Uploaded by Danny Sojo

ATLAS-COPCO-PV-351

advertisement
SYSTEM SPECIFICATION SHEET
VEHICLE OVERVIEW
ATLAS COPCO
PV-351
Blasthole Drill
WEIGHT:
415000 lb (188241 kg)
CAPACITY:
16 in (406 mm)
ENGINE(S):
CAT 3512
1
1650 hp (1230 kW)
DIESEL:
HYDRAULIC:
RECOMMENDED AFEX SYSTEM CONFIGURATION
ENGINE
Tier IV
Tier II / Tier III
DRY CHEMICAL
2x125 lb.
+ LIQUID AGENT
1x15 gal. + 1x5 gal.
ADDITIONAL HARDWARE RECOMMENDATIONS:
Fire sleeve for hoses in protected area
2 remote actuator(s)
2 portable extinguisher(s)
NOTE:
Dual agent systems combine the fast knockdown properties of A:B:C dry chemical powder with the suppression and cooling properties of the AFEX
liquid agent for greater effectiveness and to reduce the chance of fire reflash.
SYSTEM FEATURES:
CONTROL UNIT
FIRING MECHANISM
REMOTE ACTUATOR
ENGINE SHUTDOWN
Satisfies NFPA 17, Chapter 5.7.2.1: Supervision of electrically or pneumatically operated automatic systems
shall be provided unless specifically waived by the authority having jurisdiction.
Satisfies NFPA 17, Chapter 9.9.7: At least one easily accessible manual actuator or operating device shall
be provided for use by the equipment operator.
Satisfies NFPA 17, Chapter 9.9.8: An additional manual actuator or operating device shall be located so that
it is in the path of egress and operable from ground level.
Satisfies NFPA 17, Chapter 5.5.2: Where systems protect hazards that have flowing flammable or
combustible fluids or gases, the systems shall be provided with automatic means to ensure shutoff of power
and fuel valves upon operation of the extinguishing systems.
INSTALLATION CONSIDERATIONS:
The guidelines below are minimum recommendations. The system may include additional nozzles or sensors that should be used to address additional fire risks
that are identified in the fire risk assessment. Linear wire may also be used for detection. Special attention should be paid to certain hazard areas such as, but not
limited to, turbochargers, exhausts, hydraulic connections to pumps, valves and tanks, transmissions, starters, alternators, and additional fuel and heat sources.
DRY DISTRIBUTION
TOTAL DRY NOZZLES:
engine
24
hydraulics
12
boom
6
42
LIQUID DISTRIBUTION
TOTAL LIQUID NOZZLES:
engine
6
hydraulics
2
boom
2
10
(if recommended above)
DETECTION
TOTAL SENSORS:
10
engine
6
hydraulics
2
high pressure hydraulics near boom
2
NOTE:
Liquid nozzles should be aimed at the turbos, after treatment, and other hot engine components. Additional liquid nozzles should be aimed at the high
pressure hydraulic component connections around the boom.
Dry powder nozzles should be aimed to locally apply powder across the surfaces of protected components. These include the engine, power take off
(PTO), pumps, hydraulic connections to compressor, hydraulic motors, hydraulic cylinders, and high pressure hydraulic lines, especially at their
connection points. Components protected with liquid nozzles do not need dry powder locally applied on the same surface area.
Revised 6/13/2014
This information is only a guideline and does not provide definitive rules or specifications. Due to variations in vehicle models and accessories, the actual installation may vary from that listed above. All installations
should include a detailed fire risk analysis as described by NFPA 122 and the AFEX service manual.
The purpose of a fire suppression system is to mitigate fire damage to the equipment. The system cannot be designed or expected to extinguish all fires. As with all mechanical equipment, AFEX Fire Suppression
Systems require regular maintenance to assure they will operate safely and effectively.
In accordance with the manufacturers’ or designers’ recommended inspection and maintenance procedures and schedules, all fire suppression systems, including alarms, shutdowns, and other associated
equipment, shall be thoroughly examined and checked for proper operation by competent personnel. (NFPA 122)
Download