7 Un mode operating mode data + and - keys mode 1 to 4 dPhi phase shift value metering Usync1 voltage and Usync2 values metering REF restricted earth fault 64REF F641 F651 F661 Iso setting numeric keys and units 0.05 to 0.8 In BREAKER FAILURE protection against 50BF-62 F981 Is setting numeric keys and units 0.2 to 2 In T1 faulty CB retripping time delay numeric keys and units 0.05 to 65.5 s T2 adjacent CB retripping time delay numeric keys and units 0.05 to 65.5 s 3-ph I, assignment phase 1 I, of logic inputs phase 2 I, to trip data phase 3 I. data + and - keys Ioo-I1-I2 I11 to I18 I21 to I28 I31 to I38 Is setting numeric keys and units 3 to 200% In, T time delay value numeric keys and units 0.05 to 655 s circuit breaker failures UNBAL.ALx UNBAL.TRIPx percentage type overcurrent 50/51 x = capacitor number F111 F112 F121 F122 F131 F132 (1) (1) (1) according to the number of ESTOR logic input/output boards. Refer to the document entitled "testing", ref. 3140746, regarding protection testing. For further information on the protection function characteristics, .refer to the document entitled “Metering and protection functions”, ref. 3140747. Installation - Use - General characteristics - Testing 2/17 Use - commissioning Commissioning (cont’d) Sepam 2000 comprises standard program logic for operation in the most commonly used installations. The logic is adapted to suit each application diagram by parameter setting at the time of commissioning. If Sepam 2000 is customized, the parameters may serve a different purpose: please refer to the information package supplied by your OEM. Program logic and annunciation Resource and program logic chart function item for S26, S36 item for S25, S35 remarks logic input status I1, I2 I11 to I38 I1, I2 I11 to I38 1 = input supplied 0 = input not supplied output relay status O1, O2 O11 to O34 O1, O2 O11 to O34 1 = contact closed 0 = contact open internal relay status K1 to K512 K1 to K256 1 = contact closed; 0 = contact open stored bistable status B1 to B128 B1 to B32 1 = contact closed; 0 = contact open counter contents C1 to C24 C1 to C16 read time delay output status T1 to T60 T1 to T60 set between 50 ms and 655 s via numeric and units keys KP1 to KP16 set to 1 or 0 via data + and - keys or numeric keys 0 and 1 latched contacts impulse contacts KP1 to KP16 and KP33 to KP48 KP17 to KP32 KP49 to KP64 remote control contacts latched contacts impulse contacts KTC1 to KTC32 KTC33 to KTC96 KTC1 to KTC32 contacts set to 1 or 0 via a remote KTC33 to KTC64 control and monitoring system remote indication contacts KTS1 to KTS64 KTS1 to KTS32 contacts set to 1 or 0 for reading by the remote control and monitoring system alarm messages Bl1 to Bl16 not available reading of the last 16 automation activated messages (even if erased from display) parameters: latched contacts KP17 to KP32 For further information on the control and annunciation functions, refer to the document entitled “Control and monitoring functions” Réf 3140748. Connection of logic inputs ESB ESTOR1 Sepam motors Sepam substations busbars Sepam transformers Sepam capacitors Sepam (2) generators I1 closed position c c c c c (2) I2 open position c c c c c (2) I11 earthing switch position: contact open for earthing switch open c c c c c (2) I12 load shedding: NO contact c receive "blocking input" c c inhibit recloser c (1) c c VT circuit: contact closed for power ON I13 opening order: NC contact for shunt trip coil, NC contact for undervoltage release coil c c c c c (2) I14 close: NO contact c c c c c (2) I15 external protection tripping: NC or NC contact according to set up c c c c c (2) I16 pole pressure: contact closed for "breaking pole fault" c c c c c (2) I17 "drawn out" position: contact closed for "drawn out" c c c c c (2) I18 remote control enable: enables closing and acknowledgment: contact closed for enable c c c c c (1) (2) for substation application with recloser except for G00 Input I12 is used to inhibit the recloser input I12 recloser status 0 enabled/disabled status 1 inhibited 2/18 If locking takes place while a reclosing cycle is in progress, reclosing is instantly inhibited. Installation - Use - General characteristics - Testing ESTOR2 I21 reserved for external synchronization of communication I22 auxiliary voltage on, PTC sensors Sepam substations busbars Sepam transformers Sepam capacitors Sepam generators c c c c c (3) c c (1) emergency stop (NC contact) busbar VT circuit 1 (contact closed for power on) I23 c (2) c (3) c DGP: gas, level c (1) external generator shutdown control capacitor 1 switch open contact closed when switch open (C/O) I24 c DGP: pressure c (1) coupling enabled (closed for enabled) c capacitor 1 switch closed contact closed when switch closed (O/O) I25 c (3) c thermostat: alarm c (1) external de-energizing control c capacitor 1 switch open contact closed when switch closed (C/O) I26 busbar VT circuit c (5) transformer failure (alarm) c (4) c c (3) c Buchholz: alarm generator VT circuit c (5) transformer failure (tripping) c (4) c capacitor 3 switch open contact closed when switch closed (C/O) I28 c (3) c thermostat: tripping capacitor 2 switch closed contact closed when switch closed (O/O) I27 c (3) c Buchholz: tripping c capacitor 3 switch closed contact closed when switch closed (O/O) c (4) PTC sensor auxiliary voltage present ESTOR3 I31 c (3) Sepam substations busbars busbar VT circuit 2 (contact closed for power on) Sepam transformers Sepam capacitors Sepam (2) generators motors c (2) external disabling of capacitor control c I34 manual capacitor control c I35 automatic capacitor control c I36 varmeter control of capacitor 1 switch, contact closed for closing c I37 varmeter control of capacitor 2 switch, contact closed for closing c I38 varmeter control of capacitor 3 switch, contact closed for closing c (1) except for G00 for B07 for G00 (4) for G15, G16 (5) for G03, G04 (2) (3) Installation - Use - General characteristics - Testing 2/19 Use - commissioning Commissioning (cont’d) Connection of logic outputs ESB ESTOR1 O1 open: NO or NC contact according to set up Sepam motors Sepam substations busbars Sepam transformers Sepam capacitors Sepam (2) generators c c c c c (2) c (7) overcurrent or directional overcurrent O2 c close: NO contact c c c c (7) neutral or directional earth fault or restricted earth fault O11 c (2) c RTD alarm or RTD fault c neutral voltage displacement c (7) c reverse real power c neutral unbalance alarm, thermal overeload O12 cycle in progress c (1) reverse real power c (5) c fault tripping indication c c c c device fault (pressure fault or control fault) c c c c transmit "blocking input" c c c ESTOR2 Sepam motors Sepam substations busbars positive sequence undervoltage c (9) undervoltage c (6) Sepam transformers Sepam capacitors c (10) c undervoltage, or underfrequency busbars 1 (4) c closing order capacitor 1 switch c (3)(3) remanent undervoltage c c (10) overvoltage, or overfrequency c (4) undervoltage busbars 2 c closing order capacitor 1 switch O23 c (9)(11) underfrequency c intertripping O24 Sepam (2) generators c (10) c underfrequency O22 c (7) c (2) de-energizing O21 c (2) c (7) neutral voltage displacement O14 c (2) c (7) field loss (reverse reactive power) O13 c (2) neutral voltage displacement c (2) underfrequency or alarm: thermal overload, Buchholz, thermostat, gas detector, PTC sensors c (7) remanent undervoltage busbars 1 c (4) overfrequency c (8)(9)(11) overvoltage c (3) c generator shutdown c (2) overvoltage or tripping: thermal overload, Buchholz, thermostat, gas detector, PTC sensors c (7) c (4) minimum de tension rémanente barres 2 c capacitor switch fault (1) substation applications with recloser (2) except for G00 (3) except for B07 (4) for B07 (5) for S09 (6) except for S09 2/20 (7) for G00 for B12 (9) for B02 (10) except for G01, GO2, G12 (11) for S07, S08 (8) Installation - Use - General characteristics - Testing ESTOR3 O31 O32 O33 O34 Sepam substations busbars Sepam capacitors Sepam (1) generators motors c closing order capacitor 2 switch (2) overvoltage, or overfrequency busbars 1 c underfrequency setting x / rate of change of frequency setting x c (3) c opening order capacitor 2 switch (2) overvoltage busbars 2 c underfrequency setting x / rate of change of frequency setting x c (3) c closing order capacitor 3 switch synchronization c (2) underfrequency setting x / rate of change of frequency setting x c (3) c opening order capacitor 3 switch underfrequency setting x / rate of change of frequency setting x Sepam transformers c (3) (1) except for G00 for B07 (3) for B12 (2) Installation - Use - General characteristics - Testing 2/21 Use - commissioning Commissioning (cont’d) Time delay settings time delays T1 = 2 s (2) T2 = 0.2 s T3 = 0.2 s T5 = 0.2 s T6 = 0.2 s T16 = 0.2 s T4 T6 = 0.2 s T8 T9 T7 T21 T22 T23 T24 T25 T26 T27 T28 T29 T30 T31 T32 T33 T34 T35 T36 T7 = 10 s T8 T10 T24 T25 T26 T27 T4 = 1 s T25 = 0.2 s T26 = 0.2 s T10 T11 T12 T13 T14 T15 T10 (1) The time delays are factory-set by default to 200 ms. In the chart below, if the function is not used, setting of the related time delays is unnecessary. function trip circuit or open / closed matching supervision time delay for recovery of open/closed information upon changes in device position open / close control contactor diagram: tripping order duration logic discrimination inhibition of blocking input transmission after tripping open / close control by telecommunication duration of tripping order pulse transmitted via remote control duration of closing order pulse transmitted via remote control (T6 is also used by the restart function) confirmation of pressure switch fault Sepam 2000 : motor load shedding: external load shedding order time delay (input I12) restart: duration of closing order pulse transmitted via a restart order restart: maximum duration of voltage sag enabling restart restart: restart staggering time delay Sepam 2000 : capacitor after tripping, duration of reclosing inhibition (allows correct discharging of capacitors prior to re-energizing) capacitor 1 opening time delay (allows staggered opening of capacitor switches) capacitor 2 opening time delay (allows staggered opening of capacitor switches) capacitor 3 opening time delay (allows staggered opening of capacitor switches) circuit breaker opening time delay (the breaker only opens after the straggered opening of the capacitors) duration of capacitor 1 tripping pulse duration of capacitor 2 tripping pulse duration of capacitor 3 tripping pulse duration of capacitor 1 closing pulse duration of capacitor 2 closing pulse duration of capacitor 3 closing pulse after tripping, duration of capacitor 1 inhibition after tripping, duration of capacitor 2 inhibition after tripping, duration of capacitor 3 inhibition time delay for recovery of capacitor 1 switch open/closed information time delay for recovery of capacitor 2 switch open/closed information time delay for recovery of capacitor 3 switch open/closed information Sepam 2000 : busbars time during which instantaneous dF/dt data is maintained when load shedding with underfrequency only is chosen (KP33 = 1) maintain output O32 for synchro-check (set the time delay to several secondes if the output is not used) maintain closing request for synchro-check duration of load shedding pulses on O31 duration of load shedding pulses on O32 duration of load shedding pulses on O33 duration of load shedding pulses on O34 Sepam 2000 : substation time delay after closing (used to display transient phenomena) duration of tripping pulse duration of closing pulse recloser function: disengaging time delay recloser function: isolation time delay linked to cycle 1 recloser function: isolation time delay linked to cycle 2 recloser function: isolation time delay linked to cycle 3 recloser function: isolation time delay linked to cycle 4 recloser function: inhibition time delay Sepam 2000 : generator maintain closing request for synchro-check This time delay may be increased to mask switching problems. 2/22 Installation - Use - General characteristics - Testing Set up The parameters may be set using: c TSM 2001 pocket terminal, c SFT 2801 or SFT 2821 software. Sepam 2000: substation functions parameters open / close control KP1 KP2 circuit breaker with shunt-trip coil 0 0 circuit breaker with undervoltage release coil 1 0 latching contactor with tripping by shunt-trip coil 0 1 external protection logic inputs input I15, external protection tripping normally open contact KP4 = 0 normally closed contact KP4 = 1 disabled KP6 = 0 enabled KP6 = 1 inactive KP7 = 0 recloser: enable / disable with Sepam in local mode (input I18 = 0) recloser: recloser cycle set up reclosing cycle 1 active KP7 = 1 reclosing cycle 2 inactive KP8 = 0 active KP8 = 1 reclosing cycle 3 inactive KP9 = 0 active KP9 = 1 inactive KP10 = 0 active KP10 = 1 tripping linked to cycle 1 time-delayed KP11 = 0 instantaneous KP11 = 1 tripping linked to cycle 2 time-delayed KP12 = 0 instantaneous KP12 = 1 tripping linked to cycle 3 time-delayed KP13 = 0 instantaneous KP13 = 1 tripping linked to cycle 4 time-delayed KP14 = 0 instantaneous KP14 = 1 reclosing cycle 4 recloser: tripping set up definitive tripping time-delayed KP15 = 0 instantaneous KP15 = 1 counters reset to zero of operation counter KP19 = 1 reset to zero of phase fault trip counter KP20 = 1 reverse real power (Sepam 2000, S09 type) reverse real power with tripping KP36 = 1 reverse real power with annunciation KP36 = 0 remote setting remote setting enable KP38 = 0 remote setting disable KP38 = 1 disturbance recording inhibition KP50 = 1 automatic triggering KP51 = 1 manual triggering KP52 = 1 other display of program logic set up KP17 = 1 BI (blocking input) pilot wire test KP18 = 1 Installation - Use - General characteristics - Testing 2/23 Use - commissioning Commissioning (cont’d) Sepam 2000: busbars functions open / close control circuit breaker with shunt-trip coil circuit breaker with undervoltage release coil atching contactor with tripping by shunt-trip coil external protection logic inputs input I15, external protection tripping counters reset to zero of operation counter reset to zero of phase fault trip counter type of load shedding (Sepam 2000, B12 type) underfrequency or dF/dt underfrequency AND NOT dF/dt synchro-check (Sepam 2000, B07 type) acknowledgment of operating mode with power off no acknowledgment of operating mode with power off remote setting remote setting enable remote setting disable disturbance recording inhibition automatic triggering manual triggering other display of program logic set up BI (blocking input) pilot wire test parameters KP1 KP2 0 0 1 0 0 1 normally open contact normally closed contact KP4 = 0 KP4 = 1 KP19 = 1 KP20 = 1 KP33 = 0 KP33 = 1 KP35 = 1 KP35 = 0 KP38 = 0 KP38 = 1 KP50 = 1 KP51 = 1 KP52 = 1 KP17 = 1 KP18 = 1 The parameters are set using the TSM 2001 pocket terminal. Sepam 2000: SX functions open / close control circuit breaker with shunt-trip coil circuit breaker with undervoltage release coil latching contactor with tripping by shunt-trip coil inputs I1 = close, I2 = open I1 = close, I2 = receive blocking input outputs O1 = open, O2 = close O1 = open, O2 = send blocking input counters reset to zero of operation counter reset to zero of phase fault trip counter remote setting remote setting enable remote setting disable disturbance recording inhibition automatic triggering manual triggering other display of program logic set up BI (blocking input) pilot wire test 2/24 parameters KP1 KP2 0 0 1 0 0 1 KP3 = 0 KP3 = 1 KP4 = 0 KP4 = 1 KP19 = 1 KP20 = 1 KP38 = 0 KP38 = 1 KP50 = 1 KP51 = 1 KP52 = 1 KP17 = 1 KP18 = 1 Installation - Use - General characteristics - Testing Sepam 2000: transformers functions parameters open / close control KP1 KP2 circuit breaker with shunt-trip coil 0 0 circuit breaker with undervoltage release coil 1 0 latching contactor with tripping by shunt-trip coil 0 1 external protection logic input input I15, external protection tripping normally open contact KP4 = 0 normally closed contact KP4 = 1 Buchholz / thermostat / DGPT / external protection logic inputs inputs I23 to I28 excited, normally open contact KP5 = 0 if fault detection by Buchholz / thermostat / DGPT normally closed contact KP5 = 1 input I23, detection of gas or drop in level tripping KP6 = 0 alarm KP6 = 1 protection tank frame leakage KP7 = 0 restricted earth fault KP7 = 1 counters reset to zero of operation counter KP19 = 1 reset to zero of phase fault trip counter KP20 = 1 remote setting remote setting enable KP38 = 0 remote setting disable KP38 = 1 disturbance recording inhibition KP50 = 1 automatic triggering KP51 = 1 manual triggering KP52 = 1 other display of program logic set up KP17 = 1 BI (blocking input) pilot wire test KP18 = 1 Installation - Use - General characteristics - Testing 2/25 Use - commissioning Commissioning (cont’d) Sepam 2000: generators (except for G00 type) functions parameters open / close control KP1 KP2 circuit breaker with shunt-trip coil 0 0 circuit breaker with undervoltage release coil 1 0 latching contactor with tripping by shunt-trip coil 0 1 contactor with impulse control 1 1 transformer monitoring (Sepam 2000, G15 and G16 types) transformer sensors normally closed contact KP4 = 0 normally open contact KP4 = 1 counters rest to zero of operation counter KP19 = 1 reset to zero of phase fault trip counter KP20 = 1 reset to zero of running hours counter KP21 = 1 other tripping latching de-energizing shutdown undervoltage, setting 1 KP5 = 1 undervoltage, setting 2 KP6 = 1 overvoltage, setting 1 KP7 = 1 overvoltage, setting 2 KP8 = 1 neutral voltage displacement KP9 = 1 underfrequency KP10 = 1 overfrequency KP11 = 1 undervoltage, setting 1 KP13 = 1 undervoltage, setting 2 KP14 = 1 overvoltage, setting 1 KP15 = 1 overvoltage, setting 2 KP16 = 1 overvoltage, setting 1 KP7 = 1 overvoltage, setting 2 KP8 = 1 reverse real power KP12 = 1 display of set up control scheme KP17 = 1 BI (blocking input) pilot wire test KP18 = 1 remote setting remote setting enable KP38 = 0 remote setting disable KP38 = 1 disturbance recording inhibition KP50 = 1 automatic triggering KP51 = 1 manual triggering KP52 = 1 synchro-check (Sepam 2000, G03 and G04 types) with synchro-check KP34 = 0 no synchro-check KP34 = 1 acknowledgment of operating mode with power off KP35 = 1 no acknowledgment of operating mode with power off KP35 = 0 transformer monitoring (Sepam 2000, G15 and G16 types) transformer sensors normally closed contact KP35 = 0 normally open contact KP35 = 1 use of Sepam 2000, G01, G02 and G12 types with G00 (generator-transformer units) disabling of reverse real and reactive power protections 2/26 KP33 = 1 Installation - Use - General characteristics - Testing Sepam 2000: generators, G00 type functions Buchholz / thermostat / DGPT logic inputs transformer sensors parameters normally closed contact normally open contact tripping alarm input I23, detection of gas or drop in level latching underfrequency undervoltage, setting 1 undervoltage, setting 2 overvoltage, setting 1 overvoltage, setting 2 assignment of inputs / outputs outputs O21 to O24 without transformer failure outputs O21 to O24 with transformer failure input I18: remote control enable (acknowledgment, remote setting) KP5 = 0 KP5 = 1 KP6 = 0 KP6 = 1 KP10 = 1 KP13 = 1 KP14 = 1 KP15 = 1 KP16 = 1 O21 O22 O23 O24 O21 O22 O23 O24 undervoltage overfrequency underfrequency overvoltage undervoltage OR underfrequency overfrequency OR overfrequency Buchholz / thermostat / DGPT with alarm Buchholz / thermostat / DGPT with tripping enable if I18 = 1 enable regardless of position of I18 remote setting remote setting enable remote setting disable disturbance recording inhibition automatic triggering manual triggering KP33 = 0 KP33 = 1 KP34 = 1 KP34 = 0 KP38 = 0 KP38 = 1 KP50 = 1 KP51 = 1 KP52 = 1 Sepam 2000: motors functions parameters open / close control KP1 KP2 KP3 circuit breaker with shunt-trip coil 0 0 0 circuit breaker with undervoltage release coil 1 0 0 latching contactor with tripping by shunt-trip coil 0 1 0 contactor with impulse control 1 1 0 contactor with latched control 1 1 1 transformer monitoring transformer sensors normally closed contact KP4 = 0 normally open contact KP4 = 1 counters reset to zero of operation counter KP19 = 1 reset to zero of phase fault trip counter KP20 = 1 reset to zero of running hours counter KP21 = 1 remote setting remote setting enable KP38 = 0 remote setting disable KP38 = 1 disturbance recording inhibition KP50 = 1 automatic triggering KP51 = 1 manual triggering KP52 = 1 other display of program logic set up KP17 = 1 BI (blocking input) pilot wire test KP18 = 1 Installation - Use - General characteristics - Testing 2/27 Use - commissioning Commissioning (cont’d) Set up: capacitors functions parameters open / close control KP1 KP2 circuit breaker with shunt-trip coil 0 0 circuit breaker with undervoltage release coil 1 0 latching contactor with tripping by shunt-trip coil 0 1 transformer monitoring transformer sensors normally closed contact KP4 = 0 normally open contact KP4 = 1 counters reset to zero of operation counter KP19 = 1 reset to zero of phase fault trip counter KP20 = 1 reset to zero of running hours counters KP21 = 1 choice of number of capacitors KP36 KP37 3 capacitors 0 0 2 capacitors 0 1 1 capacitor 1 1 remote setting remote setting enable KP38 = 0 remote setting disable KP38 = 1 disturbance recording inhibition KP50 = 1 automatic triggering KP51 = 1 manual triggering KP52 = 1 switch open / close control capacitor 1 switch closing KP54 = 1 capacitor 1 switch opening KP55 = 1 capacitor 2 switch closing KP56 = 1 capacitor 2 switch opening KP57 = 1 capacitor 3 switch closing KP58 = 1 capacitor 3 switch opening KP59 = 1 capacitor control manual control KP60 = 1 automatic control KP61 = 1 other display of program logic set up KP17 = 1 BI (blocking input) pilot wire test KP18 = 1 2/28 Installation - Use - General characteristics - Testing The parameters in the chart below serve as operating assistance. They do not correspond to control and monitoring function parameter settings. They automatically switch back to zero 30 seconds after they are set to 1. parameter function KP17 = 1 display of program logic set up: circuit breaker with shunt-trip coil circuit breaker with undervoltage release coil latching contactor contactor with impulse orders contactor with latched orders KP18 = 1 pilot wire testing: KP18 active if output O14 set to send blocking input Sepam units which receive the blocking input display the message RECEIVE BI. This contact facilitates pilot wire testing. KP19 = 1 reset to zero of operation counter (C1) KP20 = 1 reset to zero of phase fault trip counter (C2) and earth fault trip counter (C3 for substation Sepam) KP21 = 1 motor and generator Sepam: reset to zero of running hours counter (C3) capacitor Sepam: reset to zero of running hours counters (C4, C5, C6) KP22 = 1 substation Sepam: reset to zero of specific recloser counters (C4 to C8) open / close control display message SHUNT-TRIP U/V RELEASE LATCH CTRL IMP. CTRL PERM. CTRL logic discrimination counters Installation - Use - General characteristics - Testing 2/29 Use - commissioning Commissioning (cont’d) Commands and annunciation, busbar Sepam and substation Sepam (except for B07, B12 and S09) functions commands outputs trip O1 inhibit closing lockout transmit BI O14 phase overcurrent c c (2) c (2) c earth fault c c (2) c (2) c O11 O21 annunciation O22 O23 O24 fault trip O12 device message (1) fault O13 c OVERCURRENT c E/F undervoltage setting 1 c UNDERVOLT.1 undervoltage setting 2 c UNDERVOLT.2 pos. seq. undervoltage, setting 1 c P SEQ U/V1 pos. seq. undervoltage, setting 2 c P SEQ U/V2 c remanent undervoltage overvoltage setting 1 c OVERVOLT.1 overvoltage setting 2 c OVERVOLT.2 c neutral voltage displacement c N VOLT DISP directional overcurrent c c c c DIR O/C directional earth fault c c c c DIR. E/F reverse real power c c c c REVERSE P. underfrequency setting 1 c c UNDERFREQ.1 underfrequency setting 2 c c UNDERFREQ.2 overfrequency setting 1 c OVERFREQ. 1 overfrequency setting 2 c OVERFREQ. 2 c c pole pressure c c c trip circuit supervision c c c external protection tripping c detection of plugged connectors (DPC) .(1) On Sepam 2000 display unit (according to language versions). (2) c EXT. TRIP PRESSURE ? CONTROL ? CONNECTOR Unless the recloser function is active. 2/30 Installation - Use - General characteristics - Testing Busbar Sepam B07 functions commands annunciation device fault O13 message (1) trip O1 inhibit closing lockout transmit BI O14 fault trip O12 phase overcurrent c c c c c OVERCURRENT earth fault c c c c c E/F external protection tripping c c c pole pressure c c c c PRESSURE trip circuit supervision c c c ? CONTROL ? EXT. TRIP detection of plugged connectors (DPC) CONNECTOR VT supervision BUS 1 OR 2 VT functions outputs O11 annunciation O21 undervoltage setting 1 busbars 1 c undervoltage setting 2 busbars 1 c O22 O23 O24 O31 O32 O33 message (1) U/VOLT.1 B1 U/VOLT.2 B1 undervoltage setting 1 busbars 2 c U/VOLT.1 B2 undervoltage setting 2 busbars 2 c U/VOLT.2 B2 c remanent undervoltage busbars 1 c remanent undervoltage busbars 2 overvoltage setting 1 busbars 1 c overvoltage setting 2 busbars 1 c O/VOLT.1 B1 O/VOLT.2 B1 overvoltage setting 1 busbars 2 c overvoltage setting 2 busbars 2 c neutral voltage displacement busbars 1 O/VOLT.2 B2 c N VOLT DISP underfrequency setting 1 busbars 1 c underfrequency setting 2 busbars 1 c UNDERFREQ.1 UNDERFREQ.2 overfrequency setting 1 busbars 1 c overfrequency setting 2 busbars 1 c synchronization .(1) On Sepam 2000 display (according to language versions). Installation - Use - General characteristics - Testing O/VOLT.1 B2 OVERFREQ.1 OVERFREQ.2 c SYNCHRO. 2/31 Use - commissioning Commissioning (cont’d) Busbar Sepam B12 (load shedding) functions commands annunciation device fault O13 message (1) trip O1 inhibit closing lockout transmit BI O14 fault trip O12 phase overcurrent c c c c c OVERCURRENT earth fault c c c c c E/F external protection tripping c c c pole pressure c c c c PRESSURE trip circuit supervision c c c ? CONTROL ? EXT. TRIP detection of plugged connectors (DPC) functions CONNECTOR outputs O11 annunciation O21 O22 O23 O24 O31 O32 O33 O34 message (1) undervoltage setting 1 c U/VOLT.1 undervoltage setting 2 c U/VOLT.2 positive sequence undervoltage, setting 1 c P SEQ U/V1 positive sequence undervoltage, setting 2 c P SEQ U/V2 c remanent undervoltage REM. U/V overvoltage, setting 1 c O/VOLT.1 overvoltage, setting 2 c O/VOLT.2 neutral voltage displacement c (2) N VOLT DISP c underfrequency, setting 1 UNDERFREQ.1 c underfrequency, setting 2 UNDERFREQ.2 c underfrequency, setting 3 UNDERFREQ.3 c underfrequency, setting 4 overfrequency, setting 1 c overfrequency, setting 2 c OVERFREQ.1 OVERFREQ.2 c (4)(3) rate of change of frequency, setting 1 c (4) c (3) rate of change of frequency, seting 2 UNDERFREQ.4 c (4) c (4) LOM 1 LOM 2 (1) on Sepam 2000 display (according to language versions). (2) latching type (3) and (4) two possible set-ups according to choice of KP33: (3) (4) KP33 0 1 use c load shedding in all cases c the frequency derivative may be used to load shed faster triggered only by underfrequency with moderate frequency drop c load shedding with underfrequency only c the frequency derivative may be used to inhibit load shedding in cases of a sudden drop in frequency, indicating a problem that cannot be solved by load shedding. O31 UNDERFREQ.1 OR dF/dT 1 UNDERFREQ.1 AND NOT (instantaneous dF/dT setting 1) O32 UNDERFREQ.2 OR dF/dT 2 UNDERFREQ.2 AND NOT (instantaneous dF/dT setting 1) O33 UNDERFREQ.3 UNDERFREQ.3 AND NOT (instantaneous dF/dT setting 1) O34 UNDERFREQ.4 UNDERFREQ.4 AND NOT (instantaneous dF/dT setting 1) 2/32 Installation - Use - General characteristics - Testing Substation Sepam S09 (uncoupling) functions commands outputs O11 O21 annunciation O22 O23 O24 fault trip O12 device message (1) fault O13 trip O1 inhibit closing lockout transmit BI O14 phase overcurrent c c c c c OVERCURRENT earth fault c c c c c E/F undervoltage c c c c UNDERVOLT. c overvoltage setting 1 OVERVOLT.1 overvoltage setting 2 c c c c OVERVOLT.2 neutral voltage displacement c c c c N VOLT DISP directional overcurrent c c c c DIR O/C directional earth fault c c c c DIR E/F reverse real power c (2) c (2) c (2) c (2) REVERSE P. underfrequency setting 1 c c c c UNDERFREQ.1 underfrequency setting 2 c c c c UNDERFREQ.2 overfrequency setting 1 c c c c OVERFREQ.1 overfrequency setting 2 c c c c OVERFREQ.2 rate of change of frequency setting 1 c c c c LOM 1 rate of change of frequency setting 2 c c c c LOM 2 external protection tripping c c c c EXT. TRIP pole pressure c c c PRESSURE trip circuit supervision c c c ? CONTROL ? detection of plugged connectors (DPC) c (3) CONNECTOR (1) on Sepam 2000 display (according to language versions). if KP36 = 1 (tripping triggered by reverse real power). if KP 36 = 0 (annunciation of reverse real power). (2) and (3) one or the other according to choice of KP36. (2) (3) Installation - Use - General characteristics - Testing 2/33 Use - commissioning Commissioning (cont’d) Operation: motors functions commands annunciation inhibit closing lockout thermal overload c c c c THERMAL phase overcurrent c c c c c OVERCURRENT earth fault c c c c c E/F negative sequence / unbalance c c c c UNBALANCE locked rotor / excessive start time c c c c LOCK. ROTOR LONG START undercurrent c c c c U/CURRENT number of starts positive sequence undervoltage c transmit BI O14 alarm O11 fault trip O12 device fault O13 message (1) trip O1 c STARTS/HOUR c LOAD SHED c direction of rotation ROTATION directional earth fault c c c c DIR. E/F reverse real power c c c c REVERSE P. reactive overpower c c c c FIELD LOSS RTD x (1...12) (2) alarm c c RTD X (1...12) RTD x (1...12) (2) tripping c c c c RTD X (1...12) motor differential c c c c MOTOR DIFF. external protection tripping c c c c EXT. TRIP c c c c c c RTD fault pole pressure load shedding trip circuit supervision c c c detection of plugged connectors (DPC) (1) (2) RTD FAULT PRESSURE LOAD SHED ? CONTROL ? CONNECTOR on Sepam 2000 display (according to language versions). 6 or 12 RTDs according to types of Sepam 2000. 2/34 Installation - Use - General characteristics - Testing Operation: transformers functions commands thermal overload (tripping) outputs trip O1 inhibit closing lock out c c c transmit O21 BI O14 O22 annunciation O23 O24 alarme fault trip O11 O12 device fault O13 c THERMAL phase overcurrent settings 1 and 3 (2) c c c c c LOW O/C phase overcurrent settings 2 and 4 (2) c c c c c HIGH O/C earth fault (3) c c c c neutral voltage displacement (4) c c c directional overcurrent (2) c c directional earth fault(3) c tank frame leakage neutral setting 1 neutral setting 2 undervoltage remanent undervoltage (1) THERMAL c thermal overload (alarm) message c E/F c N VOLT DISP c c DIR. O/C c c c DIR. E/F c c c c c FRAME LEAK c c c c c NEUTR. O/C1 c c c c c NEUTR. O/C2 (5) c c UNDERVOLT. c (5) overvoltage setting 1 (6) c overvoltage setting 2 (6) c c RTD x (1 to 6) alarm RTD x (1 to 6) tripping c c c c c c c c c c c c c c c c restricted earth fault Buchholz alarm Buchholz tripping c thermostat alarm thermostat tripping c gas detector alarm OVERVOLT.1 OVERVOLT.2 c RTD X (1 to 6) c RTD X (1 to 6) c REF c c BUCHHOLZ c BUCHHOLZ c TR. TEMP c TR. TEMP c TR. GAS gas detector tripping c c c c c TR. GAS pressure detector c c c c c TRPRESSURE c c c c RTD alarm RTD tripping c c TR. TEMP c TR. TEMP c RTD auxiliary voltage detected c c pole pressure c c c PRESSURE trip circuit supervision c c c ? CONTROL ? external protection tripping c RTD FAULT c EXT. TRIP c RTD sensor fault detection of plugged connectors (DPC) RTD FAULT CONNECTOR (1) on Sepam 2000 display (according to language versions). phase overcurrent. (3) earth fault. (4) neutral voltage displacement. (5) undervoltage. (6) overvoltage. (2) Installation - Use - General characteristics - Testing 2/35 Use - commissioning Commissioning (cont’d) Generator Sepam (except for G00) functions commands outputs annunciation trip O1 inhibit closing lockout O14 O21 O22 O23 O24 alarm O11 phase overcurrent c c c c (3) thermal overload tripping c c c c (3) fault trip O12 c (3) voltage restrained overcurrent c c c negative sequence/ unblance c c c neutral c c c c (3) directional overcurrent c c c c (3) message (1) c OVERCURRENT c THERMAL c thermal overload alarm device faultl O13 THERMAL c O/C V REST c UNBLANCE c (3) c E/F c (3) c (3) c DIR. O/C (3) (3) earth fault E/F’ directional earth fault c c c c c DIR. E/F restricted earth fault c c c c c c REF generator differential c c c c c c (2) c (2) c (2) c c (4) GEN. DIFF (2) UNDERVOLT.1 c (2) UNDERVOLT.2 undervoltage setting 1 c c undervoltage setting 2 c (2) c (2) c (2) overvoltage setting 1 c (2) c (2) c (2) c (2) c c (2) OVERVOLT. 1 overvoltage setting 2 c (2) c (2) c (2) c (2) c c (2) OVERVOLT. 2 neutral voltage displacement c (2) c (2) c (2) c (3) c (2) N VOLT DISP underfrequency c (2) c (2) c (2) c (2) UNDERFREQ. overfrequency c (2) c (2) c (2) c (2) OVERFREQ. c (4) c c (4) c (4) (1) on Sepam 2000 display (according to language versions). depending on set up if circuit breaker (contactor) open (4) if circuit breaker (contactor) closed (2) (3) 2/36 Installation - Use - General characteristics - Testing functions reverse real power field loss (reverse reactive power) commands outputs trip O1 inhibit closing lockout c (3) c (3) c (3) (3) (3) (3) c c c annunciation O14 O21 O22 O23 O24 alarm O11 c (2)(3) c (3) c RTD x (1...12) alarm fault trip O12 device faultl O13 message (1) c (3) REVERSE P. c (3) FIELD LOSS c RTD X RTD x (1...12) tripping c c c c RTD X external protection tripping c c c c EXT. TRIP c c c c RTD sensor fault transformer alarm transformer tripping c c RTD FAULT c TRANSFO c TRANSFO c PTC sensor auxiliary voltage pole pressure c synchro-check c VT supervision c trip circuit supervision c c PTC FAULT c (4)(2) PRESSURE ANGLE GAP (5) FREQ. GAP (5) VOLTAGE GAP (5) SYNC GAP (5) c c U. SYNC 1 FAIL U. SYNC 2 FAIL c detection of plugged connectors (DPC) ? CONTROL ? CONNECTOR emergency stop c c c de-energizing c c c c EXT. STOP. DESEXCIT. (1) on Sepam 2000 display (according to language versions). (2) phase overcurrent. (3) earth fault. (4) neutral voltage displacement. (5) undervoltage. (6) overvoltage. Installation - Use - General characteristics - Testing 2/37 Use - commissioning Commissioning (cont’d) Generator Sepam G00 functions The use of the G00 type generator Sepam 2000 is limited to the protection of average-size generator-transformer units, combined with types G01, G02 and G12. commands outputs lockout O1 phase overcurrent c directional overcurrent c neutral c directional earth fault c restricted earth fault c undervoltage c (1) overvoltage c (1) underfrequency c (1) overfrequency c neutral voltage displacement c reverse real power c field loss (reverse reactive power) c Buchholz alarm c Buchholz tripping c thermostat alarm PTC alarm c thermostat tripping PTC tripping c gas detector alarm (KP6 = 1) c gas detector tripping (KP6 = 0) c pressure detector c transmit BI O14 O2 annunciation O11 O21 O22 O23 O24 c c messages (1) OVERCURRENT c DIR. O/C c EARTH FAULT c DIR E/F c REF c UNDERVOLT.x c (2) c c (2) c (2) c (2) OVERVOLT.x UNDERFREQ. c OVERFREQ. c N VOLT DISP c detection of plugged connectors (DPC) (2) O13 c PTC sensor auxiliary voltage (1) O12 REVERSEP. c FIELD LOSS c (2) BUCHHOLZ c (2) c (2) TR. TEMP c (2) c (2) c (2) BUCHHOLZ TR. TEMP TR. GAS c (2) TR. GAS c (2) TRPRESSURE RTD FAULT CONNECTOR according to set-up (protection latching) according to set-up (assignment of outputs: according to G00-A or new assignment). 2/38 Installation - Use - General characteristics - Testing Operation: capacitors functions commands annunciation trip O1 inhibit closing lockout thermal overload tripping c c c phase overcurrent c c c earth fault c c c transmit BI O14 alarm O11 fault trip O12 device fault O13 c thermal overload alarm message (1) THERMAL c THERMAL c c OVERCURRENT c c EARTH FAULT c neutral to neutral unbalance alarm (single capacitor) UNBAL. ALARM neutral to neutral unbalance tripping (single capacitor) c c c c UNBAL. TRIP undervoltage c c c c UNDERVOLT. overvoltage setting 1 c c c c OVERVOLT.1 overvoltage setting 2 c c c c OVERVOLT.2 DISCHARGE X (2) c delay capacitor re-energizing c c pole pressure c c c PRESSURE trip circuit supervision c c c ? CONTROL ? external protection tripping c c EXT. TRIP detection of plugged connectors (DPC) CONNECTOR VT supervision VT functions commands close switch 1 O21 trip switch 1 O22 annunciation close switch 2 O31 trip switch 2 O32 close switch 3 O33 trip switch 3 O34 alarm O11 device fault O24 message (1) unbalance (3 cap.) capacitor 1 alarm c UNBAL.AL1 unbalance (3 cap.) capacitor 2 alarm c UNBAL.AL2 unbalance (3 cap.) capacitor 3 alarm c UNBAL.AL3 c unbalance (3 cap.) capacitor 1 tripping UNBAL.TRIP1 c unbalance (3 cap.) capacitor 2 tripping UNBAL.TRIP2 c unbalance (3 cap.) capacitor 3 tripping UNBAL.TRIP3 trip circuit supervision capacitor 1 switch c ? CONTROL1 ? trip circuit supervision capacitor 2 switch c ? CONTROL2 ? trip circuit supervision capacitor 3 switch c ? CONTROL3 ? varmeter control (1) (2) c c c c c c On Sepam 2000 display (according to language versions). With x = capacitor number, if several of them. Installation - Use - General characteristics - Testing 2/39 Use - commissioning Commissioning (cont’d) Disturbance recording This function is only available with S26 and S36. Activation of disturbance recording application busbars substations motors transformers capacitors generators SX KP52 c c c c c c c KTC52 c c c c c c c instantaneous O/C c c c c c c c directional inst. O/C c c instantaneous earth fault c c c c directional inst. earth fault c c c c O12 output c c c c c c c c c c c (1) c Logical states recorded function KFR1 output O1 c KFR3 KFR4 KFR5 (1) output O14 instantaneous O/C directional inst. O/C c c c c instantaneous earth fault directional inst. earth fault (1) KFR6 c output O2 output O12 KFR2 for the G00 type Sepam 2000, O12 is replaced by the OR parameter of the tripping outputs (O1, O2, O11, O12, O13, O21, O22, O23 and O24). 2/40 Installation - Use - General characteristics - Testing Use – commissioning Maintenance List of Sepam 2000 self-tests functions type of self-test execution periodicity fail-safe position power supply detection of processor supply out of range detection of a drop in supply voltage continuously YES YES current acquisition detection of analog channel saturation current channel consistency check (2) continuously YES (1) YES (2) voltage acquisition detection of analog channel saturation periodically YES (1) CB control inputs/outputs output relay supply checking Input / Output (I/O) control tests checking of Output status (3) switching on and continuously YES YES YES logic inputs / outputs program logic output relay supply checking Input / Output (I/O) control tests (3) checking of Output status (3) switching on and continuously YES YES YES processing unit switching on and: continuously periodically continuously continuously periodically continuously YES YES YES YES YES YES cartridge present test memory test number of entries in parameter backup memory test switching on and: continously periodically continuously YES YES NO memory test display CPU test switching on and periodically NO NO memory test communication CPU test monitoring of dialogue with processing unit switching on and: periodically periodically continouusly NO NO NO CPU test working memory test signal selector & signal digitization test measurement acquisition test hardware & cartridge software consistency test software watchdog (limited time allocation to each function) cartridge display communication analog inputs (3) (1) (2) (3) reference channel checking (3) input validity checking (3) continuously NO NO does not cause switching to fail-safe position for Sepam 2000 S46. seft-test not performed for Sepam 2000 S46. for Sepam 2000 S46 only. Installation - Use - General characteristics - Testing 2/41 Use - commissioning Maintenance (cont’d) Sepam 2000 comprises self-testing and self-diagnosis to facilitate installation maintenance. Indicator lamps and display messages c Green indicator lamp lit up: Le Sepam 2000 est sous tension. c No indicator lamps lit up: there is probably an auxiliary power supply fault. Check the auxiliary power supply and CE40 board connections and perform the lamp test. c Red lamp indicates internal Sepam 2000 faults. Sepam 2000 continuously performs on-line internal tests. When the test results are negative, Sepam automatically runs a series of sequences which result in either: v automatic reinitialization (minor fault, e.g. transient auxiliary power supply break). Sepam 2000 carries out a complete restart sequence. If restart is successful, Sepam operates again normally; during the sequence, all the output relays are dropped out (1), v switching to the fail-safe position (major fault). Sepam 2000 goes into the fail-safe position. All the output relays drop out (1 )in order to avoid inadvertent commands, and the watchdog drops out as well. The following may cause internal faults: c missing cartridge: v red indicator lamp lit up, v display OFF, v no dialogue with pocket terminal, v no dialogue with communication link, v watchdog dropped out, v switching to fail-safe position. Sepam 2000 will not start, lacking a program: this is a major fault, c set-up fault: v red indicator lamp lit up, v red lamp indicates CARTRIDGE, v no dialogue with pocket terminal, v no dialogue with communication link, v the watchdog is dropped out, v switching to fail-safe position. Sepam 2000 is shut down: this is a major fault. v on Sepams (S35 LS, LR, KR, KZ) with a date code higher than 97 xx, the 2 ECM boards are not the same model; two ref. 3122 288 boards or two ref. 03143179FA boards are required. v The type of cartridge is not compatible with the Sepam model. c hardware fault on cartridge: v red indicator lamps lit up, v display indicates M CARTRIDGE, v no dialogue with pocket terminal, v no dialogue with communication, v the watchdog is dropped out, v switching to fail-safe position. Sepam 2000 is shut down: this is a major fault. v the cartridge is faulty, v disconnect the auxiliary power supply, v Sepam is automatically out of order until a new cartridge is installed. Consult your maintenance department. c other major faults: v red indicator lit up, v display indicates MAINTENANCE, v no dialogue with the pocket terminal, v no dialogue with the communication link (if the CPU is faulty), v the watchdog is dropped out, v switching to the fail-safe position. Sepam 2000 is shut down: this is a major fault. Consult your maintenance department. c minor or partial fault: v red indicator extinguished, v display indicates MAINTENANCE, v dialogue with the pocket terminal is maintained, v dialogue with the communication link is maintained, v the watchdog does not drop out. Sepam 2000 is operating, however it has detected a transient fault or a component has failed to pass self-testing. Consult your maintenance department. c other minor or partial fault: v red indicator extinguished, v display indicates M CARTRIDGE, v dialogue with the pocket terminal is maintained, v dialogue with communication is maintained, v the watchdog does not drop out again Sepam 2000 is operating, but it has detected a fault in the status parameter setting or an overrun of the number of entries written in the cartridge memory (S25/S35 only). Set the status parameters that are blinking or consult your maintenance department. (1) this may cause tripping with undervoltage program logic (so-called fail-safe logic). Caution: do not insert or remove cartridge while Sepam is energized. v Disconnect the auxiliary power supply and wait 2 seconds before handling the cartridge. Check the references on the Sepam and on the cartridge (refer to your Sepam 2000 identification chapter). v Sepam 2000 is automatically disabled until the appropriate cartridge is installed. 2/42 Installation - Use - General characteristics - Testing c The display indicates: ********** or ----------v No measurements have been requested. v The requested measurement is not available. v Measure is out of range. c The display indicates: CONNECTOR v Indication that one or more connectors are unplugged. Check that the connectors are plugged in and tightened by screws on the rear of the device. Check that the DPC has been strapped on all the connectors. c The display indicates: ? CONTROL ? v The circuit breaker shunt trip mechanism is faulty. Possible causes: - loss of auxiliary power supply, - broken coil , - disconnected or damaged wiring, - device position contacts stuck. Check the cabling and the state of the different contacts. Sepam prevents the device from closing. v When the ? CONTROL ? message appears the first time that Sepam 2000 is energized Press the reset key to acknowledge the message. Set the T1 time delay to 2 s. c The display indicates: RTD FAULT The wiring of the temperature sensor (or sensors) is faulty: - broken wire, - shorted wire. Check the wiring and condition of the different RTDs as well as the PTC sensor power supply. Communication indicator lamps These lamps are located at the rear of the device on the CE40 module when the module is equipped with the communication option. c green indicator lamp blinking: indicates traffic on the line. This is the normal operating mode. c indicator lamps extinguished: there is no communication. Check the cabling and inquiries at the level above. c red indicator lamp lit up: indicates initialization of the coupler, which lasts about 2 seconds, or a coupler fault. Consult your maintenance department. c red indicator lamp lit up and the recommendations given in the maintenance chapter do not allow Sepam 2000 to be restarted. Call in the maintenance department. Unwanted tripping, no trippping Incorrect parameter setting may cause unwanted tripping or no tripping (1). Check the parameter and protection settings. Tests c Lamp test: when the user presses the A et V/Hz measurement keys simultaneously, all the indicators on the front of the device light up as well as the display which indicates alternately ******** and 0000000000. c Logic discrimination pilot wire link test. Program logic menu parameters KP18 = 1 n The display indicates: PTC FAULT The PTC sensor auxiliary voltage is faulty. activation of "blocking input" output check processing by upstream Sepam input I12 (RECEIVE BI message) Check the PTC sensor power supply. c The display indicates: PRESSURE The breaking pole pressure contact indicates a drop in gas pressure. Sepam 2000 inhibits breaking device closing. Please refer to the breaking device maintenance manual. c The display indicates: ! ERROR ! Parameter setting incoherent with parameters KP1, KP2, KP3 Check parameter setting. Sepam 2000 replacement When Sepam 2000 is replaced: c switch off Sepam 2000, c dismantle the Sepam 2000 to be replaced, c remove the cartridge, c mount the Sepam 2000 replacement, (hardware configuration) c install the cartridge, c verify the compatibility of the cartridge and Sepam 2000 (see chapter on identification), c set microswitches SW1 and SW2 on the rear of the device in the same positions as they were in on the Sepam 2000 that was replaced, c install the connectors, checking their markings, c energize Sepam 2000. (1) All the settings should be based on a network discrimination study that is to be carried out prior to commissioning. Installation - Use - General characteristics - Testing 2/43 Use – commissioning Sepam 2000 identification Sepam identification using the pocket terminal Menu: About Sepam About Sepam SFT2800 Program logic Communication Enter application type SFT2800 6XRS05FA SFT2800 CAT 98.02 Configurator version no. 6 = Sepam S36 XR = model S05 = type F = French A = rev. level CAT = standard configuration About Sepam SFT2800 Program logic Communication Enter program logic diagram refer Program Logic 161SFA CAT LDR APPLICATION SUBSTATION Program Logic program date : 97/12/01 15:08 LOGIPAM : 98.02 CAT : standard program logic (1) (1) LDR : the "source" file is loaded in the cartridge name of program diagram produced by LOGIPAM program logic programming date configurator version In the event of a cartridge error or incompatibility Sepam 2000, the message CARTRIDGE appears on the front of the device. Check the coherence between the cartridge and Sepam 2000 using the compatibility list given on the next page. Communication J bus : V 3.0 Jbus communication version 3.0 Others messages: - FIP ISIS - FIP I/O - Communication not installed press menu key (1) remark: labels LDR and NOL labels: these labels refer to the presence or absence of a “source” file visible with the “Logipam” software package. NOL: the program logic “source” file is not included in the cartridge. LDR: the “source” file has been changed in the cartridge and therefore cannnot be reinitialized (2) using a PC, equipped with the LOGIPAM software package and the PER2901 programming device. CAT: this label signifies that the standard program logic is factory-set. When this label is not present, the logic in the Sepam has been customized. (2) the “reuse” operation is described in the LOGIPAM programming manual. 2/44 Installation - Use - General characteristics - Testing Compatibility of types and models type Sepam 2000 model nb of ESTOR S25-S26 S35-S36 standard Sepam 2000 model nb of ESTOR S25-S26 S35-S36 standard S01 LX YR 1 S02 LT XR 2 T01 LX YR 2 T02 LT XR 2 S03 LT XR 2 S04 LT XR 1 T03 - KR 2 T04 LX YR 1 S05 LT XR S06 LT XR 1 T05 LT XR 1 2 T06 - LR 2 S07 LT S08 LT XR 2 T07 - LR 1 XR 2 T09 LT XR 2 S09(2) LT XR 2 T10 LT XR 2 SX1 LX - 0 T11 LT XR 1 SX2 LT - 0 T12 - LR 1 T13 - LR 1 LT XR 2 substation type transformers busbars B01 LX YR 1 T14 B02 LT XR 2 T15 - LR 2 B03 LT XR 1 T16 LT XR 1 2 T17 LT XR 2 B04 LT XR (1) - TR 3 T18 - LR 2 B12 (1) - XR 3 T19 LT XR 2 T21 LS ZR 2 T22 - SR 2 T23 - KZ 2 T24 LS ZR 1 T25 - SR 1 T26 - LS 2 T27 - LS 1 T29 - SR 2 T30 - SR 2 T31 - SR 1 T32 - LS 1 T33 - LS 1 T34 - SR 2 T35 - LS 2 T36 - SR 1 T37 - SR 2 T38 - LS 2 T39 - SR 2 B07 (1) (2) Installation - Use - General characteristics - Testing types available with S36 only. types available with S26 and S36 only. 2/45 Use – commissioning Sepam 2000 identification (cont’d) type Sepam 2000 model S25-S26 S35-S36 nb of ESTOR S46 type standard metering and control Sepam 2000 model ESTOR nb of S25-S26 S35-S36 S46 standard generators R01 LT XR - 2 G00 LT - 2 R02 - XR - 3 G01 LT XR 2 R03 - SR - 3 G02 - SR 2 R04 - SS - 2 G03 (1) - TR 2 (1) R06 - - RR 3 G04 - TS 2 R07 - - XR 3 G05 - XR 2 R08 - - NR 3 G06 - SR 2 (1) - XR 2 G08 (1) - SR 2 SS 2 R09 - - ZR motors 3 G07 M02 LX YR 1 G12 - M03 LT XR 1 G13 - SS 2 M04 LT XR 1 G15 (1) - LR 2 M05 LS ZR 1 G16 (1) - LS 2 M06 - LR 1 G17 (1) - LR 2 (1) - LS 2 M07 - LS 1 G18 M08 - LS 1 (1) M09 - SR 1 M11 - SR 1 M14 - LS 1 M15 LT XR 1 M16 - SR 1 M20 - SS 1 M21 - SS 1 M22 - SS 1 M23 - SS 1 types available with S36 only. (2) types available with S26 and S36 only. capacitors 2/46 C01 LX YR 1 C02 - KR 1 C03 LT XR 1 C04 - LR 1 C06 (1) - LR 1 C08 (1) - LR 3 Installation - Use - General characteristics - Testing Use – commissioning Sepam 2000 documentation reference (2) content use Sepam range AC0401 summarized description of the Sepam range selecting the type of Sepam: 100, 1000, 2000 motors PCRED398020 characteristics, selection table, connections installation studies substations - busbars PCRED398021 characteristics, selection table, connections installation studies transformers PCRED398022 characteristics, selection table, connections installation studies generators PCRED398023 characteristics, selection table, connections installation studies capacitors PCRED398024 characteristics, selection table, connections installation studies Sepam 2000 D22 differential protection transformer generator-transformer unit auto-transformer PCRED398061EN characteristics and connections installation studies metering and control PCRED398025 characteristics, selection table, connections installation studies SX PCRED398026 characteristics, selection table, connections installation studies for customized applications PCRED398027 description of programming resources making customized programs testing 3140746 A testing methods testing methods metering and protection 3140747 A operating principle, function characteristics installation studies, choice of protections, settings control and monitoring functions 3140748 A operating principle, caractéristiques installation studies installation, use and commissioning S25, S26, S35, S36 3140750 A cubicle mounting instructions description of display and TSM 2001 pocket terminal installation, parameter setting, commissioning, use Sepam 2000 D22 installation, use and commissioning 03146372EN-B0 cubicle mounting instructions description of display and pocket terminal, characteristics installation, parameter setting, commissioning, use installation, use and commissioning S46 03144988EN-A0 cubicle mounting instructions description of display and pocket terminal installation, parameter setting, commissioning, use Jbus/Modbus communication 3140751 A implementation of communication programming of the remote control and monitoring system RS 485 network connection guide 03146896EN-A0 choice of accessories commissioning of communication installation study and installation diagnosis guide 3140758 A diagnosis of Sepam 2000, 1000+ failures use, commissioning documentation (1) (2) (1) This documentation may be procured from your Merlin Gerin correspondent. References: followed by the letter A for documentation in English, followed by the letter F for documentation in French. Installation - Use - General characteristics - Testing 2/47 Use – commissioning Password Use of the password c at the end of the sequence, the following window is displayed: The user enters a password via the pocket terminal in order to be able to change parameters and settings. Validate settings Yes = Enter No = Clear Code key When the user presses the code key, the following menu appears: c presser enter: the new password is validated. Enter your password then press enter key Please note: If the passwords entered for "new" and "verif" are different, the following meassage is displayed: new password not valid press "clear" type the following on the keyboard 6543210 (1) and then press enter. This the password for standard Sepams. If your Sepam has been customized, refer to the documentation provided by your OEM. To exit from this mode, simply: c press the code key c wait 2 min after activating any key. When the pocket terminal is in parameter setting mode, P\ appears on the top left of the screen. Loss of the password Modification of the password c go to parameter setting mode c in the Status menu, choose the password heading using the arrow and press enter. The following window is displayed: PASSWORD old = new = verif. = If the original password has been modified and the latest password entered has been permanently lost by the user, the only means of regaining access to modification of parameters and settings is to reprogram the cartridge using a PC equipped with the LOGIPAM software package, the PER2901 programmer and the Sepam program logic “source” file (regarding the “source” file, see the section on Sepam 2000 identification using the pocket terminal). N.B. Before reprogramming the cartridge, it is advisable to make a complete record of the values set in the Sepam as well as the identification information. This operation may be carried out using the TSM 2001 pocket terminal, SFT 2801 software package or SFT 2821 software package (upload). In case of difficulties, contact the Schneider after-sales department. (1) Code by default in standard program logic; with customization, the password is given by the installer. 4 to 7 digits are necessary. (2) c enter, one after the other - the password to be modified in the "old" line (2) - the new password in the "new" and "verif" lines - after each password, press enter to go to the next line N.B. If you do not want your operating personnel to know the password that gives access to the parameter setting mode, remove this page from the user's documentation. 2/48 Installation - Use - General characteristics - Testing General characteristics Contents chapter / page Installation - Use - General characteristics - Testing general characteristics 3/2 qualification tests 3/6 electrical tests aim preliminary operating test grounding continuity insulation testing dielectric strength impulse wave withstand power supply circuit robustness 3/7 3/7 3/7 3/7 3/7 3/7 3/7 3/7 performance tests in reference conditions aim checking of parameter specifications miscellaneous 3/8 3/8 3/8 3/8 testing of output effects in rated domains aim DC power supply analog input circuits logic input circuits logic output circuits ambient temperature 3/9 3/9 3/9 3/9 3/9 3/9 3/9 effects of the equipment on the environment aim DC power supply radiofrequency interference 3/10 3/10 3/10 3/10 effects of the environment on the equipment aim sensitivity to electromagnetic interference climatic and mechanical robustness tests 3/11 3/11 3/11 3/12 dependability definition dependability needs: a trade-off between to unwanted events consideration of dependability in Sepam 2000 self-monitoring functions and fail-safe position 3/14 3/14 3/14 3/14 3/14 reference documents standards 3/16 3/16 3/1 General characteristics Characteristics phase current inputs for 1 A or 5 A CT connection of 1 or 5 A CTs by 4 mm eye lugs, to CCA 660 or CCA 650 connector (connector with incorporated CTs) disconnectable on line wire cross-section 6 mm2 max. input impedance < 0.001 Ω power consumption < 0.001 VA for 1 A < 0.025 VA for 5 A steady state thermal withstand 3 In 1-second overload 80 In operating range up to 24 In CCA 660 or CCA 650 dielectric insulation 2 kV rms 1 min. (1) - IEC 60255-5 phase current inputs for CSP sensor connection of CSP sensors to BNC inlets by 5.5 m CCA 601 connection cable steady state thermal withstand 3 In 1-second overload 80 In operating range up to 24 In insulation input not insulated from earth input for earth current measurement with CSH 120 or CSH 200 core balance CT connection by 0.93 to 2.5 mm2 wire to CCA 606 screw terminal pad input impedance 2 A rating: 10 Ω 30 A rating: 0.7 Ω power consumption < 0.01 VA steady state thermal withstand 10 x rating (2) 1-second overload 20 kA (2) operating range up to 10 x rating insulation input not insulated from earth choice of rating 2 A or 30 A, according to the terminal used on the CCA 606 screw terminal pad input for earth current measurement with 1 A or 5 A CT (CT + CSH 30) connection by 0.6 to 2.5 mm2 wire, to CCA 606 screw terminal pad input impedance <4Ω power consumption < 0.1 VA steady state thermal withstand 10 x core balance CT rating (4) 1-second overload 500 x core balance CT rating (4) operating range 10 x core balance CT rating (4) insulation input not insulated from earth (3) input for earth current measurement with core balance CT other than CSH (core balance CT + ACE 990) connection input impedance by 0.6 to 2.5 mm2 wire, to CCA 606 screw terminal pad on terminals A2-A4: < 10 Ω on terminals A1-A4: < 4 Ω on terminals A3-A4: < 0.7 Ω power consumption on terminals A2-A4: < 0.1 VA on terminals A1-A4: < 0.4 VA on terminals A3-A4: between 2 and 10 VA (5) steady state thermal withstand 10 x core balance CT rating (4) 1-second overload 20 kA on core balance CT primary (4) operating range 10 x core balance CT rating (4) insulation input not insulated from earth (3) (1) this refers to insulation provided by the CCA 660 or CCA 650 CT connector. The Sepam input on the sub D connector is not insulated from earth. (2) current in primary circuit of CSH core balance CT, expressed in amps. (3) this refers to the Sepam 2000 input. The CSH 30 primary circuit is insulated from earth. (4) expressed as CT primary current (CT or core balance CT). (5) the consumption is given for an ACE 990 interface primary wiring resistance of less than 200 mΩ. Refer to Installation: use and connection of the ACE 990 interface. 3/2 Installation - Use - General characteristics - Testing voltage inputs for voltage transformer connection by 0.6 to 2.5 mm2 wire to CCA 608 terminal input impedance > 100 kΩ steady state thermal withstand 230 V 1-second overload 480 V operating range 0 to 180 V insulation 2 kV rms 1 min. - IEC 60255-5 external residual voltage input connection by 0.6 to 2.5 mm2 wire to CCA 608 terminal input impedance > 100 kΩ steady state thermal withstand 220 V 1-second overload 480 V operating range 0 to 200 V insulation 2 kV rms 1 min. - IEC 60255-5 RTD inputs (Pt 100) connection by 1 to 2.5 mm2 wire to CCA 621 terminal 2 or 3 wire mode current injected in RTD 4 mA power consumption < 0.1 VA type of RTDs RTD using IEC 60751 variation principle recommended wiring shielded wiring insulation input not insulated from earth DC analog inputs connection by 0.6 to 2.5 mm2 wire to CCA 621 terminal input impedance i 300 Ω input current range 0-20 ; 4-20 ; 0-10 ; ± 10 mA range choice paramoterizable self-calibration yes accuracy ± 0.3% full scale at 25 °C ± 0.5% full scale at 0-55 °C permanent overload 30 mA breaking frequency i 5 Hz insulation 2 kV rms 1 min. - IEC 60255-5 output relays connection by 0.6 to 2.5 mm2 wire to CCA 621 terminal making capacity 15 A 400 ms overload 15 A steady state current 8A number of switching operations 10 000 at full load contact/coil insulation 2 kV rms breaking capacity 24/30 Vdc 48 Vdc 125 Vdc 220/250 Vdc DC with resistive load DC at L/R = 20 ms DC at L/R = 40 ms AC with resistive load AC with p.f. = 0.3 8A 6A 4A 8A 5A 4A 2A 1A 8A 5A 0.8 A 0.4 A 0.2 A 8A 5A 0.3 A 0.15 A 0.1 A 8A 5A Installation - Use - General characteristics - Testing 3/3 General characteristics Characteristics (cont’d) Output relays of ESB and ESTOR boards manufactured prior to 1.1.2000. c ref. ESB24/30V : 3124217 c ref. ESB48/125V : 3122347 c ref. ESB220/250V : 3124287 I(A) I(A) 10 10 AC : resistive load 8 6 8 6 AC : cos ϕ = 0.3 AC : resistive load 4 4 50 R 0 0 25 DC : L = 0.02 s R 25 0.8 0.8 0.6 0.6 DC : resistive load 0 W W 0.4 0 50 50 W 0.2 W 0.2 DC : L = 0.02 s R 10 10 0.4 W 1 W 1 2 W DC: resistive load DC : L = 0.04 s 0 2 25 25 20 24 40 48 60 80 100 125 200 U(V) c Sepam 2000 output relay : O1, O2, O11 to O14, O21 to O24, O31 to O34 contacts. W W 0.1 10 0.1 10 20 24 40 48 60 80 100 125 200 V(V) c Sepam 2000 "watch dog" output. Output relays of ESB and ESTOR boards manufactured as of 1.1.2000. Output relays of SBW, STOR boards. c ref. ESB24/30V : 03145141FA c ref. ESB48/125V : 03145347FA c ref. ESB220/250V : 03145149FA c ref. ESTOR24/30V : 03145157FA c ref. ESTOR48/125V : 03145161FA c ref. ESTOR220/250V : 03145165FA I(A) I(A) 10 10 AC: resistive load 8 6 8 6 AC: cos ϕ = 0.3 2 W DC : L = 0.04 s 0 50 DC: resistive load R 0 0 25 DC : L = 0.02 s R 25 0.8 0.8 0.6 0.6 DC: resistive load W 0.4 W 50 50 W 0.2 W 0.2 DC : L = 0.02 s R 0 10 0 10 0.4 W 1 W 1 AC: resistive load 4 4 2 c ref. STOR : 03143281FA c ref. SBW : 03143287FA 40 48 60 80 100 125 200 U(V) 0.1 10 W W 20 24 c Sepam 2000 output relay : O1, O2, O11 to O14, O21 to O24, O31 to O34 contacts. 3/4 25 25 0.1 10 20 24 40 48 60 80 100 125 200 V(V) c Sepam 2000 "watch dog" output. Installation - Use - General characteristics - Testing Sepam 2000 logic inputs by 0.6 to 2.5 mm2 wire to CCA 621 terminal connection according to Sepam 2000 power supply 24/30 Vdc 48/127 Vdc 220/250 Vdc consumption level 0 level 1 permissible steady state overload pick up time insulation 4 mA (4) <6V > 17 V 36 V 10 ms 2 kV 4 mA (4) < 25,4 V > 33,6 V 152 V 10 ms 2 kV 3 mA < 50 V > 154 V 275 V 10 ms 2 kV Jbus/Modbus communication input connection cable (CCA 602 or CCA 619 accessory) transmission asynchronous serial protocol Jbus/Modbus slave electrical interface according to EIA- RS 485 standard maximum distance without repeater 1200 m number of Sepam 2000s on the line 31 max. rates 300, 600, 1200, 2400, 4800, 9600 19200, 38400 bits/s insulation 1 kV rms power supply connection by 0.6 to 2.5 mm2 wire to CCA 604 terminal dielectric insulation 2 kV rms - 1 min. power supply voltage permissible variations (3) 24/30 Vdc (5) 48/127 Vdc 220/250 Vdc -20% to +20% 20 V to 36 V -20% to +20% 39 V to 152 V -20% to +10% 176 V to 275 V power supply circuit consumption (Sepam 2000) (1) power supply voltage 24 Vdc 48 Vdc 127 Vdc 220 Vdc inrush current 5 A/0.2 s 1 A/0.5 s 1,5 A/0.5 s 1 A/0.2 s Sepam S26 or S25 all relays deactivated Sepam S26 or S25 all relays activated 0.5 A 0.8 A 0.25 A 0.5 A 0.12 A 0.2 A 0.08 A 0.12 A Sepam S36 or S35 all relays deactivated Sepam S36 or S35 all relays activated 0.6 A 1A 0.28 A 0.6 A 0.12 A 0.22 A 0.08 A 0.13 A 0.24 A 0.52 A 0.11 A 0.22 A 0.07 A 0.12 A Sepam 2046 all relays deactivated Sepam 2046 all relays activated weight (2) min. max. Sepam S26 or S25 6 kg 8.5 kg Sepam S36 or S35 8 kg 10.5 kg Sepam S46 9.5 kg 10.6 kg (1) the figures are given for: c Jbus/Modbus coupler option included (Subtract 1 W for Sepam 2000 without communication). c TSM 2001 pocket terminal not connected (Add 1/2 W if the pocket terminal is connected). c Sepam S25 or S26 equipped with 2 ESTOR. boards c Sepam S35 or S36 equipped with 3 ESTOR. boards. c Sepam S46 equipped with 5 ETOR boards. (2) The figures give the weight according to the number of options for each model. (3) correct operation of Sepam is only guaranteed within these ranges. (4) 10 mA for ESB and ESTOR boards manufactured prior to 1.1.2000. (5) not available with Sepam 2000 S46. Installation - Use - General characteristics - Testing 3/5 General characteristics Qualification tests This chapter presents the main specified properties (mechanical, electrical, functional, etc...) that are verified during the qualification tests carried out in the factory ("manufacturer" tests). It describes: c the content of each test, c the standards and reference documents, c the expected results. It is divided into seven sections, grouping together the different items involved in product qualification by theme: General Description of the general conditions which apply to all the tests. Technological tests Tests designed to ensure conformity of device manufacturing (with respect to the manufacturing specifications, company standards,...), and the device's implementation capability (installation, operation,...). Electrical tests Tests related to the protection of people and equipment (grounding continuity, insulation, fuses…). Performance tests in reference conditions Verification of special functional features (hardware and software) of the product when used in the "reference environment" (i.e. temperature, power supply… using strict tolerances). Testing of output effects in rated domains Examination of the rated operating domain (input signals, output loads, power supply...), using one variable at a time. Effects of the equipment on the environment Testing of interference (electromagnetic, mechanical...) generated by the product. Effects of the environment on the equipment Testing of the product's sensitivity and/or resistance to electromagnetic, mechanical, chemical... interference. Reference documents In order to facilitate reading, only documents of prime importance are succinctly referenced in each test description. For more details, please refer to the appendix. 3/6 Installation - Use - General characteristics - Testing General characteristics Electrical tests Aim Dielectric strength The aim of these tests is to test the effectiveness of the measures taken to protect people and equipment. Aim: to ensure that the dielectric strength of the insulation complies with specifications. Preliminary operating test Acceptance criteria: During the test: c no breakdowns, perforations, warping After the test: c the device must correspond to all of its functional specifications. Aim: to ensure the integrity of the item being tested (the test procedure allows the device, its integrated components and remote functions to be tested at the same time). N.B. The test is not exhaustive. It is merely aimed at providing a good "macroscopic" view of the item before and/or after the application of potentially destructive stress, in a minimal test environment. Grounding continuity Aim: to test the continuity of grounding protection. Reference documents: Standards: IEC 61131-2 Reference documents: Standards: IEC 60255-5 Severity : circuits power supply logic inputs analog inputs logic outputs setting terminal socket test voltage common mode 2 kVrms/50 Hz 2 kVrms/50 Hz 2 kVrms/50 Hz 2 kVrms/50 Hz 0.5 kVrms/50 Hz differential mode N/A N/A N/A (incl. phase currents) 1 kVrms/50 Hz(*) N/A setting (*): with contacts open Impulse wave withstand Severity: polarizing current: 30 A. Acceptance criterion: R ≤ 0.1 Ω. Insulation testing Measurement of insulation resistance Aim: to test the constructive integrity of the item before dielectric stress is applied. Reference documents: Standards: IEC 60255-5 Special conditions: measurement is performed in both common and differential modes. Severity: applied voltage: 500 VDC Acceptance criterion: Ri ≥100 MΩ. Aim: to ensure that the device is capable of withstanding high overvoltage for very short periods of time without any damage. Reference documents: Standards: IEC 60255-5 Acceptance criteria: During the test: c no breakdowns, performations, warping After the test: c the device must correspond to all of its functional specifications. Severity : circuits power supply logic inputs analog inputs logic outputs pocket terminal socket test voltage common mode 5 kV 5 kV 5 kV 5 kV 1 kV differential mode 5 kV 5 kV 5 kV (incl. phase currents) N/A 0.5 kV Power supply circuit robustness Short-circuit current behaviour Aim: to ensure that the device's circuits are capable of withstanding, without damage, stress caused by short-circuit currents resulting from internal failures. Acceptance criteria: During the test: c short-circuit current less than 15 A for a maximum of 20 ms. c effectiveness of protective devices. After the test: c visual check of cabling, connectors, printed circuit paths. c return to normal operation after resetting or replacement of the protective devices. Polarity reversal behaviour Aim: to ensure that the device is capable of withstanding, without damage, an accidental power supply polarity reversal. Reference documents: Standards: IEC 61131-2. Severity: operation for at least 10 seconds with the power supply polarities reversed. Acceptance criterion: Return to normal operation after the power supply polarities have been correctly re-established. Installation - Use - General characteristics - Testing 3/7 General characteristics Performance tests in reference conditions Aim Checking of parameter specifications The aim of these tests is to test the special functional features (hardware and software) of a device in its "reference environment", i.e. temperature, power supply, etc., using strict tolerances. Aim: to check conformity of input/output interfacing characteristics. Analog input circuits Compostion of tests For each type of input (sensors, process, etc.), minimum testing includes: c dynamics and accuracy (examination of the rated domain), c input impedance (examination of the rated domain), c passband. Logic input circuits Composition of tests For each type of input (static relay, etc.), minimum testing includes: c input impedance (exploration of rated domain), c thresholds (high, low, hysteresis), c minimum set-up time (high and low levels). Logic output circuits Composition of tests For static type outputs, minimum testing includes: c output dynamics (I or V), c output compliance (I or V), c influence of load (transition time, over/undershoots), c for datacom: protocol, frequency, gigue, etc. For relay type outputs, minimum testing includes: c breaking capacity (min.-max. I/V, load impedance), c bounce time. Miscellaneous Initialization Aim: to verify the efficiency of self-testing carried out by the device during start-up. Downgraded operation Aim: to verify the efficiency of self-testing carried out by the device while functioning. Module interchangeability Aim: to test maintenance capability. Comments: the tests include: c power source converter, c core-connector. 3/8 Installation - Use - General characteristics - Testing General characteristics Testing of output effects in rated domains Aim Analog input circuits These tests verify the operation of the device in the rated domain of input signal variations, output loads, power supply voltage, etc. Reference documents: Standards: IEC 60255-6 , IEC 61131-2 One degree of freedom is variable for each test, the other values being kept at their reference values. DC power supply Reference documents: Standards: IEC 60255-22-xx, IEC 61131-2 for determination of sensitivity limits. Voltage amplitude Aim: to test the device’s ability to function with all acceptable power supply voltages. Alternating component Aim: to test the device’s ability to function with an alternating component (rectifier-battery charger) superimposed on its DC supply voltage. Severity: alternating component (= ripple battery voltage) with frequency >100 Hz and peak-to-peak amplitude = 0.12 Unom Comments: the test is performed: c at the extreme limits of the power supply domain. Fading cancellation Aim: to check the device’s ability to maintain operation in spite of power supply micro-outages (source changeover or faulty device nearby). Severity: 10 voltage outages, at minimum 1 sec. intervals, lasting: 75 ms for Vpower = Vnom 30 ms for Vpower = Vmin Comments: the voltage outages correspond: c first, to an opening in the power supply line (infinite impedance during disturbance), c then, to a shorting of the power supply line (zero impedance during disturbance). Accidental voltage surges Aim: to test the device’s ability to maintain operation in the presence of transient surge voltage in the power supply (handling shocks, reactive load switching). Severity: 10 surges, at minimum 1 sec. Intervals, lasting 10 ms, with a maximum slope of 100 V/ms, and maximum amplitude: + 20 V for Un < 48 V, + 40 V for Un > 48 V. Installation - Use - General characteristics - Testing Composition of tests: for each type of input (sensors, process, etc.), testing includes, in particular: c behaviour at limits (saturation, voltage limiter operation). c input currents/voltages when saturated. c passband / recovery time. c permissible overload and dynamic thermal limit for sensor inputs. Logic input circuits Reference documents: Standards: IEC 60255-6, IEC 61131-2 Composition of tests: testing includes, in particular: c static inputs. v input dynamics (examination of saturation). v input currents/voltages (examination of saturation) c relay type inputs. v maximum permissible voltage. v input impedance (voltage limiters, R.L. diodes). v resolution (min. duration of a single-shot input signal). v maximum frequency. Logic output circuits Reference documents: Standards: IEC 60255-6, IEC 61131-2 Composition of tests: Testing includes, in particular: c static outputs. v effectiveness of protective devices. v maximum length of datacom link. c relay type outputs. v effectiveness of protective devices (damping circuits, overvoltage suppressors). Ambient temperature Aim: to confirm the hypothesis of temperature rise of the device when being cooled by natural air convection in a confined area. Reference documents: Standards: IEC 60068-2-2 Comments: This test is complementary to the standardized test described in the section on "dry heat". 3/9 General characteristics Effects of the equipment on the environment Aim DC power supply These tests test the level of interference (electrical, electromagnetic, etc.) generated by the device. Reference documents: Standards: IEC 61131-2 Power consumption Aim: to check the conformity of the device to specifications. Severity: the test is performed at the rated voltages of the two operational domains, i.e. 48 V and 127 V. Inrush current Aim: to check the conformity of the device to specifications. Acceptance criteria: time inrush current maximum peak 50 µs i t < 1.5 ms 10 A 1.5 ms i t < 500 ms 10 A 500 ms i t 1.2* In (1) (1) In = steady-state current Radiofrequency interference Conducted interference Aim: to check the interference voltage introduced by the device at the energy network terminal posts. Reference documents: Standards: CISPR 22 Acceptance criteria: maximum emission (virtually peak): c 79 dB (µV) from 0.15 to 0.5 MHz, c 73 dB (µV from 0.5 to 30 MHz. Radiated interference Aim: to test the electromagnetic field interference radiated by the device. Reference documents: Standards: CISPR 22 Acceptance criteria: maximum emission (virtually peak) at 10 m: c 40 dB (mV/m) from 30 to 230 MHz, c 47 dB (mV/m) from 230 to 1000 MHz. 3/10 Installation - Use - General characteristics - Testing General characteristics Effects of the environment on the equipment Aim Sensitivity to electromagnetic interference These tests check device sensitivity and resistance to electromagnetic, mechanical, chemical, etc. interference. Sensitivity to conducted interference Reference documents: Standards: IEC 60255-22-xx for determination of sensitivity limits. 1MHz damped wave Aim: to test that the device does not operate in an unwanted manner when subjected to high frequency transients (switching of auxiliary relays or isolation switches/circuit breakers). Reference documents: Standards: IEC 60255-22-1 Severity circuits test voltage common mode differential mode power supply 2.5 kV 1 kV logic inputs 2.5 kV 1 kV analogic inputs 2.5 kV 1 kV (incl. phase currents) logic outputs 2.5 kV 1 kV Fast transient bursts Aim: to test device immunity when subjected to rapid, repeated electrical transients (inductive load breaks, relay contact bounces). Reference documents: Stadards: IEC 60255-22-4 Severity circuits test voltage [coupling] common mode differential mode power supply 4 kV [direct] logic inputs 4 kV [direct] 4 kV [direct] analog inputs 4 kV [direct] 4 kV [direct] (incl. phase currents) 4 kV [direct] logic outputs 4 kV [direct] 4 kV [direct] pocket terminal socket 1 kV [direct] 4 kV [capacitive] 1 kV [direct] 4 kV [capacitive] Impulse wave Aim: to test the device’s immunity when it is submitted to transients caused by lightning and switching (capacitor bank, short-circuit to earth, etc.). Reference document: Standard: IEC 61000-4-5 Severity Installation - Use - General characteristics - Testing circuits test voltage (test impedance) common mode differential mode power supply 2 kV (42 Ω) 1 kV (42 Ω) logic inputs 2 kV (42 Ω) 1 kV (42 Ω) logic outputs 2 kV (42 Ω) 1 kV (42 Ω) phase current inputs (ECM) 2 kV (42 Ω) 1 kV (42 Ω) earth fault current input CT+CSH 30 2 kV (42 Ω) 1 kV (42 Ω) 2 A and 30 A earth fault current inputs 2 kV (2 Ω) on shielding N/A voltage inputs 2 kV (42 Ω) 1 kV (42 Ω) RTD input 2 kV (2 Ω) on shielding N/A communication interface 2 kV (2 Ω) on shielding N/A 3/11 General characteristics Effects of the environment on the equipment (cont’d) Sensitivity to radiated interference Aim: to test that the device does not operate in an unwanted manner when subjected to an electromagnetic field of radiation (especially transmitters/receivers). Reference documents: Standards: IEC 60255-22-3, IEC 61000-4-3 Severity: intensity of field: 30V/m not modulated 10V/m amplitude-modulated Sensitivity to electrostatic discharges Aim: to test that the device does not operate in an unwanted manner when subjected to electrostatic discharge (operator contact or nearby objets). Reference documents: Standards: IEC 60255-22-2 Severity: generator load voltage: 8 kV in air 6 kV on contact Testing in a simulated MV environment Aim: to check that there is no nuisance tripping during MV switchgear operations. Composition of tests: device installed in a cubicle shunt-wired to a high voltage generator. Severity: generator voltage: 30 kV / 50Hz. Number of operations: 30 closing operations. Climatic and mechanical robustness tests Foreword: Test sequence c the same device undergoes all the tests. c the sequential testing order complies with the recommendations in the IEC 60068-1 standard (as testing order maximizes the significance of the results, each test potentially reveals deterioration caused by previous tests). Cold Aim: to test the device's ability to be used at low temperatures. Reference documents: Standards: IEC 60068-2-1 Severity: Ad test, without forced air circulation: c device in operation, c temperature: 0 ˚C, c duration: 16 hours, c recovery: 1 hour, device energized. N.B. The pocket terminal is not subjected to the tests. Dry heat Aim: to test the device's ability to be used at high temperatures. Reference documents: Standards: IEC 60068-2-2 Severity: Bd test, without forced air circulation: c device in operation, c temperature: 55 ˚C. 3/12 Installation - Use - General characteristics - Testing Fast temperature variations Aim: to test the device's ability to function during changes in ambient temperature. Vibrations / Behaviour to vibrations Aim: to test the device's ability to function in spite of vibrations during normal operation. Reference document: Standards: IEC 60068-2-14 Reference documents: Standards: IEC 60255-21-1 Severity: Nb test, device in operation: c device in operation, c low temperature: 0 ˚C, c high temperature: 55 ˚C, c speed of temperature variation: 5 ±1 ˚C/mn, c duration of exposure at each level: 2 hours, c number of cycles: 2, c recovery: 1 hour, device energized. Severity: Class 1: c device in operation, c frequency range: 10 to 150 Hz, c acceleration: 0.5 gn or 0.035 mm (peak values), c number of cycles per axis: 1, c sweep speed: 1 octave/mn ±10%, N.B. The pocket terminal is not subjected to the tests. Vibration resistance Aim: accelerated aging test to test the device's ability to withstand weak but long vibrations while in operation or during transportation. Shocks / Behaviour to shocks Aim: to test the device's ability to function in spite of shocks which may occur during normal operation. Reference documents: Standards: IEC 60255-21-2 Severity: Class 1: c device in operation, c peak acceleration: 5 gn, c pulse duration: 11 ms, c number of pulses per axis: 3 in each direction. N.B. The pocket terminal is not subjected to the tests. Shock resistance Aim: to test the device's ability to withstand shocks which may occur during transportation or handling. Reference documents: Standards: IEC 60255-21-2 Severity: Class 1: c peak acceleration: 15 gn, c pulse duration: 11 ms, c number of pulses per axis: 3 in each direction. N.B. The pocket terminal is not subjected to the tests. Bumps Aim: to check the device's ability to withstand bumps which may occur during transportation. Reference documents: Standards: IEC 60255-21-2 N.B. The pocket terminal is not subjected to the tests. Reference documents: Standards: IEC 60255-21-1 Severity: Class 1: c frequency range: 10 to 150 Hz c acceleration: 1 gn (peak value) c number of cycles per axis: 20 N.B. The pocket terminal is not subjected to the tests. Damp heat Aim: to test the device's ability to be stored under high relative humidity conditions. Reference documents: Standards: IEC 60068-2-3 Severity: Ca test (continuous test). c temperature: 40 ± 2˚C c relative humidity: 93% +2/-3% c duration: 56 days. c recovery: 1 hour drying at 55˚C, then 1 hour cooling at 20˚C before final test. N.B. The pocket terminal is not subjected to the tests. Salt mist / Test for special use only / Corrosive atmosphere Aim: to define the atmosphere to which the device may be exposed in operation and/ or storage. Reference documents: Standards: IEC 60654-4. Severity: c class 1: clean industrial air. Severity: Class 1: c peak acceleration: 10 gn, c pulse duration: 16 ms, c number of pulses per axis: 1000 in each direction. Enclosure protection degree Aim: to test the protection provided by the enclosure: c for people: against direct contact with energized parts. c or equipment: against solid foreign objects or water. N.B. The pocket terminal is not subjected to the tests. Severity: c front panel: IP51 c other sides: v without cabling accessories: IP20 v with cabling accessories: IP21. Reference documents: Standards: IEC 60529 N.B. The pocket terminal is not subjected to the tests. Fire behaviour / Glow wire test Aim: to evaluate the risk of fire and test extinction of the flames when the product is exposed to abnormal thermal conditions. Reference documents: Standards: IEC 60695-2-1 Severity: c temperature: 650˚C c applied duration: 30 ±1 s. N.B. The pocket terminal is not subjected to the tests. Installation - Use - General characteristics - Testing 3/13 General characteristics Dependability This chapter presents the main definitions of dependability and how it is taken into consideration in Sepam 2000, an analysis of the experience gained from feedback on the installed equipment base and the maintenance of Sepam 2000. Consideration of dependability in Sepam 2000 Definitions A Preliminary Risk Analysis (PRA) is used to list the unwanted events linked to the different functions performed by Sepam. Quantified dependability targets are set in accordance with the main unwanted events revealed by the PRA. The definitions which follow are the main definitions of dependability applied to protective devices: c The reliability of a protective device is its capability of performing its function (or functions) over a given period of time in the operating conditions specified by the manufacturer, i.e. mainly the capability of tripping when required and the capability of not tripping when unwanted. c The maintainability of a protective device is mainly its capability of being easily repaired when maintenance personnel dispose of the means prescribed by the manufacturer. c The availability of a protective device is its capability of being in a state to perform its function (or functions) at a given point in time in the operating conditions specified by the manufacturer. These values do not necessarily have the same meanings, depending on whether they are considered from the viewpoint of the protective device or the electrical installation. By the same token as electromagnetic compatibility, dependability is taken into consideration right from the start of the development of Sepam 2000. Specialized dependability assessment and modeling techniques are used to interpret the targets in terms of design requirements. c The predicted reliability analysis determines the failure rate of each Sepam 2000 component in use-related conditions. Compendiums of reliability data such as the Military Handbook 217 (MIL HDBK 217) and the CNET RDF93 are used for this. c The Failure Modes, Effects and Criticality Analysis (FMECA) analysis is used to analyze the effects of a simple component failure on the Sepam 2000 functions and to list the means available to detect them. The FMECA makes it possible to correct certain risks of malfunctions and specify the self-monitoring functions. c The unwanted events are modeled to calculate the probability of their occurrence and to check that the dependability targets are being met. A large share of the functions of digital protective equipment devices are performed by the software. It is therefore essential to master the quality of the software in order to attain the overall dependability targets. Software quality is mastered by the implementation of a rigorous development method. This method is derived from the recommendations set by the French (AFCIQ) and international (IEEE) quality authorities. It stipulates: c the breakdown of development into a series of phases, c the use of design and encoding rules and methods aimed at achieving a high level of software structuring, c the use of software configuration management tools which allow all the software component parts to be managed. The availability and maintainability of the protective device contribute to the safety of people and equipment. The reliability of the protective device contributes to the uninterrupted availability of the power supply. Self-monitoring functions and fail-safe position Dependability needs: a trade-off between two unwanted events c A major failure affects the system’s common hardware resources (e.g. program memory and working memory). The mission of protection systems used with circuit breakers is to guarantee the safety of the installation while, at the same time, ensuring the best level of interrupted power supply. For Sepam 2000, this mission is conveyed by two events, the target occurrence of which should be zero. c First unwanted event: unwanted tripping of the protective device. An uninterrupted power supply is essential for both industrialists and utilities. Unwanted tripping due to the protective device is liable to generate substantial financial losses. This event can be avoided by improving the reliability of the protective device. c Second unwanted event: failure of the protective device to trip. The consequences of a fault that is not cleared are liable to be disastrous. For the sake of operating safety, the protective equipment must detect power system faults selectively and as quickly as possible. Sepam 2000 units are equipped with self-monitoring functions (self-tests), which detect internal failures. The failures are classified in two categories: major failures and minor failures. Sepam 2000 is no longer operational. This type of failure may or may not lead to MV fault tripping or unwanted tripping, in which case Sepam 2000 must react quickly and go into the fail-safe position. The fail-safe position is characterized by: v lockout in neutral position of the Processing Unit, v an indicator lit up on the front of the device, v a message on the display, v the Watchdog relay in fault position (deactivated), v the relay outputs (logic outputs) in the deactivated position, v a break in the relay output supply for Sepam S46. c Following a minor failure, Sepam 2000 is in downgraded operation. It can continue to carry out all of its protection functions if the functions affected are peripheral ones (display, communication). This classification of failures makes it possible to obtain a compromise between between a high level of safety and a high level of availability. The self-tests performed in Sepam 2000 are summarized in the diagram on the next page. This event can be avoided by improving the availability of the protective device. 3/14 Installation - Use - General characteristics - Testing Sepam 2000 functional diagram current acquisition internal Bus power supply display / keypad processing unit communication voltage acquisition CB control I/O program logic logic I/O analog inputs Installation - Use - General characteristics - Testing to level 2 cartridge (EPROM) Sepam 2000 S46 3/15 Appendix 1: reference documents Standards title reference status vibration, shock, bump and seismic tests on measuring relays and protection equipment: vibration tests (sinusoidal). IEC 60255-21-1 1988 vibration, shock, bump and seismic tests on measuring relays and protection equipment: shock and bump tests. IEC 60255-21-2 1988 electrical disturbance for measuring relays and protection equipment: 1MHz burst disturbance tests. IEC 60255-22-1 1988 electrical disturbance for measuring relays and protection equipment: electrostatic discharge tests. IEC 60255-22-2 1989-10 electrical disturbance for measuring relays and protection equipment: radiated electromagnetic field disturbance tests. IEC 60255-22-3 1989-10 electrical disturbance for measuring relays and protection equipment: 1 MHz damped oscillating wave tests. sensitivity to fast transient interference tests. IEC 60255-22-4 1992 electromagnetic compatibility (EMC) part 4-3: testing and measurement techniques immunity to electromagnetic fields radiated at radioelectric frequencies test IEC 61000-4-3 1998 single input energising quantity measuring relays with dependent specified time. IEC 60255-5 1977 electrical relays: insulation tests for electrical relays: IEC 60255-6 1988 degrees of protection provided by enclosures (IP code). IEC 60529 1989 programmable logic controllers: equipment characteristics. IEC 61131-2 1992 environmental testing: general and guidance. IEC 60068-1 1988 environmental testing: test A: cold. IEC 60068-2-1 1990-04 basic environmental testing procedures: test N: change of temperature. IEC 60068-2-14 1986 basic environmental testing procedures: test B: dry heat. IEC 60068-2-2 1974 basic environmental testing procedures: test Ca: damp heat, steady state. IEC 60068-2-3 1969 basic environmental testing procedures: test Kb: salt mist, cyclic (sodium chloride solution). IEC 60068-2-52 1984 limits and methods of measurement of radio interference: characteristics of information technology equipment. IEC CISPR 22 1993 test methods fire behaviour: glow wire test. IEC 60695-2-1 1994 operating conditions for measurement and control equipment in industrial processes: effects of corrosion and erosion. IEC 60654-4 1987 3/16 Installation - Use - General characteristics - Testing Testing – setting record sheets Contents chapter / page Installation - Use - General characteristics - Testing testing – setting record sheets 4/2 commissioning tests test sheets setting record sheets 4/2 4/3 4/6 4/1 Testing – setting record sheets Commissioning tests Sepam 2000 commissioning does not call for individual testing of the metering and protection functions. Sepam 2000 has been designed and developed to ensure all of the functions: c protection, c metering, c program logic. Each of the functions has been factory-tested in its entirety. In addition, Sepam 2000 has a high performing self-testing system which continually checks function integrity, (e.g. no settings outside the tolerance range, etc.). The product is ready to use and commissioning has been simplified accordingly. Simple testing of one function ensures the correct operation of the whole group of functions, provided that the product is installed correctly. It is therefore sufficient to check the Sepam 2000 installation. Checking relates to: c parameter setting, c connection to current, voltage and temperature sensors, c connection of switchgear control and annunciation. 4/2 Installation - Use - General characteristics - Testing TEST SHEET Sepam 2000 Project : .................................................................................................... Switchboard: ......................................................................................... Panel: ........................................................................................................ ....................................................................................................................... Type of Sepam 2000 serial number Commissioning tests Check current and voltage sensor wiring and phase rotation order beforehand. Set the status parameters and set the protections according to the setting record sheet. type of test Sepam connected to current sensors only secondary injection of rated current scheme result display B6 primary rated current I1 = ................................ I2 = ................................ I3 = ................................ B6 P=+ (1) I1 = 1 or 5 A I2 = 1 or 5 A I3 = 1 or 5 A Sepam connected to current and voltage sensors 3-phase secondary injection rated current (1 or 5 A) rated voltage (Uns) phase shift ϕ = -30° inductive Q=+ P=- Q=- 3Un.In 2 P = + ............................. 3 Un.In 2 feeder Q = + ............................. 3Un.In 2 P = - ............................. 3 Un.In 2 Q= - incomer ............................. residual current according to assembly Sum 3I 3-phase secondary injection in 1 phase CSH primary injection primary injection B6 rated current (1 or 5 A) rated current (1 or 5 A) residual I = 0 residual I = rated I Ir = ................................ Ir = ................................ 28.5 ≤ residual I ≤ 31.5 A 0.18 ≤ residual I ≤ 0.22 A Ir = ................................ Ir = ................................ B7 30 A 0.2 A CT (with CSH 30 or ACE 990) secondary injection(with CSH 30) rated current (1 or 5 A) primary injection B7 residual I = rated I Ir = ................................ residual I = injected current residual voltage according to assembly VT in broken delta single-phase secondary injection VT in star 3-phase secondary injection B7 Uns 3 residual voltage = phase voltage Vo = .............................. residual voltage = phase voltage Vo = .............................. B6 Uns 3 logic input / output wiring check the conformity of logic input and output connection circuit breaker/contactor program logic closing control by closing button closing of device tripping control by tripping button opening of device pilot wire test (standard Sepam) Tests carried out on: (message) RECEIVE.BI (on upstream Sepam) Signature Signature by: Comments: (1) see “Testing” documentation test the link (KP18) Installation - Use - General characteristics - Testing 4/3 Program logic parameters (customized logic) KP 0 or 1 comments KP KP1 KP33 KP2 KP34 KP3 KP35 KP4 KP36 KP5 KP37 KP6 KP38 KP7 KP39 KP8 KP40 KP9 KP41 KP10 KP42 KP11 KP43 KP12 KP44 KP13 KP45 KP14 KP46 KP15 KP47 KP16 KP KP17 KP48 KP18 KP49 KP19 KP50 KP20 KP51 KP21 KP52 KP22 KP53 KP23 KP54 KP24 KP55 KP25 KP56 KP26 KP57 KP27 KP58 KP28 KP59 KP29 KP60 KP30 KP61 KP31 KP62 KP32 KP63 0 or 1 comments 0 or 1 impulse KP64 4/4 Installation - Use - General characteristics - Testing Program logic parameters (customized logic) time delay (value) comments time delay (value) comments T1 s T31 s T2 s T32 s T3 s T33 s T4 s T34 s T5 s T35 s T6 s T36 s T7 s T37 s T8 s T38 s T9 s T39 s T10 s T40 s T11 s T41 s T12 s T42 s T13 s T43 s T14 s T44 s T15 s T45 s T16 s T46 s T17 s T47 s T18 s T48 s T19 s T49 s T20 s T50 s T21 s T51 s T22 s T52 s T23 s T53 s T24 s T54 s T25 s T55 s T26 s T56 s T27 s T57 s T28 s T58 s T29 s T59 s T30 s T60 s v tick off the box when the setting is done Installation - Use - General characteristics - Testing 4/5 Sepam 2000 Substation SETTING RECORD SHEET Project: ..................................................................................................... Switchboard: ......................................................................................... Panel: ........................................................................................................ ....................................................................................................................... S Type of Sepam 2000 serial number Status menu parameters menu name function frequency Fn network frequency phase CT ratio 60 Hz board 2 (ECM or ECA) In CT rating or CSP (in Amps) A kA Ib basis current (in Amps) A kA number number of current sensors I1-I3 I1-I2-I3 Io sensor board 2 (ECM or ECA) Ino residual current measurement Sum 3I Sum1 3I or Sum2 3I 2 A core bal. CT CT + CSH 30 for S26, S36 A A core bal. CT + ACE 990 A for CT for CSP 30 A core bal. CT kA kA for S25, S35 kA max. demand interval interval max. demand integration time 5 mn 60 mn 10 mn 15 mn VT ratio number number of wired VTs V U21 1U U21-U32 3U S26, S36 3U S25, S35 Unp rated VT primary voltage Uns rated VT secondary voltage 100 V 110 V 115 V Vnso type of residual voltage measurement Sum 3V Uns/ 3 Uns/3 incomer feeder reverses the signs of power and energy measurements Incomer = cables to busbars Feeder = busbars to cables power flow direction oscillography pretrig communication time tagging number of periods before triggering event of the disturbance recording bauds transmission speed address Sepam station number in network parity synchro 1200 19200 transmission format even odd no parity type of synchronization used via network KTS33 to 64 for S26, S36 only 120 V periods 600 9600 N.B. For each event, choose 0 or 1 0 = not time-tagged 1 = time-tagged all events are set to 0 by default 30 mn volts kilovolts 300 4800 events 4/6 50 Hz 2400 38400 via input I11 via input I21 KTS1 to 8 KTS9 to 16 KTS17 to 24 KTS25 to 32 KTS33 to 40 KTS41 to 48 KTS49 to 56 KTS57 to 64 I1 I2 I11 to I18 I21 to I28 I31 to I38 Installation - Use - General characteristics - Testing Status menu parameters (cont’d) menu name Microswitch settings function voltage board current board SW1 board 2 board 3 CT (ECM 1) CSP (ECA) CT (ECM 2) SW2 SW2 SW2 SW1 SW1 SW1 put an X in the box to indicate switch setting e.g. switch set to right X Sepam 2000 substation program logic parameters KP 0 or 1 KP 0 or 1 KP16 input I12 BI receipt and inhibit recloser / inhibit recloser KP17 display of programmed program logic recloser enabled/disabled KP18 BI pilot wire test KP7 reclosing cycle 1 inactive / active KP19 reset operation counter KP8 reclosing cycle 2 inactive / active KP20 KP9 reclosing cycle 3 inactive / active reset phase fault tripping counter KP10 reclosing cycle 1 inactive / active KP22 KP11 cycle 1 tripping time-delayed / instantaneous reset specific recloser counters KP36 reverse P with annunciation / tripping KP12 cycle 2 tripping time-delayed / instantaneous KP1 open/close control KP2 open/close control KP4 external protection NO/NC KP6 KP38 KP remote setting active / inactive 0 or 1 impulse KP13 cycle 3 tripping time-delayed / instantaneous KP50 inhibition of disturbance recording records KP14 cycle 4 tripping time-delayed / instantaneous KP51 automatic triggering of disturbance recording KP15 definitive tripping time-delayed / instantaneous KP52 manual triggering of disturbance recording time delay (value) T1 T2 T3 time delay (value) s recovery of open/closed data upon change in device position T10 s confirmation waiting time after successful reclosing T11 s T12 inhibition of transmit blocking input after tripping T13 T15 s s s s s duration of cycle 1 isolation duration of closing order s s s confirmation of pressure switch fault s T5 s duration of remote control tripping impulse T6 s duration of remote control closing impulse T14 T16 T25 T26 Installation - Use - General characteristics - Testing duration of cycle 2 isolation duration of cycle 3 isolation duration of cycle 4 isolation duration of recloser inhibition with manual circuit breaker closing tripping pulse closing pulse 4/7 Sepam 2000 Substation function identification overcurrent setting curve Is T curve Iso T F011 F012 F013 F014 earth fault F081 F082 F083 F084 undervoltage Us T Us T Us T F321-341-361 remanent undervoltage F351 overvoltage F301 F302 directional overcurrent θ curve Is T F511-F521 directional earth fault angle Iso T F501 reverse power Ps T Fs T Fs T dFs/dt T F531 underfrequency F561 F562 overfrequency F571 F572 rate of change of frequency F581 F582 tick off the box when the setting is done Settings made on: Signature Signature by: Comments: 4/8 Installation - Use - General characteristics - Testing Sepam 2000 Busbars SETTING RECORD SHEET Project: ..................................................................................................... Switchboard: ......................................................................................... Panel: ........................................................................................................ ....................................................................................................................... B Type of Sepam 2000 serial number Status menu parameters menu name function rated frequency Fn network frequency In CT rating or CSP (in Amps) A kA Ib basis current (in Amps) A kA number number of current sensors I1-I3 I1-I2-I3 phase CT ration 50 Hz 60 Hz board 2 (ECM or ECA) Io sensor board 2 (ECM or ECA) Ino residual current measurement Sum 3I Sum1 3I or Sum2 3I 2 A core bal. CT CT + CSH 30 for S26, S36 A A core bal. CT + ACE 990 A for CT for CSP 30 A core bal. CT kA kA for S25, S35 kA max. demand interval interval max. demand integration time 5 mn 60 mn 10 mn 15 mn VT ratio number number of wired VTs V U21 1U U21-U32 3U S26, S36 3U S25, S35 Unp rated VT primary voltage Uns rated VT secondary voltage 100 V 110 V 115 V Vnso type of residual voltage measurement Sum 3V Uns/ 3 Uns/3 power flow direction incomer feeder reverses the signs of power and energy measurements Incomer = cables to busbars Feeder = busbars to cables oscillography pretrig number of periods before triggering event of the disturbance recording communication bauds transmission speed address Sepam station number in network parity synchro time tagging volts kilovolts 600 9600 1200 19200 transmission format even odd no parity type of synchronization used via network N.B.: For each event, choose 0 or 1 0 = not time-tagged 1 = time-tagged all events are set to 0 by default KTS33 to 64 for S26, S36 only Installation - Use - General characteristics - Testing 120 V periods 300 4800 events 30 mn 2400 38400 via input I11 via input I21 KTS1 to 8 KTS9 to 16 KTS17 to 24 KTS25 to 32 KTS33 to 40 KTS41 to 48 KTS49 to 56 KTS57 to 64 I1 I2 I11 to I18 I21 to I28 I31 to I38 4/9 Status menu parameters (cont’d) menu name Microswitch settings function 3U +Vo 1 voltage board current board 3U + Vo 2 SW1 SW1 board 2 board 3 CT (ECM 1) CSP (ECA) CT (ECM 2) SW2 SW2 SW2 SW1 SW1 SW1 put an X in the box to indicate switch setting e.g. switch set to right X Sepam 2000 substation program logic parameters KP 0 or 1 KP 0 or 1 KP1 open/close control KP33 choice of type of load shedding KP2 open/close control KP35 acknowledgment of operating mode with voltage absent for synchro-check KP4 external protection NO/NC KP38 remote setting active / inactive KP17 display of programmed program logic KP 0 or 1 impulse KP18 BI pilot wire test KP19 reset operation counter KP50 inhibition of disturbance recording records KP20 reset phase fault tripping counter KP51 automatic triggering of disturbance recording KP52 manual triggering of disturbance recording time delay (value) time delay (value) T1 T7 extension of dF/dT = 1 (KP33=1) T16 confirmation of pressure switch fault s recovery of open/closed data upon change in device position s duration of closing order T8 s maintain output O33 for synchro-check s inhibition of transmit blocking input after tripping T10 s maintain closing request for synchro-check T5 s duration of remote control tripping impulse T24 T6 s duration of remote control closing impulse T2 T3 T25 T26 T27 4/10 duration of load shedding pulse (O31) duration of load shedding pulse (O32) duration of load shedding pulse (O33) duration of load shedding pulse (O34) Installation - Use - General characteristics - Testing Sepam 2000 Busbars function identification setting overcurrent curve Is T curve Iso T F011 F012 F013 F014 earth fault F081 F082 F083 F084 undervoltage Us T Vsd T Us T Us T Vso T Fs T Fs T dFs/dt T F321-341-361 F322-342-362 F241-331-371 F242-332-372 positive sequence undervoltage F381 F382 remanent undervoltage F351 F251 overvoltage F301 F302 F311 F312 neutral voltage displacement F391 underfrequency F561 F562 F563 F564 overfrequency F571 F572 rate of change of frequency F581 F582 synchro-check F181 dUs dFs mode Ta dϕs Us high Us low tick off the box when the setting is done Settings made on: Signature Signature by: Comments: Installation - Use - General characteristics - Testing 4/11 Sepam 2000 Transformer SETTING RECORD SHEET Project: ..................................................................................................... Switchboard: ......................................................................................... Panel: ........................................................................................................ ....................................................................................................................... T Type of Sepam 2000 serial number Status menu parameters menu name function rated frequency Fn network frequency In CT rating or CSP (in Amps) A kA A kA Ib basis current (in Amps) A kA A kA number number of current sensors I1-I3 I1-I2-I3 I1-I3 I1-I2-I3 phase CT ratio 50 Hz 60 Hz board 2 (ECM 1 or ECA) Io sensor board 2 (ECM 1 or ECA) Ino residual current measurement board 3 (ECM 2) board 3 (ECM 2) Sum 3I Sum1 3I or sum2 3I 2 A core bal. CT CT + CSH 30 for S26, S36 A A core bal. CT + ACE 990 A for CT for CSP 30 A core bal. CT kA kA for S25, S35 kA max. demand interval interval max. demand integration time 5 mn 60 mn 10 mn 15 mn VT ratio number number of wired VTs V U21 1U U21-U32 3U S26, S36 3U S25, S35 Unp rated VT primary voltage Uns rated VT secondary voltage 100 V 110 V 115 V Vnso type of residual voltage measurement Sum 3V Uns/ 3 Uns/3 power flow direction incomer feeder reverses the signs of power and energy measurements Incomer = cables to busbars Feeder = busbars to cables oscillography pretrig number of periods before triggering event of the disturbance recording communication bauds transmission speed address Sepam station number in network parity synchro time tagging 1200 19200 transmission format even odd no parity type of synchronization used via network KTS33 to 64 for S26, S36 only 120 V periods 600 9600 N.B.: For each event, choose 0 or 1 0 = not time-tagged 1 = time-tagged all events are set to 0 by default 4/12 volts kilovolts 300 4800 events 30 mn 2400 38400 via input I11 via input I21 KTS1 to 8 KTS9 to 16 KTS17 to 24 KTS25 to 32 KTS33 to 40 KTS41 to 48 KTS49 to 56 KTS57 to 64 I1 I2 I11 to I18 I21 to I28 I31 to I38 Installation - Use - General characteristics - Testing Status menu parameters (cont’d) menu name Microswitch settings function voltage board current board SW1 board 2 board 3 CT (ECM 1) CSP (ECA) CT (ECM 2) SW2 SW2 SW2 SW1 SW1 SW1 put an X in the box to indicate switch setting e.g. switch set to right X Sepam 2000 transformer program logic parameters KP 0 or 1 KP 0 or 1 KP1 open/close control KP18 BI pilot wire test KP2 open/close control KP19 reset operation counter KP4 external protection NO/NC KP20 reset phase fault tripping counter KP5 Buchholz / thermostat / DGPT NO/NC KP38 remote setting active / inactive KP6 tripping / alarm input I23 KP KP7 tank earth leakage choice KP17 display of programmed control scheme time delay (value) 0 or 1 impulse KP50 inhibition of disturbance recording records KP51 automatic triggering of disturbance recording KP52 manual triggering of disturbance recording time delay (value) T1 s recovery of open/closed data upon change in device position T2 s duration of closing order T3 s inhibition of transmit blocking input after tripping Installation - Use - General characteristics - Testing T5 s duration of remote control tripping impulse T6 s duration of remote control closing impulse T16 s confirmation of pressure switch fault 4/13 Sepam 2000 Transformer function identification thermal overload setting Adjust. F431 overcurrent T1 and T2 OL1 alarm OL2 trip 0 curve Is T curve Iso T F011 F012 F013 F014 earth fault F081 F082 F083 F084 neutral voltage displacement Vso T F391 directional overcurrent θ curve Is T F521 directional earth fault angle Iso T curve Is T curve Iso T F501 tank frame leakage F021 neutral F091 F092 undervoltage Us T Us T Us T Ts1 Ts2 F321-341-361 remanent undervoltage F351 overvoltage F301 F302 RTD F461 F462 F463 F464 F465 F466 restricted earth fault Is F651 tick off the box when the setting is done Settings made on: Signature Signature by: Comments: 4/14 Installation - Use - General characteristics - Testing Sepam 2000 Motor SETTING RECORD SHEET Project: ..................................................................................................... Switchboard: ......................................................................................... Panel: ........................................................................................................ ....................................................................................................................... M Type of Sepam 2000 serial number Status menu parameters menu name function rated frequency Fn network frequency In CT rating or CSP (in Amps) A kA A kA Ib basis current (in Amps) A kA A kA number number of current sensors I1-I3 I1-I2-I3 I1-I3 I1-I2-I3 phase CT ratio 50 Hz 60 Hz board 2 (ECM 1 or ECA) Io sensor board 2 (ECM 1 or ECA) Ino residual current measurement board 3 (ECM 2) board 3 (ECM 2) Sum 3I Sum1 3I or sum2 3I 2 A core bal. CT CT + CSH 30 for S26, S36 A A core bal. CT + ACE 990 A for CT for CSP 30 A core bal. CT kA kA for S25, S35 kA max. demand interval interval max. demand integration time 5 mn 60 mn 10 mn 15 mn VT ratio number number of wired VTs V U21 1U U21-U32 3U S26, S36 3U S25, S35 Unp rated VT primary voltage Uns rated VT secondary voltage 100 V 110 V 115 V Vnso type of residual voltage measurement Sum 3V Uns/ 3 Uns/3 power flow direction incomer feeder reverses the signs of power and energy measurements Incomer = cables to busbars Feeder = busbars to cables oscillography pretrig number of periods before triggering event of the disturbance recording communication bauds transmission speed address Sepam station number in network parity synchro time tagging volts kilovolts 600 9600 1200 19200 transmission format even odd no parity type of synchronization used via network N.B.: For each event, choose 0 or 1 0 = not time-tagged 1 = time-tagged all events are set to 0 by default KTS33 to 64 for S26, S36 only Installation - Use - General characteristics - Testing 120 V periods 300 4800 events 30 mn 2400 38400 via input I11 via input I21 KTS1 to 8 KTS9 to 16 KTS17 to 24 KTS25 to 32 KTS33 to 40 KTS41 to 48 KTS49 to 56 KTS57 to 64 I1 I2 I11 to I18 I21 to I28 I31 to I38 4/15 Status menu parameters (cont’d) menu name Microswitch settings function voltage board current board SW1 board 2 board 3 CT (ECM 1) CSP (ECA) SW2 CT (ECM 2) SW2 put an X in the box to indicate switch setting e.g. switch set to right SW2 not used X SW1 SW1 SW1 Sepam 2000 motor program logic parameters KP 0 ou 1 KP 0 ou 1 KP1 open/close control KP2 open/close control KP3 open/close control KP4 external protection NO/NC KP17 display of programmed control scheme KP KP18 BI pilot wire test KP50 storage of disturbance recording records KP19 reset operation counter KP51 automatic triggering of disturbance recording KP52 manual triggering of disturbance recording time delay (value) reset phase fault tripping counter KP21 reset to zero of running hours counter KP38 remote setting active / inactive 0 or 1 impulse time delay (value) T1 s recovery of open/closed data upon change in device position T2 s duration of closing order T3 s inhibition of transmit blocking input after tripping T4 s external load shedding order T5 s duration of tripping pulse from a remote control order 4/16 KP20 T6 s T8 s maximum duration of voltage sag enabling restart T9 s restart staggering T16 duration of remote control closing impulse s confirmation of pressure switch fault Installation - Use - General characteristics - Testing Sepam 2000 Moteur function identification thermal overload setting Adjust. T1 T2 OL1 warm state OL2 trip F431 overcurrent curve Is T curve Iso T curve Is T Is ST LT F011 F012 earth fault F081 F082 negative sequence / unbalance F451 locked rotor / excessive starting time F441 undercurrent Is T F221 number of starts n° start per hour n° cold start n° hot start T F421 positive sequence undervoltage Vsd T F381 F382 directional earth fault angle Iso T F501 reverse power Ps T Qs T Ts1 Ts2 F531 reactive overpower F541 RTD F461 F462 F463 F464 F465 F466 F471 F472 F473 F474 F475 F476 motor differential Is F621 tick off the box when the setting is done Settings made on: Signature Signature by: Comments: Installation - Use - General characteristics - Testing 4/17 Sepam 2000 Capacitor SETTING RECORD SHEET Project: ..................................................................................................... Switchboard: ......................................................................................... Panel: ........................................................................................................ ....................................................................................................................... C Type of Sepam 2000 serial number Status menu parameters menu name function rated frequency Fn network frequency In CT rating or CSP (in Amps) A kA A kA Ib basis current (in Amps) A kA A kA number number of current sensors I1-I3 I1-I2-I3 I1-I3 I1-I2-I3 phase CT ratio 50 Hz 60 Hz board 2 (ECM 1 or ECA) Io sensor board 2 (ECM 1 or ECA) Ino residual current measurement board 3 (ECM 2) carte 3 (ECM 2) Sum 3I Sum1 3I or sum2 3I 2 A core bal. CT CT + CSH 30 for S26, S36 A A core bal. CT + ACE 990 A for CT for CSP 30 A core bal. CT KA KA for S25, S35 kA max. demand interval interval max. demand integration time 5 mn 60 mn 10 mn 15 mn VT ratio number number of wired VTs V U21 1U U21-U32 3U S26, S36 3U S25, S35 Unp rated VT primary voltage Uns rated VT secondary voltage 100 V 110 V 115 V Vnso type of residual voltage measurement Sum 3V Uns/ 3 Uns/3 incomer feeder reverses the signs of power and energy measurements Incomer = cables to busbars Feeder = busbars to cables power flow direction oscillography pretrig number of periods before triggering event of the disturbance recording communication bauds transmission speed address Sepam station number in network parity synchro time tagging 1200 19200 transmission format even odd no parity type of synchronization used via network KTS33 to 64 for S26, S36 only 120 V periods 600 9600 N.B.: For each event, choose 0 or 1 0 = not time-tagged 1 = time-tagged all events are set to 0 by default 4/18 volts kilovolts 300 4800 events 30 mn 2400 38400 via input I11 via input I21 KTS1 to 8 KTS9 to 16 KTS17 to 24 KTS25 to 32 KTS33 to 40 KTS41 to 48 KTS49 to 56 KTS57 to 64 I1 I2 I11 to I18 I21 to I28 I31 to I38 Installation - Use - General characteristics - Testing Status menu parameters (cont’d) menu name Microswitch settings function voltage board current board SW1 board 2 board 3 CT (ECM 1) CSP (ECA) CT (ECM 2) SW2 SW2 SW2 SW1 SW1 SW1 put an X in the box to indicate switch setting e.g. switch set to right X Sepam 2000 capacitor program logic parameters KP 0 or 1 KP1 open / close control KP2 open/close control KP4 external protection NO/NC KP17 display programmed control scheme KP18 KP 0 or 1 impulse KP50 inhibition of disturbance recording records KP51 automatic triggering of disturbance recording KP52 manual triggering of disturbance recording KP54 capacitor 1 switch closing BI pilot wire test KP55 capacitor 1 switch opening KP19 reset operation counter KP56 capacitor 2 switch closing KP20 reset phase fault tripping counter KP57 capacitor 2 switch opening KP58 capacitor 3 switch closing KP21 running hours counter reset KP59 capacitor 3 switch opening KP36 choice of number of capacitors KP60 manual capacitor control KP37 choice of number of capacitors KP61 automatic capacitor control KP38 remote setting enable / disable Installation - Use - General characteristics - Testing 4/19 Status menu parameters (cont’d) Sepam 2000 capacitor program logic parameters time delay (value) T1 T2 T3 T5 time delay (value) s s s s recovery of open/closed data upon change in device position T26 s duration of capacitor 2 tripping pulse T27 s duration of capacitor 3 tripping pulse duration of closing order T28 s duration of capacitor 1 closing pulse inhibition of transmit blocking input after tripping T29 s duration of capacitor 2 closing pulse duration of remote control tripping impulse T30 s duration of capacitor 3 closing pulse T6 s duration of remote control closing impulse T31 s after tripping, duration of inhibition of capacitor 1 closing T7 s duration reclosing inhibition after tripping T32 s after tripping, duration of inhibition of capacitor 2 closing T21 s capacitor 1 opening time delay T33 s after tripping, duration of inhibition of capacitor 3 closing T22 s capacitor 2 opening time delay T34 s time delay for recovery of capacitor 1 switch open/closed information T35 s time delay for recovery of capacitor 2 switch open/closed information T36 s time delay for recovery of capacitor 3 switch open/closed information T23 s capacitor 3 opening time delay T24 s circuit breaker opening time delay T25 s duration of capacitor 1 tripping pulse 4/20 Installation - Use - General characteristics - Testing Sepam 2000 Capacitor function identification thermal overload setting Adjust. T1 T2 OL1 hot status OL2 tripping F431 overcurrent curve Is T curve Iso T curve Iso T F011 F012 earth fault F081 F082 neutral unbalance 1 capacitor F091 F092 neutral unbalance 3 capacitor Is T F111 F112 F121 F122 F131 F132 undervoltage Us T Us T F321-341-361 overvoltage F281 F282 F301 F302 tick off the box when the setting is done Settings made on: Signature Signature by: Comments: Installation - Use - General characteristics - Testing 4/21 Sepam 2000 Generator SETTING RECORD SHEET Project: ..................................................................................................... Switchboard: ......................................................................................... Panel: ........................................................................................................ ....................................................................................................................... G Type of Sepam 2000 serial number Status menu parameters menu name function rated frequency Fn network frequency In CT rating or CSP (in Amps) A kA A kA Ib basis current (in Amps) A kA A kA number number of current sensors I1-I3 I1-I2-I3 I1-I3 I1-I2-I3 phase CT ratio 50 Hz 60 Hz board 2 (ECM 1 or ECA) Io sensor board 2 (ECM 1 or ECA) Ino residual current measurement board 3 (ECM 2) board 3 (ECM 2) Sum 3I Sum1 3I or sum2 3I 2 A core bal. CT CT + CSH 30 for S26, S36 A A core bal. CT + ACE 990 A for CT for CSP 30 A core bal. CT kA kA for S25, S35 kA max. demand interval interval max. demand integration time 5 mn 60 mn 10 mn 15 mn VT ratio number number of wired VTs V U21 1U U21-U32 3U S26, S36 3U S25, S35 Unp rated VT primary voltage Uns rated VT secondary voltage 100 V 110 V 115 V Vnso type of residual voltage measurement Sum 3V Uns/ 3 Uns/3 power flow direction incomer feeder reverses the signs of power and energy measurements Incomer = cables to busbars Feeder = busbars to cables oscillography pretrig number of periods before triggering event of the disturbance recording communication bauds transmission speed address Sepam station number in network parity synchro time tagging 1200 19200 transmission format even odd no parity type of synchronization used via network KTS33 to 64 for S26, S36 only 120 V periods 600 9600 N.B.: For each event, choose 0 or 1 0 = not time-tagged 1 = time-tagged all events are set to 0 by default 4/22 volts kilovolts 300 4800 events 30 mn 2400 38400 via input I11 via input I21 KTS1 to 8 KTS9 to 16 KTS17 to 24 KTS25 to 32 KTS33 to 40 KTS41 to 48 KTS49 to 56 KTS57 to 64 I1 I2 I11 to I18 I21 to I28 I31 to I38 Installation - Use - General characteristics - Testing Status menu parameters (cont’d) menu name Microswitch settings function voltage board current board SW1 board 2 board 3 CT (ECM 1) CSP (ECA) CT (ECM 2) SW2 SW2 SW2 SW1 SW1 SW1 put an X in the box to indicate switch setting e.g. switch set to right X Sepam 2000 generator program logic parameters KP 0 or 1 KP KP1 open/close control KP2 open/close control KP4 external protection NO/NC KP5 undervoltage tripping, setting 1 KP6 undervoltage tripping, setting 2 KP7 undervoltage tripping, setting 1 KP8 undervoltage tripping, setting 2 KP9 neutral voltage displacement tripping KP10 underfrequency tripping KP11 overfrequency tripping KP12 generator shutdown by reverse power active KP13 lockout by undervoltage setting 1 KP14 lockout by undervoltage setting 2 KP15 lockout by undervoltage setting 1 time delay (value) KP16 KP17 KP18 KP19 KP20 KP21 KP33 KP34 KP35 KP38 KP KP50 KP51 KP52 0 or 1 lockout by undervoltage setting 2 display of programmed program logic BI pilot wire test reset operation counter reset phase fault tripping counter reset to zero of running hours counter for G01, G02, G12 used with G00, deactivation of reverse power P and Q for G00, assignment of outputs O21 to O24 closing without synchro-check for G00, use of I18 for G03, G04: acknowledgment of operating mode with voltage absent remote setting active / inactive 0 or 1 impulse inhibition of disturbance recording records automatic triggering of disturbance recording manual triggering of disturbance recording time delay (value) T1 s recovery of open/closed data upon change in device position T5 s duration of remote control tripping impulse T2 s duration of closing order T6 s duration of remote control closing impulse T3 s inhibition of transmit blocking input after tripping T10 s maintaining of closing request with synchro-check T16 s confirmation of pressure switch fault Installation - Use - General characteristics - Testing 4/23 Sepam 2000 Generator function identification overcurrent setting curve Is T F011 F012 F013 F014 F021 F022 thermal overload Adjust. T1 T2 OL1 alarm OL2 trip. F431 voltage restrained overcurrent negative sequence / unbalance curve Is T curve Is T curve Iso F191 F451 earth fault T R and H2 F061 F062 F063 F064 F071 F072 F091 F092 undercurrent Us T Us T Vso T Fs T Fs T F321-341-361 F322-342-362 overcurrent F301 F302 positive sequence undervoltage F391 underfrequency F561 overfrequency F571 directional overcurrent curve angle Is T F511-F521 θo directional earth fault Iso T F501 reverse power Ps T Qs T Ts1 Ts2 F531 reactive overpower F541 RTD F461 F462 F463 F464 F465 F466 tick off the box when the setting is done 4/24 Installation - Use - General characteristics - Testing Sepam 2000 Generator (cont’d) function identification setting RTD (cont’d) Ts1 Ts2 F471 F472 F473 F474 F475 F476 synchro-check F181 dUs dFs dϕs Us high Us low mode Ta restricted earth fault Iso F641 F651 generator differential Is F621 tick off the box when the setting is done Settings made on: Signature Signature by: Comments: Installation - Use - General characteristics - Testing 4/25 Schneider Electric Postal address F-38050 Grenoble cedex 9 Tel: 33 (0)4 76 57 60 60 Telex: merge 320842 F http://www.schneider-electric.com Rcs Nanterre B 954 503 439 3140750A-F ART.75751 As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper. Publishing: Schneider Electric Design, production: Idra Printing: 12 / 1999