Insulation Resistance Test Or Megger Test Procedures With Circuit Diagram
marinesite.blogspot.in
Suka
In this article we will go through Megger test first of all i want to say both insulating
resistance tests and megger test are same. which is usually carries out to find the insulation
of different machines windings conductor wires generator windings etc.
1.444 orang menyukai marinesite.blogspot.in.
Megger Testing Instrument
Megger testing instrument is a high resistance Ohmmeter with a build in
generator
Plugin sosial Facebook
It is equipped with three connections Line Terminal (L), Earth Terminal (E) and
Guard Terminal (G)
Resistance is measured between the Line and Earth terminals
The “Guard” terminal is provided for special testing situations where one
resistance must be isolated from another.
Popular Posts
The generator can be hand-cranked or line-operated to develop a high DC
voltage which causes a small current through and over surfaces of the
insulation being tested
What is Tappet Clearance?
How to check And Adjust
tapper clearance?
Which is measured by an ohm meter having an indicator scale
Simple Explanation Of
Crankshaft Deflections,
Measurement Procedure,
Readings,Curves
Importance Of Insulation Resistance Test Or Megger Test
An insulation test is carried out to test the integrity of the insulation between
conductors.
Which help to find the short circuit problems in the circuit
How Does Brushless
Alternator Works? (With
Diagram)
It also serves as the best guide to indicate the health of the equipment
Procedure To tests the Insulation
Test the megger before use, whether it gives INFINITY value when not
connected, and ZERO when the two terminals are connected together and the
handle is rotated.
To do the test you ensure the cable is disconnected from any devices (megger
normally work on 500v, 1000v testers for higher voltage testing).
Make sure that no eddy current in the device by earthing it.(very important)
What is Gravity Disc Of
Purifier? Selection and
fuctions of Purifier Gravity
Disc
Specific Fuel Oil Consumption
Definition,Formula And Calculation
Instrument should be in normal working temperature because resistance is
related to temperature.
What is Governor Droop In electric
generators? Why Governor Droop
Required?
Ensure both ends of the cables are separated from each other (connect one end
in terminal strip if necessary).
SOPEP - Ship Oil Pollution Emergency
Plan and List of Equipment Requirement.
Now connect the megger terminals to the conductors which has to be meassured
Then hand crank the generator and a high DC voltage generated which causes a
small current through and over surfaces of the insulation being tested.
Difference Between Safety Valve And
Relief Valve
Insulation Resistance Test Or
Megger Test Procedures
With Circuit Diagram
If the Reading shows Infinity means the conductors having good insulation.
Here it shows a megger circuit diagram
Emergency Fire Pump Regulation
Blog Archive
► 2014 (32)
▼ 2013 (106)
► December (13)
► November (5)
► October (20)
Image credits:tpub.com,electrical-engineering-portal.com
▼ September (34)
What is Bow Thruster and how its
works?
List Out Lube Oil Properties
Bijoy
About The Author:
He is a marine engineer sailing with ESM.He loves to share his views and opinion
regarding marine exams and coordinate Marinesite. Apart from this he is having keen
interest on blogging.
You can catch him on Google+
List Of Boiler Mountings
What is Governor Droop In electric
generators? Why...
Fuel Injector For Marine Engines
Variable Injection Timing (VIT) In
Marine Diesel E...
Boiler Water Treatment Basics
Why AC Is Preferred On Board Ship
Than DC
Related Posts:
Types of Explosion Protection for
Electrical Equip...
What is Governor Droop In electric generators? Why Governor Droop Required?
Air bottle Regulations,Air bottle
Mountings, Air b...
Types of Explosion Protection for Electrical Equipments
Safety Precaution To Be Followed During Any Electrical Maintenance Work
Insulation Resistance Test Or Megger Test Procedures With Circuit Diagram
Preferential Trips Generators
Safety Devices On Air Compressors
LEAD ACID BATTERIES
SOLAS Life Raft Equipment and Life
Raft Ration
Thrust Bearing
SOLAS Lifeboat Requirements
Why Liners are Generally Thinner at the Bottom than at the Top ?
Diference between P Alkalinity T
Alkalinity and M ...
Regulation for Sewage
Bunker Delivery Note (BDN) And
Bunker Delivery Not...
What is BOD?
Lifeboat Equipment SOLAS
OILY WATER SEPARATOR
Steering gear test
How Does Brushless Alternator Works? (With Diagram)
Emergency Generator Regulations
Main Switchboard Safeties
Emergency Fire Pump Regulation
...
Boiler Water Tests onboard
Insulation Resistance Test Or Megger
Test Procedur...
Posted by Marine site
Labels: Article Electrical, oral, Oral Electrical
Ideal Boiler Water Properties And
Effects
No comments:
Ship Stabilizers And Different Types Of
Ship stabi...
Post a Comment
MEK (Motor) asked Questions Part 4
Regulation For Sewage Holding Tanks
Bumping Clearance In Air Compressor,
How to messur...
Trips and Alarms In Purifier
Trips And Alarms In Auxiliary Engines
Comment as:
Safety Features In Ship Air
Compressors
Publish
7 Causes Of Ship Turbocharger Surging
,Prevention ...
How Smoke Detectors And Heat
Detectors Works (Fire...
Why Inert Gas (ig) is not used in bunker
tanks and...
Newer Post
Subscribe to: Post Comments (Atom)
Older Post
Home
► August (21)
► July (5)
► June (3)
► May (2)
► March (1)
► January (2)
► 2012 (32)
Help others
rakesh
in reeds its saying... at some rudder angle
there will be no torque on the stock for
balanced type... this may be the reason bt i
cudnt understand it....
MARINE SITE: Discussion orals class
IV · 3 days ago
rakesh
minimum torque is required for balanced
one in terms of toque unbalanced having
more toque thn semi banalnced minimum
is balanced one...
MARINE SITE: Discussion orals class
IV · 3 days ago
Vineeth M
bcz balanced rudder require more torque to
move compared to semi balanced rudder.
MARINE SITE: Discussion orals class
psyc00
as reg 34......
en route
should pass from odmc
not with in special area
50 nm away frm nearest l
MARINE SITE: Discussion orals class
IV · 5 days ago
Rupam Kanathey
what r the AC compressor parameters
MARINE SITE: Discussion orals class
IV · 1 week ago
rakesh
most of the ships are using balanced rudder
not semi balanced i thk... if m wrong plz
correct me..
MARINE SITE: Discussion orals class
IV · 3 weeks ago
santosh
why we r not using a balanced type
rudder.....why semi balance is in use?
MARINE SITE: Discussion orals class
IV · 3 weeks ago
rakesh
.An odd number of pistons have smaller
output pressure fluctuations than an even
number of pistons .....
MARINE SITE: Discussion orals class
IV · 3 weeks ago
Murugappan
Chandrasekaran
WHY SWASH PLATE PUMP HAS ODD
NUMBER OF PISTONS WHY NOT
EVEN NUMBERS OF PISTONS?
MARINE SITE: Discussion orals class
IV · 3 weeks ago
rakesh
The formula used to calculate the
Temperature Corrected Density is: =
(Density of Fuel Oil @ 15⁰C) x [1- {(T-15)
x 0.00064}] Where: T = temperature of oil
in bunker tanks in degree celcius,
0.00064...
MARINE SITE: Discussion orals class
IV · 3 weeks ago
Total Pageviews
Like to Share your knowledge contact us
2 4 9 7 2 6
Gladly inviting any suggestion, quires and question answers. mail to marinesite.blogspot@gmail.com. Powered by Blogger.
Download