Wiring Methods and Materials Conductors are substances or materials used to convey or allow the flow of electric current Conductors shall be insulated Conductors Wires o are those electrical conductors 8mm2 (AWG No. 8) and smaller in sizes. Cables o are those larger than wires Wires and Cables are either: o Stranded Wire o Solid Wire Conductors Stranded Wires oconsist of a group of wires twisted to form a metallic string o the circular mil area of a stranded wire is found by multiplying the circular mil area of each strand by the total number of the strand Mil- the word mil is equal to 1/1000 of an inch was used to describe or measure a round wire diameter conductors of size 8mm2 and larger shall be stranded Different Types of Cables o Armored Cable: Type AC is a fabricated assembly of insulated conductors enclosed in flexible metal sheath. used on oBoth exposed and concealed work oCable trays oDry locations oEmbedded in plaster finish on brick or other masonry, except in damp or wet locations o run or fished in the air voids of masonry block or tile walls where such walls are not exposed to excessive moisture or dampness. Different Types of Cables oFlat Conductor Cable: Type FCC consist of three or more flat copper conductor placed edge to edge separated and enclosed within an insulating assembly used in o Branch circuits o hard smooth continuous floor surfaces Different Types of Cables o Integrated Gas Spacer Cable: Type IGS A factory of one or more conductors, each individually insulated and enclosed in a loose fit, nonmetallic flexible conduit as an integrated gas spacer cable rated through 0 to 600V. Use in o Service entrance conductors o Feeder or branch circuit conductor Different Types of Cables o Metal-Clad Cable: Type MC A factory assembly of one or more insulated circuit conductors with or without optical fiber members enclosed in an armor of interlocking metal tape , or a smooth or corrugated metallic sheath. used for o services, feeders, and branch circuits o power, lighting control, and signal circuits oIndoors or outdoors oExposed or concealed o any raceway o as aerial cable on a messenger o in hazardous locations as permitted Different Types of Cables o Medium Voltage Cable: Type MV A single or multi-conductor solid dielectric insulated cable rated 2001V or higher. used in o wet or dry locations o Raceways o In messenger supported wiring Different Types of Cables oMineral Insulated Cable: Type MI Is a factory assembly of one or more conductors insulated with a highly compressed refractory mineral insulation enclosed in a liquid and gas tight continuous copper sheath. used in o dry, wet, or continuously moist location o As service feeders or branch circuits Different Types of Cables oNon-metallic Sheathed Cable: Type NM is also a factory assembly of two or more insulated conductors having moisture resistant, flame retardant, and non-metallic material outer sheath. Used for o one or two family dwellings not exceeding 3 storey buildings Different Types of Cables oShielded Non-metallic Sheathed Cable: Type SNM This type of cable is a factory assembly of two or more insulated conductors in an extruded core of moisture resistant and flame retardant material covered within an overlapping spiral metal tape. used in o hazardous locations o Cable trays o raceways Different Types of Cables o Underground Feeder and Branch Circuit Cable: Type (UF) Is a moisture resistant cable used for underground connections including direct burial in the ground as feeder or branch circuit. o Service Entrance Cables: Type SE and USE A single or multi-conductor assembly provided with or without an overall covering primarily used for service wire. Table 3.10.1.5 Minimum Size of Conductors Minimum Conductor Size mm2 (mm dia.) Conductor Voltage Rating (Volts) 0-2000 2001-8000 8001-15000 15001-28000 28001-35000 Copper 2.0(1.6) 8.0(3.2) 30 38 50 Aluminum ore Copper- Clad Aluminum 3.5(2.0) 8.0(3.2) 30 38 50 Insulated Conductors and Cables oLocations Dry and Damp Locations FEP RHW THHW XHH FEPB RHW-2 THHW-2 XHHW-2 MTW SA THWN Z PFA THHN THWN-2 ZW RHH THW-2 TW Insulated Conductors and Cables oLocations Wet Locations - Moisture impervious metal-sheated - types MTW, RHW, RHW-2, TW,THW, THW2, THHW, THHW-2, THWN, THWN-2, XHHW, XHHW-2, ZW - Of a type listed for use in wet locations Insulated Conductors and Cables oLocations Exposed to Direct Sunlight - sunlight resistant cables - sunlight resistant conductors - covered with insulating materials such as tape or sleeving, that is listed, or listed or marked as being sunlight resistant. Conductors of the same circuit shall be contained in the same: o raceway oAuxiliary gutter oCable tray ocable bus assembly oTrench o cable or cord Marking All conductors and Cables shall be marked to indicate the following information: oThe maximum rated voltage oThe proper type letter or letters for the type of wire or cable oThe manufacturers name, trademark, or other distinctive marking by which the organization responsible for the product can be readily identified oThe size in millimeter square or millimeter diameter oCable assemblies where the neutral conductor is smaller than the ungrounded shall be so marked. Protection Against Corrosion and Deterioration oRaceways ocable trays oCable bus oauxiliary gutters ocable armor oBoxes o o o o o o o Cabinets Elbows Couplings Fittings Support Support hardware Cable sheathing Shall be materials suitable for the environment in which they are to be installed. Protection Against Corrosion and Deterioration oFerrous Metal Equipment shall be protected by a coating of corrosion resistant material. listed EXEPTION: stainless steel shall not be required to have protective coatings Protection Against Corrosion and Deterioration oProtected from Corrosion Solely by Enamel shall not be used outdoors or in wet locations oOrganic Coatings on Boxes or Cabinets marked with “Raintight,” “Rainproof,” Type” shall be permitted outdoors or “Outdoor Protection Against Corrosion and Deterioration o Non-Ferrous Metal Equipment shall be provided with supplementary protection. o Nonmetallic Equipment Exposed to Sunlight shall be listed as sunlight resistant Chemical Exposure shall either be inherently resistant to chemicals corrosion Protection Against Corrosion and Deterioration oIndoor Wet Locations the entire wiring system, where installed exposed, including all boxes fittings, raceways, and cable used therewith shall be mounted so that there is at least a 6 mm airspace between it and the wall or supporting surface Raceways -------are channels or wiring accessories so designed for holding wires, cables, or busbars that are either made of metal, plastic, or any insulating mediums. Common Types of Raceways o Conduits o Connectors and Other Accessories Other Types of Raceways oConduit coupling, elbows, and other fittings oConduit supports, such as clamps, hanger, etc. oCable trays, cable bus, etc. oMetal Raceways oNonmetal Raceways and other Raceways To a Different Temperatures oSealing shall be filled with an approved material to prevent the circulation of warm air to a colder section of the raceway or sleeve An explosion proof seal shall not be required for this purpose. Raceways To a Different Temperatures oExpansion Fittings Raceways shall be provided with expansion fittings where necessary to compensate for thermal expansion and contraction . Raceway Installations oComplete Runs exposed raceways having hinged or removable covers, shall be installed complete between outlet, Junction Splicing points Prior to the installation of conductors Raceway Installations oWelding Metal Raceways shall not be supported, terminated, or connected by welding to the raceway unless specifically designed to be or otherwise permitted to be in this code. Installations of Conductors with Other Systems oRaceways or cable trays containing electric conductors shall not contain any pipe, tube, or equal for steam, water, air, gas, drainage, or any other services other than electrical. Induced currents in Metal Enclosures or Metal Raceways oConductors Grouped Together --to avoid heating the surrounding metal by induction oIndividual Conductors inductive effect shall be minimized by cutting slots in the metal between the individual holes through which the individual conductors pass Passing all conductors in a circuit through an insulating wall sufficiently large for all the conductors of the circuit. Underground Installations oMinimum Cover Requirements shall meet the minimum cover of table 3.0.1.5 requirements table 3.0.1.5 Minimum Cover Requirements, 0 to 600V, Nominal, Burial in Millimeters LEGEND • Column 1- Direct Burial Cables or Conductors • Column 2- Rigid Metal Conduit or Intermediate Metal Conduit • Column 3- Nonmetallic Raceways Listed for Direct Burial w/o Concrete Encasement or other Approved Raceways • Column 4- Residential Branch Circuits Rated 230 Volts or Less with GFCI Protection and Maximum Overcurrent Protection of 20 Amperes • Column 5- Circuits for Control of Irrigation and Landscape Lighting Limited to not more than 30 Volts and Installed w/ Type UF or in other Identified Cable or Raceway TYPES OF WIRING METHODS OR CIRCUIT Location of Wiring Method or Circuit Column 1 Column 2 Column 3 Column 4 Column 5 All Locations not specified below 600 150 450 300 150 In trench below 50mm thick concrete or equivalent 450 150 300 150 150 Under a building 0 (In 0 0 0 (In 0 (In raceway only) raceway only) 150 150 raceway only) Under minimum of 100 mm thick concrete exterior slab with no vehicular traffic and the slab extending not less than 150 mm beyond the underground installation 450 100 100 (direct burial) 100 (In raceway) TYPES OF WIRING METHODS OR CIRCUIT Location of Wiring Method or Circuit Column 1 Column 2 Column 3 Column 4 Column 5 Under streets, highways, roads, alleys, driveways, and parking lots 600 600 600 600 600 One and two family dwelling driveway and outdoor parking areas, and used only for dwelling related purposes 450 450 450 300 450 In or under airport runways, including adjacent areas where trespassing prohibited 450 450 450 450 450 Underground Installations oListing Cables and Insulated Conductors installed in enclosures or raceways shall be listed for use in wet locations. o Underground Cables Under Buildings shall be in raceway that is extended outside walls of the building. beyond the Underground Installations oConductors Entering Buildings shall be protected to the point of entrance oService Conductors shall have their location identified by a warning ribbon that is placed in the trench at least 300mm above the underground installation Underground Installations o Enclosure or Raceway Damage shall be installed in rigid metal conduit, intermediate metal conduit, thick wall rigid nonmetallic conduit or equivalent o Splices and Taps Direct-buried conductors or cable shall be permitted to be spliced or tapped without the use of splice boxes. Underground Installations oBackfill that contains large rocks, paving materials, cinders, large or sharply angular substances, or corrosive material shall not be placed in an excavation where materials may damage raceways, cables, or other substructures. Underground Installations oRaceway Seals Conduits or Raceways through which moisture may contact live parts shall be sealed or plugged at either or both ends. oBushing shall be used at the end of the conduit Underground Installations o Conductors of the Same Circuit shall be installed in the same raceway oGround Movement shall be arranged to prevent damage to the enclosed conductors or to the equipment connected to the raceways. SCOPE Construction Specification USE Installation Article 3.32- Mineral- Insulated, Metal Sheated Cable: Type MI Mineral- Insulated, Metal Sheated Cable: Type MI -A factory assembly of one or more conductors insulated with a highly compressed refractory mineral insulation and enclosed in a liquid tight and gas tight copper or alloy steel sheath. Article 3.32- Mineral- Insulated, Metal Sheated Cable: Type MI Uses Permitted services, feeders, branch circuits power, lighting, control and signal circuits dry or wet location Indoors and outdoors exposed to oils, and gasoline In or attached to cable tray Article 3.32- Mineral- Insulated, Metal Sheated Cable: Type MI Uses not Permitted In underground runs Where exposed to conditions that are destructive and corrosive to the metallic sheath . Bending Radius 5 times the external diameter of metallic sheath for cable not more than 19mm Article 3.32- Mineral- Insulated, Metal Sheated Cable: Type MI 3.32.2.1 Securing and Supporting Staples straps, hangers or similar fittings Article 3.32- Mineral- Insulated, Metal Sheated Cable: Type MI 3.32.3 Construction Specification Conductors Copper Nickel Nickel coated copper Equipment Grounding copper, shall provide an adequate path for grounding steel, an equipment grounding conductor shall provided Article 3.32- Mineral- Insulated, Metal Sheated Cable: Type MI 3.32.3 Construction Specification Insulation Sh all be highly compressed refractory mineral Sheath shall be continuous construction Article 3.34- Non Metallic- Sheathed Cable: Types NM,NMC, and NMS Non metallic- Sheathed Cable -A factory assembly of two or more insulated conductors enclosed within an overall nonmetallic jacket. Type NM -Insulated conductors enclosed within an overall non metallic jacket Article 3.34- Non Metallic- Sheathed Cable: Types NM,NMC, and NMS 3.34.1.2 Definitions 3. Type NMC -Insulated conductors enclosed within an overall, corrosion resistant, non metallic jacket 4. Type NMS -Insulated power or control conductors within signaling and communications conductors within an overall nonmetallic jacket. Article 3.34- Non Metallic- Sheathed Cable: Types NM,NMC, and NMS 3.34.2 Installation Uses Permitted Type NM, NMC,NMS -dry locations -Air voids in masonry block or tile walls Uses Not Permitted Types NM and NMS -corrosive fumes Embedded masonry, concrete, adobe, fill, plaster excessive moisture or dampness Article 3.34- Non Metallic- Sheathed Cable: Types NM,NMC, and NMS 3.34.2 Installation Ampacity 60°C (140°F) conductor temperature rating 3.34.3 Construction Specification Construction Outer cable sheath should be nonmetallic material Conductors 2.0 mm square (1.6 mm dia.) -3.5 mmthrough 30 mm^2 copper conductors or sizes Article 3.34- Non Metallic- Sheathed Cable: Types NM,NMC, and NMS 3.34.3 Construction Specification Equipment Grounding -insulated or bare conductor Insulation The overall covering shall be flame retardant and moisture resistant Article 3.36 Power and Control Tray Cable : Type TC Power and Control Tray Cable, type TC -a factory assembly of two or more insulated conductors,with or without associated bare or covered grounding conductors, under a nonmetallic jacket. Uses Permitted Power ,lighting, control and signal circuits Cable Trays, raceways, outdoor locations industrial establishments and in wet locations Article 3.36 Power and Control Tray Cable : Type TC 3.36.2 Installation Uses not Permitted exposed to physical damage installed outside a raceway or cable tray system exposed to direct rays of the sun, unless identified as sunlight resistant Direct buried, unless identified for such use Article 3.36 Power and Control Tray Cable : Type TC Bending Radius Four times the overall diameter for cables 25 mm or less in diameter 3.36.3.1 Construction Specification Construction A metallic sheath or armor Conductors shall be sizes 0.75 mm^2 through 500 mm^2 copper 3.5 mm^2 through 500 mm^2 aluminum and copper-clad aluminum Article 3.36 –Service Entrance Cable:type SE and Use 3.38.1.1 Definition Service Entrance Cable - A single conductors or multi conductor assembly provided with or without an overall covering an overall covering, primarily used for services and of the following types Type SE –Service entrance cable having a flame retardant, moisture-resistant covered Article 3.36 –Service Entrance Cable:type SE and Use Type USE -Service entrance cable, identified for underground use, having a moisture resistant covering but not required to a flame retardant covering Article 3.36 –Service Entrance Cable:Type SE and Use 3.36.2 Installation Uses Permitted Service entrance conductors Branch circuits or feeders - Grounded Conductor Insulated Grounded Conductor Not Insulated Temperature Limitations Construction cabled single conductor, type USE construction recognized for underground use shall permitted to have a bare copper conductor cabled with the assembly. Article 3.40- Underground Feeder and Branch Circuit Cable: Type UF 3.40.2 Definition Underground Feeder and branch Circuit Cable, Type UF - a factory assembly of one or more insulated conductors with integral or an overall covering of non metallic material suitable for direct burial on the earth. Article 3.40- Underground Feeder and Branch Circuit Cable: Type UF 3.40.2 Installation Uses Permitted use underground single conductor cables For wiring in wet, dry or corrosive locations For solar photovoltaic locations As single conductor cables Supported by cable trays Article 3.40- Underground Feeder and Branch Circuit Cable: Type UF 3.40.2 Installation Uses not Permitted As service entrance cable In commercial garage In theaters and similar location In storage battery rooms Hoistways, elevator, escalators Hazardous locations Ampacity 60°C (140°F) conductors Article 3.40- Underground Feeder and Branch Circuit Cable: Type UF 3.40.3.1 Conductors 2.0 mm^2 copper 3.5 mm^2 copper clad aluminum Sheath flame retardant; moisture, fungus, and corrosion resistant Insulation moisture-resistant types the conductor insulation shall be rated 90°C (194°F). Article 3.42 Intermediate Metal Conduit : Type IMC Intermediate Metal Conduit : Type IMC - A steel threadable raceway of circular cross section designed for physical protection and routing of conductors and cables and for use as an equipment grounding conductor when installed with its integral couplings Article 3.42 Intermediate Metal Conduit : Type IMC Uses Permitted All atmospheric Conditions and Occupancies Corrosion Environments Cinder fill Wet locations Dissimilar metals Size Minimum-IMC 15 mm Maximum- IMC larger than raceway size 100 mm shall not be used Article 3.44- Rigid Metal Conduit: Type RMC Rigid Metal Conduit: Type RMC - a threadable raceway of circular cross section designed for the physical protection and routing of conductors and cables and for use as an equipment grounding conductor -made of steel with protective coatings or aluminum. Article 3.44- Rigid Metal Conduit: Type RMC 3.44.2 Installation Uses Permitted All atmospheric Condition and Occupancies Corrosion Wet location Size Minimum- RMC smaller than15mm shall not be used Maximum- RMC smaller than raceway size 150 mm shall not be used. Article 3.44- Rigid Metal Conduit: Type RMC Reaming and Threading All cut ends shall be reamed or otherwise finished to remove rough edges. Where conduit is threaded in the field, a standard cutting die with a taper of 1 in 16 (¾ in. taper per foot) shall be used. Article 3.48- Flexible Metal Conduit : Type FMC Flexible Metal Conduit (FMC) -a raceway of circular cross section made of helically wound, formed, Uses Permitted to used in exposed and concealed location Article 3.48- Flexible Metal Conduit : Type FMC 3.48.2 Installation Uses not Permitted In wet locations Hoistways, storage battery room hazardous location Where exposed to materials having a deteriorating effect on the installed conductors, such as oil and gasoline Where subject to physical damage Article 3.50- Liquid Tight Flexible Metal Conduit: Type FMC Article 3.50- Liquid Tight Flexible Metal Conduit: Type LFMC Liquid tight flexible Metal Conduit: Type LFMC - a raceway of circular cross section having an outer liquid tight, nonmetallic sunlight resistant jacket over an inner flexible metal core with associated couplings, connectors and fittings for the insullation of electric conductors. Article 3.50- Liquid tight flexible Metal Conduit: Type LFMC Uses Permitted Where conditions of installation, operation and maintenance require flexibility or protection from liquids, vapors or solids For direct burial Uses not permitted subject to physical damage Article 3.50- Liquid tight flexible Metal Conduit: Type LFMC 3.50.2 Installation Size Minimum- LFMC smaller than 15 mm electrical raceway should not be used Maximum- the maximum size of LFMC shall be 100 mm electrical raceway size 3.50.3 Construction Specification Marking- conduit suitable for direct burial shall be so marked. Article 3.52- Rigid Non metallic Conduit: Type RNC Rigid Non metallic Conduit: Type RNC -A non metallic raceway of circular cross section, with integral or associated couplings, connectors and fittings for the installation of electrical conductors and cables. Article 3.52- Rigid Non metallic Conduit: Type RNC 3.52.2 Installation Uses Permitted: Concealed Corrosive influence Cinders wet location dry and damp location exposed underground installation Article 3.52- Rigid Non metallic conduit: Type RNC 3.52.2 Installation Uses not permitted Hazardous locations Support of luminaires Physical damage Ambient temperature Insulation temperature Limitation Theaters and Similar Locations Article 3.52- Rigid Non metallic conduit: Type RNC 3.52.2 Installation Size Minimum – RNC smaller than raceway size 15 mm shall not be used Maximum – RNC larger than raceway size 150 mm shall not be used Article 3.52- Rigid Non metallic conduit: Type RNC Supports Conduit Raceway Size (mm) Maximum Spacing Between Supports (mm) 15-25 900 32-50 1500 65-80 1800 90-125 2100 150 2400 Article 3.52- Rigid Non metallic conduit: Type RNC 3.52.3 Construction Specification RNC and fittings shall be composed of suitable non metallic material that is resistant to moisture and chemical atmosphere Flame retardant to impact and crushing Each length of RNC shall be clearly and durably mark 3000 mm Article 3.53 – High Density Polyethylene Conduit: Type HDPE Conduit High Density Polyethylene Conduit: Type HDPE Conduit -A non metallic raceway of circular cross section, with associated couplings, connectors, and fittings for the installation of electrical conductors Article 3.53 – High Density Polyethylene Conduit: Type HDPE Conduit3.53.2 Installation Uses Permitted In discrete lengths from reels In location subject to severe corrosive influence In cinder fill In direct burial installation on earth or concrete Article 3.53 – High Density Polyethylene Conduit: Type HDPE Conduit 3.53.2 Installation Uses not permitted Where exposed Within a building In hazardous location Where subject to ambient temperature Article 3.53 High Density Polyethylene Conduit: Type HDPE Conduit 3.53.2 Installation Size Minimum- HDPE conduit smaller than raceway 15 mm shall not be used Maximum- HPDE conduit larger than raceway size 100 mm shall not be used. Article 3.54- Non metallic underground conduit conductors: Type NUCC Non metallic underground conduit conductors: Type NUCC -A factory assembly of conductors or cables inside a nonmetallic, smooth wall conduit with a circular cross section. Article 3.54- Non metallic Underground conduit conductors: Type NUCC 3.54.2 Installation Uses Permitted: For direct burial underground installation Encased or embedded in concrete In cinder fill In underground locations subject to severe corrosive influence Article 3.54- Non metallic underground conduit conductors: Type NUCC 3.54.2 Installation Uses Not permitted: In exposed location Inside Buildings Bends -shall be manually made so that the conduit will not damage Article 3.54- Non metallic underground conduit conductors: Type NUCC 3.54.2.51 Construction Specification 1. General- NUCC is an assembly that is provided in continuous length, shipped in a coil, reel or carton Article 3.56- Liquid tight flexible Non metallic conduit: Type LFNC Liquid tight flexible Non metallic conduit: Type LFNC -a smooth seamless inner core and cover bonded together and having one or more reinforcement layers. -a smooth inner surface with integral reinforcement within the conduit wall, designated as Type LFNC-B Article 3.56-Liquid tight flexible Non metallic conduit: Type LFNC Uses permitted Where flexibility is required for installation, operation and maintenance Where protection of the contained conductors is required from vapors, liquids, solids For outdoor location Article 3.56-Liquid tight flexible Non metallic conduit: Type LFNC Uses not permitted: Where subject to physical damage Where the operating voltage of the contained conductors is in excess of 600 volts. Size Minimum: LFNC smaller than raceway size 15 shall not be used Maximum: larger than raceway size 100 mm shall not be used Article 3.56-Liquid tight flexible Non metallic conduit: Type LFNC Bends Bends in conduit shall be so made that the conduit is not damae and internal diameter of the conduit is not effectively reduced 3.56.3 Construction Specification Construction shall be provided in continuous length capable of being shipped in a coil, reel, or carton without damage. Marking -shall be marked at least every 600 mm Article 3.58 Electrical Metallic Tubing:Type EMT Electrical Metallic Tubing (EMT) - An unthreaded thin wall raceway of circular cross section designed for he physical protection and routing of conductors and cables and for use as an equipment grounding conductors when installed utilizing appropriate fittings. Article 3.58 Electrical Metallic Tubing:Type EMT 3.58.2 Installation Uses Permitted Exposed and concealed Corrosion Protection Wet Locatiions Uses Not Permitted Where during installation or afterward/ it will subject to dammage Where protected from corrosion solely by enamel Article 3.58 Electrical Metallic Tubing:Type EMT Size Minimum-EMT smaller than raceway size 15mm shall not be used Maximum-shall be raceway size 100mm 3.58.3 Construction Specification Construction factory threaded integral couplings shall be permitted, theads should be factory made Marking -EMT shall be clearly and durably marked at least every 3000mm Article 3.60 Flexible Metallic Tubing: Type FMT • Flexible Metallic Tubing (FMT) - A raceway that is circular in cross section, flexible, metallic and liquid tight without a nonmetallic jacket. Uses Permitted In dry location Where concealed In accessible location For system voltage of 1000 volts maximum Article 3.60 Flexible Metallic Tubing: Type FMT Uses not permitted In hoistways Storage battery rooms Hazardous location Underground for direct earth burial Where subject to physical damage In lengths over 1800 mm Size Minimum-smaller than raceway size 15 mm shall not be used Maximum-shall be raceway size 20mm Article 3.62 Electrical Non metallic Tubing:Type ENT Electrical Non metallic Tubing: Type ENT -a non metallic or associated couplings, connectors, annd fittings for the installation of electric conductors. Uses Permitted In any building not exceeding above grade as follows For exposed work Concealed within walls,floors, ceilings. Article 3.62 Electrical Non metallic Tubing:Type ENT Uses permitted In location subject to corrosive influence and where subject to chemicals. In concealed dry and damp locations Above suspended ceilings Uses not permitted Hazardous locations For the support of luminaires and other equipment Where subject to ambient temperature For direct earth burial Article 3.62 Electrical Non metallic Tubing:Type ENT Uses not permitted Where the voltage is over 600 volts In theaters Exposed to the direct rays of the sun Size Minimum -ENT smaller than raceway size 15 mm shall not be used Maximum -ENT larger than raceway size 50mm shall not be used. Article 3.62 Electrical Non metallic Tubing:Type ENT 3.62.3 Construction Specification Construction -ENT shall be made of material that does not exceed the ignitibility, flammability, smoke generation, and toxicity characteristic of rigid polyvinyl chloride Markings -shall be clearly and durably marked at least every 3000 mm. -The type of material shall also be included in the marking -type, printed, quantity are identified by printed tag Article 3.66-Auxiliary Gutters 3.66.1.2 Definition Metallic Auxiliary Gutters -Sheet metal enclosure with hinged or removable covers for housing and protecting electric wires, cable, and bus bars in which conductors are laid in place after the wire ways has been installed as a complete system. Non Metallic Auxiliary Gutters -flame retardant, nonmetallic enclosure with removable covers for housing and protecting electric wires, cables, and bus bars in which conductors are laid in place after the wire way has been installed as a complete system. Article 3.66-Auxiliary Gutters Article 3.66-Auxiliary Gutters 3.66.2 Installation Uses Permitted Sheet Metal Auxiliary Gutters Non metallic Auxiliary Gutters Uses not Permitted To enclose switches over current devices, appliances or other similar equipment. To extend a greater distance than 9000mm beyond the equipment that it suplements. Article 3.66-Auxiliary Gutters 3.66.3.1 Construction Specification Construction Electrical and mechanical Continuity Substantial Construction Smooth rounded edges Covers Clearance of Bare live parts Article 3.66-Auxiliary Gutters Markings Outdoors -Suitable for exposure to sunlight -Suitable for use in wet locations -Installed conductor insulation temperature rating Indoors Installed conductor insulation temperature rating Article 3.68 -Busways 3.6.1.2 Definition • Busway - a grounded metal enclosure containing factory mounted bare or insulated conductors, which are usually copper, aluminum, bars, rods, or tubes. 3.68.2 Installation • Uses permitted 1. Exposed 2. Concealed 3. Through walls and floors Article 3.68 -Busways • Uses not Permitted 1. Physical damage 2. Hoistways 3. Hazardous locations 4. Wet locations 5. Working platform Article 3.68 -Busways 3.68.3 Construction Markings -shall be marked with the voltage and current rating and with manufacturer’s name / trademark visible after installation Article 3.70-Cable Bus Cable Bus -an assembly of insulated conductors with fittings and condutor terminations in a completely enclosd, ventilated protective metal housing. Use -permitted at any voltage or current for which spaced conductors are rated and shall installed only for exposed work Article 3.70-Cable Bus Types of Conductors insulation rating of 75°C (167°F) or higher Size and Number of Conductors The size and number of conductors shall be that for which the cablebus is designed, and in no case smaller than 50 mm^2 ARTICLE 3.72 CELLULAR CONCRETE FLOOR RACEWAYS 3.72.1.2 Definitions Cell - A single, enclosed tubular space in a floor made of precast cellular concrete slabs, the direction of the cell being parallel to the direction of the floor member. Header - Transverse metal raceways for electric conductors, providing access to predetermined cells of a precast cellular concrete floor. ARTICLE 3.72 CELLULAR CONCRETE FLOOR RACEWAYS Uses Not Permitted Where subject to corrosive vapor In any hazardous (classified) 5.1.2.1(b)(3) In commercial garages, othe r than for supplying ceiling outlets or extensions to the area below the floor but not above ARTICLE 3.74 — CELLULAR METAL FLOOR RACEWAYS Cellular Metal Floor Raceway -The hollow spaces of cellular metal floors, together with suitable fittings, that may be approved as enclosures for electric conductors. Cell - A single enclosed tubular space in a cellular metal floor member, the axis of the cell being parallel to the axis of the metal floor member. ARTICLE 3.74 — CELLULAR METAL FLOOR RACEWAYS Header -A transverse raceway for electric conductors, providing access to predetermined cells of a cellular metal floor. Uses Not Permitted Where subject to corrosive vapor In any hazardous (classified) location exc ARTICLE 3.76 — METAL WIREWAYS 3.76.1.2 Definition Metal Wireways - Sheet metal troughs with hinged or removable covers for housing and protecting electric wires and cable and in which conductors are laid in place af ter the wireway has been installed as a complete system. ARTICLE 3.78 — NONMETALLIC WIREWAYS 3.78.1.2 Definition Nonmetallic Wireways -Flame retardant, nonmetallic troughs with removable covers for housing and protecting electric wires and cables in which conductors are laid in place after the wireway has been installed as a complete system. ARTICLE 3.82 — NONMETALLIC EXTENSIONS Nonmetallic Extension. -An assembly of two insulated conductors within a (anonmetallic jacket or an extruded thermoplastic covering. Uses Permitted. From an Existing Outlet Exposed and in a Dry Location. Residential or Offices ARTICLE 3.82 — NONMETALLIC EXTENSIONS Uses Not Permitted In unfinished basements, attics, or roof spaces Where the voltage between conductors exceeds 150 volts for nonmetallic surface extension and 300 volts for aerial cable Where subject to corrosive vapors Where run through a floor or partition, or outside the room in which it originates ARTICLE 3.84 — STRUT-TYPE CHANNEL RACEWAY Strut-Type Channel Raceway -A metallic raceway that is intended to be mounted to the surface of or suspended from a structure, with associated accessories for the installation of electrical conductors and cables. ARTICLE 3.86 — SURFACE METAL RACEWAYS 3.86.1.2 Definition Surface Metal Raceway -A metallic raceway that is intended to be mounted to the surface of a structure, with associated couplings, connectors, boxes, and fittings for the installation of electrical conductors. ARTICLE 3.88 — SURFACE NONMETALLIC RACEWAYS Surface Nonmetallic Raceway -A nonmetallic raceway that is intended to be mounted to the surf ace of a structure, with associated couplings, connectors, boxes, and fittings for the installation of electrical conductors. ARTICLE 3.90 — UNDERFLOOR RACEWAYS Use Permitted be permitted beneath the surface of concrete or other flooring material or in office occupancies where laid fl ush with the concrete floor and covered with linoleum or equivalent floor covering. ARTICLE 3.92 — CABLE TRAYS Cable Tray System -A unit or assembly of units or sections and associated fittings forming a structural system used to securely fasten or support cables and raceways. ARTICLE 3.94 — CONCEALED KNOBAND-TUBE WIRING 3.94.1.2. Definition Concealed Knob-and-Tube Wiring -A wiring method using knobs, tubes, and flexible nonmetallic tubing for the protection and support of single insulated conductors. ARTICLE 3.94 — CONCEALED KNOBAND-TUBE WIRING 3.94.2 Installation Uses Permitted For extensions of existing installations Elsewhere by special permission Uses Not Permitted. Commercial garages Theaters and similar locations Motion picture studios Hazardous (classified) locations ARTICLE 3.96 — MESSENGER SUPPORTED WIRING Messenger Supported Wiring -An exposed wiring support system using a messenger wire to support insulated conductors by any one of the following: A messenger with rings and saddles for conductor support A messenger with a field-installed lashing material for conductor support Factory-assembled aerial cable ARTICLE 398 — OPEN WIRING ON INSULATORS 3.98.1.2 Definition. Open Wiring on Insulators -An exposed wiring method using cleats, knobs, tubes, and flexible tubing for the protection and support of single insulated conductors run in or on buildings. H V D C It is related to the tap changer control system. It occurs on both rectifier and the inverter side of the transmission. (TC cont) Designed to control the Load tap changers of the converter transformers. Objective is to keep the ordered alpha α gamma γ DC voltage - at the preset values determined by the Voltage and Angle Reference Calculation (VARC). • Operate much slower than the basic control function, acting on control angle alpha α • One tap changer step takes some seconds to execute. • Thus there is no risk for interference between the basic converter control function and the tap changer control systems. • One step gives a change of 1-1.5% of rated value in the valve side voltage. (TC @ Rec Sta) PURPOSE: to maintain the delay angle alpha in a certain range • If the alpha reduces below the predefined value, it starts to increase the voltage by varying the number of turns in the primary side to keep the alpha in certain range for fast controlling current • If alpha increased above a certain predefined maximum value then the tap changer would decrease the voltage to keep the alpha within the limit. • • • • • The voltage in the rectifier end of the line can be controlled by adding a proportional amount of the line voltage drop, Rd *Id to the measured inverter end voltage. • Normally used to keep the firing angle α as close as possible to the rated value which normally chosen to 15 degrees. • The control characteristics must include a dead band also here and ± step of 1.25% from rated value corresponds to a region from 12° to 17.5° in α. • Udio *cos a in the expression constant, at varying rectifier AC voltage, the current control system responds to it by changing α. • The (TCC) system in the rectifier compares an a response signal to a reference value and at a significant deviation it orders the tap changer to step and change Udio. • (TC @ Inv Sta) Tap changer control maintains the DC voltage equal to reference voltage. • Normally, gamma is kept as constant for proper commutation. • Any increase or decrease in the DC voltage will be controlled by tap changer • Since tap changers would take more time to control the converter voltage than current or voltage controller, dynamic interaction between both controllers can be avoided. • The tap changers in the inverter in the extinction angle γ control are normally used to control the voltage on the DC line. • The voltage response measured by a voltage divider is compared to an order, Udi0. • For a significant difference between the two signals, the tap changer control system (TCC) orders increase or decrease of the valve side voltage. • Because of the stepwise character of the tap changer, the control than characteristic harmonics system must be provided with dead band. To bring the voltage back to the reference value and thus avoid hunting, the dead band• These are due to: should have a width of at least one tap changer step 1. Inbalance in the operation s)of two bridges firing a 12 pulse converter (residual harmonics) • When the inverter takes over the current control, the DC voltage tap changer control must be locked (generation of 2. firing angle errors triplen and eve Harmonics harmonics and 3. unbalance and distortion of AC Voltages their analysis is • Harmonics are electric voltages and currents that appear on the 4.unequal transformer leakage impedances complex) electric power system as a result of non-linear electric loads. • Harmonic instability may occur in high-voltage dc (HVDC) links due to dynamic interactions between HVDC terminals and the impedance of the dc lines or cables. • The harmonics that come from the HVDC will not only increase loss, thermal stress of equipment, reduce equipment life,• interference with communications, metering, protection and control devices to work properly and in some cases, it can even lead to the collapse of the system. • • Two types of harmonics in electrical power systems 1. current harmonics 2. voltage harmonics • Generation of Harmonics 1. harmonics-characteristic 2. non-characteristic • Characteristic Harmonics - harmonics of those order which are always present even under ideal operation• Non Characteristic Harmonics- the harmonics of the order other The presence of harmonics leads to low system efficiency, poor power factor, increased loss and reactive power components from AC and also on the equipment present in the system and interference on the telecommunication lines. for reduction of harmonics, filters are used. Here we use a hybrid configuration of both passive and active filters for improved power handling capacity of semiconductor devices and better performance. • The above circuit diagram consists of a three- phase generator shunt and series. But these filters also have hybrid configuration source of 345Kv at frequency of 50Hz which is connected to the of passive filters to improve the power handling capacity of converter transformer for stepping down voltage to 211KV for semiconductor devices. transmission over long distance. Further a 12-pulse thyristor bridge converter is connected, which is called as rectifier forharmonic analysis in a basic HVDC transmission system and the converting AC to DC while the converter at the other end isimportance of using filters for the reduction of the harmonic referred as inverter for vice-versa conversion. The rectifier-enddistortions in the system to improve the efficiency and reduce has firing angle (α) control for ignition of the thyristor while thevarious ill effects due to the harmonics. inverter-end contains the extinction/gamma control (δ). On observing the various waveforms with and without the insertion of filters, we may conclude that on connecting the harmonic filters the voltage values is increased and optimized while the high current values are reduced. • A. Three Phase Converter - The converter transformers are constructed by three phase three winding on same core material by connecting primary and secondary windings as either wyes or deltas. • B. Pulse Generator - a discrete twelve pulse generator is used to fire the thyristors of HVDC rectifier built with two six pulse bridges. The four inputs of a pulse generator are alpha firing angle (in degrees), other three inputs are phase to ground synchronizing voltages. There are two outputs of a pulse generator, one connected to wye secondary winding of transformer and other connected to delta winding of secondary transformer. Similarly for gamma angle control at the inverterside, a twelve-pulse firing control and discrete gamma measurement subsystem is used for the two extinction/gamma angle triggering for the inverter. • C. Filters - Both the ends have AC filters for reducing the harmonic distortion in the AC-side of the system and DC filters or smoothening reactors on the DC line for reducing the ripple content in the current. The AC filters comprises of both passive and active components for efficient performance and economy. Generally the passive filters used are of damped (high-pass) and tuned (single, double or triple) types while active filters are of