2vaa002100 en s control hpc800 pni800 pdp800 hai hao805 revision a1 release notes

advertisement
Symphony Plus - Harmony
S+ Control: HPC800, PNI800, PDP800, HAI/HAO805
Release Notes
Symphony Plus
Release Notes
New Functions and Known Problems
NOTICE
This document contains information about one or more ABB products and may include a description of or a
reference to one or more standards that may be generally relevant to the ABB products. The presence of
any such description of a standard or reference to a standard is not a representation that all of the ABB
products referenced in this document support all of the features of the described or referenced standard. In
order to determine the specific features supported by a particular ABB product, the reader should consult the
product specifications for the particular ABB product. ABB may have one or more patents or pending patent
applications protecting the intellectual property in the ABB products described in this document.
The information in this document is subject to change without notice and should not be construed as a
commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. In no
event shall ABB be liable for direct, indirect, special, incidental or consequential damages of any nature or
kind arising from the use of this document, nor shall ABB be liable for incidental or consequential damages
arising from use of any software or hardware described in this document.
This document and parts thereof must not be reproduced or copied without written permission
from ABB, and the contents thereof must not be imparted to a third party nor used for any unauthorized
purpose.
The software or hardware described in this document is furnished under a license and may be used, copied,
or disclosed only in accordance with the terms of such license. This product meets the requirements
specified in EMC Directive 2004/108/EEC and in Low Voltage Directive 2006/95/EEC (pending).
TRADEMARKS
Symphony is a registered or pending trademark of ABB S.p.A.
All rights to copyrights, registered trademarks, and trademarks reside with their respective owners.
Copyright © 2012 ABB.
All rights reserved.
Release:
June 2012
Document number:
2VAA002100R0001
Release Notes
1.
INTRODUCTION .............................................................................................6
1.1
Overview ..................................................................................................................6
1.2
S+Control & I/O Module Descriptions ..................................................................7
1.2.1 PNI800 ...............................................................................................................7
1.2.2 HPC800 Controller .............................................................................................8
1.2.3 PROFIBUS Master Module - PDP800 ...............................................................8
1.2.4 HART Analog Input and Output Modules – HAI805 & HAO805 ........................9
1.3
Symphony and Symphony Plus Architecture Comparison .............................10
2.
RELATED DOCUMENTATION .....................................................................10
3.
COMPATIBILITY MATRIX ............................................................................10
4.
KNOWN PROBLEMS ...................................................................................11
5.
REVISION HISTORY ....................................................................................11
1. INTRODUCTION
This document is the release notes for the HPC800, PNI800, PDP800, HAI/HAO805 Symphony Plus Control
and IO products. This document provides a brief overview on Symphony Plus functionality. It enumerates
known problems encountered in the final testing of this product release and identifies workarounds that help
overcome the problem. The document contains additional notes that may be valuable to customers and
service personnel working with the product.
1.1
Overview
Symphony Plus is a completely new Control System based on field proven Harmony technology.
 PN800 Plant Network is redundant, 100 MB Ethernet running “Infi-Net over Ethernet” protocol
o The PNI800 module allows S+ Operations and S+ Engineering tools to interface to the
PN800 network
 HPC800 is DIN-Rail Controller / PCU consisting of 2 modules mounted in a common base (MB810)
o HC800 Control Processor – Similar to the functionality provided by the Symphony system’s
BRC controller.
o CP800 Communications Processor – Similar to the functionality provided by the Symphony
system’s NIS / NPM modules.
 PDP800 Profibus Interface for HPC800
o Supports S800 I/O, S+ Turbine Control & Protection modules, and Profibus PA using DPPA protocol adaptors
 HAI805 and HAO805 HART Analog I/O Modules.
Figure 1 shows the PN800 network architecture.
Figure 1 S+ Control & I/O Components
INICI800
Release Notes
1.2
S+Control & I/O Module Descriptions
All Symphony Plus modules are DIN-rail mounted devices and are powered using 24 VDC. See the user manuals for
installation, configuration, operation and troubleshooting procedures. The following sections provide a brief overview of
each Symphony Plus product.
1.2.1 PNI800
Figure 2 PNI800 Module Mounted in the MB805 Base
The PNI800 provides the hardened, industrial PC Workstation to PN800 Plant Network interface, similar to the CIU for
Infi-Net. The PNI800 establishes and maintains the XR database for HMI console applications and the Communications
Server function for Composer. Similar to IET800, PNI800 requires a software license, is configured using the
“HsysConfig“ utility that is embedded within Composer, S+ Operations, 800xA for Harmony, etc.
1.2.2 HPC800 Controller
Figure 3 Redundant HPC800 Controller
The HPC800 employs a high performance MCF5475 ColdFire CPU processor with over 400 MIPS, 64 MB DDR2, 2 MB
NVRAM, and 1MB Flash (firmware). Each module only consumes 5 W of power @ 24VDC.
The HPC800 has expanded ModBus TCP interface capability over previous Symphony controllers such as the BRC400.
The HPC800 supports up to 8 Servers, 128 Clients and 10,000 ModBus points. The HPC800 consists of the HC800
Control Processor, CP800, Communications Processor, and the MB810 Mounting Base.
1.2.3 PROFIBUS Master Module - PDP800
Figure 4 Redundant PDP800 Modules Mounted in the PTU810 Base
The PDP800 Profibus DP Interface is a PROFIBUS Master. The PDP800 is based on the latest generation ColdFire
54418 CPU from Freescale (Motorola). The PDP800 has 128 MB DRAM, and 4 MB Flash Memory. The PDP800
supports Profibus DP – V0, V1, V2 directly on the module, and Profibus PA using DP to PA protocol adaptors (e.g. P+F
Profibus PowerHub). The PDP800 provides both Master & Line Redundancy and supports baud rates from 9.6 kB to
12.0 MB.
INICI800
Release Notes
When communicating @ 12 MB, PDP800 can be configured to scan Profibus in as little as 2 msec.
Turbine Control closed loop step response time of 25 msec has been demonstrated using the HPC800, PDP800 and the
DIN-Rail TC modules.
1.2.4 HART Analog Input and Output Modules – HAI805 & HAO805
The HAI805 HART AI and HAO805 HART AO modules have been designed to provide the highest possible performance
possible with current HART communications technology. Both modules have a dedicated HART modem on each of their
8 channels. This enables the modules to scan the each Input / Output channel for up to 4 “Secondary” variables in under
1 second. Thus, the secondary variables are can be used for control within the HPC800 controller. The HAI805 support
both System & Field powered 4 – 20 mADC inputs, and HAO805 supports only System powered 4 – 20 mADC outputs.
1.3
Symphony and Symphony Plus Architecture Comparison
The following diagram compares the Symphony architecture to the new Symphony Plus architecture.
2. RELATED DOCUMENTATION
Following is a list of documents applicable to the system configuration of Symphony Plus software products:
Product
S+ Control: HPC800
S+ Control: PNI800
S+ Control: PDP800
S+ Control: HAI/HAO805
S+ Engineering:
Composer Harmony
S+ Engineering:
Composer Harmony
Document Title
S+ Control: HPC800 User Manual
S+ Control: PNI800 Harmony Plant Network
(PN800) Interface User Manual
S+ Control: PDP800 PROFIBUS Master Module
Hardware and Operation User Manual
S+ Control: HAI/HAO805 HART TM Analog
Input/Output Modules User Manual
S+ Engineering: Composer Harmony Function Code
Application Manual
S+ Engineering: Composer Harmony Primary
Interface Manual
Document ID
2VAA001586
2VAA001719
2VAA001446
2VAA001714
2VAA000844
2VAA000812
All related documents are provided in PDF format and most of them are included on the Symphony Plus
DVD, the others are available for download from ABB’s Solutionsbank website. To access the
documentation on the DVD, select the option “Browse DVD” from the Installation Manager menu, and
navigate to the folder Documentation, containing one subfolder for each functional area.
3. COMPATIBILITY MATRIX
These products are compatible with S+ Engineering: Composer Harmony version 6.0 and later. Composer
Harmony Composer version 6.0 includes the Harmony System Configuration program that is used to
configure the PNI800 module and its connection to the host computer.
INICI800
Release Notes
4. KNOWN PROBLEMS
The following problems have been identified in the Symphony Plus HC800, CP800, PDP800, HAI805 and
HAO805 products.
Product
Issue
All
The S+ Control & IO modules do not support
Sequence of Events (SOE)
PDP800
Cannot connect to Profibus devices to set
parameters or observe values from Composer
Field.
A running primary PDP800 may halt when a
redundant PDP800 is inserted into the PTU810
mounting base.
PDP800
PDP800
PDP800
The PDP800 modules lose communications with
the CI840 modules and connected S800 I/O
modules
Redundant PDP800 module halted with MFT
Workarounds, Clarifications, and Helpful
Hints
SOE is not supported in this release of
Symphony Plus.
Retry until connection is successful or use
Composer Harmony to monitor PROFIBUS
devices.
Recover the halted module by pressing the
STOP/RESET pushbutton once.
To prevent the condition from occurring
remove and insert modules directly into the
mounting base, i.e. do not tilt the module at
an angle. See the user manual for insertion
and removal instructions.
Restart the CI840 modules to recover
communications with the CI840 and any
connect S800 I/O modules
Reset the PDP800 module
PDP800
Redundant PDP800 module halted with an
address/bus error (error 32).
Reset the PDP800 module
CP800,
PNI800
Loss of I/P address and PNI800 license string
may occurs during power cycling.
1.
2.
HC800
The backup controller takes a long time to come
online when the "Go Back" option is used during
online configuration.
Unable to download parameters to PDP800,
HAI805, or HAO805 module.
Reformat the backup module after
performing a “Go Back” during online
configuration.
Retry download until successful.
PDP800 may halt with an MFT when attempting to
download a CLD containing FC222. May result in
loss of PROFIBUS I/O subsystem
Reset PDP800 module and attempt
download again.
PDP800,
HAI805,
HAO805
PDP800
Avoid power cycling
Re-load I/P address and license string
(PNI800 only) in to module.
5. REVISION HISTORY
Rev.
1
Date / Initial
New Document, first Release S+ Control
5 June
2012/initial
ABB AG
Power Generation
Mannheim, Germany
E-Mail: powergeneration@de.abb.com
www.abb.com/controlsystems
ABB Pte. Ltd.
Power Generation
Singapore
E-Mail: powergeneration@sg.abb.com
www.abb.com/controlsystems
Document Number 2VAA002100R0001