Three-Phase Transformers Three Phase Transformers • Large scale generation of electric power is usually 3 phase at 11 kV or higher. • But transmission voltage is 110 kV, 132 kV and 400 kV. • Generated voltage needs to be increased. • Hence 3 phase transformers are used. • 3 single phase transformers can be used to construct a 3 phase transformer. • But it occupies more space and 15% more costlier than using a single unit. Three Phase Transformer Three phase transformer can be constructed in two way: 1) To take three single-phase transformers and connect them in a three phase bank. 2) To make a three phase transformer consisting of three sets of windings wrapped on a common core. Advantages: Lighter, smaller, cheaper and slightly more efficient Three single transformer banked composed of independent transformers Three phase transformer wound on a single three legged core Three Phase Transformers Three Phase Transformer Connections • Star / Star (Y – Y) • Delta / Delta (Δ – Δ) • Star / Delta(Y – Δ) • Delta / Star (V – Y) Star / Star (Y/Y) Connection • It is also called zero degree connection. ππβ = ππΏ πππ πΌπΏ = πΌπβ 3 • Hence number of turns / phase and the amount of insulation required is minimum. • This connection is economical for small rating high voltage transformers. • It works well for balanced load. Delta / Delta (Δ/Δ) Connection • It is also called zero degree connection. ππΏ = ππβ and πΌπβ = πΌπΏ 3 • Hence number of turns / phase required is more. • This connection is economical for large rating low voltage transformers. • This connection is satisfactory for both balanced and unbalanced loads. • But neutral unavailable. Star / Delta (Y/Δ) Connection • On primary side, ππβ = ππΏ 3 • On secondary side, ππΏ = ππβ πππ πΌπΏ = πΌπβ and πΌπβ = πππ ππΏπ = πππ ππΏπΰ΅ =πΎ 3 ππΏπ 1 = πΎ ππΏπ 3 πΌπΏ 3 Delta / Star (Δ /Y) Connection • On primary side, ππΏ = ππβ and πΌπβ = πΌπΏ 3 • On secondary side, ππβ = ππΏ 3 πππ = πππ πππ ππΏπ ΰ΅ ππΏπ πΌπΏ = πΌπβ 3 =πΎ ππΏπ = 3πΎ ππΏπ Tap Changing Transformers • Voltage variation in power system is a normal phenomenon due to rapid growth of industries and distribution network. • Therefore system voltage control is essential for: β Adjustment of consumer’s terminal voltage within prescribed limits. β Control of real and reactive power flow in the network. • Turns ratio of the transformer is varied for achieving tap changing. Off Load Tap Changing • It is required to de-energise the transformer before changing the tap. On Load Tap Changing • Tap changing is done while transformer is delivering load. • The operating efficiency of electrical system is improved. • It is fitted with almost all power transformers.