Engineering Standard SAES-J-510 1 January 2018 Process Analyzer Systems Document Responsibility: Instrumentation Standards Committee Contents 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Scope .......................................................2 Conflicts and Deviations.............................2 References ...............................................2 Definitions .................................................4 General Requirements ...............................7 Electrical Requirements .............................8 Sample Systems ..................................... 11 Tubes and Tube Fittings .......................... 21 Sample Recovery Systems ...................... 23 3-Sided Shelter ....................................... 24 Analyzer Cabinet Design.......................... 26 Walk-In Analyzer Shelters ........................ 31 Headers and Vents .................................. 39 Calibration and Gas Cylinders Racks ........ 40 Combustible Gas / Toxic Gas / Oxygen Detection ................................ 41 16 Sour Service Applications ........................ 42 17 Inspection ............................................... 43 18 Packing/Shipping/Storage ........................ 43 19 Documentation ........................................ 44 Revision Summary .......................................... 45 Previous Issue Date: 15 September 2016 Next Planned Update: 15 September 2019 Revised paragraphs are indicated in the right margin Contact: David Tamez (tamezdx) on phone +966-013-8801345 ©Saudi Aramco 2018. All rights reserved. Page 1 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 1 SAES-J-510 Process Analyzer Systems Scope This standard describes the minimum mandatory design and installation requirements related to analyzer sample points, analyzer sample transport systems, sample conditioning systems, analyzer shelters, analyzer cabinets, 3-sided analyzer shelter, and safety systems related to online process analyzer measurement systems. 2 Conflicts and Deviations Any conflicts between this document and other applicable Mandatory Saudi Aramco Engineering Requirements (MSAERs) shall be addressed to the EK&RD Coordinator. Any deviation from the requirements herein shall follow internal company procedure SAEP-302. 3 References The selection of material and equipment, and the design, construction, maintenance, and repair of equipment and facilities covered by this standard shall comply with the latest edition of the references below, unless otherwise noted. 3.1 Saudi Aramco References Saudi Aramco Engineering Procedure SAEP-302 Waiver of a Mandatory Saudi Aramco Engineering Requirement Saudi Aramco Engineering Standards SAES-A-112 Meteorological and Seismic Design Data SAES-B-054 Access, Egress, and Materials Handling for Plant Facilities SAES-B-068 Electrical Area Classification SAES-J-002 Technically Acceptable Instruments SAES-J-003 Instrumentation-Basic Design Criteria SAES-J-505 Combustible Gas and Hydrogen Sulfide in Air Detection Systems SAES-J-902 Electrical System for Instrumentation SAES-J-903 Intrinsically Safe Systems SAES-N-001 Basic Criteria, Industrial Insulation Page 2 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems SAES-P-100 Basic Power System Design Criteria SAES-P-104 Wiring Methods and Materials SAES-P-111 Grounding SAES-P-116 Switchgear and Control Equipment SAES-P-123 Lighting SAES-W-011 Welding Requirements for On-Plot Piping Saudi Aramco Materials System Specifications 3.2 12-SAMSS-014 Pre-Engineered Metal Buildings 16-SAMSS-518 Low Voltage Panelboards 34-SAMSS-510 Online Analyzers 34-SAMSS-514 Combustible Gas and Hydrogen Sulfide Monitor Industry Codes and Standards American National Standards Institute ANSI Z97.1 Safety Glazing Material Used in Buildings American Petroleum Institute API RP 555 Process Analyzers American Society for Testing and Materials ASTM A269 Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing for General Service American Society of Mechanical Engineers ASME B31.3 Process Piping ASME PTC 19.3 TW-2010 Thermal Well Design Standard International Electrotechnical Commission IEC 60079-0 Explosive Atmospheres - Part 0: Equipment General Requirements National Association of Corrosion Engineers NACE MR0175/ISO 15156 Petroleum and Natural Gas Industries – Materials for Use in H2S Containing Environments in Oil and Gas Production Page 3 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems National Electrical Manufacturers Association NEMA ICS 6 Enclosures for Industrial Controls and Systems National Fire Protection Agency 4 NFPA 70 National Electrical Code (NEC) NFPA 496 Purged and Pressurized Enclosures for Electrical Equipment in Hazardous (Classified) Areas Definitions Analyzer Cabinet: An upright prefabricated enclosed non-walk-in structure that provides environmental protection and climate control for a single process analyzer. Analyzer maintenance is performed while standing on the outside of the structure with the doors open. The analyzer cabinet system is not designed for personnel entry. Analyzer cabinets should not be confused with terminal strip junction boxes or analyzer enclosures. Analyzer Enclosures: Are used for protecting analyzer circuit boards and detection hardware. These enclosures are normally attached to wall supports, panels, or instrument stands. Analyzer Manufacturer: Analyzer company that manufactures, supplies, provides, or builds, certified process analytical measurement devices. 3-Sided Analyzer Shelter (sunshade): A prefabricated structured roof and wall system that has one open side; which protects process analyzer equipment from direct sunlight exposure and allows natural air ventilation for equipment cooling. Analyzer Shelter: Analyzer shelters are prefabricated unmanned walk-in structures that provide protection for complex and semi-complex process analyzers systems. Analyzer shelters provide environmental protection against extreme ambient temperatures, dust contamination, and corrosive environments. Analyzers shelters provide humidity and climate control for sensitive process analyzer electronic equipment. Analyzer Slip Stream: The sample stream flow between the sample conditioning system and the analyzer sample inlet port. Analyzer System Integrator: Company or vendor that provides pre-packaged analyzer designs and engineering services; builds and provides pre-packaged analytical systems. Asphyxiant: Asphyxiant is a substance that can cause unconsciousness or suffocation due to displacement or depletion of oxygen concentration in breathing air (e.g., nitrogen, carbon dioxide, etc.) Page 4 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems Conventional Gas Chromatograph: A chromatograph that is designed to operate in a climate controlled environment. Critical Instrumentation: Critical Instrumentation is defined as a system, upon loss of power, would cause: (1) a process failure that is not fail-safe, (2) area or plant shutdown, (3) loss of custody transfer metering or accounting system, or (4) other adverse facility operating scenarios. Such systems shall include, but not be limited to: ESD systems, gas detection systems, process heater safety, critical process monitoring and control; and custody transfer metering systems. Dead Leg: Sections of pipe or tubing that, by design, do not allow for the flow of material through them. Fast Loop: High velocity, continuously operation sample loop bringing fresh sample in close proximity to the analyzer sampling conditioning system. Fast loop may also be referred to as bypass loop or bypass stream. Field Mounted Analyzer: Process analyzers that are designed for outdoor use and are certified for high ambient temperature environments. Field mounted analyzers do not require climate or humidity control environments. Field Mounted Gas Chromatograph: A chromatograph that is designed and certified to operate in outdoor environments. Packaged Systems: Systems developed and manufactured by a Analyzer System Integrator. Systems may include but not limited to analyzer shelters, analyzer cabinets, sunshades, sample conditioning systems, cylinder racks, and other ancillary analyzer equipment. Process Analyzer: A measuring device that determines the intrinsic property of a material and/or concentration of one or more chemical compounds in the presence of other chemical compounds. Process Analyzer, Complex: Process analyzers that are complicated in nature, which are extremely sensitive to environmental heat, humidity, dust contamination, corrosion, and require climate control and humidity control. Such analyzers require tight temperature control (climate control) for proper electronic heat dissipation, require a high level of troubleshooting skills, and require highly intrusive maintenance activities. (e.g., conventional gas chromatographs, mass spectrometers, physical properties analyzers, continues emission monitors (CEMS), Fourier Transform (FTNIR), etc.) Process Analyzer, Semi Complex: Process analyzers that are sensitive to environmental conditions and require climate control for heat dissipation and require some level of intrusive maintenance activity. (e.g., infrared, UV, SRU tail gas, mercury, total carbon analyzers, wet chemistry analyzers, etc.) Page 5 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems Process Analyzer, Simple: Process analyzers that are simplistic in nature that require minimal non-intrusive maintenance activities and are normally designed for direct field mounting. (e.g., pH, conductivity, ORP, ion-selective probes, etc.) Process Line: The piping used to transport of process fluids (other than sample lines). Representative Sample: A portion extracted from total volume that contains the constituents in the same proportion that are present in the total volume. Remote Cylinder Rack: A cylinder rack system used for storing carrier gases and/or calibration cylinders that is normally located away from the analyzer shelter or analyzer cabinet. Sample Probe: A sampling device in the form of a special tube or pipe assembly or flanged probe that is inserted in a defined location into the process stream. The probe is used to continuously extract a small portion of process medium as sample. Sample Conditioning System: A system which prepares a portion of the sample from the sample transport system to be compatible with the analyzer requirements. This enables the analyzer to reliably perform its analytical measurement/determination unattended. Sample Pre-Conditioning: A system that consists of one or more devices that condition the sample (pressure, temperature, flow or change of state) so that is transportable to the sample conditioning system. Sample Line: The tube used to transport continuous process sample from sample probe to the analyzer sample conditioning system. Sample Point: The location where the sample is extracted from process line. It may also be referred to as sample nozzle or process tap location. Sample Recovery Systems: A custom built system that provides the means to recover process samples or reclaim analysis byproducts from process analyzers and returns it back to the process or other containment system. Toxic Gas: Gaseous substances that, if released in an area, will cause a health hazard by contact with the skin or by inhalation from the surrounding atmosphere. Examples of toxic gas include but not limited to carbon monoxide (CO), carbon dioxide (CO2), sulfur dioxide (SO2), chlorine (CL2), ammonia (NH3), hydrogen chloride (HCL), hydrogen sulfide (H2S), and others. Page 6 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 5 SAES-J-510 Process Analyzer Systems General Requirements 5.1 Packaged Equipment Requirements 5.1.1 The package systems shall be supplied as completely assembled systems suitable for direct mounting in a process plant. 5.1.2 All analyzers shall be supplied per Saudi Aramco Regulated Vendors List. 5.1.3 No equipment other than process analyzers and analyzer ancillary equipment shall be mounted in analyzer shelters, analyzers cabinets, or under analyzer sunshades. Installation of non-related process analyzer equipment in shelters is not permitted. 5.1.4 Analyzers shall be single-stream analyzers. Multi-stream gas chromatograph analyzers will be considered only if the conditions listed in 34-SAMSS-510 Section 5.2 are applicable. 5.1.5 Stream switching in liquid phase services is prohibited. 5.1.6 All equipment including wiring, tubing, and supports shall be installed in such a manner that it will not interfere with the operation, maintenance, or removal of sample system hardware, analyzers, or other ancillary items. 5.1.7 The top elevation of a sample conditioning systems, analyzers, or any other high maintenance items shall not exceed 1.8 m (6 ft) in height from the grade elevation. 5.1.8 Field connections for shelters and analyzer cabinet internal wiring shall terminate at externally mounted analog or digital junction boxes. Junction boxes shall be kept to a minimum and shall be mounted at elevations above higher maintenance equipment. 5.1.9 Sample conditioning systems and calibration cylinders mounted outside of analyzer shelters and analyzer cabinets shall be protected with an overhead sunshield. 5.1.10 Field connections for shelters and analyzer cabinet piping or tubing shall terminate at the bulkhead connections or pipe flanges. 5.2 Environmental Requirements Analyzers and ancillary equipment shall be suitable for installation in the applicable environmental conditions specified in SAES-J-003 and shall be Page 7 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems designed for contaminant levels specified in Ambient Air Quality section of SAES-A-112. 6 Electrical Requirements 6.1 6.2 General Requirements 6.1.1 Electrical systems shall be designed and installed in accordance with NFPA 70 National Electrical Code and SAES-P-100. 6.1.2 All electrical and electronic equipment in hazardous areas shall meet listing/certification requirements specified in this document and the NEC. 6.1.3 Process analyzers shall be powered by a non-UPS system unless the analyzers or analyzer ancillary equipment is identified as Critical Instrumentation as defined in Section 4. Analyzer equipment defined as Critical Instrumentation shall be powered by a UPS system. 6.1.4 Electric panelboards shall be mounted outside the shelter or analyzer cabinet systems. 6.1.5 Installation of analyzer wiring systems shall meet requirements specified in SAES-J-902. Area Classification 6.2.1 Shelters, analyzer cabinets, sample conditioning systems, and ancillary equipment shall be classified in accordance with SAES-B-068, Electrical Area Classification. 6.2.2 Analyzer shelters, analyzer cabinets, process analyzers, and ancillary analyzer equipment designed for non-flammable or non-toxic samples and are designed for general purpose use; such equipment shall be located only in non-classified areas. 6.2.3 Analyzer shelters, analyzer cabinets, process analyzers and ancillary analyzer equipment located in hazardous areas and/or analyze flammable or toxic samples shall be suitable for use in the electrical classified area in which they are installed; but at minimum shall be certified for use in a Class 1, Zone 2 hazardous area and for the gas groups and temperature class appropriate to the materials handled within the area. Commentary Note: When hydrogen is introduced within the shelter as a carrier gas, the equipment internal to the shelter does not have to be certified to gas Page 8 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems group B or IIB + Hydrogen, provided that hydrogen supply line has a built in orifice or flow limiting device, an LEL detector is placed inside the upper region of the shelter atmosphere to detect any abnormal release, and the shelter is equipped with an auxiliary ventilation fan that automatically starts upon detection of LEL gas. 6.3 Equipment Certification Equipment used in a hazardous location shall be labeled, listed or certified as required by SAES-P-100. 6.4 6.5 Electrical Protection Design 6.4.1 All instrument enclosures and junction boxes shall be third party certified. Self-certification is not acceptable. 6.4.2 Enclosures for instruments and field junction boxes in outdoor plant areas shall be in compliance with SAES-J-902. 6.4.3 Intrinsically Safe Systems shall only be used where other methods of protection are impractical. Intrinsically Safe Systems when required shall meet the requirements for P&CSD review of the design, system certification, and installation listed in SAES-J-903. Equipment Purging The enclosures of analyzers containing sources of flammable gases or vapors shall be equipped with a Type Z pressurization system in accordance with NFPA 496. Purged analyzers shall be approved by one of the following certification bodies: UL, FM, CSA, CENELEC or IECEx. 6.6 6.7 Grounding 6.6.1 Analyzer shelters, analyzer cabinets, 3-sided sunshades, process analyzers, and ancillary analyzer equipment shall be grounded in accordance with SAES-P-111 and SAES-J-902. 6.6.2 Intrinsically Safe Systems shall be grounded in accordance with certification requirements and SAES-J-903. Power and Wiring Methods 6.7.1 Panelboards shall be selected, designed, and installed in accordance with 16-SAMSS-518 and SAES-P-116. 6.7.2 All on/off power switches shall be provided with lockout provisions or lockout hole for padlock installation. On/Off power switches shall be Page 9 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems provided for analyzers, lighting fixtures, and other ancillary equipment requiring power isolation. On/Off power switches shall be located next to the analyzer. 6.7.3 Analyzer power and service power supplies shall be designed and installed in accordance with SAES-P-104. Motors, motor control equipment, and panelboards shall be mounted outside the shelter or analyzer cabinet. 6.7.4 Instrument wiring systems shall be designed and installed in accordance with SAES-J-902. Commentary Note: SAES-J-902 does not apply to the internal wiring requirements for analyzers or analyzer accessories. 6.7.5 Analog and digital signal wiring shall terminate on external junction boxes located on the exterior wall of the analyzer shelter or analyzer cabinet. 6.7.6 Power supply wiring from the power panel to the analyzer shall terminate at the analyzer on/off power switch. 6.7.7 Separate enclosures shall be provided for analog, digital, and instrument power supplies. Wiring shall be segregated in accordance with SAES-J-902 and shall be clearly labeled. 6.7.8 Power cables, communication signals, signal wires, wiring, etc., entering analyzer shelters, or analyzer cabinets shall utilize a recessed bulkhead plate or multi-cable transit (MCT) system. 6.7.9 Conduit if used shall penetrate shelter or cabinet walls through recessed bulkhead plates and shall use a conduit seal fittings located immediately outside the shelter or cabinet bulkhead plate. Conduit seal fittings shall be sealed with sealing compound in accordance with SAES-J-902 Section 6 requirements. 6.7.10 Armored cables if used shall sealed with cables glands at the analyzer, panelboard, and signal junction box locations. Cable glands shall be installed in accordance with SAES-J-902 Section 6 requirements. 6.8 Communications Equipment Install all network communication devices associated with the analyzers (fiber optic hubs, fiber optic WIC boxes, Ethernet hubs, data net hubs, etc.) inside analyzer shelter or analyzer cabinet. Page 10 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 7 SAES-J-510 Process Analyzer Systems Sample Systems Sample conditioning systems shall be designed to deliver a representative sample at a temperature, pressure, flow, and dew point consistent with the analyzer manufacture requirements. The Analyzer System Integrator shall guarantee the performance of the sample conditioning system under normal, start up, and process upset conditions and as specified in relevant analyzer specification sheet. 7.1 Sample Taps and Sample Probes 7.1.1 Sample probes shall be used in process analyzer applications. Probes shall be installed in locations that provide representative samples from process streams. 7.1.2 Sample taps located on dead legs are not permitted. 7.1.3 The sample tap process isolation valve shall be located where the process time lapse is minimum under the conditions compatible with the operation of the analyzer. 7.1.4 The mechanical design and construction of the sample taps shall comply with process piping codes. 7.1.5 Sample probes shall only be installed on process lines with line diameters 101 mm (4 in) and above. 7.1.6 Flanged all welded sample probes shall be used for all processes containing hydrocarbons, sour and toxic components. 7.1.7 Retractable probes shall be shall not be used in hydrocarbon, sour, or toxic services. 7.1.8 Retractable probes may be used in applications such as furnaces, boilers, thermal oxidizers, flue stacks, tanks, continuous monitoring systems (CEMS), or process lines that vent to the atmosphere, operate at or near atmospheric pressure, or negative draft pressures. 7.1.9 Sample probes shall protrude into the process line approximately 30% from the pipe inner wall; unless natural and wake frequency calculations dictate shorter probe length or compliance or regulatory applications require specific probe lengths. 7.1.10 Natural frequency and wake frequency calculations shall be performed on all probes to determine maximum allowable length. Calculations shall be performed per ASME PTC 19.3-2010. Page 11 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 7.1.11 Sample probes shall be all welded and designed in accordance with the process pipe specifications and shall have the mechanical strength to avoid failure under normal or abnormal flow conditions. 7.1.12 All sample probe data shall be included in the analyzer specification sheet and probe drawings maintained in the appropriate database. 7.1.13 The sample point shall be located at least 3 pipe diameters downstream from any flow disturbance or 90 degree bends. Applications or processes that involve mixing stations; special consideration shall be taken to ensure the sample is representative. 7.1.14 Sample taps/fast loops may be installed across plant equipment or process pumps with relatively constant differential pressure. 7.1.15 Fast loops shall be designed based on 50% of the available differential pressure between sample point pressure and sample return pressure. 7.1.16 Sample tap and fast loop locations that are not permitted: Locations where there is a possibility of sample contamination. Locations where multi-phase sample may present. Locations where the flow is stagnant (dead legs). Across a control valve or an orifice plate. 7.1.17 Installation of sample tap at the bottom of process pipe line shall be avoided. Low point bleed shall not be used for sample tap. 7.1.18 For mixing reaction process applications; sample tap shall be located at the point where the chemical reaction is completed. 7.1.19 Sample taps shall be accessible from grade or permanent platforms for safe installation, maintenance, and isolation of process samples. 7.1.20 Sample taps shall be designed such that the bore size shall be the same as that of nozzle size. If the nozzle penetrates the pipe wall, it shall be set so that its end is in line with the pipe wall. This precaution reduces the accumulation of deposits that tends to build up at sharp edges in the sample path. 7.1.21 Sample tap/probe shall be fitted with a welded full bore isolation gate valve. The assembly shall be hydrostatically tested and certified to three times the operating pressure. 7.1.22 Sample probe shall be designed to minimize lag time. Probe sizing Page 12 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems shall consider sample lag time on the overall response, viscosity of the process sample, and particle size of the contaminants in the process sample. 7.1.23 Sufficient clearance and space shall be provided for maintenance of the sample probes. 7.1.24 Sample probes shall be marked to indicate the direction of flow with respect to the process flow. 7.1.25 Sample probes for special applications such as continuous emission monitoring system (CEMS) and sulfur recovery plant analyzer applications shall be designed in consultation with analyzer manufacturer as a complete package. 7.1.26 Sample lines, sample taps and sample return valves shall be clearly identified with the service and shall be tagged. 7.2 Sample Pre-Conditioning 7.2.1 Samples taken from the process may require pre-conditioning such as cooling, heating, vaporizing, pre-filtering, pressure reduction or pressure increase to meet the analyzer sample inlet condition requirements. 7.2.2 Depending on the application, the pre-conditioning system components shall be mounted on a 316 SS panel or enclosed in a 316 SS box, with all components accessible for maintenance. 7.2.3 The pre-conditioning system shall be installed at or as close as possible to the sample point. 7.2.4 All components in the pre-conditioning system shall be rated for the relevant process conditions. 7.2.5 Pressure reduction of gas or vapor samples shall be done in the sample pre-conditioning unit. 7.2.6 For vapor applications, a heated vaporizing pressure reducing regulator shall be required if condensation is expected upon pressure reduction. The vaporizer shall be heated above the maximum temperature at which the sample exists in vapor phase to maintain sample dew point temperature. 7.2.7 An electrically heated vaporizing pressure reducing regulators shall be used if the liquid sample has to be vaporized for analysis. Page 13 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 7.2.8 The sample line downstream of the pressure reducing regulator shall be electrically heat traced to maintain sample dew point. 7.2.9 A pressure gauge shall be installed directly downstream of the pressure regulator or pressure reducer. A proportional relief valve shall be installed at sample conditioning cabinet location. 7.2.10 The length of the sample line diameter from the sample probe to the sample pre-conditioning system shall be kept as minimum to reduce sample lag time. 7.2.11 For cryogenic services, the pre-conditioning cabinet shall be kept at a constant elevated temperature. 7.2.12 Pumps shall be avoided unless absolutely necessary. Unless otherwise specified, a pump shall be used only in the following situation: If the pressure at the sample point is too low or if the liquid sample may flash in the sample system. If an analyzer such as a physical properties analyzer requires liquid phase sampling and system pressure does not meet manufacture specification requirements. 7.2.13 Pump selection shall be based on the flow and pressure requirement of the analyzer and sample conditioning system. 7.3 Sample Lines 7.3.1 Length of sample lines shall be kept to a minimum and shall not exceed 100 m (328 ft). 7.3.2 Unless otherwise specified, overall sample lag time (from the sample probe to the analyzer inlet port) shall not exceed 90 seconds. 7.3.3 Pressure drop, bubblepoint, phase diagram, and lagtime calculations shall be performed on all liquid sample transport systems. 7.3.4 Dewpoint, phase diagram, and lagtime calculations shall be performed on all vapor sample transport systems. 7.3.5 Lagtime and pressure drop calculations shall be used to determine minimum sample transport tube diameter. 7.3.6 Two phase flow in the sample transport lines is not allowed. 7.3.7 For H2S, mercury, and moisture applications; sample transport tube Page 14 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems metallurgies (e.g., electro-polished/chemically passivated) for trace level measurements (ppb or ppm) shall be selected to prevent chemical reaction, adsorption and/or subsequent desorption effects between the process sample and the sample line transport tube. 7.3.8 Liquid or vapor phase samples shall be transported to the analyzer sample conditioning system using a continuous pre-insulated tube bundle. 7.3.9 Continuous pre-insulated/pre-traced tube bundles shall be used for applications that require heat tracing or cooling of process samples. 7.3.10 Pre-insulated electrical heat trace bundle shall be used for all process sample transport lines that require heat tracing to prevent condensation or require sample temperatures above its dewpoint. If the application requires steam tracing the same requirement applies. 7.3.11 Field fabricated heat trace bundles are not allowed. 7.3.12 Electronic heat trace controllers shall be used to monitor electric traced tube bundles. Controllers shall provide ground fault protection, current protection, and shall alarm on high or low temperature conditions. 7.3.13 Electrical heat tracing components shall meet the area classification of the area in which it is installed. 7.3.14 Pre-insulated steam trace tube bundle may be used for special applications that require high heat loads or when technically required by the analyzer manufacture. 7.3.15 Steam trace stainless steel tubes within the pre-insulated tube bundles shall have a minimum of ⅜ inch diameter. ¼ inch stainless steel or copper steam tracing tubes are not allowed. 7.3.16 Both ends of the pre-insulated sample bundle shall be sealed to prevent moisture intrusion. Bundle ends located in the field or sample points shall be sealed with heat shrink boots to provide weather proofing. Bundle ends located inside the sample conditioning enclosures shall be sealed with a black silicone sealant type. 7.3.17 Steam trace systems shall be equipped with a steam trap. 7.3.18 Sample dewpoint temperatures shall be at least 10 degrees higher than the highest possible dew point of the sample and shall be controlled within ±3 degrees of the required set point. Page 15 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 7.3.19 All sample transport lines (supply and return lines) shall be continuous (without splices) from the sample tap / return point in a pre-insulated tube bundle. Line splicing shall be avoided. 7.3.20 Pre-Insulated tube bundles shall use polyurethane jackets. Polyvinyl chloride (PVC) jacket material shall not be used. 7.3.21 All sample transport lines and tube bundles shall be installed in appropriate tray. 7.3.22 Pre-insulated sample bundles shall be installed and properly spaced in tray according to manufacture specifications. 7.3.23 Pre-Insulated sample bundles shall be fastened to trays using vinyl coated stainless steel straps. Use of nylon cable ties and non-coated straps is not allowed. Bundles shall be fastened to the tray every 1 m (3.3 ft). 7.3.24 Sample transport lines and sample bundles shall be installed and sloped for self-draining and with minimum low points to avoid liquid traps. 7.3.25 Single sample transport line systems shall be considered if suitable return point in the process is not available for simple analyzers. (i.e., pH, conductivity, and other water treatments analyzers). 7.3.26 If viscosity of the sample is more than 10 poise (1 Pa.s) at 30C (86°F), the size of the transport line shall be 1.0 inch minimum to avoid clogging. Highly viscous samples such as bitumen and asphalt typically require 2.0 inch sample lines. 7.3.27 Non-heated sample transport lines (supply and return) shall have a lockable shut-off isolation valves external to the sample condition system. Applications that are temperature sensitive or require heat tracing to maintain samples above its dewpoint shall have the shut-off isolation valves located inside the sample conditioning system enclosure to avoid cold spots. 7.4 Sample Conditioning Systems 7.4.1 The sample conditioning systems shall be designed and manufactured to supply the analyzer with a continuous/representative and measurable sample. It shall be designed in such a way that none of the process sample analytical properties are changed between sample extraction point and analyzer inlet and shall have no diurnal effect. 7.4.2 Sample conditioning systems designed by analyzer manufacturer shall Page 16 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems meet or exceed the requirements of this standard. Analyzer System Integrator shall take full responsibility for the performance of the complete analyzer system. 7.4.3 Sample conditioning systems shall be built for the application for which it is intended. Sample systems shall contain all the necessary metering and filtering devices needed for conditioning of a representative sample. 7.4.4 Sample conditioning system enclosures shall only be used for housing sample system components. Process analyzers and electronic sample chillers are not allowed to be installed in sample system enclosures. 7.4.5 All sample system components and elastomers shall be rated and compatible for the process conditions. All wetted parts shall be 316L SS minimum for general applications. 7.4.6 All components shall be installed on a 316 SS mounting plate and enclosed in a 316 SS enclosure. Exception: Simple analyzers that are designed for direct field installation; such analyzers and their measurement cells/probes shall be installed on a 316 stainless steel mounting plate and mounted on a prefabricated instrument pipe stanchion per Section 7.5. 7.4.7 Painted carbon steel or galvanized steel mounting plates and enclosures are not permitted. 7.4.8 The sample conditioning systems and fast loop systems shall be mounted on the outside walls of the analyzer shelter or analyzer cabinet in a back-to-back configuration with the associated analyzer. Exceptions: The only scenario where a sample conditioning systems is allowed inside the shelter or analyzer cabinet is when the analyzer is manufactured with built-in sample conditioning hardware. The analyzer must be certified as a complete (analyzer and sample conditioning) system and cannot be separated without voiding its certification. Examples of such analyzers with integrated sample conditioning systems are SRU tail gas analyzers, physical properties analyzers, FTNIR analyzers, etc. 7.4.9 All components shall be attached to the mounting plate in a manner that they can be maintained, serviced, or removed from the front side of the panel. Page 17 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 7.4.10 Sample system enclosures shall meet requirements of NEMA 4X or IP 66 to prevent dust/water ingress and corrosion. A caution warning plate shall be provided on the front door, if the box is heated. 7.4.11 Samples shall be transported to the analyzer sample conditioning cabinet using pre-insulated tubing through a fast loop system and shall be filtered with a self-cleaning filter technology. Sample slip streams shall be conditioned to meet analyzer vendor specification requirements. 7.4.12 All wet components installed in sour services applications shall comply with requirements defined in Section 16. 7.4.13 Exterior mounted sample conditioning systems containing toxic gas 10 ppm or above shall be continuously vented with instrument air. Effluent air from these systems shall be vented through an independent cabinet bottom vent tube and monitored by a toxic gas detector mounted next to the cabinet. The continuous vented air shall be metered with an adjustable flowmeter and air flow shall be kept to a minimum (cc/min) to allow heat retention within heated sample conditioning enclosure. The toxic gas monitor shall alarm locally at the shelter and shall be integrated into the plant gas detection system in accordance with SAES-J-505. 7.4.14 Materials of construction shall be chosen to prevent chemical reaction, adsorption and/or subsequent desorption effects between the process sample and sample conditioning system. 7.4.15 Sample system enclosures shall be constructed of 316 stainless steel. Galvanized steel is not allowed. 7.4.16 In corrosive applications wherever 316L stainless steel is not a suitable material; preference shall be given to materials such as Monel, Hastelloy or Incoloy. 7.4.17 Heated sample system enclosures shall be insulated for personnel protection and heat loss prevention. 7.4.18 Top entry sample system cabinet penetrations are not allowed. 7.4.19 Sample tubing, sample bundles, drain lines shall be installed and bent in a manner that they self-drain in a downward direction. Liquid traps shall be avoided. 7.4.20 Sample conditioning system enclosures shall be closed and sealed with a with 316 SS latch mechanisms. Page 18 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 7.4.21 All incoming and outgoing connections shall be permanently tagged or labeled. 7.4.22 All pressure, temperature, and flow components shall be provided with tags or labels showing the respective settings. 7.4.23 All identification tags and name plates shall be engraved 316 SS and shall be attached to the equipment securely with stainless steel or Monel fasteners. 7.4.24 The maximum height of sample conditioning system shall not exceed 1.8 m (6.0 ft) from grade. 7.4.25 Vapor and liquid sample systems shall be provided with hardware for introducing a calibration sample from outside the analyzer shelter or analyzer cabinet. 7.4.26 Liquid samples shall be returned to the process. If liquid samples cannot be returned directly to the process; then a liquid recovery system shall be used to collect liquid process samples. The recovery system shall have a collecting receiver with level-control, pump, and alarms. An overflow drain or feature shall be provided in case the pump or motor fails. 7.4.27 An adjustable proportional relief valve shall be installed downstream of the pressure reducing regulator in the sample conditioning cabinet. Based on the process pressure, the relief valve setting shall be 10% less than the pressure rating of the lowest rated device within the sample system. The relieved gas shall be vented to the flare line or sample recovery system. 7.4.28 If the process sample inlet temperature to the analyzer is required to be within specific limits, cooling or heating as appropriate shall be provided within the sample conditioning system. Fresh water from the main cooling systems shall be used. Sea water shall not be used as cooling medium. 7.4.29 If the cooling water temperature is too high or not suitable, cooling by means of a refrigeration chiller shall be considered. The refrigerated chiller shall have an electric motor with single phase power supply. 7.4.30 Tubing shall be installed and arranged so that the removal of one component does not require the dismantling of other parts. 7.4.31 Sample conditioning systems shall have facilities for flushing, venting and/or draining with vent and/or drain valve(s). The vent/drain outlets Page 19 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems shall be connected to a vent or drain system. 7.4.32 Dead volumes in the sample conditioning systems shall be kept to minimum. 7.4.33 Armored flow meters shall be used in all hydrocarbon services. 7.4.34 Glass components shall only be used for N2, O2, or instrument air service. 7.4.35 Glass components shall be rated for 2.0 times the maximum operating pressure of the related system. 7.4.36 Instrument air lines and pneumatic signal lines shall be 316 stainless steel tubing with compression fittings unless otherwise specified. 7.4.37 Pressure gauges for sample fluids shall have 2 in dial and provided with a ¼ inch NPTM threaded connection. Pressure gauges shall be positioned in the sampling system to avoid dead legs. 7.4.38 Pressure gauges shall be provided both upstream and downstream of primary filters. 7.4.39 Unless otherwise specified, electrical heaters shall be used for heating the sample conditioning enclosures. 7.4.40 A liquid recovery system shall be provided if process liquid sample and/or byproducts cannot be returned to process due to non-availability of low pressure return point. One common liquid recovery system can be designed to serve one analyzer house or a cluster of analyzers. A suitable common return point must be identified for each recovery system. 7.4.41 The instrument air and nitrogen supply lines shall be provided with all metal construction filtered regulators complete with pressure gauge and back flow protection. Nitrogen regulators shall be of the non-bleeding type. Plastic construction is not permitted. 7.4.42 Solenoid valves shall be used only for switching instrument air and nitrogen. Pneumatically operated valves in combination with a solenoid valve shall be selected for all other process fluids. Pneumatic actuator shall be provided with a direct coupled mechanical position indicator. 7.4.43 The insulation of sample conditioning system enclosures shall be in compliance with SAES-N-001. Page 20 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 7.4.44 Flow restrictors shall be installed on all lines entering the shelter or analyzer cabinet that contain flammable, toxic, asphyxiants, or hazardous materials that are directly connected to a high pressure (above 50 PSIG) source. Commentary Note: NFPA 496, 9.3.1.1 requires that orifices or other flow limiting devices be installed outside and close to the wall of the shelter on any potential source of uncontrolled leakage. Exception: Process streams that are prone to plugging (e.g., sulfur plant tail gas analysis) are exempt from the above requirement. Also, when the sample conditioning system is supplied as a “factory assembled” field proven package, the sampling system can be integrated inside the analyzer enclosure without flow restriction. 7.4.45 Sample systems containing highly toxic or flammable components shall include facilities for purging with an inert gas prior to maintenance of the sample system hardware. 7.5 8 Field Mounted Component Panels and Supports Stands 7.5.1 Simple analyzers and measurement probes as defined in Section 4 shall be mounted on a 316 SS panel and prefabricated pipe stand. 7.5.2 Analyzer transmitters, measurement cells, and probes shall be installed on panels for easy maintenance or replacement. 7.5.3 Prefabricated pipe stands shall be 2-inch schedule 40 pipe with a welded anchor plate base. 7.5.4 The top of the pipe stand shall be sealed to prevent sand or water entry. 7.5.5 Pipe stands shall be hot-dipped galvanized. Tubes and Tube Fittings 8.1 All tube fitting connectors shall be dual ferrule compression type and supplied by an approved supplier listed in SAES-J-002. 8.2 Unless otherwise specified, 316 stainless steel type tubing shall be used as a minimum for all process wetted parts downstream of the process sample isolation valve. 8.3 As a minimum, tubing shall be seamless type, annealed 316 stainless steel in accordance with ASTM A269. Page 21 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems Tubing minimum wall thickness shall be supplied per the Table below. Tube Outside Diameter Wall Thickness ½ inch 0.049 inch ⅜ inch 0.035 inch ¼ inch 0.035 inch ⅛ inch 0.028 inch 8.4 Aluminum or plastic tubing shall not be used as instrument tubing external to an analyzer. 8.5 Tubing shall be cut using tube cutters and shall be bent or formed using tube benders. 8.6 Tube fitting connections shall be made up according to manufacture specifications and shall be inspected for proper makeup using a gap gauge. 8.7 Tubing shall be installed in perforated tray and secured with stainless steel clamps. Perforated tray shall be within 150 mm (6 in) of the tube connection point. Tubing shall be secured in tray with stainless steel tubing clamps every 1 m (3.3 ft). 8.8 Instrument tubing shall be adequately supported and secured on tray or channel using clamps designed for and of the appropriate size for the tubing. 8.9 Pipe threaded or NPT connections 6 mm (½ inch) or smaller connections shall be pre-coated with Teflon tape. Anaerobic pipe thread sealant may only be used on threaded or NPT connections above 6 mm (½ inch). 8.10 Piping shall be designed, fabricated, and tested accordance with SAES-W-011 in addition to ASME B31.3. 8.11 Standard specification for seamless tubing shall be as specified in SAES-J-003. 8.12 Tubing and headers shall penetrate analyzer shelters and analyzer cabinets through a recessed bulkhead metal plate using bulkhead fittings. Holes drilled through wall panels is not allowed. 8.13 Pre-insulated sample bundles shall penetrate shelter or cabinet through a recessed bulkhead metal plate using a heat shrink entry seal assembly. 8.14 Tube unions in tray shall be installed with offset. Page 22 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 9 SAES-J-510 Process Analyzer Systems 8.15 Tube fittings in hydrocarbon and toxic service and vent lines shall be kept to a minimum to minimize leak sources. 8.16 Tube runs shall be installed in such a manner that it will not interfere with maintenance activities or obstruct space allocated for future analyzer installations. 8.17 All tubing and associated valves inside the shelter used for sampling, utilities (carrier gas, air, water, etc.) and venting shall be furnished and installed with, and terminated at, bulkhead fittings on the shelter bulkhead plates. Each bulkhead fitting shall be tagged. Stainless steel, letter-stamped nameplates, secured by stainless steel screws to the bulkhead plate, shall be used. Sample Recovery Systems 9.1 Process samples and/or analysis byproducts, liquids or gases shall not be discharged to atmosphere and shall be returned to process streams or flare where possible. 9.2 Sample recovery systems as defined in Section 7.4.40; if required shall be custom built for the intended service by the Analyzer System Integrator to meet the specific needs of the analyzer systems. 9.3 Sample recovery systems shall have a suitable collection system consisting of a level-control vessel or vessels with alarms and pump suitable for liquid samples. 9.4 A recovery system overflow drain shall be connected to a suitable drain system in the event that a pump or motor failure occurs. 9.5 Sample recovery system liquid vessels shall be pressure tested and certified for the intended service by a Third Party company. Self-certification is not allowed. 9.6 Sample recovery system vessels and piping shall meet the plants process pipe pecification requirements. 9.7 Process samples and/or analysis byproducts, both liquids and gases shall not be discharged to atmosphere and shall be returned to process streams or flare where possible. 9.8 Process gas samples shall be vented to the flare system. Gases or vapors which are returned to a flare system shall be routed to a header and shall have a check valve installed to avoid backflow. 9.9 Aqueous fluids from analyzers using reagents or titration chemicals shall be discharged into a plant containment system. Page 23 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 10 SAES-J-510 Process Analyzer Systems 3-Sided Shelter 10.1 Sunshade General Requirements 10.1.1 3-sided shelters shall be naturally ventilated. 10.1.2 The pre-engineered shelter shall be shipped with the analyzer and all ancillary equipment installed and tested before shipment. 10.1.3 Process analyzers placed under an outdoor 3-sided shelter shall meet the environmental conditions listed in SAES-J-003. 10.1.4 Analyzers designed and certified as field mountable analyzers; (e.g., field mounted gas chromatograph, BS&W analyzer, etc.) which dissipate heat or require direct sunlight protection to prevent possible electronic overheating may be installed under a 3-sided shelter. 10.1.5 Semi-Complex and Complex analyzer as defined in Section 4 shall not be installed under 3-sided shelters. 10.2 Sunshade Structural Design 10.2.1 Pre-fabricated shelter shall be built in accordance with 12-SAMSS-014, Pre-Engineered Metal Buildings for minimum design loads and design procedures. 10.2.2 In addition to the basic construction requirements defined in 12-SAMSS-014 above, the sunshade shall incorporate the following features: 10.2.2.1 Shelter walls shall be designed and installed to allow natural air draft ventilation. A 150 mm (6 in) opening at the top of the three walls is required with a 457 mm (18 in) open air bottom is required. 10.2.2.2 The side walls shall extend 1 m (3.3 ft) beyond the front edge of the analyzer enclosure. 10.2.2.3 The roof panel edges shall extend beyond the outer walls and front side (all four sides) approx. 305 mm (12 in). 10.2.2.4 The shelter shall be sized to allow adequate work space around the analyzer enclosure and sample conditioning system. A minimum of 0.6 m (24 in) spacing shall be available on either side of the analyzer enclosure (side wall to analyzer distance) for maintenance activities. Page 24 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 10.2.2.5 Lifting eyebolts shall be located on roof and attached to all four corners. 10.2.3.6 Sunshade designed with a roof and no side walls or back wall is not be permitted. 10.3 Sunshade Equipment Installation 10.3.1 Analyzers and sample conditioning systems installed under the sunshade shall be attached to the back wall on unistrut to allow airflow and heat dissipation. Direct wall mounting of equipment is not allowed. 10.3.2 Analyzers mounted on side walls is not allowed. 10.3.3 Signal junction boxes, power panel, and other analyzer ancillary equipment can be mounted under the sunshade on the side walls. 10.3.4 Carrier gas regulators, calibration gas regulators, and bottle gas racks shall be installed on the outer wall surface. 10.4 Sunshade Field Installation 10.4.1 Shelters located at grade shall be mounted on a concrete slab. The concrete slab shall extend 1 m (3.3 ft) beyond the outer walls and front side of the shelter. 10.4.2 Shelters shall be anchored in the field per vendor design. 10.4.3 Shelters shall be installed with the open side facing North or South to avoid direct sun light exposure on the analyzer from the East or West directions. 10.5 Sunshade Lighting and Power Outlets 10.5.1 Lighting and power outlet shall be provided under 3-sided shelters. 10.5.2 Light fixtures and switches shall be certified for Class I, Zone 2, Groups IIC, IIB, & IIA or as necessary depending on the materials being handled within the area. 10.5.3 A power outlet for the connection of test equipment shall be provided. Receptacles shall be suitable for operation in Class I, Zone 1, Groups IIC, IIB, & IIA or as necessary depending on the materials handled within the area. Page 25 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 11 SAES-J-510 Process Analyzer Systems Analyzer Cabinet Design 11.1 Cabinet General Requirements 11.1.1 Process analyzers placed inside analyzer cabinets shall meet the minimum environmental temperature requirements listed in SAES-J-003. 11.1.2 Cabinets shall be rainproof and dustproof and shall be designed to withstand the environmental conditions specified in SAES-A-112 Meteorological and Seismic Design Criteria. 11.1.3 Pre-engineered analyzer cabinets shall be shipped with the analyzer installed and all systems (air conditioner, auxiliary ventilation fan, purge systems, lighting, and power supply systems) in place and tested before shipment. 11.1.4 Analyzer cabinets shall only be used in analyzer applications that require installation on elevated platforms that have limited space, are in remote plant locations, or are in toxic service. 11.1.5 Complex analyzers as defined in Section 4 shall not be installed in analyzer cabinets. Complex analyzers shall only be installed in analyzer shelters. 11.1.6 Maintenance and repairs shall be performed on analyzer equipment while standing outside of the cabinet with the doors open. Analyzer cabinets shall not be designed for personnel entry. 11.1.7 Cabinet interior shall be large enough to allow adequate space for maintenance activities. 11.1.8 Analyzer cabinets shall provide environmental protection and climate control for only one single process analyzer and gas detectors. Multiple process analyzer installation in cabinets is not allowed. 11.1.9 Only the process analyzer and ancillary equipment associated with analyzer operation (e.g., HMI, control unit, etc.) shall be permitted inside the cabinet. 11.1.10 Wall mounted ventilator and louvers shall be made of corrosion resistant material. 11.1.11 The cabinet shall be insulated per 12-SAMSS-014. Page 26 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 11.2 SAES-J-510 Process Analyzer Systems Cabinet Structural Design 11.2.1 Pre-fabricated cabinets shall be built in accordance with 12-SAMSS-014, Pre-Engineered Metal Buildings for minimum design loads and design procedures. 11.2.2 Cabinet exterior dimensions shall not exceed 2 m (L) x 1.2 m (W) x 2.5 m (H) and shall have two front doors. 11.2.3 Analyzer cabinets shall be designed for a single analyzer installation with no extra analyzer slot for future expansion. 11.2.4 Cabinets external wall space shall be used to install air conditioner and all exterior ancillary equipment. 11.2.5 In addition to the basic construction requirements defined in 12-SAMSS-014 above, the cabinet shall incorporate the following features: 11.2.5.1 Doors shall open outwards and shall have steel frames. Doors shall be sized to permit the removal and installation of analyzer equipment. 11.2.5.2 Cabinet doors shall be equipped with locks and door stops. 11.2.5.3 One door shall be equipped with internal upper and lower slide bar latches and the main door shall have an external key lock/door handle mechanism. 11.2.5.4 Detachable sunshade covers 1 m (3.3 ft) long shall be provided on all four sides of the cabinet. 11.2.5.5 Cabinets shall have an integrated seal welded floor to prevent ingress of hydrocarbons. Use of silicone or other sealants is not allowed. 11.3 Cabinet Equipment Installation 11.3.1 Process analyzers in the cabinet systems shall be installed in such a manner that will allow airflow around the analyzer for maximum heat dissipation. Direct wall mounting of equipment with no air gap between the analyzer and wall is not allowed. 11.3.2 Analyzer equipment or ancillary equipment mounted on cabinet internal side walls is not allowed. Page 27 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 11.3.3 Analyzers mounted in cabinets (e.g., process analyzer, gas detectors, etc.) shall be as close as possible to the front door plane. The maximum allowable distance between the front plane of the process analyzer and the back side of the closed front doors shall not exceed 150 mm (6 in). All analyzers and gas detectors shall maintainable or repairable within arms’ reach; while standing on the outside of the cabinet. 11.3.4 The top elevation of the process analyzer shall not exceed 2 m (6 ft) in height while standing in front of the cabinet. 11.3.5 Electrical power panels, signal junction boxes, utility headers, calibrations cylinders, gas regulators, instrument air filters, air conditioner, etc., shall be mounted on the exterior walls of the cabinet. 11.3.6 Bulkhead plates 300 mm x 300 mm (12 in x 12 in) shall be placed at the top and bottom of the walls. 11.3.7 Tubing, sample lines, calibration gas, utility headers, etc., shall be penetrate cabinet walls through recessed bulkhead plates. 11.3.8 Flare header and atmospheric vent header piping shall be located outside the cabinet and installed below the sample conditioning system to allow condensables to drain downward. Headers shall have a low point drain valve. Cabinet flare headers and atmospheric vent headers installed above the sample conditioning systems is not allowed. 11.4 Cabinet Installation 11.4.1 A minimum walking space of 1.5 m (5 ft) shall be provided around all exterior cabinet sides. Commentary Note: The intent is to provide adequate working space around analyzer cabinets to facilitate routine maintenance (the movement of equipment around the cabinet, calibration cylinders, and working space for maintenance personnel) and to provide a clear path in the event of an emergency. 11.4.2 Cabinet applications that require to be as close as possible to the sample point (e.g., SRU Air Demand analyzer) due to low sample supply and return pressure shall be placed at an elevation higher than the sample point to allow the sample system to self-draining back to the sampling point. 11.4.3 Analyzer cabinets designed to handle flammable or toxic samples shall be installed in Class 1 Zone 2 areas. Page 28 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 11.4.4 Analyzer cabinets shall not be installed in Class 1, Zone 0 or Zone 1 areas. 11.4.5 Analyzer cabinets designed to handle non-flammable or non-toxic samples and are designed for general purpose use; such cabinets shall be installed only in non-hazardous areas. 11.4.6 Cabinets located at grade shall be mounted on a elevated concrete slab. The finished cabinet floor elevation shall be a minimum of 8 in above grade. 11.4.7 The concrete slab shall extend 1.5 m (5 ft) minimum beyond the front doors of the cabinet and the width of the slab shall be the same as the cabinet width. 11.4.8 Cabinets installed on elevated platforms or metal grading shall be installed at grading elevation. Grading underneath the cabinet shall be designed to support the weight of the cabinet system. 11.4.9 Cabinets shall be anchored to concrete slab or metal grading structure per vendor design. 11.5 Cabinet Ventilation and Air Conditioning Requirements 11.5.1 Cabinet installations shall be provided with a minimum of one air conditioner. If the analyzer is deemed critical and is specified as such or on-line analyzer availability requirements are mandated within the Saudi Aramco instrument specification sheet; such installation shall require two air conditioners. 11.5.2 Air conditioners shall be commercial grade and suitable for use in a Class 1, Zone 2 locations for the gas groups and temperature class appropriate to the analyzer application and hazardous area classification. 11.5.3 Air conditioning system shall maintain 24°C (75°F) internal air temperature (±5°F throughout the cabinet). 11.5.4 Analyzer cabinets are not designed for personnel entry; therefore, cabinet pressurization is not required. 11.5.5 Vortex coolers and thermal electric coolers shall not be used for cooling analyzer cabinet applications. 11.5.6 Air conditioner shall be window type unit. Page 29 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 11.5.7 Window type air conditioning units shall be removable from the outside mounting flange/bracket assembly for quick replacement or repair. Removal of air conditioner unit from the inner side of the cabinet is not allowed. 11.5.8 A temperature transmitter with local display shall be installed on the exterior side wall of the analyzer cabinet. An RTD sensor shall be installed internal to the cabinet. 11.5.9 Temperature transmitter shall alarm HIGH Internal Cabinet Temperature in the control room when cabinet internal temperature reaches within 20% of the analyzer maximum allowable ambient temperature limit. The transmitter shall alarm HIGH HIGH when the internal temperature reaches 5% of the analyzer maximum ambient temperature limit as defined by the analyzer equipment manufacturer specification. 11.5.10 Cabinets shall be provided with a wall mount auxiliary ventilation fan. 11.5.11 The auxiliary ventilation shall be powered from a non-ups power source. 11.5.12 The auxiliary ventilation fan shall be interlocked and energized to provide fresh air ventilation into the cabinet upon detection of a HIGH HIGH internal hydrocarbon or toxic gas or HIGH HIGH internal cabinet temperature. Exception: Analyzer cabinets installed in non-classified areas; auxiliary ventilation fans in such installations shall provide fresh air ventilation into the cabinet upon detection of HIGH HIGH internal cabinet temperature. 11.5.13 The external wall mounted auxiliary ventilation fan shall be sized to provide a minimum of 6 air changes per hour of fresh air. 11.5.14 The fresh air intake shall be provided with rain hood and bug screen. 11.5.15 Cabinet gas detection alarms and alarm management shall be provided by the plant DCS per SAES-J-505. 11.5.16 The auxiliary ventilation fan shall have a local Hand/Automatic control selector switch feature with pilot light. The pilot light shall be illuminated and visible from the front of the cabinet upon fan activation. 11.5.17 The auxiliary ventilation fan shall provide fresh air into the analyzer cabinet and out through a corrosion resistant barometric discharge louver. Page 30 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 11.5.18 Cabinet barometric louvers shall be placed at elevations and locations that maximizes the hydrocarbon dilution rate upon loss of hydrocarbon containment. 11.5.19 The auxiliary ventilation fan shall have a direct-drive motor. Belt driven fans are not allowed. 11.5.20 The auxiliary ventilation fan shall have a self-closing corrosion resistant back-draft louver. 11.5.21 Auxiliary ventilation and air conditioning fans shall be spark resistant. 11.6 Cabinet Lighting and Power Outlets 11.6.1 Lighting shall be provided inside analyzer cabinets, over the exterior door entrance underneath the front sunshade, and under the sunshade cover above exterior sample conditioning system. 11.6.2 Light fixtures and switches associated with the analyzer cabinet shall be certified for Class I, Zone 2, Groups IIC, IIB, & IIA or as necessary depending on the materials being handled within the area. 11.6.3 A power outlet for the connection of test equipment shall be provided on the external wall of the cabinet. The receptacle shall be suitable for operation in Class I, Zone 1, Groups IIC, IIB, & IIA or as necessary depending on the materials handled within the area. 12 Walk-In Analyzer Shelters 12.1 Shelter General Requirements 12.1.1 Pre-engineered shelters shall be shipped with analyzers installed and all systems (air conditioners, ventilators, purge systems, lighting and power supply systems) in place and tested before shipment. 12.1.2 Shelters shall be rainproof and dustproof and shall be designed to withstand the environmental conditions specified in SAES-A-112 Meteorological and Seismic Design Criteria. 12.1.3 Only analyzers and equipment associated with analyzer operation (e.g., analyzer HMI’s, analyzer control panels, etc.) shall be permitted inside the shelter. Furniture, tables, sinks, storage cabinets, etc., are not allowed in shelters. 12.1.4 Shelter interior shall be large enough to allow adequate access and space for maintenance and repair activities. Analyzers shall have a Page 31 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems maximum 600 mm (24 in) of free space on each side or between individual analyzers. 12.1.5 Where plant instrument air is not available (e.g., pipeline or remote facilities), the instrument air supply system if required, shall be provided with the analyzer system and shall either be installed in a separate shelter room or external to the analyzer shelter. 12.1.6 Detachable sunshade covers 1.2 m (4 ft) long shall be attached on the two longest sides of the shelter over the sample system cabinets. 12.1.7 Finished floor elevation shall be a minimum 8 in. above grade. 12.1.8 The shelter shall be insulated per 12-SAMSS-014. 12.1.9 Inert gas shall not be used for purging an analyzer shelter and shall only be used for enclosure purging when instrument air is not suitable. When inert gas is required to purge an enclosure within the analyzer shelter, an oxygen detector shall be provided inside the shelter. An alarm shall be initiated remotely at the DCS and a magenta colored beacon shall be activated outside the analyzer shelter over every door entrance and an internal and external audible horn shall activate when the oxygen level drops below the safe occupational exposure limit. Commentary Note: Instrument air is preferred for enclosure purging as leakage of inert gases used for purging or pressurizing of enclosures in an analyzer shelter can deplete the room's oxygen content. 12.2 Shelter Structural Design 12.2.1 Pre-fabricated shelters shall be skid-mounted and shall be supplied in accordance with Sections 5, 9, and 11 of 12-SAMSS-014, Pre-Engineered Metal Buildings for minimum design loads and design procedures. 12.2.2 Shelters shall be designed for multiple analyzer use and shall provide one extra analyzer slot with additional sample system slot on the outside wall of the shelter for future expansion. Exception: In cases where only one complex or semi complex analyzer needs to be installed in a walk-in analyzer shelter and there is no foreseeable analyzer expansion requirement; the shelter size may be sized for only one analyzer installation with no extra analyzer slot. Minimum size shelter for such application shall be 2.5 m x 2.5 m x 2.5 m with single door. Page 32 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 12.2.3 In addition to the basic construction requirements defined in 12-SAMSS-014, the shelter shall incorporate the following features: 12.2.3.1 Shelter doors shall open outwards, be self-closing, and shall have steel frames. Doors shall be sized to permit the removal and installation of equipment. 12.2.3.2 All shelters greater than 10 m² in size, shall have a minimum of two door exits, located at opposite ends of the shelter. 12.2.3.3 An inspection window shall be installed in each shelter door. Glass shall be laminated or tempered safety glass meeting the requirements of ANSI Z 97.1. The window shall not exceed 0.065 m2 (100 in2) in area. 12.2.3.4 All doors shall be equipped with quick-opening bars (panic bars) on the inside, which shall override exterior locks. 12.2.3.5 Roof or wall mounted ventilators and louvers shall be made of corrosion-resistant material. 12.2.3.6 Lifting holes in the skid shall be provided to permit a safe four-point lift to a minimum height of 6 m using spreader bars and a single hook. 12.2.3.7 Prefabricated shelters shall be provided with a slip resistant integrated floor. 12.2.3.8 The integrated floor shall be seal welded to prevent the ingress hydrocarbons. Use of silicone or other sealants is not allowed. 12.3 Shelter Equipment Installation 12.3.1 Analyzers shall be installed in such a manner that will allow airflow around the devices for heat dissipation. Direct wall mounting of equipment is not allowed. 12.3.2 Electrical power panels, signal junction boxes, and instrument air filters shall be mounted on the exterior walls of the shelter. 12.3.3 Bulkhead plates 300 mm x 300 mm (12 in x 12 in) shall be placed at the top and bottom of the walls. 12.3.4 Tubing, sample lines, calibration gas, utility headers, etc., shall penetrate shelter walls through a recessed bulkhead plates. Page 33 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 12.3.5 Shelter flare headers and atmospheric vent headers installed above the sample conditioning cabinets is not allowed. Flare headers, atmospheric vent headers, nitrogen headers, and steam headers shall be located outside the shelter and installed below the sample conditioning systems elevation. 12.4 Shelter Installation 12.4.1 A minimum walking space of 3 m (10 ft) from the exterior shelter walls shall be provided around all shelter sides. Commentary Note: The intent is to provide adequate working space around analyzer shelters to facilitate routine maintenance (the movement of equipment in and out of the shelter, storage of gas cylinders, and working space for maintenance personnel) and to provide a clear path in the event of an emergency. A minimum of 1 m distance from the analyzer shelter to structural steel columns is acceptable provided free access to sample conditioning systems and exit doors is available. 12.4.2 Analyzer shelters designed to handle flammable or toxic samples shall be installed in Class 1 Zone 2 areas. 12.4.3 Analyzer shelters shall not be installed in Class 1 Zone 0 or Zone 1 areas. 12.4.4 Analyzer shelters designed to handle non-flammable or non-toxic samples and are designed for general purpose use; such shelters shall be located only in non-classified areas. 12.5 Analyzer Shelter Ventilation and Air Conditioning Requirements 12.5.1 Shelters which are located in Class I, Zone 2 areas; the HVAC systems shall be designed to prevent the accumulation of flammable vapors or toxic gases. 12.5.2 Pressurization and HVAC systems for analyzer shelters shall comply with NFPA 496, Chapters 7 and 9. Commentary Note: Analyzer shelters are force ventilated to prevent hazardous gas or vapor from accumulating inside the shelter. The inside of an analyzer shelter presents special safety problems because hazardous vapor or gas is being introduced into an enclosed structure. An unventilated shelter is classified as a Class 1, Zone 1 area. It is normal practice in Saudi Aramco to ventilate analyzer shelters to maintain a Class 1, Zone 2 area. This is achieved by ensuring that the worst single contingency leak can Page 34 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems be diluted to less than 25% of its LEL or occupational hazard threshold limit value. This design philosophy is based on a single contingency failure. 12.5.3 Analyzer shelter HVAC’s shall be provided with a pressurization system that continuously ventilates the shelter with a flow of clean fresh air in accordance with NFPA 496. 12.5.4 HVAC’s shall be commercial grade units designed for use in hazardous areas. 12.5.5 HVAC systems shall maintain 24°C (75°F) indoor air temperature (±5°F throughout the shelter). 12.5.6 HVAC systems shall be fitted with a humidistat to control humidity levels within the shelter. 12.5.7 HVAC requirements for shelters shall be met by using two separate HVAC/air handler units (primary and standby) located at opposite ends of the shelter and an independent roof mounted auxiliary ventilation fan as backup. The cooling capacity of each HVAC shall be adequate to handle all cooling loads of the shelter. Commentary Note: Dual redundant HVAC/air handler units provide a completely independent backup to facilitate continuous operation of process analyzers when HVAC failure occurs or when maintenance is required. Roof mounting is required for the back-up auxiliary ventilation fan to allow a built-in escape path for any accumulation of lighter-than-air flammable gas concentrations during an extended ventilation failure and to provide a means to purge the shelter prior to starting the HVAC units. 12.5.8 Each HVAC unit shall be powered from different power sources to ensure redundancy. 12.5.9 Each HVAC shall have an individual switching device (power disconnect switch) intended to be used for electrical isolation. This switching device shall be equipped with a pad lockable lock-off device which will mechanically prevent the connection of the primary power to the HVAC when the padlock is installed and shall be located near each HVAC unit. Primary power for each HVAC unit shall be supplied from the substation breaker. 12.5.10 Each HVAC/air handler unit shall be capable of providing a minimum of 6 air changes per hour of fresh ventilation to dilute any release of flammable gas or vapor to a concentration less than 25% of the lower flammable limit. Page 35 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 12.5.11 One HVAC shall operate continuously with the other as standby. Auto changeover switches shall be provided between the operating and standby unit. These switches shall be capable of providing changeover and equal wear and tear between operating and standby unit. Standby unit shall auto-start upon loss of air flow from the primary unit. 12.5.12 Heat gain from introducing outside air into the shelter shall be included in the HVAC load calculation. 12.5.13 Ventilation fresh air make up shall be taken from a non-hazardous area. If this is not available, Class 1 Zone 2 air may be used if the equipment installed in the analyzer shelter is suitable for Zone 2 or worse location. 12.5.14 Corrosion resistant barometric weighted louvers shall be used to maintain the internal pressure at 25 Pa (0.1 inch W.C.). 12.5.15 Shelter barometric louvers shall be strategically placed at elevations and locations that maximize the hydrocarbon dilution rate upon loss of hydrocarbon containment. 12.5.16 Fresh air stack inlet shall include a rain shield and bug screen. 12.5.17 Dust filters shall be located in the fresh air ventilation air intake duct and HVAC air return. Filters shall be installed at an easily accessible location for cleaning or replacement. 12.5.18 Air flow shall ensure adequate cross ventilation and air discharge louvers shall be located at the top and bottom of the room to prevent the accumulation of vapor pockets. Commentary Note: Air flow shall capture flammable vapors as close as possible to the source, taking into account that vapors such as heavier-than-air hydrocarbon vapors shall be removed at floor level and lighter-than-air gases such as hydrogen and methane shall be removed at the ceiling. 12.5.19 The analyzer shelter shall be provided with an auxiliary ventilation fan/motor. The auxiliary ventilation fan shall provide a minimum of 6 fresh air changes in the event of an internal flammable/toxic gas leak or oxygen deficiency event. 12.5.20 The auxiliary ventilation shall be powered from a non-UPS power source. 12.5.21 The auxiliary ventilation fan fresh air stack intake shall be located Page 36 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 3 m (10 ft) above the shelter roof. The fresh air stack shall have a 3-point support system. 12.5.22 The fresh air intake shall be provided with rain hood and bug screen. 12.5.23 The auxiliary ventilation fan shall interlock and energize upon any HIGH HIGH alarm associated with flammable gas, toxic gas, or LOW oxygen deficiency. 12.5.24 The auxiliary ventilation fan shall have a direct-drive motor. Belt driven fans are not allowed. 12.5.25 The auxiliary ventilation fan shall have a self-closing corrosion resistant back-draft louver. 12.5.26 Roof mounted ventilation fan/blower shall be of a non-sparking construction and the drive motor shall be suitable for use in a Class 1, Zone 1 location for the gas groups appropriate to the analyzer applications. The roof mounted ventilation fan shall be capable of meeting dilution requirement of Section 7.3 [NFPA 496, 9.2.1(2)] and provide the pressurization via weighted louvers of Section 7.5 (NFPA 496, 7.4.1) with both of the HVAC systems out of service. Exception: Ventilation fans or purge blower motors that are located external to the air handling ductwork shall be suitable for the hazardous area where they are mounted. Commentary Notes: Air conditioners must be certified for the area in which they are installed. However, individual electrical components (ventilation fan motors, etc.) may be certified or the unit may be certified as a package. When hydrogen is introduced within the shelter as carrier gas, the ventilation fan motor does not have to be certified to gas group B or IIC provided the hydrogen supply line has an orifice restrictor outside the shelter. 12.5.27 Roof mounted auxiliary ventilation fan motor shall be equipped with a manual starter or a contactor type starter mounted on the exterior of the shelter. The auxiliary ventilation fan shall have a local manual / automatic control selector switch with a red pilot light indicator. The pilot lights shall be illuminated and visible at each exterior door entrance upon fan activation. Commentary Note: The requirement for an exterior mounted manual starter for the roof Page 37 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems mounted ventilation fan provides a way to purge the shelter of any combustible vapors that may have accumulated during an extended power outage prior to entering the shelter and starting the HVAC system. 12.5.28 Ventilation or HVAC air handling unit fans shall be fabricated with spark resistant construction. 12.5.29 A flow switch shall be provided within the air duct of each HVAC air handling unit to give a low-flow alarm in the control room (or other constantly attended location) and to initiate a white beacon mounted outside the analyzer shelter door upon low-flow condition (recommend 60% of design flow). The two flow switches shall be voted (2-out-of-2) to alarm only upon loss of air flow through both the primary and the standby HVAC systems. A time delay of up to 1 minute may be used to prevent spurious alarms. Flow switches shall be certified for a Class 1, Zone 1, Group IIC, IIB, & IIIA. Upon loss of air flow through both the primary and the standby HVAC systems, the roof-mounted auxiliary ventilation fan shall be automatically started. Upon loss of all shelter ventilation (HVAC and auxiliary fan), the roof mounted back-up fan shall be started first to purge the shelter prior to restarting the HVAC system. Commentary Note: Because the interior of the shelter is classified as Class I, Zone 2, all the equipment inside the shelter is suitable for use in a "limited release" environment (under normal operating conditions). Two failures are required to introduce a hazard inside the shelter (undetected pressurization failure for sufficient time for an explosive mixture to accumulate and a fault in the Class I, Zone 2 certified equipment). The design requirements are based on NFPA 496, 9.3.8 (3) that offers an exception to automatic shutdown upon loss of pressurization if the anticipated release is "limited" and the analyzer room is classified as Class I, Zone 2. 12.6 Shelter Lighting and Power Outlets 12.6.1 Lighting shall be provided inside analyzer shelters, over each exterior door entrance, and under the sunshade covers above exterior sample conditioning systems per SAES-P-123 requirements. 12.6.2 Light fixtures and switches associated with the shelter shall be certified for Class I, Zone 2, Groups IIC, IIB, & IIA or as necessary depending on the materials being handled within the area. 12.6.3 A power outlet for the connection of test equipment shall be provided inside the shelter. Receptacles shall be suitable for operation in Class I, Page 38 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems Zone 1, Groups IIC, IIB, & IIA or as necessary depending on the materials handled within the area. 13 Headers and Vents 13.1 Carrier gas, zero gas, steam, and instrument air purge headers shall be used whenever two or more analyzers share common services. An isolation valve shall be provided at each header take off point. All headers shall be provided with a minimum of two spare un-valved capped connections. 13.2 Instrument air headers shall slope to a low point drain. A drain valve shall be installed inside the shelter. The drain line shall be connected to a bulkhead fitting. 13.3 A wall mounted compressed instrument air membrane air dryer designed for analyzer shelters with built-in coalescing prefilter shall be installed on the exterior wall of the shelter or analyzer cabinet; upstream of the outer bulkhead plate fitting or analyzer systems. 13.4 The membrane air dryer/coalescing prefilter shall have an automatic drain feature, self-regenerate, and must output -20°C or lower dewpoint or shall meet the analyzer equipment manufacture specification requirements. 13.5 The membrane air dryer/coalescing prefilter shall be sized for output flow capacity based on the analyzers worst case consumption rates located within the shelter or analyzer cabinet. 13.6 The instrument air system shall have a built-in bypass system that allows air dryer/coalescing filter maintenance or replacement. 13.7 Analyzer slip-stream gas sample flows shall be vented to the flare header or back to the process line if liquid. 13.8 Analyzers requiring atmospheric reference vents (e.g., gas chromatographs) shall be connected to an external atmospheric vent header. 13.9 Atmospheric reference vents and carrier gas/column vents shall be led to a freely ventilated point more than 3 m above the shelter and more than 7.5 m from any ventilation air intake or ignition source. The area around the vent discharges should be classified Class 1, Zone 0 per SAES-B-068 Electrical Area Classification. 13.10 Atmospheric reference vent headers and carrier gas vent headers shall be provided with a low point drain with isolation valve and separate bulk head connections. Page 39 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 13.11 The functions and content of piping, tubing, and valves shall be clearly marked. 14 Calibration and Gas Cylinders Racks 14.1 Remote cylinder racks shall be used for storing carrier gases and calibration blends. Racks shall be located near the analyzer shelter or analyzer cabinet. 14.2 Low volume liquid or low pressure calibration cylinders that require close proximity to the sample conditioning system shall be located on the exterior wall of the shelter next to the sample conditioning cabinet. All other calibration cylinders shall be tubed up from a nearby cylinder rack to free up shelter wall space. 14.3 Remote cylinder racks shall have a sun shade cover to reduce direct sun light exposure. Sunshade roof shall provide 1 m (3.3 ft) of shade on each side of the rack from the center line of the rack. 14.4 If calibration cylinders require a temperature controlled environment; such system shall be provided by the Analyzer System Integrator. 14.5 Remote cylinder racks shall have approx. 30% additional space for spare cylinder storage. 14.6 Carrier gas and hydrogen gas cylinder manifold systems shall be designed so that the secondary or standby cylinder automatically supplies gas when the primary bottle is empty. 14.7 Carrier gas and hydrogen gas cylinder manifolds systems shall be designed to permit the removal of any cylinder without stopping the gas flow from the other remaining cylinder(s) in the manifold. 14.8 The manifold's maximum allowable working pressure shall exceed the pressure in the cylinders connected to it. 14.9 The vendor shall supply manifold piping or tubing, fittings, pressure gauges and pressure reducing regulators for each cylinder (primary and secondary) position. 14.10 Each cylinder storage position shall have a safety chain or safety bar to hold the cylinder in position. 14.11 Each GC shall have a dedicated carrier gas tubing header. Connecting multiple GC(s) on the same carrier gas header is not permitted. Commentary Note: If a carrier gas leak develops and multiple GCs are installed on the header it becomes difficult to determine which GC is the source of the leak. Page 40 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems 14.12 Cylinder gas manifolds shall incorporate discharge safety devices at the rack or external to the shelter or analyzer cabinet. 14.13 Calibration gas and carrier gas cylinders containing flammable gas shall not be closer than 7.5 m to pumps or other possible sources of ignition when possible. 15 Combustible Gas / Toxic Gas / Oxygen Detection 15.1 If a source of combustible or toxic gas is analyzed or present in the area, combustible gas and/or toxic gas monitors shall be installed in each analyzer shelter or analyzer cabinet in accordance with SAES-J-505. 15.2 Detectors shall be integrated into the plant wide gas detection system to provide alarm indication and alarm management. 15.3 Detectors shall be installed with fail-safe alarms. 15.4 Combustible gas and toxic gas monitors shall comply with 34-SAMSS-514 requirements. 15.5 Upon detecting combustible or toxic gas, low oxygen concentration, or monitor malfunction; the combustible gas, toxic gas, or oxygen deficiency monitors shall actuate both an alarm in the manned control room (or other constantly attended location) and local alarms. In addition, separate warning exterior light beacons and audible horns mounted outside the shelter or analyzer cabinet doors shall be provided. 15.6 Walk-In analyzer shelters shall be provided with a low decibel internal audible horn in addition to the external beacon and horn requirements. 15.7 Beacon colors shall be as follows: Blue beacon for high hydrogen sulfide Red beacon for combustible gas Magenta beacon for oxygen deficiency 15.6 Shelter auxiliary ventilation fan shall be interlock and energize upon any HIGH HIGH alarm associated with internal combustible or toxic gas detection or low oxygen deficiency detection. Shelter alarms and alarm management shall be provided by the plant DCS. 15.7 The analyzer cabinet auxiliary ventilation fan shall be interlocked and energized upon any HIGH HIGH alarm associated with internal combustible or toxic gas detection or HIGH HIGH internal cabinet temperature. Gas detection alarms and alarm management shall be provided by the plant DCS. Page 41 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems Commentary Note: Combustible and Toxic gas sensors should not be used to initiate automatic power isolation or to isolate the pressurization fans or air handling units. 15.8 Analyzer sample conditioning system enclosures utilized in toxic service shall be monitored by a toxic gas monitor and shall be integrated into the plant wide gas detection system to provide alarm indication and alarm management. 15.9 Combustible gas monitors shall be mounted on the inside walls of the analyzer shelter. 15.10 Analyzer shelters shall be provided with an oxygen deficiency monitor. 15.11 Beacons and audible alarms shall be located over each analyzer shelter door entrance or above the analyzer cabinet and shall be clearly visible from all directions. 15.12 Shelters and analyzer cabinets shall be provided with fail-safe hermetically sealed interposing relays. Interposing relays shall de-energize to activate beacons and audible alarms. 15.13 Outdoor audible alarms shall be audible both inside and outside the shelter with shelter doors closed. 15.14 Detector locations shall depend upon the relative densities of the hazardous substances being handled. It may be necessary to detect light gases near the roof level and heavy gases and vapors near the floor level. At least one sensor for every 14 m² of floor area shall be installed. 15.15 Detector logic system or control unit for alarm and alarm management shall be per SAES-J-505 requirements. 15.16 Detector setpoints and calibration ranges shall be set per SAES-J-505 requirements. 16 Sour Service Applications 16.1 All analyzer sample probes, sample isolation valves, pipe fittings, welded pipe connections, pressure reducing regulators, sample lines, etc., operating under sour gas and oil environments service shall utilize materials, alloys, fabrication techniques, and coatings as specified within NACE MR0175/ISO 15156. 16.2 Gas analyzers in sour service shall have their sample supply pressure reduced at the sample point location to a pressure below 65 psia. Page 42 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems Commentary Note: This could potentially allow the use of standard commercial materials downstream of the pressure reducing regulator depending on H2S concentration, H2S partial pressure, gas properties, corrosiveness, and application temperature. 17 18 16.3 The gas pressure setting must be supported by calculations or support documentation to ensure materials selected are suitable for the intended service. If such system cannot be supported by calculations or support documentation; then a conservative approach shall be taken with material selection downstream of the sample point pressure reducing regulator; such materials shall be selected per NACE recommendations. 16.4 Analyzer systems in sour service that require liquid phase sampling; such systems shall be installed or located as close as possible to the sample supply tap. 16.5 If it is not possible to install the liquid phase analyzer system close to the sample supply tap; then sample supply and return lines shall be extended to the analyzer system using continuous welded pipe. Such piping installations shall be kept to an absolute minimum distance and shall comply with NACE requirements. 16.6 Sample tubes, tube fittings, valves, and other sample system components used in sour service shall comply with NACE requirements. Inspection 17.1 Package systems shall be subject to random inspection by a Saudi Aramco Vendor Inspection Department representative. 17.2 The Package System Supplier shall furnish all facilities, utilities, and test equipment to accomplish factory acceptance tests. 17.3 Package systems shall be thoroughly inspected by a Saudi Aramco Vendor Inspection Department representative. Representative shall witness all packaged system tests and operation of all packaged systems as related to inspection forms. Packing/Shipping/Storage 18.1 Analyzer packaged systems shall be packaged or prepared for safe delivery to its final destination. 18.2 A suitable desiccant or silica gel shall be placed inside all electronic enclosures to protect electronics from humidity damage during shipment. 18.3 Special precaution shall be taken with fragile or sensitive equipment during Page 43 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems shipment; such equipment shall be packaged separately if deemed necessary. 19 18.4 All lines shall be cleaned and dried with clean air or nitrogen and shall be plugged or capped prior to shipment to prevent foreign material intrusion. 18.5 All valves shall be in closed position and flange connections shall covered with metal cover plates. 18.6 Equipment or items that may move, shift, or vibrate during shipment must be properly secured or supported to prevent damage during shipment. 18.7 All analyzer equipment or items shall be packaged or protected for extended period storage or at the jobsite site. Electronic analyzer equipment located inside analyzer shelters or analyzer cabinets that require humidity, moisture, or climate control shall have their HVAC systems temporarily powered during storage or placed in a climate controlled environment at the jobsite. Documentation 19.1 Shelter or analyzer cabinet layout drawings shall be provided by the analyzer shelter integrator and approved by the proponent organization. The drawings shall include a plan views of the entire shelter or cabinet with analyzer locations, doors locations, HVAC unit locations, and other ancillary equipment locations. 19.2 A set of documentation shall be prepared by the supplier for each sample conditioning system indicating the position of components on the mounting plate, interconnections and installation details as well as bill of materials for all materials associated with each system. 19.3 An engineering drawing for each analyzer indicating the complete schematic from sample point, preconditioning, sample line, sample conditioning, analyzer, vent/drain and return lines shall be provided. Information on stream switching valve operation, process conditions, line sizes, connections, and settings shall be included on the drawings. 19.4 Analyzer Manufacturer/Analyzer System Integrator shall supply procedures for start-up, shutdown, operation, and maintenance of the sample conditioning systems. 19.5 Hardcopy documents shall be compiled into a binder complete with cover sheet, index sheet, bill of materials, technical information, engineering drawings, and test certificates. Electronic copy of the same documents arranged in similar arrangement shall be provided in electronic format. 19.6 Analyzer Manufacturer/Analyzer System Integrator shall submit the compiled drawings for review and approval from proponent before start of manufacturing Page 44 of 45 Document Responsibility: Instrumentation Standards Committee Issue Date: 1 January 2018 Next Planned Update: 15 September 2019 SAES-J-510 Process Analyzer Systems of sample handling systems. 19.7 As-built drawings shall be submitted in hard copy and electronic copy, minimum three copies each to Saudi Aramco. 19.8 All process analyzers shall be provided with the manufactures technical manuals and electronic circuit drawings. Revision Summary 15 September 2016 1 January 2018 New Saudi Aramco Engineering Standard that defines the minimum mandatory requirements governing the design, installation, and safety of process analyzer equipment. Editorial revision to delete paragraph 7.4.43. Page 45 of 45