Uploaded by aries arive

Lighting-Design

advertisement
Lighting Design Procedures
The best option available for lighting design is the use of standard lighting software. If no
such facility is available, any one of the following techniques can be used for the design
ο‚·
ο‚·
ο‚·
Short hand method
Long hand method
Simplified method
Short hand method
In this method it is assumed that the average maintained quantity of lumens arriving
on the work plane will be half the quantity of the total new lamp lumens. This method
assumes “normal” sized rooms, “normal” surface reflectance and “normal” dirt conditions”. A
normal sized room is the one in which the mounting height (distance from the luminaire
bottom to the work plane) is less than half of the smallest room dimension. It is also
assumed that conventional fixtures are used. A high bay fixture is used when mounting
height is over 6 m. Otherwise low bay fixtures are recommended. The total number of
fixtures (luminaires) to be used is then calculated as follows.
Step-1
Obtain the required level of illumination in lux.
Step-2
Choose a particular lamp and obtain the lam lumens form the lamp data.
Step-3
Delivered maintained lamp lumen (DMLL) = 0.5 x Rated lamp lumens.
Step-4
Number of fixtures (Luminaires)
=
π‘…π‘œπ‘œπ‘š π΄π‘Ÿπ‘’π‘Ž π‘₯ 𝐿𝑒π‘₯
𝐷𝑀𝐿𝐿
Select the nearest round figure.
Step-5
π‘…π‘œπ‘œπ‘š π΄π‘Ÿπ‘’π‘Ž
Area per fixture
=
Spacing between fixtures
= √π΄π‘Ÿπ‘’π‘Ž π‘π‘’π‘Ÿ 𝑓𝑖π‘₯π‘‘π‘’π‘Ÿπ‘’
π‘π‘’π‘šπ‘π‘’π‘Ÿ π‘œπ‘“ 𝑓𝑖π‘₯π‘‘π‘’π‘Ÿπ‘’
Step-6
Note:
Spacing should not be more than the mounting height (MH) for high bay fixtures and
1.5 times the mounting height for low bay fixtures. Check for conformity. If the spacing is too
large, go back to step-2 and start again with a lower lamp rating.
Long hand method
This is a more accurate and effective method of estimating the number of light
fixtures (luminaires) and their spacing, because it takes into account the differences in
Photometric performance caused by room geometry and system lumen depreciation. The
core idea of this method is the determination of Coefficient of Utilization (CU) on the concept
that the area to be lighted has three cavities or spaces that have effective reflectance with
respect to each other and the work plane. The given space to be lighted is divided into three
cavities as shown below. The space between the ceiling and the bottom of the luminaire is
known as the Ceiling Cavity (CC) and the distance is h cc or the height of ceiling cavity. The
space between the work plane and the bottom of luminaire is Room Cavity (RC) and the
distance is hrc or the height of room cavity. The space between the work plane and the floor
is Floor cvity (FC) and the height is hfc or the height of floor cavity. The room cavities are
shown in the figure below.
The cavity ratios represent the geometric properties of the ceiling, room and floor
cavities and can be found using the formula:
πΆπ‘Žπ‘£π‘–π‘‘π‘¦ π‘Ÿπ‘Žπ‘‘π‘–π‘œ =
2.5 π‘₯ β„Ž π‘₯ (π‘π‘’π‘Ÿπ‘–π‘šπ‘’π‘‘π‘’π‘Ÿ)
π΄π‘Ÿπ‘’π‘Ž
Where:
h = hcc, for Ceiling Cavity Ratio (CCR)
h = hrc, for Room Cavity Ratio (RCR)
h = hfc, for Floor Cavity Ratio (FCR)
Ceiling Cavity
hcc
Fixture
Fixture
Pc
Room Cavity
hRC
Pw
Work plane
hFC
PF
Step-1
Study the site plan and elevation of the installation. Determine the lighting needs in
the consultation with standards and the end user.
Step-2
Select the light sources and luminaire, appropriate to the installation geometry,
nature of virtual task and energy criteria.
Step-3
Calculate the ceiling, room and floor cavity ratios and using Table for “Percentage
Effective Ceiling and Floor Reflectances ” to find out the ceiling and floor cavity reflectances.
Step-4
Use the given chart for the coefficient of utilization, the effective ceiling and floor
reflectances and RCR; find out the value of effective coefficient of utilization.
Step-5
Select the light loss factor (LLF0, this factor was previously referred as maintenance
factor (MF), accepted values are
AC rooms, clean rooms, etc.
Industrial environment
Dusty areas
0.8
0.7
0.6
Step-6
Use the formula to arrive at the quantity of luminaires (fixtures)
Number of luminaires =
π΄π‘Ÿπ‘’π‘Ž π‘₯ πΌπ‘™π‘™π‘’π‘šπ‘–π‘›π‘Žπ‘‘π‘–π‘œπ‘›
πΆπ‘ˆ π‘₯𝐿𝐿𝐹 π‘₯ πΏπ‘’π‘šπ‘’π‘› π‘œπ‘’π‘‘π‘π‘’π‘‘ π‘œπ‘“ π‘™π‘’π‘šπ‘–π‘›π‘Žπ‘–π‘Ÿπ‘’
Step-7
Arrange the luminaires symmetrically giving due considerations to spacing criterion to
achieve uniformity of illumination.
π΄π‘Ÿπ‘’π‘Ž π‘π‘’π‘Ÿ π‘™π‘’π‘šπ‘–π‘›π‘Žπ‘–π‘Ÿπ‘’ (𝑓𝑖π‘₯π‘‘π‘’π‘Ÿπ‘’) =
π‘…π‘œπ‘œπ‘š π‘Žπ‘Ÿπ‘’π‘Ž
π‘π‘’π‘šπ‘π‘’π‘Ÿ π‘œπ‘“ 𝑓𝑖π‘₯π‘‘π‘’π‘Ÿπ‘’π‘ 
π‘‡β„Žπ‘’π‘Ÿπ‘’π‘“π‘œπ‘Ÿπ‘’, 𝑓𝑖π‘₯π‘‘π‘’π‘Ÿπ‘’ π‘ π‘π‘Žπ‘π‘–π‘›π‘” = √π΄π‘Ÿπ‘’π‘Ž π‘π‘’π‘Ÿ 𝑓𝑖π‘₯π‘‘π‘’π‘Ÿπ‘’
Note:
Spacing should not be more than the mounting height (MH) for high bay fixtures and
1.5 times the mounting height for low bay fixtures. Check for conformity. If the spacing is too
large, go back to step-2 and start again with a lower lamp rating.
Simplified design procedure
A simplified design procedure for lighting system design by lumen method for a
simple interior is given below (Assumption: C.O.U. chart are based on room index is
available)
Step-1
Study the site plan and elevation of the installation. Determine the lighting needs in
consultation with standards and the end user.
Step-2
Select the light sources and luminaire, appropriated to the installation geometry,
nature of visual task and energy criteria.
Step-3
Calculate the room index (RI) using the formula:
π‘…π‘œπ‘œπ‘š 𝑖𝑛𝑑𝑒π‘₯ (𝑅𝐼) =
πΏπ‘’π‘›π‘”π‘‘β„Ž π‘₯ π΅π‘Ÿπ‘’π‘Žπ‘‘π‘‘β„Ž
(πΏπ‘’π‘›π‘”π‘‘β„Ž + π΅π‘Ÿπ‘’π‘Žπ‘‘π‘‘β„Ž)π‘₯ π‘€π‘œπ‘’π‘›π‘‘π‘–π‘›π‘” β„Žπ‘’π‘–π‘”β„Žπ‘‘
Step-4
Based on this, coefficient of utilization value can be obtained from the C.O.U. table
for the selected luminaire. These values are generally based on the RI and room surface
reflectances which are generally 70% for light colored, 50% for average and 30% for dark
walls and 50%, 30%, and 10% for corresponding ceilings.
Step-5
Select the light loss factor (LLF), this factor was previously referred to as
maintenance factor (MF). Generally, accepted values are:
AC rooms, clean rooms, etc.
Industrial environment
Dusty Areas
0.8
0.7
0.6
Step-6
Use the formula to arrive at the quantity of luminaries:
π‘π‘’π‘šπ‘π‘’π‘Ÿ π‘œπ‘“ π‘™π‘’π‘šπ‘–π‘›π‘Žπ‘–π‘Ÿπ‘’π‘  =
π΄π‘Ÿπ‘’π‘Ž π‘₯ πΌπ‘™π‘™π‘’π‘šπ‘–π‘›π‘Žπ‘‘π‘–π‘œπ‘›
πΆπ‘ˆ π‘₯ 𝐿𝐿𝐹 π‘₯ πΏπ‘’π‘šπ‘’π‘› π‘œπ‘’π‘‘π‘π‘’π‘‘ π‘œπ‘“ π‘™π‘’π‘šπ‘–π‘›π‘Žπ‘–π‘Ÿπ‘’
Step-7
Arrange the luminaires symmetrically giving due considerations to spacing criterions
to achieve uniformity of illumination.
π΄π‘Ÿπ‘’π‘Ž π‘π‘’π‘Ÿ π‘™π‘’π‘šπ‘–π‘›π‘Žπ‘–π‘Ÿπ‘’(𝑓𝑖π‘₯π‘‘π‘’π‘Ÿπ‘’) =
π‘…π‘œπ‘œπ‘š π΄π‘Ÿπ‘’π‘Ž
π‘π‘’π‘šπ‘π‘’π‘Ÿ π‘œπ‘“ 𝑓𝑖π‘₯π‘‘π‘’π‘Ÿπ‘’π‘ 
π‘‡β„Žπ‘’π‘Ÿπ‘’π‘“π‘œπ‘Ÿπ‘’, 𝑓𝑖π‘₯π‘‘π‘’π‘Ÿπ‘’ π‘ π‘π‘Žπ‘π‘–π‘›π‘” = √π΄π‘Ÿπ‘’π‘Ž π‘π‘’π‘Ÿ 𝑓𝑖π‘₯π‘‘π‘’π‘Ÿπ‘’
Note:
If spacing is too wide, repeat the process with a fixture with lower wattage of lamps.
Normally, spacing should not be more than the mounting height for high bay fixtures and 1.5
times the mounting height for low bay fixtures.
Arrangement of fixtures
Fixtures shall be arranged from the middle of the room to the outside. A square array
is the best option but rectangular array also will work satisfactorily as long as the spacing to
mounting height ratio is not violated. With an odd quantities of fixtures of rows or columns,
there will be a fixture line on the center line. With even quantities of rows or columns, the
locations are half the spacing off the center line. The closest fixture to a wall should be one
half the spacing or less.
Download