© ABB Group - 1 2-Jul-18 Protection Application Handbook Autoreclosing © ABB Group - 2 2-Jul-18 Autoreclosing Autoreclosing Auto reclosing Cycle OH-lines High fault-rate (80-90%) Fast simultaneous © ABB Group - 3 2-Jul-18 Fault clearing Autoreclosing AUTORECLOSING CYCLE OH-lines Intermittent faults (80-90%) Successful AR-rate : © ABB Group - 4 2-Jul-18 High (80-90%) Autoreclosing Auto reclosing principles 95% of faults are transient type 3 Ph autoreclosing synchrocheck is used 1 Ph autoreclosing needs identification of faulty phase © ABB Group - 5 2-Jul-18 Helps verify phase angles are not out of phase e.g: due to heavy power swing Phase identification is difficult for high resistance faults Autoreclosing © ABB Group - 6 2-Jul-18 Auto reclosing principles Autoreclosing Autoreclosure in a Line bay © ABB Group - 7 2-Jul-18 AR- Autorecloser BFR- Breaker failure relay COM- Communication COND-CB condition DLC SC-Dead line check and synchronism check LP- Line protection MAN- Manual CB control PD- Pole discordance relay Autoreclosing Auto reclosing principles © ABB Group - 8 2-Jul-18 Protections that start autoreclosing Main 1 protection Main 2 protection Protections that block autoreclosing CB fail detected by Breaker fail relay & Pole discrepancy relay CB not ready Delayed tripping ( Zone2 or3 of distance relay , Back up relay) Manual CB operation Communication fail Direct transfer trip receive , BB protection , O/V protection, Reactor protection Autoreclosing Contact position Circuit-breaker Contact Travel t6 t2 Closed Time Open © ABB Group - 9 2-Jul-18 t1 t3 Closed t4 t5 Autoreclosing Dead time for Automatic Reclosing Equipment A B F Contact position t © ABB Group - 10 2-Jul-18 t 1A t t2A 6A Closed Open t 1B t 2B A Dead time Open Closed t 6B B Interruption time 0 Time Autoreclosing Single-pole Reclosing Single-Pole Reclosing © ABB Group - 11 2-Jul-18 A B C A B C Autoreclosing Temporal Description of Automatic Reclosing HSR = High-Speed Automatic Reclosing DR = Delayed Automatic Reclosing R = Automatic Reclosing SR = Slow Automatic Reclosing DR HSR R SR © ABB Group - 12 2-Jul-18 TD 0.1 1 3 10 100 s Autoreclosing Classical Three-pole Reclosing A t F 1A t2A Contact position © ABB Group - 13 2-Jul-18 t B Dead time Closed Open A t 6A Interruption time t 0 t2B 1B Closed Open t B 6B Time Autoreclosing © ABB Group - 14 2-Jul-18 Factors affecting extinction of Primary Arc Fault current magnitude Fault clearance time Coupling from energized conductors Closing or opening of resistors Magnitude of reenergizing voltage Point of wave for reenergizing Magnetic forces on the fault current Length of insulating string Weather conditions Shape of grading ring Autoreclosing Minimum Dead Time (IEEE) System Voltage kV © ABB Group - 15 2-Jul-18 23 46 69 115 132 230 345 400 500 Minimum deionization time [ms] Based on Field and Based on Operating Laboratory Tests Experience 110 120 130 150 160 210 260 280 330 180 200 210 230 240 280 340 370 420 Autoreclosing Minimum Dead Time for Three-pole Reclosing Minimum Dead Time Three-Pole Reclosing ms 500 400 Based on Operating Experience 300 200 © ABB Group - 16 2-Jul-18 100 Based on Field and Laboratory Tests 100 200 300 400 500 System Voltage 600 kV Autoreclosing Double Fault on a Double-circuit Line A B C A B C L1 R L © ABB Group - 17 2-Jul-18 L2 Autoreclosing Capacitive Coupling and Single-pole Tripping A B C C C p p C A B C p L R © ABB Group - 18 2-Jul-18 Ce Ce Ce Autoreclosing Secondary arc © ABB Group - 19 2-Jul-18 Secondary arc is phasor sum of currents maintained by capacitive and inductive coupling from the energised phase conductors Autoreclosing Critical Line Lengths for Single-pole Reclosing System Voltage kV © ABB Group - 20 2-Jul-18 230 345 500 765 Critical Line Length [miles] Successful Range Doubtful Range 0-300 0-140 0-60 0-50 300-500 140-260 60-100 50-80 Autoreclosing © ABB Group - 21 2-Jul-18 Artificial extinction of secondary arc Where high-speed automatic reclosing is to be implemented, secondary arcs must be artificially extinguished since they would otherwise last too long. There are several methods to extinguish artificially the secondary arc: Fixed Four-Reactor Scheme Switched Four-Reactor Scheme High speed Earthing Switch Scheme Autoreclosing Fixed Four-reactor Scheme ABC ABC L R Lp Lp Lp © ABB Group - 22 2-Jul-18 Ln Autoreclosing Secondary Arcing Time (Haubrich) Secondary Arcing Time s T sa Haubrich 1971 2.0 1.5 1.0 0.5 © ABB Group - 23 2-Jul-18 Is 50 100 150 A © ABB Group - 24 2-Jul-18 Autoreclosing Autoreclosing © ABB Group - 25 2-Jul-18 Auto reclosing in one and a half breaker system Autoreclosing © ABB Group - 26 2-Jul-18 Auto reclosing in one and a half breaker system Autoreclosing © ABB Group - 27 2-Jul-18 Special problems Memory Circuit Priority circuit Autoreclosure out of service © ABB Group - 28 2-Jul-18 Autoreclosing Autoreclosing Synchronism and Energizing check UBus ULine UBus FreqDiff < 50-300 mHz o PhaseDiff < 5-75 UDiff < 5-50% Ur UHigh > 50-120% Ur U Bus 1-ph U Line 3-ph (or 1-ph) ULow < 10-100% Ur © ABB Group - 29 2-Jul-18 SYNC-BLOCK Fuse fail ULine Autoreclosing © ABB Group - 30 2-Jul-18 DLC and SC at Auto reclosing © ABB Group - 31 2-Jul-18 CBIP manual on Protection of Generators, generator transformers and 220kV and 400 kV networks Auto Reclosing Autoreclosing 1.0 GENERAL • The auto-reclosing of power lines has become a generally accepted practice. • Reports from different parts of the world show that in certain networks in region subject to a high lightening intensity only about 5% of the faults are permanent. • Auto reclosing therefore provides significant advantages. • Outage times will be short compared to where station personnel have to re-energize the lines after a fault. © ABB Group - 32 2-Jul-18 • In interconnected networks auto-reclosing helps in maintaining system stability Autoreclosing 1.1 Recommendations for provisions of auto-reclosing • Presently 1 phase high speed auto-reclosure (HSAR) at 400kV and 220kV level is widely practised including on lines emanating from Generating Stations and the same is recommended for adoption. © ABB Group - 33 2-Jul-18 • If 3-phase auto-reclosure is adopted in future the application of the same on lines emanating from generating stations should be studied and decision taken on case to case basis. Autoreclosing 2.0 SETTING CRITERIA 2.1 Dead Time • Auto- reclosing requires a dead time which exceeds the de-ionising time • Time required for the de-ionising of the fault path depends on:- arcing time, fault duration, wind conditions, circuit voltage, capacitive coupling to adjacent conductors, etc. © ABB Group - 34 2-Jul-18 • Single phase dead time of 1.0 sec is recommended for both 400kV and 220kV system. Autoreclosing 2.2 Reclaim Time • The time during which a new start of the auto-reclosing equipment is blocked. • If reclosing shot has been carried out and the line is energized and a new fault occurs before the reclaim time has elapsed, the auto-reclosing equipment is blocked and a signal for definite tripping of the breaker is obtained. © ABB Group - 35 2-Jul-18 • After the reclaim time has elapsed, the auto-reclosing equipment returns to the starting position and a new reclosing sequence can occur. • The reclaim time must not be set to such a low value that the intended operating cycle of the breaker is exceeded, when two faults incidents occur close together. Autoreclosing • If the breaker is closed manually, the auto reclosing equipment is blocked and cannot start again until the reclaim time has elapsed. © ABB Group - 36 2-Jul-18 • For the breaker to be used for auto-reclosing, it is essential that it has the operating mechanism and breaking capacity necessary for it to be able to perform the auto-reclosing sequences required. Autoreclosing 2.3 Circuit Breaker Requirement • According to IEC Publication 56.2, a breaker must be capable of withstanding the following operating cycle with full rated breaking current: O + 0.3 s + CO + 3 min + CO • The recommended operating cycle at 400kV and 220kV is as per the IEC standard. © ABB Group - 37 2-Jul-18 • Reclaim time of 25 sec is recommended. © ABB Group - 38 2-Jul-18 Autoreclosing