1298 IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, VOL. 11, NO. 6, DECEMBER 2015 Adaptive Roles of Islanded Microgrid Components for Voltage and Frequency Transient Responses Enhancement Hebatallah M. Ibrahim, Mohamed Shawky El Moursi, Senior Member, IEEE, and Po-Hsu Huang, Student Member, IEEE Abstract—This paper introduces a novel framework of coordinated voltage and frequency control strategy for islanded microgrid (MG) operation. The proposed control schemes rely on local measurements as communication-free control approach. Therefore, the distributed controllers of the MG components have been deployed based on their slow, medium, and fast dynamic responses to maintain the voltage and frequency in adherence to IEEE Standards 1547 and 929. The various voltage and frequency control responses associated with reactive power management scheme are efficiently utilized based on well-defined states of operation and transient management scheme. In each state, the roles of each device for voltage and frequency regulations are defined with its regulation capability, and response time based on its local measurements. Consequently, the fast reactive power compensation and rapid frequency regulation are ensured based on the inverterbased devices at challenging operating conditions. As a result, the proposed control strategy improves the voltage and frequency regulation, transient response, and MG stability. A comprehensive simulation study has verified the superior performance of the communication-free approach during steady state and in response to severe disturbances. Index Terms—Communication-free coordinated voltage and frequency control, dynamic reactive power reserve, islanded microgrid (MG), MG stability, transient response. I. I NTRODUCTION T HE CONCEPT of microgrid (MG) in which renewable energy resources (RESs), diesel generator (DZ), and energy storage systems (ESSs) can be conjugated and integrated to the grid has been growing in importance to cope with the increasing environmental and resources is problems [1]. Extensive studies have been done on MGs to ensure their stability and reliability in supplying electrical power with a Manuscript received December 24, 2014; revised May 12, 2015 and June 29, 2015; accepted September 06, 2015. Date of publication September 16, 2015; date of current version December 02, 2015. Paper no. TII-14-1423. H. M. Ibrahim is with the Department of Electrical Engineering and Computer Science, Masdar Institute of Science and Technology, Abu Dhabi, United Arab Emirates. M. S. El Moursi is with the Department of Electrical Engineering and Computer Science, Masdar Institute of Science and Technology, Abu Dhabi, United Arab Emirates. He is currently on leave from the Faculty of Engineering, Department of Electrical Power Engineering, Mansoura University, Mansoura, 35516, Egypt (e-mail: melmoursi@masdar. ac.ae). P.-H. Huang is with the Department of Electrical Engineering and Computer Science, Massachusetts Institute of Technology, Cambridge, MA 02139 USA. Color versions of one or more of the figures in this paper are available online at http://ieeexplore.ieee.org. Digital Object Identifier 10.1109/TII.2015.2479580 large amount of intermittent renewable energy resources. To allow integrating more distributed generation (DG)-based RESs to MGs, some measures should be taken into consideration according to the IEEE Standards 1547 and 929 [2], [3] to ensure the reliability and stability of the grid-tied MG operations. However, these voltage and frequency standards will be very conservative to the islanded MG. Thus, it requires a well-defined control structure and actions to manage the MG dynamics and transient operation. Therefore, two control levels must be implemented to ensure the stability of the MG islanded and grid-tied modes of operation which are primary control (local control) and secondary control (centralized control) [1]. Primary control is mainly devoted to maintain the local variables on site such as voltage and frequency within the standard limits involving control loops for current injections and droop control [1], [4]–[6]. As for the secondary control level, it is dedicated for controlling the system voltage profile and frequency to maintain the MG parameters within the permissible operational limits. Hence, the secondary level mainly depends on the communication between the generation units to achieve the proper coordination in regulating the active and reactive power flow. Many studies have been carried out using different communication techniques to enhance the reliability of the system performance [7]–[17]. A simple coordinated control scheme was proposed in [7] to maintain a constant output power from a hybrid MG consisting of multiple photovoltaic photo voltaic (PV) arrays integrated with a DZ. However, it required a high-speed communication network with the addition of measurement units, data unit, and a battery system to each of the PV systems, adding up the total system cost. The studies carried out in [8] and [9] proposed a high-speed communication interface to coordinate between the DERs operation in order to sustain the power system stability. The voltage problems in the distribution network with penetration of DGs and MGs have been tackled in the literature by means of coordinating voltage control [18]–[21]. The coordinated voltage controllers are structured in different combination of voltage control devices such as static synchronous compensator (STATCOM) with capacitor (CAP) banks, on-load tap changer (OLTC) with static var compensator (SVC) for the aim of enhancing the voltage regulation [19]–[21]. However, these coordinated controllers did not consider the proper utilization of response time and maximizing the fast dynamic reactive power reserve to react during severe system disturbances. In [22]–[24], 1551-3203 © 2015 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission. See http://www.ieee.org/publications_standards/publications/rights/index.html for more information. Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. IBRAHIM et al.: ADAPTIVE ROLES OF ISLANDED MG COMPONENTS the DGs have been utilized with their ancillary service of voltage controllers to regulate the voltage profile within acceptable operating criteria. Therefore, the coordination between the DGs and OLTC is proposed with managing the active and reactive power generation from DGs to achieve an effective voltage regulation. This coordinated voltage control has inquired high bandwidth communication infrastructure resulted in increasing the system complexity [25]–[27]. In [28], a new method was proposed to minimize the requirement of communication infrastructure by employing the state estimator. The coordinated voltage control based on multiagent system has been deployed among the OLTC, CAP banks, and DGs. The OLTC was controlled based on a line drop compensation scheme so that few RTUs were installed at selected buses, mainly for the DGs and CAP banks; also, the voltage profile along the feeder was estimated. The measured and estimated voltages at all buses have been processed to identify the pilot bus to control the OLTC. Consequently, the generation status of the DGs has been accounted in controlling the OLTC to avoid the violation of operating voltage criteria along the feeder. Also, the coordinated voltage controller in the distribution network with the penetration of DGs and MG was considered as an important optimization problem formulation. In this context, several optimization techniques with different objective functions such as minimizing the voltage deviation, system losses, and reducing the tap movements and switching CAP banks have been deployed [29]–[41]. The voltage control for the islanded MG becomes a challenge due to the low X/R ratio so that the intermittency of renewable-based DGs will significantly impact the voltage profile. Therefore, a robust voltage controller should be developed to ensure higher system stability by maximizing the fast dynamic reactive power reserve. Hence, the coordinated voltage controller is required to manage the reactive power at each component of the MG to react effectively during the system disturbances. Such controller has been developed in the literature based on centralized concept with a very complex communication infrastructure resulting in increasing the cost and complexity of the MG. A coordinated voltage control based on meta-heuristic approach was proposed in [10]. Evolutionary particle swarm optimization (EPSO) algorithm was used to mitigate between voltage/VAR controls issues at medium voltage (MV) levels. The proposed algorithm was based on artificial neural network (ANN) as a secondary level to reduce the computational time. However, a communication infrastructure and the proper training of ANN are required to achieve optimal coordination. A control scheme for the state-of-charge (SOC) of an ESS has been proposed in [12] to switch from fixed power control to voltage/frequency control when the MG mode of operation changes from grid-tied mode to islanded mode. The concept was based on exchange of information between the DG units and ESS connected to the MG. In [13], a new model predictive control algorithm was employed to tackle the steadystate and transient control problems of a hybrid MG. Thus, an energy management system (EMS) was needed to coordinate between the parallel operations of different DG units, whereas the important parameters were sent to a centralized server for processing. All these studies required high bandwidth communication system as its secondary level. Despite the fact 1299 that using a communication level is important in enhancing the system performance, any malfunction in this level will lead to the entire system failure. Therefore, researchers started working on control techniques employing no communication link. Load sharing has been proposed in [14] to maintain the stability of MG without communication link. However, it did not achieve the proper system coordination and regulation in response to severe system disturbances. A study carried out in [15] proposed installing ESS in each DG to mitigate the load and generation changes and such a configuration was found to be very costly. In [16], one ESS has been integrated to the MG enhancing frequency stability. However, this method needed communication. A study carried out in [17] proposed a power-sharing technique to be employed for voltage source converter (VSC)-based MGs. This technique ensured the active power stability (frequency stability) without communication link. However, it has not covered the voltage stability and reactive power management. This paper introduces a communication-free coordinated voltage and frequency technique to enhance the dynamic and transient performance in response to severe system disturbances. The MG employed in this study integrates a doubly fed induction generator-based wind turbine (DFIG-WT), a PV power plant, a battery energy storage system (BESS), a CAP bank, and a DZ. The distributed controllers of the MG components have been utilized based on their slow, medium, and fast dynamic responses to maintain the voltage and frequency in adherence to IEEE Standards 1547 and 929 as conservative operation limit for islanded MG. The adaptive roles of each device for voltage and frequency regulations are deployed based on its regulation capability and response time in steadystate, dynamic, and transient conditions. The active and reactive power management schemes are tested in all states of operation in the view of achieving fast voltage and frequency regulations, maximizing the fast dynamic reactive power reserve and enhancing the system stability. Consequently, the performance is evaluated with considering conservative operational voltage and frequency constraints to demonstrate the superior performance of the communication-free control strategy for islanded MG. This paper is organized as follows. Section II provides the configuration of the MG under study. Section III explains the droop scheme applied to the MG components. In Section IV, the proposed framework control strategy is demonstrated. Finally, Section V provides the simulation results based on PSCAD/EMTDC, verifying the performance of the proposed control strategy. II. I SLANDED MG S YSTEM D ESCRIPTION The MG under study consists of DFIG-WT, PV, BESS, CAP bank, DZ generator, an induction motor, and several fixed loads that used to test the over frequency (OF), under frequency (UF), over voltage (OV), and under voltage (UV) states of operation. The parameters of the MG components and controllers are given in the Appendix as shown in Tables I–IV. The PV and BESS are connected through dc–ac inverters, three-phase step-up transformers and cables to the 11-kV bus as shown in Fig. 1. Each of DFIG-WT, DZ generator, and induction motor Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. 1300 IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, VOL. 11, NO. 6, DECEMBER 2015 Fig. 1. Configuration of the MG under study. Fig. 2. Nine states of operation for the MG. is connected to the 11-kV bus through a three-phase step-up transformer and cables as illustrated. A three-phase step-down transformer 132 kV/11 kV is used in the connection between the utility grid and MG with islanding capability using the main circuit breaker (CB1). The cases presented in this paper are carried out based on an islanded MG so that CB1 will be opened. The performance of MG will be tested during islanded mode in response to UF, OF, UV–UF, UV–OF, OV–UF, and OV–OF with and without employing the proposed control strategy as defined in Fig. 2. III. D ROOP -BASED VOLTAGE AND F REQUENCY C ONTROLLERS MGs require different operation and control methods than strong utility grids. Voltage and frequency control are important for ensuring the stability especially for the islanded MGs with employing effective droop controllers [44]–[45]. Therefore, a proper coordinated control scheme between the DG units integrated in the MG is needed. Decentralized droop controllers are developed for proper coordination between the RES-based generation units, BESS, and DZ generator; the controllers’ setpoints are chosen depending on the local measurements of the voltage and frequency during both steady-state and dynamic Fig. 3. QV droop controllers. (a) For synchronous-based machines. (b) For inverter-based devices (DFIG-WT, PV, and BESS). conditions. The proposed control scheme consists of droop controllers whose parameters are selected according to the reactive and active power supply capability by the DG units. This method coordinates the active and reactive power flow in the MG for enhancing the voltage and frequency profiles at point of common coupling (PCC). Two droop control strategies have been developed in this paper for voltage and frequency regulations. Starting with the voltage droop, for reactive power in an MG, the following requirements should be satisfied, maintaining the bus voltage within the specified limits and avoiding the reactive power circulation among the sources. To satisfy these requirements, a self-adjusting control scheme for proper reactive power coordination between the DG units integrated to this MG is required. Consequently, the controllers have been implemented in the PV, DFIG-WT, DZ generator, and BESS based on voltage droop control to accurately share the reactive power needs. As can be seen from Fig. 3(a), the voltage droop scheme has been implemented for the inverter-based devices to inject the reactive power when the voltage at the PCC falls below 1 p.u. or to absorb the reactive power once the voltage increases over 1 p.u. As for the synchronous-based machines like the DZ Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. IBRAHIM et al.: ADAPTIVE ROLES OF ISLANDED MG COMPONENTS Fig. 4. Pf droop control. (a) For BESS. (b) For PV. (c) For DZ generator. generator, the voltage droop control scheme was considered to avoid overexcitation as shown in Fig. 3(b). The frequency droop scheme was implemented in this paper for proper active power coordination between the DG units integrated to the MG. Thus, the droop control has been modified for the BESS to accurately share the active power demand from the loads. As can be seen from Fig. 4(a), for the BESS the droop control is designed to regulate the frequency within a range of 1.008–0.99 p.u. Nonetheless, for the PV system the power curtailment loop starts curtailing the active power when the frequency reaches above 1.002–1.008 p.u., where at 1.008 p.u., the PV power is completely inhibited as shown in Fig. 4(b). The frequency droop control is also implemented with the DZ generator for appropriate active power sharing between the DG units in the MG as shown in Fig. 4(c). Hence, the DZ generator operates at rated capacity when the frequency is 0.99 p.u. and decreases till it reaches 30% of its full capacity at 1.002 p.u. The simulation studies will verify the performance of the proposed method in maintaining the voltage and frequency profiles within the standard limits under the aforementioned nine states of operation. The thresholds and limits of the reactive current support from the invert-based DGs have been identified to achieve the desired voltage and frequency regulation according to the IEEE Standards 1547 and 929. The proposed CVC relies on the adjustment of the reactive power/current support from the inverter-based DGs during steady state with minimum loading to react with full reactive power/current capacity during severe system disturbances. Therefore, a hard limit of 40% has been imposed on the reactive current support from the PV, DFIG-WT, and BESS to force the CAP banks (slow response device) to take more steps and provide sufficient reactive power compensation during normal operation. Thus, the thresholds of the hard limits have been determined with considering the following aspects. 1) The load flow analysis of the MG is conducted at peak load with the presence of CAP banks, BESS, PV, DFIGWT, and DZ and the voltage profile at the PCC is evaluated. 2) The power factor of the inverter-based DGs is adjusted to ±0.95 (maximum) and the mechanically switching CAP banks in association with the DZ are used to regulate the voltage at PCC within the operating voltage criteria (0.9–1.1 p.u.). The % of the hard limits of the reactive power/current compensation at the inverter-based DGs is gradually increased until the voltage is regulated to the permissible operating range. 1301 3) The previous two steps should be carried out with considering the worst/challenging operating conditions as follows. a) The inverter-based DGs are generating the full active power that allows limited reactive power compensation with the defined pf range ±0.95. b) The MG is operated at minimum SCR and X/R. 4) The hard limits are not applied in the inverter-based DGs for the inductive mode of operation to allow maximizing the fast dynamic reactive power reserve to react during system disturbances. In this context, the power flow analysis is carried out again at minimum loading condition of the MG with freezing the CAP banks regulation in case of overvoltage. Hence, the inverter-based DGs operate in inductive mode of operation to regulate the voltage within the operating voltage range resulting in maximizing the fast dynamic reactive power reserve. 5) Finally, the percentage of reactive power/current compensation during steady-state operation is adjusted. 6) Also, the upper and lower thresholds of the frequency controllers were chosen to maintain the islanded MG frequency in steady-state, dynamic, and transient operations within the range defined in the IEEE Standards 1547 and 929. Therefore, the proposed control strategy is developed to achieve fast frequency regulation by relying on the BESS and PV during dynamic operating conditions and DZ generator at steady-state condition. 7) Under steady-state operating conditions, the SOC of the BESS is set to be between 40% and 80% to ensure the maximum efficiency throughout the battery lifetime. 8) When the MG experiences OF, the SOC upper limit is released to 90% to allow the BESS to further charge until the frequency profile is regulated, DZ generator reduces its operation to 30% (minimum allowed loading condition) and the PV starts curtailing active power until the frequency profile is regulated. 9) During UF operating conditions, the SOC lower limit is released to further supply the MG with active power and the DZ generator operates at its rated capacity. IV. F RAMEWORK FOR C OORDINATED VOLTAGE AND F REQUENCY C ONTROL S TRATEGY (CVC AND CFC) A coordinated voltage and frequency control scheme is applied to this MG to regulate the voltage and frequency without any means of communication links between MG components shown in Fig. 1. The system is designed to provide slow and medium speed response, using low-pass filters (LPFs), for the CAP banks and DZ generator, respectively, and fast response for inverter-based DG units. Therefore, it achieves different regulation bandwidths dedicated by the decentralized voltage controllers and reactive power management scheme according to the adaptive reactive current limits in steady-state and transient operations. The four main states and the actions taken by each DG unit under the proposed control scheme are shown in Fig. 5. The state detector is used to identify which state the MG is experiencing based on the local measurements at each device. If the MG is under steady-state conditions, the Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. 1302 IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, VOL. 11, NO. 6, DECEMBER 2015 addition to this is the assistance from the PV system that starts curtailing power to maintain the frequency profile within the permissible limits. The combined states of operation such as UV-UF, UV-OF, OV-UF, and OV-OF will consider the defined rules from individual states. As per the flowchart shown in Fig. 6, the control scheme imposed on each of the devices integrated in the MG is explained as follows. A. BESS Model Fig. 5. State detector flowchart. PV, DFIG-WT, and BESS are limited to inject maximum of 40% reactive current of their available reactive current. During steady-state and OV conditions, the maximum reactive current allowed to be absorbed by the inverter-based devices is released to 100% for inductive mode of operation to maximize the dynamic reactive power reserve of the MG as shown in Fig. 5. In addition to that, the SOC of the battery is limited between 40% and 80% to ensure proper efficiency throughout the battery lifetime. Under dynamic-state conditions, a control scheme is approached to maintain the voltage and frequency of the MG within the allowed limits approved by IEEE 1547 Standard. Thus, the actions taken for the defined states of operation are described as follows. 1) Under the UV state, the PV, DFIG-WT, and BESS are allowed to inject up to 100% reactive current as shown in the flowchart in Fig. 6 to enhance the transient response and voltage profile. Meanwhile, the DZ generator supports by increasing its excitation operation and the CAP bank increases the number of steps to support the reactive power deficiency. 2) When the UF state is detected, the BESS and DG act to maintain the frequency within the allowed standard limits. The DZ generator operates at its rated capacity and the BESS releases the lower limit of the SOC to 20% instead of 40% to compensate the active power shortage. 3) In addition, when OV state is triggered, the CAP bank will freeze the number of the steps to maximize the fast dynamic reactive power reserve and the DZ generator excitation operation is then reduced and the inverterbased RESs may operate in inductive mode of operation and absorb the reactive power. 4) Finally, when the OF state is detected, the BESS will increase the SOC upper limit to 95% so as to buffer more active power, so that the OF situation can be mitigated. In The BESS model is designed according to Li-ion battery parameters. The model was integrated with a dc-link capacitor, a three-phase inverter, an ac filter, and a step-up transformer. The BESS model of 1.5 MWh consisting of 147 batteries in series and 3780 in parallel is developed in PSCAD/EMTDC, shown in Fig. 1. To achieve separate active and reactive power control, a decoupled current control is implemented for the inverters. Fig. 7(a) shows the decoupled current control implemented for the inverter-based BESS model and the Fig. 7(b) for the inverter-based PV. The direct axis (d) is used to represent the active power component and the quadrature axis (q) is used to represent the reactive power component. Fig. 7(a) and (b) is provided to understand how the proposed scheme is applied to the controllers under study; it can be observed from Fig. 7(a) and (b) that the voltage measured (Vm ) at the low-voltage side of the transformers is compared to the reference voltage (Vref ) value which is 1 p.u. and the error is processed by the PI controller to determine the current value to be injected to or received from the MG. A current limiter is employed for a proper active and reactive power sharing between the DG units under steady-state and dynamic conditions. Focus on Fig. 7(a) to explain how the BESS control model works; if the voltage at the PCC is less than 0.9 p.u., then BESS reactive current component will be released to 100%. If not, then the BESS reactive current component (Iq ) will be limited to 40%. Nonetheless, the frequency at the PCC is measured; if the frequency was measured to be greater than 1.008 p.u., the BESS SOC limit will be released to 95%. If the frequency was measured to be lower than 0.95 p.u., the BESS SOC lower limit will be released to 20%. The BESS frequency control droop strategy is designed to regulate the frequency within 1.008 and 0.99 p.u. The voltage droop scheme implemented for BESS is to regulate injecting the MG with reactive current as the voltage at the PCC falls below 1 p.u. and receiving the reactive current as the voltage increases over 1 p.u. B. PV System The model used in this study integrates PV system of 8 series and 20 parallel modules, a dc-link capacitor, a dc–dc boost converter, a three-phase inverter, an ac filter, and a step-up transformer. The PV system’s reactive power loop reacts to maintain the voltage within the allowed limits specified by the control strategy, similar to the BESS shown in Fig. 7(b). The control of the PV inverter is based on decoupled current control loops to achieve active and reactive power control through dq currents separately as described in [41]–[43]. The developed model is Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. IBRAHIM et al.: ADAPTIVE ROLES OF ISLANDED MG COMPONENTS 1303 Fig. 6. Flowchart for a framework control strategy for coordinated voltage and frequency controllers of DG units and BESS. aggregated and scaled up to the desired capacity as shown in Fig. 1. If the OV condition is triggered, the PV reactive current component limit to be absorbed (inductive mode) has a fixed limit of 100% to maximize the dynamic reactive power reserve at steady-state and OV conditions. Regarding Fig. 7(b), if the frequency crosses 1.002 p.u., the PV power will be curtailed to support in regulating the frequency profile. Frequency droop control has been implemented in the PV model to curtail the active power as the frequency increases from 1.002 to 1.008 p.u., where at 1.002 p.u. and below, the PV injects active power at its rated capacity and at 1.008 p.u., the PV power is completely curtailed as can be seen from Fig. 7(b). Finally, a supplementary power curtailment loop is employed in the PV controller to allow the curtailing capability of the PV power when the OF state is triggered. Also, the PV reacts to maintain the voltage within the allowed limits. If OV condition is triggered, the PV reactive current component limit to be received has a constant limit of 100% to maximize the reactive power reserve at steady-state condition as well as OV condition. If UV condition is triggered, the PV reactive current component to be injected to the MG is released to 100%. C. DFIG-WT Model The wind turbine generator (WTG) used in this study is DFIG-WT rated at 0.9 MVA. The WTG model employs a wound rotor induction generator and a back-to-back converter based on decoupled current control. The converters are rated at 30% of the WTG-rated capacity and modeled as controlled voltage sources [46]. The rotor-side converter (RSC) is dedicated to control the generator electromagnetic torque so as to adjust the speed of the generator to reach the maximum power point; the rotor-side converter is also used to regulate the voltage [47], [48]. The model is set to maintain the voltage within the standard limits as PV and BESS. The grid-side converter is connected to the dc-link and dedicated to regulate the active power flow to maintain the dc-link voltage constant. Nonetheless, the grid-side converter (GSC) plays a role in exchanging reactive power with the grid. The reactive current references of the RSC and GSC are restricted with the limits based on the defined operation shown in Fig. 6. D. DZ Generator and CAP Bank Models The DZ generator model is rated at 1 MVA with implicit transformer and the CAP bank of 20 steps is rated at 1.2 MVAR; both models are equipped with the LPF to delay the voltage signal reaching the CAP bank and DZ generator to utilize the DG units connected to the MG according to transient and steady-states analysis. The DZ generator and CAP bank are controlled in a way to achieve the fast response from the inverter-based DGs. Thereafter, inverter-based DG is unloaded due to the delayed regulation actions from DZ generator and CAP banks that have been achieved by deploying the LPFs. Also, if the OV condition is triggered, the DZ generator reduces its excitation operation and the CAP bank freezes the capacitor steps to maximize the fast reactive power reserve. However, if the UV condition was triggered, the DZ generator increases its excitation and the CAP bank increases its steps based on the local voltage control. For the frequency regulation, under UF cases, the DZ generator operates at its rated power to supply the MG with active power, if the OF condition is triggered, instead the DZ generator reduces its active power up to the minimum loading condition of 30% of its rated capacity. V. E VALUATION OF THE P ROPOSED C ONTROL S TRATEGY This chapter investigates four case studies to test the MG performance under dynamic and transient states. First, two case studies are presented to verify the actions taken by the BESS and PV models in response to OF and UF operating conditions. Second, a case study will be carried out combining two Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. 1304 IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, VOL. 11, NO. 6, DECEMBER 2015 Fig. 8. Frequency profile at the PCC in p.u. Fig. 9. BESS SOC in (%). in Section IV and on an MG only employing control loops for current injection and droop control (scenario two). A. MG Performance Under OF Operating Condition The OF case is first simulated by disconnecting a load rated at 0.3 MW at 400 s. As can be seen from Fig. 8, the frequency in scenario 2 reaches up to 1.108 p.u. and violates the IEEE 1547 Standard by having the frequency above 1.008 p.u. for more than 0.16 s. However, the frequency response for scenario 1 fulfills the standard without exceeding 1.008 p.u. The OF condition is triggered when the SOC reaches 80% to test the proposed CFC that reacts due to the OF. Fig. 9 shows how the SOC value went slightly above 80% caused by a slew rate block for the d-current component to gradually reach zero to avoid any sudden spikes in the frequency by a sudden change in the value of the current charging the BESS. After the OF condition has been triggered, the SOC for scenario 2 already reached its upper limit preventing the BESS from charging anymore. However, for scenario 2, the SOC upper limit was released to 95% allowing the BESS to charge until the operating conditions are restored to normal. As the load demand on the MG remains lower than the generation capacity till the end of the simulation, the frequency fails to be maintained at 1 p.u. for scenario 2. However, for scenario 1, the BESS will keep on charging as shown in Fig. 9 until the load demand and generation capacity are balanced. B. MG Performance Under UF Operating Condition Fig. 7. Inverter controllers for BESS and PV power system. (a) BESS inverter controller incorporating the droop controller. (b) PV inverter control incorporating the droop and power curtailment controller at OF operation. of the four operating conditions mentioned earlier as UF–UV, OF–OV, OF–UV, and UF–OV. Finally, the MG performance will be tested under transient condition of a three-phase-toground fault, which is applied at PCC and lasts for 140 ms. Each of the case studies is carried out on an MG employing the proposed CVC and CFC control scheme (scenario one) introduced To test the system performance under UF condition, a load of 0.105 MW is suddenly connected to the MG at 400 s in a different simulation case. It can be observed that the frequency profile for scenario 1 is significantly enhanced than the frequency profile for scenario 2, as shown in Fig. 10. When the UF operating condition was detected, the frequency for scenario 1 dropped to 0.96 p.u. not violating the IEEE 1547 Standard (for power system greater than 30 kW). However, the frequency profile for scenario 2 dropped below 0.95 p.u. for 2.5 s, violating the IEEE 1547 Standard as the system failed to regulate the frequency back above 0.95 p.u. for more than 0.16 s. Since the proposed Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. IBRAHIM et al.: ADAPTIVE ROLES OF ISLANDED MG COMPONENTS 1305 Fig. 10. Frequency profile at the PCC (FPCC ) in p.u. Fig. 11. BESS SOC in (%). Fig. 12. Frequency profile of the MG in p.u. control strategy allows the SOC lower limit to be released from 40% to 20%, the BESS is allowed to discharge further if the system generation capacity could not meet the load demand. It can be observed from Fig. 11 that the battery cells in both cases are set to reach the minimum SOC limit before the UF operating condition is triggered at 400 s. The SOC limit shown in Fig. 11 goes slightly below 0.4 for both scenarios before triggering the UF condition due to the slew rate block employed with the real current component to avoid sudden change in the current injected to the MG causing fluctuations in the frequency profile. After triggering the UF operating condition, it can be observed from Fig. 11 that the SOC minimum limit has been released for scenario 1 to allow the battery to further discharge, whereas for scenario 2, the SOC remained the same so that the BESS does not participate into the frequency regulation. C. MG Performance Under UF–UV, OF–OV, OF–UV, and UF–OV Operating Conditions Fig. 13. Voltage profile at the PCC (VPCC ) in p.u. In this session, the case study carries out the combined states of operation to further verify the robustness of the proposed control strategy under dynamic operation. First, the case is simulated without load changing between 0 and 400 s. Thus, it ensures time for the CAP bank to reach the steady state before testing individual operating conditions. Also, a base load of 1.8 MW and 0.15 MVAR is connected over the period of the simulation. At 400 s, load 1 (0.6 MW) and load 2 (0.6 MVAR) are suddenly connected to the MG to stimulate UF–UV operating conditions. At 700 s, load 1, load 2, and load 4 (0.3 MVAR) are suddenly disconnected from the MG for testing the OF–OV operating condition. Later on, at 900 s, load 3 (0.3 MW) disconnects from the MG and load 5 (0.3 MVAR) engages. This aims to drive the system into the OF–UV operating conditions. Finally, load 3 connects and load 5 disconnects again causing UF–OV operating conditions at 1200 s. Fig. 12 shows the frequency profile for the reported four cases. To highlight the change of the operation conditions, a color code is provided with the results to distinguish between the states. The UF–UV case is stimulated at 400 s; it can be observed from Fig. 12 that the frequency profile does not violate the standard limit for both scenarios 1 and 2. At 700 s, the OF–OV case is initiated; the frequency profile for scenario 2 crossed the limit (1.008 p.u.) for 1.3 s (> 0.16 s), thus violating the IEEE 1547 Standard. For scenario 1, the frequency profile was successfully maintained below 1.008 p.u., thus not violating the IEEE standards. In addition, during the OF-UV condition triggered at 900 s, the system frequency profile for scenario 1 was enhanced compared to the frequency profile for scenario 2. It can be observed from Fig. 12 that the frequency profile for scenario 2 crossed 1.008 p.u. for 0.7 s (> 0.16 s) violating the IEEE 1547 Standard. However, the frequency profile for scenario 1 did not violate the 1.008-p.u. limit. For the last case based on the UF– OV operating conditions at 1200 s, the frequency profile was maintained within the limit for both scenarios. All in all, the system performance without the proposed scheme may violate the standard, while the CVC and CFC control method ensures satisfactory performance against load disturbances. Fig. 13 illustrates the voltage profile at the PCC (VPCC) under the four examined cases. At 400 s where the UF–UV case is stimulated, the VPCC profile for scenario 1 and 2 dropped below 0.9 p.u. for 0.0185 s (< 0.16 s). Thus, neither of the scenarios violated the voltage lower limit specified by the IEEE Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. 1306 IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, VOL. 11, NO. 6, DECEMBER 2015 Fig. 14. CAP bank steps each rated at 0.1 MVAR. Fig. 15. Active power (P ) flow in the MG (MW). 1547 Standard which is 0.88 p.u. nor the voltage limit specified by the protection settings for WTG 0.9 p.u. At 700 s, the OF–OV case is activated causing the VPCC profile for both scenarios to rise over 1.1 p.u. for less than 0.16 s, which is allowed by the IEEE 1547 Standard. At 900 s, the OF-UV case was triggered causing the VPCC profile for both scenarios to drop within the allowed limits, thus neither violating the IEEE 1547 Standard nor the protection settings. The last case is triggered at 1200 which is UF–OV, causing the VPCC profile for scenario 1 to cross the 1.1-p.u. limit for 0.019 s (< 0.16 s), where the VPCC profile for scenario 2 did not cross the upper voltage level. This shows the robustness of the proposed control strategy in regulating the voltage profile while maximizing the reactive power reserve. The above observations can be further explained by referring to Fig. 14, where it can be seen that the CAP bank for scenario 1 took four more steps than for scenario 2 at the beginning and nine (equivalent to 0.9 MVAR) toward the end of the case study. Consequently, the proposed method maximizes the fast dynamic reactive power reserve by unloading the inverter-based RES devices. Thus, the VPCC profile remains slightly above 1 p.u. as can be seen in Fig. 13. Fig. 15 is provided to illustrate the active power flow in the MG and the interaction between the BESS, PV, wind turbine (WT), and DZ generator without communication infrastructure. At 400 s, when the UF–UV case was triggered, both scenarios reacted similarly as the frequency remained within the lower Fig. 16. BESS SOC in (%). limit specified by the control strategy (0.96 p.u.). The BESS injected active power (PBESS ) instantaneously as per the load demands, as shown in Fig. 15(a). As a result, the SOC profile decreased for both scenarios as shown from Fig. 16. The DZ generator took more time to react for both scenarios and increased PDZ injected to the MG due to the UF case triggered; as for the PPV, no change can be observed as the PV is already operating at its rated capacity and the WT did not take part in regulating the frequency profile as explained earlier as shown in Fig. 7. For the OF–OV case triggered at 700 s, the PBESS profile for scenario 1 decreased while remained positive. However, the PBESS of the second scenario dropped to slightly below zero since the BESS aims to mitigate the OF case triggered. The actions taken by the BESS for scenario 1 can be explained by observing the PPV profile when the frequency profile reached 1.008 p.u. The PPV curtailment was triggered instantaneously, as shown in the dashed box in Fig. 15(b), to mitigate the frequency profile successfully as shown previously in Fig. 12. The PBESS for scenario 1 provided active power to smoothen the quick action taken by the PV resulting in a smooth frequency profile as shown in Fig. 12. However, for the PV model under scenario 2, the PV curtailment was not triggered, so this resulted in charging the BESS from the MG; therefore, the PBESS for the BESS model for the second scenario dropped below zero. This can be further verified by observing SOC profile for both scenarios in Fig. 16, where the SOC profile for scenario 1 continued decreasing, thus injecting active power to the MG. On the other hand, the SOC profile under the second scenario increased, thus charging and absorbing active power from the MG. Consequently, this case showed the success of the proposed control scheme in providing virtual interaction between the PV and BESS without communication. The DZ generator took a slow action in comparison to PV and BESS in decreasing the active power (PDZ) injected to the MG for both scenarios as shown in Fig. 15(c). Moreover, at 900 s, the OFUV condition was triggered resulting in PV curtailment; the PV curtailment took place more severely in this case as the generation capacity exceeds the load demand significantly. Therefore, the BESS started charging, as shown in Figs. 15(a) and 16 to support the PV system in regulating the frequency profile back to 1 p.u. The DZ generator took a relatively slow action again by restoring the PV power so as to support in regulating the frequency profile. At 1200, the UF–OV operating condition was triggered; it can be seen from Figs. 15(a) and 16 that the BESS started discharging and injecting the MG with active power to mitigate Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. IBRAHIM et al.: ADAPTIVE ROLES OF ISLANDED MG COMPONENTS 1307 Fig. 19. Natural resources profiles. (a) Solar radiation. (b) Wind speed. Fig. 17. Reactive power (Q) flow in MG (MVAR) for the measured QBESS , QPV , QDZ , and QWT . Fig. 20. Voltage at the PCC (VPCC ). the proposed control strategy in maximizing the fast dynamic reactive power reserve. The differences are highlighted in the figure with notations ΔQs , ΔQ1 , ΔQ2 , ΔQ3 , and ΔQ4 (the subscript “s” refers to steady state). Fig. 18 has been provided to further verify the reactive power flow in the MG, by showing the relationship between the Q measurements shown in Fig. 17 and the measured q-current components shown in Fig. 18. D. Performance of the CVC and CFC with Considering the Variations in Solar Radiation and Wind Speed Fig. 18. Measured quadrature current component (Iq) of the inverter-based DGs in (kA): (a) IqBESS ; (b) IqPV ; (c) IqWTG (GSC) ; and (d) IqWT(RSC) . the drop in the frequency profile; meanwhile, the PV is operating at its rated capacity and the DZ generator took a slower action in comparison to the BESS to provide the MG with further PDZ. Finally, Fig. 17 shows the reactive power flow in the MG for both scenarios, indicating the superior performance of To test the reliability of the control strategy under generation changes, the variable solar radiation and wind speed profiles have been incorporated. Fig. 19(a) and (b) shows the variable solar radiation and wind speed profiles that have been used in this case study. The voltage and frequency profiles are shown in Figs. 20 and 21, respectively. It can be observed that the performance of the MG under the proposed control strategy is improved compared to the MG without employing the CVC and CFC. The frequency profile shown in Fig. 21 for the MG not employing the proposed control strategy violated the IEEE 1547 Standard for crossing the upper and lower frequency limits (1.008 and 0.95 p.u.) for more than 0.16 s. However, the frequency profile for the MG following the proposed control strategy did not violate the limits stated by the IEEE 1547 Standard and showed an improved performance. The voltage profile was also given to show how the proposed control scheme succeeded in maintaining a firm voltage profile. Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. 1308 IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, VOL. 11, NO. 6, DECEMBER 2015 Fig. 23. Frequency profile of the MG in p.u. Fig. 21. Frequency profile of the MG in p.u. Fig. 24. Voltage at the PCC (VPCC ) profile of the MG in p.u. Fig. 22. Voltage at the PCC (VPCC ) profile of the MG in p.u. VI. T RANSIENT P ERFORMANCE OF THE P ROPOSED C ONTROL S TRATEGY To verify the reliability and robustness of the proposed control strategy, the MG transient performance has been evaluated in response to islanding and reconnecting the MG, tripping of MG components, and three phase-to-ground faults. A. MG Performance While Islanding and Reconnecting to the Electric Grid To verify the reliability of the control strategy on regulating the voltage and frequency when islanding or reconnecting an MG, a case study has been carried out. The MG presented earlier is initially connected to the grid, then islanded at 50 s, and eventually reconnected at 100 s. Figs. 22 and 23 show the resulting voltage and frequency profiles. The voltage profile under the proposed control strategy shows an enhanced performance of the voltage profile compared to the scenario without employing the proposed control strategy, which is shown in the zoomed in figures shown in Fig. 22. Also, the frequency profile under the proposed control strategy shown in Fig. 23 indicates an enhanced performance over the MG without employing the proposed control strategy. B. Performance in Response to Tripping BESS The BESS plays an important role for regulating the frequency and voltage of the MG. Therefore, the performance of the proposed control strategy has been evaluated in response to sudden trip of the BESS and the capability of regulating the voltage and frequency within the acceptable range has been evaluated. Figs. 24 and 25 show the rapid regulation of the voltage and frequency while employing the proposed control strategy and great enhancement of the transient response for the MG frequency. This enhancement is accounted due to the activation of the PV curtailment that mitigates the excessive power generation, which is used to charge the BESS before tripping as shown in Fig. 26. The case without CVC and CFC shows frequency violation to the IEEE Standards 1547 and 929. Also, the CVC and CFC serve to maximize the fast dynamic reactive power reserve in the inverter-based devices by ΔQ1 and ΔQ3 Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. IBRAHIM et al.: ADAPTIVE ROLES OF ISLANDED MG COMPONENTS Fig. 25. Frequency profile of the MG in p.u. 1309 Fig. 28. Reactive power compensation from the CAP banks. Fig. 29. Voltage at the PCC (VPCC ) profile of the MG in p.u. Fig. 26. Active power (P ) flow in the MG (MW). Fig. 30. Frequency profile of the MG in p.u. C. Performance in Response to Tripping PV Fig. 27. Reactive power (P ) flow in the MG (MVAr). and to improve the voltage profile at PCC as shown in Figs. 27 and 24, respectively. Thus, the CAP bank provides higher reactive power compensation while employing the CVC and CFC as shown in Fig. 28. Hence, it helps to unload the inverter-based DGs to react effectively during system disturbances. As the PV is participated in voltage and frequency regulation control strategy, the performance of the proposed control strategy is evaluated in response to tripping the PV to demonstrate the reliability of the proposed control strategy. The simulation results show superior performance of the CVC and CFC for enhancing the transient voltage response and achieving similar frequency response compared to the case without employing the proposed control strategy due to the presence of BESS as shown in Figs. 29 and 30, respectively. The BESS support the MG with the deficiency of the active power generation with rapid discharging as shown in Fig. 31. Also, the proposed control strategy maximizes the dynamic reactive power reserve in the inverter-based DGs by switching more CAP banks as shown in Figs. 32 and 33, respectively. The aforementioned tests by alternatively tripping the BESS and PV demonstrate the superior performance and reliability of the proposed free communication control strategy for achieving fast frequency and voltage regulation to the islanded MG. Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. 1310 IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, VOL. 11, NO. 6, DECEMBER 2015 Fig. 34. Voltage at the PCC (VPCC ). Fig. 31. Active power (P ) flow in the MG (MW). Fig. 35. Frequency at the PCC (FPCC ). recover after the fault. This study verified the benefit of maximizing the reactive power reserve in enhancing the system stability and reliability under faulty conditions. The voltage profile for scenario 1 recovered after the fault and crossed the upper limit specified by the IEEE 1547 Standard of 1.1 p.u. for 0.19 s, indicating improved performance of an islanded MG under three-phase-to-ground faults. For the frequency profile shown in Fig. 35, the frequency of the MG employing the proposed control strategy crossed 1.008 p.u. for 0.2 s, then was regulated back to 1 p.u., thus again showing the superior performance of an islanded MG following the proposed control strategy under three-phase-to-ground fault. VII. C ONCLUSION Fig. 32. Reactive power (P ) flow in the MG (MVAr). Fig. 33. Reactive power compensation from the CAP banks. D. MG Performance Under Three-Phase-to-Ground Fault A three-phase-to-ground fault has been stimulated at the PCC for 140 ms. As illustrated from Figs. 34 and 35, the MG under scenario 2 went unstable after triggering the three-phase-toground fault. However, the MG under scenario 1 was able to A communication-free coordinated voltage and frequency control strategy demonstrates superior performance for maintaining the voltage and frequency profiles within an acceptable range in various conditions including steady, dynamic, and transient states. The distributed controllers implemented for the MG components have been utilized efficiently based on their slow, medium, and fast dynamic responses to act coordinately during system disturbances. The control strategy managed the active and reactive power flow and transient response in adherence to IEEE Standards 1547 and 929 and enhanced the system stability and reliability. Comprehensive case studies have been carried out and verified the robustness and performance of the control scheme in the view of transient responses and system stability. The fast dynamic reactive power reserve capability and rapid frequency regulation have been demonstrated by the simulations cases under all operating conditions, including tripping of MG components and three-phases-to-ground faults. The proposed CVC and CFC control strategy achieves a costeffective solution for islanded MGs without communication that achieves the centralized features based on decentralized controllers. Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. IBRAHIM et al.: ADAPTIVE ROLES OF ISLANDED MG COMPONENTS A PPENDIX TABLE I P OWER S YSTEM , DZ, DFIG-WT, PV, BESS, AND CAP BANK PARAMETERS TABLE II L OAD PARAMETERS TABLE III PV M ODEL PARAMETERS STC, standard test condition. TABLE IV MPPT M ODEL PARAMETERS 1311 R EFERENCES [1] J. Rocabert, A. Luna, F. Blaabjerg, and P. Rodriguez, “Control of power converters in AC microgrids,” IEEE Trans. Power Electron., vol. 27, no. 11, pp. 4734–4749, Nov. 2012. [2] IEEE Recommended Practice for Utility Interface of Photovoltaic (PV) Systems, IEEE Standard 929-2000, 2000, p. i. [3] IEEE Standard for Interconnecting Distributed Resources with Electric Power Systems, IEEE Standard 1547-2003, 2003, pp. 1–28. [4] F. Gonzalez-Espin, I. Patrao, E. Figueres, and G. Garcera, “An adaptive digital control technique for improved performance of grid connected inverters,” IEEE Trans. Ind. Informat., vol. 9, no. 2, pp. 708–718, May 2013. [5] J. C. Vasquez, J. M. Guerrero, A. Luna, P. Rodriguez, and R. Teodorescu, “Adaptive droop control applied to voltage-source inverters operating in grid-connected and islanded modes,” IEEE Trans. Ind. Electron., vol. 56, no. 10, pp. 4088–4096, Oct. 2009. [6] S. Dasgupta, S. N. Mohan, S. K. Sahoo, and S. K. Panda, “A plug and play operational approach for implementation of an autonomous-microgrid system,” IEEE Trans. Ind. Informat., vol. 8, no. 3, pp. 615–629, Aug. 2012. [7] M. Datta, T. Senjyu, A. Yona, T. Funabashi, and K. Chul-Hwan, “A coordinated control method for leveling PV output power fluctuations of PV& diesel hybrid systems connected to isolated power utility,” IEEE Trans. Energy Convers., vol. 24, no. 1, pp. 153–162, Mar. 2009. [8] E. J. Bueno, A. Hernandez, F. J. Rodriguez, C. Girón, R. Mateos, and S. Cobreces, “A DSP-and FPGA-based industrial control with high-speed communication interfaces for grid converters applied to distributed power generation systems,” IEEE Trans. Ind. Electron., vol. 56, no. 3, pp. 654– 669, Mar. 2009. [9] A. Timbus, M. Larsson, and C. Yuen, “Active management of distributed energy resources using standardized communications and modern information technologies,” IEEE Trans. Ind. Electron., vol. 56, no. 10, pp. 4029–4037, Oct. 2009. [10] B. Bahrani, M. Saeedifard, A. Karimi, and A. Rufer, “A multivariable design methodology for voltage control of a single-DG-unit microgrid,” IEEE Trans. Ind. Informat., vol. 9, no. 2, pp. 589–599, May 2013. [11] H. Ma, K. W. Chan, and M. Liu, “An intelligent control scheme to support voltage of smart power systems,” IEEE Trans. Ind. Informat., vol. 9, no. 3, pp. 1405–1414, Aug. 2013. [12] R. Majumder, “Reactive power compensation in single-phase operation of microgrid,” IEEE Trans. Ind. Electron., vol. 60, no. 4, pp. 1403–1416, Apr. 2013. [13] K. Jong-Yul, K. Seul-Ki, and J. Jin-Hong, “Coordinated state-of-charge control strategy for microgrid during islanded operation,” in Proc. IEEE 3rd Int. Symp. Power Electron. Distrib. Gener. Syst. (PEDG), 2012, pp. 133–139. [14] K. T. Tan, X. Y. Peng, P. L. So, Y. C. Chu, and M. Z. Q. Chen, “Centralized control for parallel operation of distributed generation inverters in microgrids,” IEEE Trans. Smart Grid, vol. 3, no. 4, pp. 1977–1987, Dec. 2012. [15] N. Pogaku, M. Prodanovic, and T. C. Green, “Modeling, analysis and testing of autonomous operation of an inverter-based microgrid,” IEEE Trans. Power Electron., vol. 22, no. 2, pp. 613–625, Mar. 2007. [16] H. Nikkhajoei and R. H. Lasseter, “Distributed generation interface to the CERTS microgrid,” IEEE Trans. Power Del., vol. 24, no. 3, pp. 1598– 1608, Jul. 2009. [17] K. Jong-Yul et al., “Cooperative control strategy of energy storage system and microsources for stabilizing the microgrid during islanded operation,” IEEE Trans. Power Electron., vol. 25, no. 12, pp. 3037–3048, Dec. 2010. [18] K. M. Son, K. S. Moon, S. K. Lee, and J. K. Park, “Coordination of an SVC with a ULTC reserving compensation margin for emergency control,” IEEE Trans. Power Del., vol. 15, no. 4, pp. 1193–1198, Oct. 2000. [19] C. A. Sepulveda, J. A. Munoz, J. R. Espinoza, M. E. Figueroa, and C. R. Baier, “FPGA v/s DSP performance comparison for a VSC-based STATCOM control application,” IEEE Trans. Ind. Informat., vol. 9, no. 3, pp. 1351–1360, Aug. 2013. [20] J. Y. Park, S. R. Nam, and J. K. Park, “Control of a ULTC considering the dispatch schedule of capacitors in a distribution system,” IEEE Trans. Power Syst., vol. 22, no. 2, pp. 755–761, May 2007. [21] M. E. Baran and I. M. El-Markabi, “A multiagent-based dispatching scheme for distributed generators for voltage support on distribution feeders,” IEEE Trans. Power Syst., vol. 22, no. 1, pp. 52–59, Feb. 2007. [22] M. Brenna et al., “Automatic distributed voltage control algorithm in smart grids applications,” IEEE Trans. Smart Grid, vol. 4, no. 2, pp. 877– 885, Jun. 2013. Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply. 1312 IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, VOL. 11, NO. 6, DECEMBER 2015 [23] M. L. Di Silvestre, G. Graditi, and E. R. Sanseverino, “A generalized framework for optimal sizing of distributed energy resources in micro-grids using an indicator-based swarm approach,” IEEE Trans. Ind. Informat., vol. 10, no. 1, pp. 152–162, Feb. 2014. [24] K. A. Alobeidli, M. H. Syed, M. S. El Moursi, and H. H. Zeineldin, “Novel coordinated voltage control for hybrid micro-grid with islanding capability,” IEEE Trans. Smart Grid, vol. 6, no. 3, pp. 1116–1127, May 2015. [25] A. Kulmala, S. Repo, and P. Järventausta, “Coordinated voltage control in distribution networks including several distributed energy resources,” IEEE Trans. Smart Grid, vol. 5, no. 4, pp. 2010–2020, Jul. 2014. [26] A. Kulmala, A. Mutanen, A. Koto, S. Repo, and P. Jarventausta, “RTDS verification of a coordinated voltage control implementation for distribution networks with distributed generation,” in Proc. IEEE PES Innov. Smart Grid Technol. Conf. Eur. (ISGT Eur.), Oct. 11–13, 2010, pp. 1–8. [27] M. E. Elkhatib, R. El-Shatshat, and M. M. A. Salama, “Novel coordinated voltage control for smart distribution networks with DG,” IEEE Trans. Smart Grid, vol. 2, no. 4, pp. 598–605, Dec. 2011. [28] A. Borghetti et al., “Short-term scheduling and control of active distribution systems with high penetration of renewable resources,” IEEE Syst. J., vol. 4, no. 3, pp. 313–322, Sep. 2010. [29] F. Pilo, G. Pisano, and G. G. Soma, “Optimal coordination of energy resources with a two-stage online active management,” IEEE Trans. Ind. Electron., vol. 58, no. 10, pp. 4526–4537, Oct. 2011. [30] L. Yu, D. Czarkowski, and F. de Leon, “Optimal distributed voltage regulation for secondary networks with DGs,” IEEE Trans. Smart Grid, vol. 3, no. 2, pp. 959–967, Jun. 2012. [31] A. Viehweider, H. Schichl, D. B. de Castro, S. Henein, and D. Schwabeneder, “Smart robust voltage control for distribution networks using interval arithmetic and state machine concepts,” in Proc. IEEE PES Innov. Smart Grid Technol. Conf. Eur., 2010, pp. 1–8. [32] A. Timbus, M. Larsson, and C. Yuen, “Active management of distributed energy resources using standardized communications and modern information technologies,” IEEE Trans. Ind. Electron., vol. 56, no. 10, pp. 4029–4037, Oct. 2009. [33] R. Caldon, F. Rossetto, and A. Scala, “Reactive power control in distribution networks with dispersed generators: A cost based method,” Elect. Power Syst. Res., vol. 64, pp. 209–217, 2003. [34] A. A. Aquino-Lugo, R. Klump, and T. J. Overbye, “A control framework for the smart grid for voltage support using agent-based technologies,” IEEE Trans. Smart Grid, vol. 2, no. 1, pp. 173–180, Mar. 2011. [35] D. Villacci, G. Bontempi, and A. Vaccaro, “An adaptive local learningbased methodology for voltage regulation in distribution networks with dispersed generation,” IEEE Trans. Power Syst., vol. 21, no. 3, pp. 1131– 1140, Aug. 2006. [36] V. Galdi, A. Vaccaro, and D. Villacci, “Voltage regulation in MV networks with dispersed generations by a neural-based multi objective methodology,” Elect. Power Syst. Res., vol. 78, pp. 785–793, 2008. [37] T. Senjyu, Y. Miyazato, A. Yona, N. Urasaki, and T. Funabashi, “Optimal distribution voltage control and coordination with distributed generation,” IEEE Trans. Power Del., vol. 23, no. 2, pp. 1236–1242, Apr. 2008. [38] N. Nimpitiwan and C. Chaiyabut, “Centralized control of system voltage/reactive power using genetic algorithm,” in Proc. Int. Conf. Intell. Syst. Appl. Power Syst., 2007, pp. 1–6. [39] T. Niknam, A. M. Ranjbar, and A. R. Shirani, “Impact of distributed generation on volt/var control in distribution networks,” in Proc. IEEE Bologna Power Tech Conf., 23–26 Jun. 2003, vol. 3, p. 7. [40] A. G. Madureira and J. A. Pecas Lopes, “Coordinated voltage support in distribution networks with distributed generation and microgrids,” IET Renew. Power Gener., vol. 3, no. 4, pp. 439–454, Dec. 2009. [41] P. H. Divshali, A. Alimardani, S. H. Hosseinian, and M. Abedi, “Decentralized cooperative control strategy of microsources for stabilizing autonomous VSC-based microgrids,” IEEE Trans. Power Syst., vol. 27, no. 4, pp. 1949–1959, Nov. 2012. [42] R. A. Mastromauro, M. Liserre, and A. Dell’Aquila, “Control issues in single-stage photovoltaic systems: MPPT, current and voltage control,” IEEE Trans. Ind. Informat., vol. 8, no. 2, pp. 241–254, May 2012. [43] A. Al Nabulsi and R. Dhaouadi, “Efficiency optimization of a DSP-based standalone PV system using fuzzy logic and dual-MPPT control,” IEEE Trans. Ind. Informat., vol. 8, no. 3, pp. 573–584, Aug. 2012. [44] B. Shoeiby, R. Davoodnezhad, D. G. Holmes, and B. P. McGrath, “A new current control droop strategy for VSI-based islanded microgrids,” in Proc. Int. Power Electron. Conf. (IPEC-Hiroshima 2014-ECCE-ASIA), May 18–21, 2014, pp. 1482–1489. [45] B. Shoeiby, D. G. Holmes, B. P. McGrath, and R. Davoodnezhad, “Dynamics of droop-controlled microgrids with unequal droop response times,” in Proc. Australas. Univ. Power Eng. Conf. (AUPEC), Sep. 29/Oct. 3, 2013, pp. 1–6. [46] M. S. El Moursi, H. H. Zeineldin, J. L. Kirtley, and K. Alobeidli, “A dynamic master/slave reactive power-management scheme for smart grids with distributed generation,” IEEE Trans. Power Del., vol. 29, no. 3, pp. 1157–1167, Jun. 2014. [47] M. El Moursi, G. Joos, and C. Abbey, “A secondary voltage control strategy for transmission level interconnection of wind generation,” IEEE Trans. Power Electron., vol. 23, no. 3, pp. 1178–1190, May 2008. [48] M. S. ElMoursi and A. M. Sharaf, “Voltage stabilization and reactive compensation using a novel FACTS STATCOM scheme,” in Proc. Can. Conf. Elect. Comput. Eng., May 1–4, 2005, pp. 537–540. Hebatallah M. Ibrahim was born in Cairo, Egypt, in 1989. She received the B.Sc. degree in electronics engineering from German University, Cairo, Egypt, in 2011, and the M.Sc. degree in electrical power engineering from the Masdar Institute of Science and Technology, Abu Dhabi, United Arab Emirates, in 2013. Her research interests include in microgrid, power system stability, and control. Mohamed Shawky El Moursi (M’12–SM’15) received the B.Sc. and M.Sc. degrees from Mansoura University, Mansoura, Egypt, in 1997 and 2002, respectively, and the Ph.D. degree from the University of New Brunswick (UNB), Fredericton, NB, Canada, in 2005, all in electrical engineering. From 2002 to 2005, he was a Research and Teaching Assistant with the Department of Electrical and Computer Engineering, UNB. He joined as a Postdoctoral Fellow with the Power Electronics Group, McGill University, Montréal, QC, Canada. He joined Technology R&D, Wind Power Plant Group, Vestas Wind Systems, Arhus, Denmark. He was a Senior Study and Planning Engineer with TRANSCO, Abu Dhabi, United Arab Emirates, and was promoted to an Associate Professor with the Faculty of Engineering, Mansoura University, where he is currently on leave. He was a Visiting Professor at the Massachusetts Institute of Technology, Cambridge, MA, USA. Currently, he is an Associate Professor with the Department of Electrical Engineering and Computer Science, Masdar Institute of Science and Technology, Abu Dhabi. His research interests include power system, power electronics, flexible ac transmission system technologies, system control, WT modeling, wind energy integration, and interconnections. Dr. El Moursi is currently an Editor for the IEEE TRANSACTIONS ON P OWER D ELIVERY , an Associate Editor of the IEEE T RANSACTIONS ON P OWER E LECTRONICS , the Regional Editor for IET Renewable Power Generation, and an Associate Editor for the IET Power Electronics Journal. Po-Hsu Huang (S’11) was born in Taiwan, China, in 1985. He received the B.Sc. degree from National Cheng-Kung University, Tainan, Taiwan, and the first M.Sc. degree from National Taiwan University, Taipei, Taiwan, in 2007 and 2009, respectively, both in electrical engineering, and the second M.Sc. degree in electrical power engineering from the Masdar Institute of Science and Technology, Abu Dhabi, United Arab Emirates, in 2013. Currently, he is pursuing the Ph.D. degree at the Department of Electrical Engineering and Computer Science, Massachusetts Institute of Technology, Cambridge, MA, USA. His research interests include dc/ac microgrids, power electronics, wind power generation, linear/nonlinear system dynamics, power system stability, and control. Authorized licensed use limited to: UNIV OF WISCONSIN - MILWAUKEE. Downloaded on January 02,2022 at 06:41:31 UTC from IEEE Xplore. Restrictions apply.