Selection Criteria for Claus Tail Gas Treating Processes Mahin Rameshni, P.E. Technical Director, Sulphur Technology and Gas Processing 181 West Huntington Drive, Monrovia, California 91016, USA Mahin.Rameshni@WorleyParsons.com Introduction With the sulphur content of crude oil and natural gas on the increase and tightening sulphur content in fuels, refiners and gas processors are pushed for additional sulphur recovery capacity. At the same time, environmental regulatory agencies of many countries continue to promulgate more stringent standards for sulphur emissions from oil, gas and chemical processing facilities. It is necessary to develop and implement reliable and cost effective technologies to cope with the changing requirements. In response to this trend, several new technologies are now emerging to comply with the most stringent regulations. Typical sulphur recovery efficiencies for Claus plants are 90-96% for a two- stage, and 95-98% for a three- stage plant. Most countries require sulphur recovery efficiency in the range of 98.5% to 99.9+%. Therefore the sulphur constituents in the Claus tail gas need to be reduced further. The key parameters effecting the selection of the tail gas clean-up process are: f Feed Gas composition, including H2S content and hydrocarbons and other contaminants f Existing equipment and process configuration f Required recovery efficiency f Concentration of sulphur species in the stack gas f Ease of operation f Remote location f Sulphur product quality f Costs (capital and operating) -1- Various aspects and considerations when choosing the most optimum process configuration for tail gas treating are discussed. There are several key features effecting the selection of the tail gas clean-up process that three steps should be taken. When required recovery efficiency and concentration of sulphur species in the stack gas is known, selection of the tail gas process is one step closer. The first step is one the most important criteria for the selection of the tail gas treating processes. When the required sulphur recovery is established, the selection of the tail gas process will be limited. Table 1 represents the various tail gas clean-up process with the recovery will be achieved. When concentration of impurities in the acid gas such as COS and CS2, H2S content, and feed gas composition, and finally treated gas specifications are established, the type of amine used for a particular application could be selected in step two. Finally the third step is the evaluation between the identical process chosen for ease of operation, capital and operating cost, and remote location. For revamp units, minimum equipment modifications and process configuration should be considered as a main key factor. The WorleyParsons BSR Amine process for Claus tail gas treatment clearly represents Best Available Control Technology (BACT), potentially achieving 99.99+% overall sulphur recovery with emissions of < 10 ppmv H2S and 30 ppmv total sulphur. There are other processes such as direct oxidations processes, Sub dew point processes that are able to achieve higher sulphur recovery from the conventional 3-stage Claus unit up to 99.8 % depending on the feed compositions to the Claus unit. WorleyParsons offer DEGSULF a sub dew point process with partnership with DEG-ITS for those applications with the relaxed overall recovery. Brief History Under the leadership of David Beavon of the Ralph M. Parsons Company, Parsons and Union Oil of California (Unocal) co-developed the Beavon Sulphur Removal Process (BSRP) in San Pedro, California, in the late 1960s, for which US Patent 3,752, 877 was awarded to Parsons in 1973. The fundamental process, still employed today, typically heats the Claus tail gas to 550-650°F (~ 290-340°C) by inline sub-stoichiometric combustion of natural gas in a Reducing Gas Generator (RGG) for subsequent catalytic reduction of virtually all non-H2S sulphur components to H2S. Conversion of SO2 and elemental sulphur (Sx) is by hydrogenation: SO2 + 3 H2 → H2S + 4 H2O + ΔH Sx + x H2 → x H2S + ΔH Conversion of COS and CS2 is by hydrolysis: COS + H2O → H2S + CO2 + + ΔH CS2 + 2 H2O → 2 H2S + CO2 + ΔH -2- CO is essentially hydrolyzed to yield additional H2 according to the “water gas shift” reaction: CO + H2O → H2 + CO2 + ΔH CO and H2 naturally present in the Claus tail gas will typically satisfy up to 70% of TGU demand, with the balance generated in the RGG. A cobalt-moly catalyst, similar to hydrodesulphurization catalyst, is typically employed. As received, the catalyst is an alumina substrate impregnated with oxides of cobalt and molybdenum which must be converted to the active sulfided state. To convert the cobalt oxide to the sulfide, a simple exchange of the oxide with H2S is all that is necessary: CoO + H2S → CoS + H2O + ΔH Converting molybdenum trioxide to the active disulfide, however, requires a change in oxidation number that also requires hydrogen: MoO3 + 2 H2S + H2 → MoS2 + 3 H2O + ΔH The reduced tail gas is then cooled to 90-100°F (~ 30-40°C) to condense most of the water vapor, which accounts for ~ 35% of the stream. While Beavon recognized the potential for H2S recovery using an alkanolamine, he was concerned about formation of heat stable thiosulfate resulting from SO2 breakthroughs. Consequently, Parsons adopted the Stretford redox process which employed an alkaline vanadium salt solution to oxidize absorbed H2S to elemental sulphur particles which were subsequently removed by froth flotation, filtered and melted. The Beavon Stretford process actually had some advantages over amine absorption: f No acid gas recycle to the Claus unit f No steam consumption f < 5 ppm residual H2S, obviating incineration f Temporary high capacity for excessive Claus tail gas H2S or SO2 resulting from off-ratio operation However, these were outweighed by poor sulphur quality, high chemical makeup costs, high disposal costs from purging of byproduct thiosulfate, absorber fouling, oxidizer foaming, inconsistent froth formation, troublesome filter operation and atmospheric corrosion. By the 1980s, Parsons essentially abandoned the Stretford process in favor of MDEA absorption/ regeneration. Today, WorleyParsons retains the BSR trademark in reference to the catalytic reduction stage and subsequent cooling/condensation. A typical BSR Amine system is shown in Figure 1. Figure 2 is a typical BSR amine system including the start up blower. -3- Reducing Gas Generator (RGG) Many competitors use the inline burner design in Figure 3. Burner vibration is common, the extreme temperature gradient between the combustion and tail gas mixing zones makes it difficult to optimize skin temperatures at the transition, and a combustion zone shell leak resulting from localized refractory failure forces a shutdown. The proposed BSR unit comprises of three process steps: f Reducing Gas Generation (RGG) and tail gas preheat f Hydrogenation/Hydrolysis of SO2 and other sulphur species to H2S f Gas cooling and waste heat recovery f WorleyParsons proprietary RGG design provides process gas reheating and reducing gas (H2 and CO) generation in one single process unit. No external supply of hydrogen gas is required. This feature enhances the reliability of the process unit by eliminating the uncertainties associated with the availability of external hydrogen supply and the quality of hydrogen gas. WorleyParsons design has the following advantages compare to the other licensors. WorleyParsons Conventional BSR Section f Start Up Blower – reduce the emission during start up to the stack f Caustic wash – reduce breakthrough of SO2 to amine during start up and prevent degrade of the solvent, No SO2 breakthrough to the amine unit f Stable operation for different mode of operation f Good Turn down f No external hydrogen required f Less pressure drop f Less heat loss in RGG configuration f Could be started up independently from SRU’s f No vibration in RGG Burner f No heat Loss in RGG -4- f No Refractory damages as the results of un-uniform heat distribution f Proprietary RGG design provides process gas reheating and reducing gas (H2 and CO) generation in one single process unit. External supply of hydrogen gas is not required in most cases. f Start up blower, to eliminate violating the emission during the start up -5- Figure 1 – WorleyParsons BSR Amine Flow Scheme -6- Figure 2 – WorleyParsons BSR Amine Flow Scheme with start up blower -7- Figure 3– Common TGU Feed Heater By comparison, the WorleyParsons design (Figure 4) employs a brick-lined internal combustion zone for stable combustion unaffected by downstream turbulence. Optimum outer-shell skin temperatures are easily ensured, heat loss is minimized and potential leakage through the combustion zone wall does not result in atmospheric release. Some units have been in service for 30+ years with no major refractory repairs. The RGG is typically elevated so that minor entrained sulphur will free-drain to the reactor (and vaporize). Figure 4 – WorleyParsons Reducing Gas Generator (RGG) Industry consensus is apparently lacking with regard to the optimum air/fuel ratio. Many competitors’ units operate at stoichiometric air and rely on supplemental H2 for hydrogenation of SO2 and Sx. Perhaps contrary to intuition, equilibrium O2 is nominally 0.6 % at stoichiometric air, and only goes to zero at < 90% of stoichiometric. There is experience to suggest that chronic O2 leakage leads to catalyst sulfation, although there is disagreement within the industry on this point. Nonetheless, WorleyParsons generally recommends operating at 80% of stoichiometric to avoid, or at least minimize, O2 leakage (and also maximize H2 yield). The advisability of supplemental H2 is also a source of controversy. Many clients consider the availability of import H2 necessary to minimize the risk of SO2 breakthroughs, whereas in reality it is as easy to reduce Claus combustion air (with the same effect) as increase H2 addition. In the absence of supplemental H2, the operator quickly learns the value of monitoring residual H2 as a -8- sensitive indicator of Claus tail gas ratio, and arguably is more likely to routinely optimize Claus air demand when constrained by a limited H2 supply. Three-stage Claus units clearly do not need supplemental H2, while residual H2 may be marginal with 2-stage units, in which case supplemental H2 may be advisable to ensure ability to optimize the Claus tail gas H2S/SO2 ratio. H2 analyzers based on thermal conductivity measurement are very reliable, with minimal servicing. Where the TGU is coupled to a single Claus train, the H2 analyzer can in fact supplant the Claus air demand analyzer. Where multiple Claus trains are coupled to a single TGU, combustion air to a Claus unit whose air demand analyzer is out of service can be temporarily adjusted based on TGU residual H2. LP steam injection to the burner in the nominal ratio of 1/1 lb/lb steam/fuel is generally advisable for soot inhibition when firing sub-stoichiometrically, by virtue of the following reactions: C + H2O → CO + H2 - ΔH C + 2 H2O → CO2 + 2 H2 - ΔH While modern high-intensity burners may be operable at as low as 80% of stoichiometric air without steam injection, injection is still prudent in view of the possibly of lower air/gas ratios resulting from meter error or localized fuel-rich zones due to burner damage or fouling. With high intensity burners, steam injection via a dedicated steam gun is preferred. Otherwise, injection into the combustion air is the most practical. Figure 5 – WorleyParsons Reducing Gas Generator (RGG) Details -9- Hydrogenation Reactor With good catalyst activity and no excessive HCs in the acid gas feed to the Reaction Furnace, organic residuals in the Absorber offgas should be as shown in Table 1: Table 1 – Residual Sulphur with Fresh Catalyst Contaminant PPMV Carbonyl sulfide (COS) < 20 Carbon monoxide (CO) < 200 Carbon disulfide (CS2) 0 Methyl mercaptan (CH3SH) 0 With fresh conventional catalyst, temperatures of 400-450°F (204-232°C) are typically required to initiate the hydrogenation reactions, and 540-560°F (282-293°C) for hydrolysis. As the catalyst loses activity with age, progressively higher temperatures may be required. Typically, activity loss is first evidenced by (1) reduced COS, CS2 and CO conversion, and (2) potential methyl mercaptan formed by the reaction of CS2 and H2, while hydrogenation of SO2 and Sx may still be complete because of the lower initiation temperatures required. The potential formation of methyl mercaptan at low temperature or impaired catalyst activity is perhaps not widely appreciated. In cases where the TGU tail gas is discharged without incineration, nominal mercaptan levels can result in serious nuisance odors. In Stretford units, there is reason to expect that the mercaptan is oxidized to disulfide oil (DSO) which can impair froth formation. Excessive HCs in the SRU acid gas feed will tend to increase the carbon-sulphur compounds in the Reactor effluent. In the Figure 4 example, HCs in the amine acid gas are evidenced by (1) increased air demand per volume of gas, (2) increased tail gas volume resulting from the additional air and HC combustion products, and (3) increased Total Reduced Sulphur (TRS) in the Absorber offgas – predominantly COS, but also potentially including CS2 and methyl mercaptan (RSH). (While TRS also includes H2S, the H2S content did not increase in this case.) Low Temperature Hydrogenation Catalyst WorleyParsons has started offering low temperature catalyst if requested by client as applicable and meet the project emissions. Low temperature catalyst eliminate of using the reducing gas generator and indirect heating system could be used instead. Low-temperature TGU catalysts reportedly capable of operating at inlet temperatures of 210-240°C (410-464°F), achievable with steam reheat, have recently become available. The primary advantage (in a new unit) is elimination of the RGG, translating to (1) lower capital cost, (2) operating simplicity, (3) improved turndown, (4) reduced TGU tail gas volume, (5) reduced CO2 recycle to the SRU, and (6) elimination of risk of catalyst damage by RGG misoperation. - 10 - Historically, Claus tail gas treating units (TGTU) have required reactor inlet temperatures of ~ 550°F for appreciable hydrolysis of COS, CS2 and CO, typically requiring preheat by inline firing or heat exchange with hot oil or heat transfer fluid. Vendor claims of energy savings are questionable since they tend to (1) assume the plant is long on LP steam, and (2) disregard the cost of HP steam. Long term performance of low-temperature catalysts is still uncertain. The following considerations should be taken into account: f A steam reheater will limit the ability to compensate for normal catalyst activity loss with age, potentially limiting its useful life. f A bottom layer of titania in the first Claus converter may be required for COS/CS2 hydrolysis. f Higher residual CO levels could mean operating the incinerator at 1500°F (~ 800°C) instead of 1200°F (~ 650°C). f Incomplete CS2 destruction, and hence methyl mercaptan formation, can result in serious nuisance odors if the TGU tail gas is discharged without incineration. Reactor inlet temperatures are only half the story; outlet temperatures are the other half. Any catalyst will probably initiate SO2 hydrogenation at 400-450°F (~ 205-230°C) and, with sufficient temperature rise and excess catalyst, will subsequently achieve virtually complete hydrolysis. New catalysts by Criterion and Axens require lower activation temperatures achievable by indirect reheat by 600# steam, thus reducing investment cost, operating complexity and, in some cases, energy consumption. In addition, lower reactor outlet temperatures may obviate the downstream waste heat boiler. While reduced investment and complexity are a given, whether the claimed energy savings is real is site-specific. Reduced feed preheat energy only constitutes a savings if the plant is already long on low-pressure waste heat steam (40-70 psig). Otherwise, incremental heat input is fully recovered. Furthermore, in the absence of a steam surplus, elimination of the waste heat boiler may have forfeited recoverable BTUs. Relative COS, CS2 and CO conversion efficiencies need to be compared. It is not necessarily sufficient to achieve regulatory compliance. COS, CS2 and CO Hydrolysis using low temperature catalyst Relative COS, CS2 and CO conversion efficiencies can be critical. It is not necessarily sufficient to achieve regulatory compliance. f Regulations could become more stringent in the future. - 11 - f Some plants must also buy emission credits per pound of SO2 discharged. f Excessive CO residuals could require higher incinerator temperatures, or require incineration otherwise obviated in units able to achieve TGTU absorber H2S emissions < 10 ppm by the use of acid-aided MDEA. Hydrolysis of COS, CS2 and CO typically requires higher temperatures than hydrogenation of SO2 and Sx. Perhaps accordingly, COS, CS2 and CO conversion efficiencies are the first to suffer as conventional catalysts lose activity with age. Higher reactor inlet temperatures will tend to compensate for deactivation, thus extending catalyst life considerably. Depending on the design limits, temperatures can generally be increased by 50-150°F (28-83°C). Assuming the same holds true for the low temperature catalysts, a steam reheater will substantially limit the extent to which temperatures can be increased, in effect potentially shortening catalyst life. The lower initiation temperature of the Criterion 734 at start-of-run is thus significant, as it affords the greatest margin for increase. At 464°F (240°C) – generally the limit of a 600# steam reheater – hydrolysis of CO, COS and CS2 approaches that of conventional high temperature catalysts. At 428°F (220°C), however, Axens concedes that COS/CS2 conversion must be accomplished in the 1st Claus stage by (1) supplementing the alumina bed with a bottom layer of expensive titania catalyst, or (2) increasing the inlet temperature to 550-600°F (288-316°C). The latter will nominally f reduce Claus recovery efficiency from f increase SRU tail gas rate f increase TGTU sulphur load However, the 1st stage will not effect CO conversion. Conventional cobalt-moly catalyst will generate minor, but significant, levels of methyl mercaptan by the reaction of CS2 and hydrogen at 480°F (249°C) when in good condition, and at much higher temperatures if the catalyst is aged or damaged. While the manufacturers claim no residual mercaptans with the low temperature catalysts, there is some uncertainty – in the author’s view – as to whether that will remain true a few years into the run. Hydrogen Balance using low temperature catalyst Compared with firing the feed heater at stoichiometric air and importing H2, a steam reheater will of course have no impact on the H2 balance. However, many plants avoid the need for supplemental H2 by the use of a reducing gas generator (RGG), typically burning natural gas substoichiometrically to generate H2 and CO. - 12 - In the absence of an RGG, the alternative is to operate the SRU more air-deficient as necessary to maintain, say, 2% residual H2 downstream of the TGTU reactor. This will nominally f reduce Claus recovery efficiency f increase SRU tail gas rate f increase TGTU sulphur load CO2 Balance using low temperature catalyst Eliminating the inline burner has the benefit of reducing the TGTU tail gas volume (for the assumed basis with an RGG). Assuming 85% CO2 slip, the acid gas load on the TGTU amine is reduced. Energy Balance using low temperature catalyst A steam reheater will not only eliminate the following natural gas required by the RGG, but will also reduce incinerator fuel by virtue of the reduced tail gas rate: f RGG fuel savings f Incinerator fuel savings Assuming H2S/SO2 = 2 in the SRU tail gas, of supplemental H2 will be required to maintain a 2% residual in the TGTU tail gas. As a rule-of-thumb, the value of relatively pure (non-reformer) H2 is four times that of natural gas. Figure 6 represents WorleyParsons BSR/amine with the low temperature catalyst. - 13 - SRU TAIL GAS STARTUP BLOWER H2 RECYCLE WATER HP STEAM CONTACT CONDENSER SOUR WATER BLOWDOWN HYDROGENATION REACTOR DESUPERHEATER REDUCED TAIL GAS 10% NaOH TREATED TAIL GAS TO ATMOSPHERE OR INCINERATOR ABSORBER ACID GAS RECYCLE TO SRU REFLUX INTERMITTENT PURGE TO SWS REGENERATOR RICH AMINE PROCESS STEAM LEAN AMINE Figure 6 – WorleyParsons BSR Amine Flow Scheme with Low Temperature Catalyst - 14 - Figure 7 – WorleyParsons Impact of Hydrocarbons in Acid Gas to SRU In the event of a burner trip, there is usually ample time to relight the RGG before the reactor bed cools to the point of SO2 breakthrough. In the Figure 7 example, relight was delayed by a plugged pilot fuel gas restriction orifice, and the main burner was down ~ one hour (65 minutes). At all times at least one point in the bed was 510ºF or higher, which likely explains the absence of an SO2 breakthrough. By the end of, say, a 2-hour outage, all temperatures would have been < 400ºF, and it is possible that serious SO2 breakthrough would thus start to occur within 1½-2 hours. The reactor contained 37.5 Mlb of Criterion 534 cobalt-moly catalyst, a 2-Mlb top layer of ½” alumina and a 4.5-Mlb support layer of ceramic balls. - 15 - Reactor Temperatures 800 700 Temperature, F 600 500 400 300 11:00 10:55 10:49 10:44 10:39 10:34 10:29 10:24 10:20 10:15 10:09 9:59 10:05 9:54 9:49 9:44 9:39 9:34 9:29 9:25 9:20 9:14 9:10 9:05 9:00 8:55 8:50 8:45 8:40 8:35 8:30 8:25 8:20 8:14 8:09 8:05 8:00 200 Figure 8 – WorleyParsons Hydrogenation Reactor Bed Temperatures During RGG Outage The total tail gas rate is shown in Figure 9. There are actually two identical reactors in parallel, with only half of the indicated flow through each. - 16 - TGTU Tail Gas Rate 1400 1350 Tail gas rate, MSCFH 1300 1250 1200 1150 1100 1050 Figure 9 – WorleyParsons TGU Tail Gas Rate During RGG Outage Resultant TRS (measured at the absorber outlet) and SOx emissions are shown in Figure 10. - 17 - 11:00 10:54 10:49 10:44 10:39 10:34 10:29 10:24 10:19 10:15 10:09 10:04 9:55 10:00 9:50 9:44 9:40 9:35 9:29 9:24 9:19 9:14 9:09 9:04 8:59 8:54 8:49 8:45 8:40 8:35 8:29 8:24 8:19 8:15 8:09 8:05 8:00 1000 Emissions 400 350 absorber TRS F-754 PPM, corrected to air-free basis 300 250 200 150 100 50 10:59 10:54 10:49 10:44 10:39 10:35 10:29 10:24 10:19 10:14 10:09 9:59 10:04 9:54 9:49 9:45 9:39 9:34 9:30 9:25 9:20 9:15 9:10 9:05 9:00 8:55 8:50 8:45 8:40 8:34 8:30 8:25 8:19 8:14 8:10 8:04 8:00 0 Figure 10–WorleyParsons Impact of RGG Outage on Emissions Contact Condenser (2-Stage Quench) Common industry practice is to cool the reduced tail gas from the reactor by the generation of LP waste heat steam followed by direct quench with a recirculating water stream to cool it to 90100°F (~ 30-40°C), thus condensing most of the water vapor which accounts for ~ 35% of the stream. WorleyParsons utilizes a unique 2-stage tower comprised of a bottom Desuperheater section and top Contact Condenser. f The contact condenser has 2 sections, the first section de-superheats the gas and scrub any SO2 may breakthrough from hydrogenation reactor, and the second section cools the gas and condensate the water, therefore there is no need for make up water to maintain the caustic concentration. The condense water will provide the water to maintain the caustic concentration. We do not have continuous purge, but we provide water make up for the water is evaporated, just like any other quench system. - 18 - f Tail gas is desuperheated in the lower section of the contact condenser by a circulating water stream. This water is maintained alkaline to protect against any SO2 breakthrough from the reactor. In the upper packed section of the tower, most of the water vapor in the tail gas is condensed by direct contact with a circulating stream of cooled water. A pH analyzer with a low-pH alarm is installed in the quench water circulation line and will indicate when the pH of the quench water is reducing, from either a breakthrough of SO2, or incomplete reduction of the sulphur compounds in the gas stream from the Hydrogenation Reactor. (Figure 1 and 2) A 10 %-wt NaOH solution is recirculated through the Desuperheater to capture SO2 potentially resulting from a process upset, while also cooling it to its dewpoint of ~ 165°F (~ 75°C). The only cooling is by vaporization. The gas is further cooled to 90-100°F (~ 30-40°C) by direct contact with an externally cooled recycle water stream in the upper Contact Condenser section. A recycle water slipstream is returned to the Desuperheater on Desuperheater levelcontrol via two bubble-cap wash trays to capture entrained caustic. A blowdown slipstream of recycle water is purged, usually to sour water, on Contact Condenser level-control. While the recycle water is usually classified as sour water, the H2S content is typically < 50 ppmv by virtue of CO2 saturation. In situations where the increased load on the plant sour water stripper is undesirable, a simple blowdown stripper is occasionally provided at the TGU. This typically involves LP stripping steam injection (as opposed to a reboiler) and return of the uncondensed overhead stream to the Desuperheater. Startup Blower WorleyParsons provide a start up blower on the contact condenser overhead to eliminate flaring large quantities of H2S to atmosphere and to prevent violation of the emission. For those cases that a booster blower required then booster blower will have dual function as a start up blower and as a booster blower. Booster Blower Many of the Claus units that are in operation do not have enough pressure to handle a new tail gas unit in other words the provision of operating the Claus unit at the higher pressure was not considered, if the source pressure changed the existing amine unit requires higher reboiler duty and in most cases required significant changes in the amine unit. WorleyParsons have been offering a booster blower in the tail gas unit to overcome the pressure limitation. Retrofit Tail Gas Units will typically require a booster blower downstream of the Contact Condenser to overcome the additional pressure drop. The blower is located after the Contact Condenser to minimize the actual volume (by virtue of cooling and condensation), and before the Absorber to take advantage of the higher pressure. With proper design and operation, booster blowers are inherently very reliable, requiring minimal maintenance. Typically, the case is cast iron or carbon steel, with an aluminum impellor. N2- - 19 - purged tandem shaft seals (typically carbon rings) eliminate process leakage to atmosphere on the discharge end as well as air aspiration into the process on the suction end, which is typically at a vacuum. Though often viewed as a liability by clients, booster blowers arguably improve operability in several ways: f By recirculating tail gas, the TGU can be started up and shut down independent of the SRUs. f Tail gas recycle ensures process stability at high SRU turndown by (1) avoiding undue RGG burner turndown potentially conducive to sooting due to poor mixing or air/gas flowmeter inaccuracy, and (2) diluting potentially high SO2 levels often typical of high SRU turndown. With advance warning, tail gas recycle can avoid RGG shutdown in the event of an SRU trip. f By routing the SRU and TGU tail gas to the incinerator via a common header, a vacuum can be maintained at the RGG without risk of leaking air from the incinerator back into the TGU, thus potentially further increasing SRU capacity. In the event that the tail gas bypass valve leaks, clean TGU tail gas is recycled to the RGG rather than SRU tail gas bypassing the TGU (as when the RGG pressure is positive). Any such reverse flow will improve bypass valve reliability by excluding sulphur vapor, and the valve can be partially stroked periodically to verify operability without increased emissions. Figure 11– WorleyParsons RGG Vacuum Operation In the absence of a booster blower, a single startup blower recycle is usually provided for tail gas recycle. While these machines tend to be less sophisticated, N2-purged tandem shaft seals are still required. - 20 - The overall configuration of using the booster blower is shown in the Figure 10. This configuration could be used with low temperature catalyst and indirect reheater instead of the RGG. HYDROGENATION REACTOR RGG SRU TAIL GAS REACTOR EFFLUENT COOLER TO INCINERATOR HY-250 PC HC HY-251 CONTACT CONDENSER ABSORBER XY-292 FC BOOSTER BLOWER DESUPERHEATER WATER WASH Figure 12 – WorleyParsons BSR-TGU with Booster Blower configuration - 21 - Solvent Selection Criteria in the Tail Gas Unit The most common solvent is 40-45 %-wt MDEA, (HS-101, or similar) designed for a maximum rich loading of 0.1 mol acid gas (H2S + CO2) per mol amine with typical emission reduction to ~ 100 ppmv H2S. Cooling of the lean amine to at least 100°F (38°C) is important for minimization of emissions and amine circulation rate. Specialty TGU amines are essentially pH-modified MDEA to facilitate stripping to lower residual acid gases for treatment to < 10 ppm H2S, potentially obviating incineration. CO2 slip is also improved. These products are variously marketed as f Dow UCARSOL HS-103 f Ineos Gas/Spec TG-10 f Huntsman MS-300. An alternative to MDEA is ExxonMobil’s Flexsorb SE, a proprietary hindered amine patented by Exxon in partnership with the Ralph M. Parsons Company. The main advantage is a 20-30% reduction in circulation rate. The solvent is much more stable than MDEA, but is also more expensive. Flexsorb SE Plus is also available for treatment to < 10 ppmv H2S. Both solvents require a license agreement with ExxonMobil. It used to be assumed that TGU carbon filtration was not required in view of the absence of hydrocarbons. For MDEA-based solvents, at least, this has proven untrue, presumably due to the generation of surfactant amine degradation products. f Solvent Applications f FLEXSORB® SE Selective removal of H2S f FLEXSORB® SE Plus Selective removal of H2S to less than 10 ppm f FLEXSORB® SE Hybrid Removal of H2S, CO2, and sulphur compounds (mercaptans and COS) f In sulphur plant tail gas applications, FLEXSORB® SE solvents can use as little as one half of the circulation rate and regeneration energy typically required by MDEA based solvents. CO2 f Rejection in TGTU applications is very high, typically >90% rejection. f Flexsorb solvents offer other advantages compare to the other amine solvents for instance, most of applications requires no reclaiming, have good operating experience, low corrosion, and low foaming due to low hydrocarbon absorption, by providing water wash of treated gas at low pressure system amine losses are minimum. - 22 - DEGSulf Sub Dew Point process by WorleyParsons& DEG-ITS DEGSulf-SDP is a sulphur recovery process of the Claus type. A plant consists typically of a Claus furnace plus downstream just 2 catalytic reactors and sulphur condensers. The reactors contain a heat exchanger which keeps the operating temperature for each reactor at its optimum. This simple system, described in detail below, allows reaching up to 99.85% sulphur recovery rate. Gas containing hydrogen sulfide (=H2S) is sent to the Claus furnace. There it is burned with a stoichiometric deficiency of air so that one third of the H2S is converted to SO2. The residual H2S and the SO2 react to elemental sulphur according to the Claus reaction (I): (I) 2 H2S + SO2 3/x Sx + 2 H2O x = 2,4,6,8 indicates the different sulphur modifications Typically a recovery rate of over 60 % is realized in the furnace. Gas from the waste heat boiler and sulphur condenser of the Claus furnace is reheated by a hot gas bypass. It then flows via 4-way valve to the adiabatic part of the first reactor, which is filled with a catalyst of high COS and CS2 conversion capability. Residual traces of free oxygen from the Claus furnace are eliminated in this layer. The gas enters the cooled section of the reactor bed at a temperature of between 300 and 350°C. Cooling takes place by evaporating boiler feed water or hot oil. Here the Claus reaction continues further close to the equilibrium at appr. 260 °C, which is slightly above the sulphur dew point at outlet conditions. The gas leaves the reactor and passes via the second 4-way valve to the only sulphur condenser of the catalytic part. The sulphur condenser operates at gas outlet temperatures of between 135 °C and 150 °C and produces low pressure steam. The process gas leaves the condenser through a mist eliminator. Total sulphur recovery up to this point exceeds 95 %. The gas is reheated again before entering the second reactor which can be regarded as the tail gas treatment. In the steam jacketed pipe the temperature is raised by appr. 20°C in order to be safely above the sulphur dew point. In the adiabatic zone of the second reactor the Claus reaction proceeds. Claus gas then enters the cooled part of the second reactor, where the reaction temperature is lowered to 100 - 125 °C by the cooling coils. Elemental sulphur from the adiabatic zone and formed in the cooled zone is adsorbed by the aluminum-based catalyst. The coils keep the reactor outlet temperature at constant level throughout the complete adsorption period. The evenly low temperature throughout the bed causes a substantial increase of the sulphur recovery rate compared to state-of-the-art processes. - 23 - E-201 WASTE HEAT BOILER F-201 REACTION FURNACE PC E-202 SULFUR CONDENSER E-203 NO. 1 REHEATER R-201 NO. 1 REACTOR V-203 NO. 1 REACTOR STEAM DRUM E-205 NO. 1 REACTOR STEAM CONDENSER E-204 NO. 2 REHEATER R-202 NO. 2 REACTOR V-204 NO. 2 REACOR STEAM DRUM E-206 NO. 2 REACTOR STEAM CONDENSER PA-201 DEGASSING PACKAGE T-201 SULFUR PIT ED-201 SULFUR PIT VENT EDUCTOR FC ACID GAS FROM KO DRUM - X FC TC TC X E-205 MP STEAM E-206 MP STEAM M + X PC MP STEAM F-201 PC TAIL GAS TO INCINERAOR E-204 E-203 X PC R-201 R-202 LI E-201 LI V-203 T CONDENSATE V-204 FC BFW LC NH3 GAS FROM KO DRUM T BFW CONDENSATE TC REACTOR SWITCHING CONTROLS TC AC M H2S/SO2 E-202 BLOWDOWN VENT FC BFW FC VENT GAS TO INCINERATOR B-201 FC ED-201 MP STEAM PA-201 SULFUR M COMBUSTION AIR FROM SPARE BLOWER M T-201 P-203A/B B-201 COMBUSTION AIR BLOWER P-203A/B SULFUR DEGASSING PUMP PROCESS FLOW DIAGRAM - SULFUR RECOVERY UNIT – TRAIN 2 Figure 13, WorleyParsons /DEG-ITS Sub Dew Point process (DEGSULF) - 24 - P-204A/B P-204A/B SULFUR TRANSFER PUMP AIR Ammonia Destruction in a TGU (RACTM) The general industry consensus is that the amount of ammonia that can be conventionally processed in the SRU is limited to 30-35 %-vol on a wet basis. With what appears to be a trend toward higher-nitrogen crudes, refiners are increasingly faced with the need for alternative processing schemes, as well as SRU debottlenecking. With sour water stripping schemes such as Chevron’s Waste Water Treatment (WWT) process for separating H2S and NH3, producing a pure marketable NH3 product is relatively difficult compared with bulk separation of NH3 containing minor H2S. WorleyParsons’ Rameshni Ammonia Conversion (RACTM) process, for which a patent is pending, substoichiometrically combusts a high-NH3 H2S-contaminated stream in the RGG. (Figure 14) Typically, the NH3-gas heat release will exceed that required to reheat the Claus tail gas, thus necessitating a waste heat boiler prior to the TGU reactor. A supplemental natural gas fire ensures process stability in the event of NH3-gas curtailment. Sub-stoichiometric combustion of the NH3-gas generates supplemental H2 for the hydrogenation reactor and minimizes NOx. Most of any NOx that is made is reduced in the reactor. Minor unconverted NH3 is automatically recycled to the sour water stripper via the Contact Condenser blowdown. Table 2 defines the nominal feed bases for two hypothetical cases, where Case 1 involves a pure NH3 stream, and Case 2 a high-NH3 low-H2S stream. Table 2 compares the nominal impact on key parameters of routing those NH3 streams to the TGU (Cases 1b and 2b) as opposed to the SRU reaction furnace (Case 1a and 2a). - 25 - Figure 14 – WorleyParsons Ammonia Destruction in TGU (RAC TM) - 26 - Table 2 – WorleyParsons RACTM Hypothetical Feed Streams Fresh Feed Gas, Mol % Component Case 1 Acid Gas Case 2 NH3 Gas Acid Gas H2S 80 80 CO2 16 16 NH3 Gas 5 96 NH3 H2O Total 65 4 4 4 30 100 100 100 100 95 5 100 Fresh feed, LTPD S 29 NH3 / total fresh feed, mol % 28 Table 3 – WorleyParsons RACTM Impact on Key Parameters Comparison Case 1 NH3 Gas Route Key Parameter Case 2 NH3 Gas Route Case 1A SRU Case 1B TGU ∆ % Case 2A SRU Case 2B TGU ∆ % Claus tail gas, MSCFH 689 364 -47 760 346 -54 Claus recovery, % 92.7 96.5 92.3 96.5 RGG fuel, MMBTU/hr 10.4 0.5 -95 11.4 0.5 -96 TGU amine AG, MSCFH 17.5 10.1 -42 18.1 15.3 -15 BSR Selectox Selectox catalyst is a proprietary catalyst patented by WorleyParsons for low-temperature H2S-oxidation and Claus-reaction catalyst development by the Ralph M. Parsons Company and Unocal. Reduced tail gas from the BSR Contact Condenser is steam-reheated to about 400°F (~ 200°C) and combined with a stoichiometric quantity of air in the reactor to produce elemental sulphur, which is subsequently condensed. (Figure 15) Overall recoveries of 98.5-99.5% are achievable. The reactor inlet is limited to 5 %-vol H2S, above which recycle dilution (or inter-bed heat removal) is necessary to limit the exothermic. - 27 - SRU TAIL GAS RECYCLE WATER NATURAL GAS COMBUSTION AIR CONTACT CONDENSER RGG SOUR WATER BLOWDOWN HYDROGENATION REACTOR DESUPERHEATER STEAM REHEATER REDUCED TAIL GAS 10% NaOH AIR SELECTOX REACTOR LP STEAM SULFUR CONDENSER TAIL GAS TO INCINERATOR SULFUR Figure 15 – WorleyParsons BSR Selectox - 28 - WorleyParsons Current Case Histories The following are the case histories of the different projects have been recently designed by WorleyParsons. Project Case 1 WorleyParsons designed a new tail gas unit for a US refinery to meet the emission requirements. The following were the key elements of the project. f The existing sulphur plant did not have adequate pressure to handle the tail gas pressure f Total H2S of less than 100 ppm f COS, CS2 hydrolysis f SO2 concentration at reactor outlet f Hydraulic and unit capacity WorleyParsons evaluated this project and the final design was based according to the following criteria. f Reducing gas generator (RGG) was selected to achieve high temperature in the hydrogenation reactor for COS and CS2 hydrolysis without changing any catalyst in the existing SRU. f Flexsorb solvent was selected because it requires less circulation rate compare to the other tail gas amine solvent Therefore, the capital cost reduced. f A booster blower is provided to boost the pressure in the tail gas unit downstream of the quench section. The booster blower has dual function where it will be used as a start up blower to eliminate large volume of H2S to the flare and recycle back to the unit and the booster blower will boost the pressure in the unit. f The final design is according to the Figure 12 that is provided in this paper. Project Case 2 WorleyParsons has designed two new tail gas units one for a US refinery and one for a Canadian refinery with the following configuration. f The existing sulphur plant did not have adequate pressure to handle the tail gas pressure f Total H2S of less than 100 ppm f COS, CS2 hydrolysis - 29 - f Hydraulic and unit capacity WorleyParsons evaluated this project and the final design was based according to the following criteria. f Reducing gas generator (RGG) was selected to achieve high temperature in the hydrogenation reactor for COS and CS2 hydrolysis without changing any catalyst in the existing SRU. f MDEA solvent was selected simply they do not need to deal with two different solvent for the amine and tail gas unit and there was no cost saving to use other solvent. f A booster blower is provided to boost the pressure in the tail gas unit downstream of the quench section. The booster blower has dual function where it will be used as a start up blower to eliminate large volume of H2S to the flare and recycle back to the unit and the booster blower will boost the pressure in the unit. f The final design is according to the Figure 2 that is provided in this paper. Project Case 3 WorleyParsons has designed a new sulphur recovery and BSR/MDEA tail gas unit for a refinery in South America with the following configuration. f Total H2S of less than 100 ppm f COS, CS2 hydrolysis f Hydraulic and unit capacity WorleyParsons evaluated this project and the final design was based according to the following criteria. f Low temperature catalyst is selected in the tail gas unit and the first reactor bed in the Claus unit will contain some Ti catalyst f MDEA solvent was selected simply they do not need to deal with two different solvent for the amine and tail gas unit and there was no cost saving to use other solvent. f A n start up blower is provide only for start up purposes and will not be used at normal operation except where is the very low turn down and may be used to boost the pressure. f The final design is according to the Figure 6 that is provided in this paper. - 30 - References 1. Ammonia Destruction in a Claus Tail Gas Treating Unit, by M. Rameshni, presented at British Sulphur Conference, Canada, 2007 2. Operating experience of a 2-reactor Claus plant for up to 99.85% sulphur recovery, by J. Kunkel, P.M. Heisel, LINDE AG, Ulf Nilsson, Peter Eriksson, NYNÄS AB - 31 -