Uploaded by Simon Lam

ASHRAE 15: Refrigerating Systems & Machinery Rooms Safety

advertisement
1
Refrigerating Systems
and Machinery Rooms
Applying ASHRAE Standard 15
Advanced HVAC Training
ACES-Trane Air Cond Clinics
30 January 2015
K Y Yow
Director, Technical Center of Excellence
HVAC & Transport , Climate Sector
API , Ingersoll Rand
2
refrigerating systems and machinery rooms
ANSI/ASHRAE Standards
Standard 34-2004:
Designation and Safety
Classification of Refrigerants
Standard 15-2004:
Safety Standard for
Refrigeration Systems
3
ANSI/ASHRAE Standard 34-2004
Purpose
To establish a …

“… uniform system for assigning reference
numbers and safety classifications to
refrigerants.”

“… simple means of referring to common
refrigerants instead of using the chemical
name, formula, or trade name.”
Designation and Safety Classification of Refrigerants
4
ANSI/ASHRAE Standard 34-2004
Numbering
R-####
carbon-carbon
bonds
fluorine atoms
carbon atoms
minus 1
hydrogen
atoms plus 1
Designation and Safety Classification of Refrigerants
5
ANSI/ASHRAE Standard 34-2004
Safety Criteria


Flammability:
3 classes
Toxicity:
2 classes
Designation and Safety Classification of Refrigerants
6
ANSI/ASHRAE Standard 34-2004
Flammability Criteria



Class 1
No flame propagation
Class 2
Lower flammability
Class 3
Highly flammable
Designation and Safety Classification of Refrigerants
7
ANSI/ASHRAE Standard 34-2004
Toxicity Criteria


Class A
No known toxicity at
< 400 ppm
Class B
Evidence of toxicity at
< 400 ppm
… Based on TLV-TWA data or
consistent indexes
Designation and Safety Classification of Refrigerants
8
ASHRAE Standard 34-2004
Safety Classifications
refrigerant safety groups
higher
flammability
A3
B3
lower
flammability
A2
B2
no flame
propagation
A1
B1
lower
toxicity
higher
toxicity
9
ANSI/ASHRAE Standard 34-2004
Safety Classifications
Refrigerant blends:

Rated based on worst-case fractionation …
most toxic, most flammable mix

Considers response to temperature and
pressure changes over time

azeotropic blends = consistent

zeotropic blends = altered
10
ASHRAE Standard 34-2004
Refrigerant/Blend Data
refrig
number
chemical name or composition
(% by weight)
compositiondesignating
prefix
normal
boiling
point
safety
group
methane series
R-11
R-12
R-22
trichlorofluoromethane
dichlorodifluoromethane
chlorodifluoromethane
CFC
CFC
HCFC
75°F
-22°F
-41°F
A1
A1
A1
CFC
HCFC
HFC
HFC
118°F
81°F
-15°F
-13°F
A1
B1
A1
A2
CFC/HFC
HCFC/CFC
-27°F
–49°F
A1
A1
ethane series
R-113
R-123
R-134a
R-152a
1,1,2–trichlorotrifluoroethane
2,2–dichloro–1,1,1–trifluoroethane
1,1,1,2–tetrafluoroethane
1,1–difluoroethane
azeotropes
R-500
R-502
R-12/R-152a (73.8/26.2)
R-22/R-115 (48.8/51.2)
11
ANSI/ASHRAE Standard 15-2004
Purpose and Scope
“… specifies the safe design, construction,
installation, and operation of refrigeration
systems”
“… establishes safeguards for life, limb,
health, and property and prescribes safety
requirements”
Safety Standard for Refrigeration Systems
12
ANSI/ASHRAE Standard 15-2004
Applicability
New construction:
“ … the design, construction, test,
installation, operation and inspection of
mechanical and absorption refrigeration
systems, including heat pumps systems
used in stationary applications”
Safety Standard for Refrigeration Systems
13
ANSI/ASHRAE Standard 15-2004
Applicability
Certain replacements:
“… modifications including replacement
of parts or components if they are not
identical in function and capacity …”
Safety Standard for Refrigeration Systems
14
ANSI/ASHRAE Standard 15-2004
Applicability
Certain conversions:
“… and to substitutions of refrigerant
having a different designation”
Safety Standard for Refrigeration Systems
15
ANSI/ASHRAE Standard 15-2004
Enforceability
standard of care
model code
“influential”
state law
“enforceable”
16
ANSI/ASHRAE Standard 15-2004
Classification Criteria

Refrigerant safety
Allowable tolerance for human exposure

Building occupancy
Speed of evacuation

Refrigerating system
Probability of occupant exposure
Safety Standard for Refrigeration Systems
17
ANSI/ASHRAE Standard 15-2004
Refrigerant Safety
refrigerant safety groups
(ANSI/ASHRAE Standard 34-2004)
higher
flammability
A3
B3
lower
flammability
A2
B2
no flame
propagation
A1
B1
lower
toxicity
higher
toxicity
our focus
18
ASHRAE Standard 15-2004
Building Occupancy




Institutional
Occupant impairment prevents quick exit
Public assembly
Large congregation congests exits
Residential
Individual and multi-unit living facilities
Industrial
Restricted access to specific areas
19
ANSI/ASHRAE Standard 15-2004
Building Occupancy



Commercial
Where people transact business, receive
personal services, or purchase food/goods
Large mercantile
Where > 100 people congregate to purchase
personal merchandise
Mixed
Two or more occupancy types within the same
building
20
ANSI/ASHRAE Standard 15-2004
Refrigerating System
SYSTEM TYPE
cooling or
heating source
material to be
cooled/heated
SYSTEM
CLASSIFICATION
direct
high probability
indirect
open spray
high probability
(conditional)
double indirect
open spray
low probability
indirect closed
low probability
indirect
vented closed
low probability
21
ANSI/ASHRAE Standard 15-2004
Refrigerant Quantity Limits
High-probability systems:

Concentrations must not exceed Table 1
values (Section 7.2)

Maximum quantity based on volume of
occupied space (Section 7.3)

Special considerations for institutional
and industrial occupancies
(Sections 7.2.1, 7.2.2)
Safety Standard for Refrigeration Systems
22
ANSI/ASHRAE Standard 15-2004
Occupied Volume
Nonconnecting spaces (Section 7.3.1)

Refrigeration system in occupied space

No permanent openings, no HVAC duct

Use volume of smallest occupied space

Limit height to 8.2 ft for spaces on
different levels
Safety Standard for Refrigeration Systems
23
ANSI/ASHRAE Standard 15-2004
Occupied Volume
Ventilated spaces (Section 7.3.2)

Refrigeration system in air handler

Omit spaces that can be isolated from leak
source
Excludes smoke dampers, shutoff (<10%) VAV
boxes

Use smallest occupied space

Include plenums and ductwork
Safety Standard for Refrigeration Systems
24
ANSI/ASHRAE Standard 15-2004
Occupied Volume
Summary:

Occupied volume calculation depends on
application

Determines worst-case dilution scenario …


Smallest occupied-space volume

Largest refrigerant quantity in a single circuit/unit
Assumes that refrigerant disperses equally
throughout air in occupied space
Safety Standard for Refrigeration Systems
25
ANSI/ASHRAE Standard 15-2004
Refrigerant Quantity Limits
refrigerant qty
per occupied space
common
name
chemical name or composition
(% by weight)
safety
group
lb per
Mft³
ppm
by vol
A1
A1
A1
1.6
12.0
9.4
4,000
40,000
42,000
A1
B1
A1
A2
1.9
0.4
16.0
1.2
4,000
1,000
60,000
7,000
A1
A1
12.0
19.0
47,000
65,000
methane series
R-11
R-12
R-22
trichlorofluoromethane
dichlorodifluoromethane
chlorodifluoromethane
ethane series
R-113
R-123
R-134a
R-152a
1,1,2–trichlorotrifluoroethane
2,2–dichloro–1,1,1–trifluoroethane
1,1,1,2–tetrafluoroethane
1,1–difluoroethane
azeotropes
R-500
R-502
R-12/R-152a (73.8/26.2)
R-22/R-115 (48.8/51.2)
26
ANSI/ASHRAE Standard 15-2004
Equipment Location
Place all refrigeration components in a
“machinery room” or outdoors IF:

Refrigerant quantity exceeds Table 1

Direct-fired absorption is used
Safety Standard for Refrigeration Systems
27
ANSI/ASHRAE Standard 15-2004
Equipment Location
Machinery room:
“… a space, meeting the
requirements of 8.11 or
8.12, that is designed to
house compressors and
pressure vessels”
(Section 3)
28
Equipment Location
Aliases:
Signifies compliance
with Standard 15

Equipment room

Mechanical room

Mechanical equipment
room (MER)

Refrigeration room

Machinery room
29
ANSI/ASHRAE Standard 15-2004
Equipment Location
Refrigerant class determines machinery
room requirements:

For nonflammable refrigerants (A1 or B1),
conform to Section 8.11

For flammable refrigerants (A2, B2, A3 or
B3), conform to Sections 8.11 and 8.12
Safety Standard for Refrigeration Systems
30
ANSI/ASHRAE Standard 15-2004
Summary of Restrictions


Place chillers in machinery rooms
Conform with Section 8.11 when
machinery room houses A1 or B1
refrigerants
Safety Standard for Refrigeration Systems
31
section 8.11 requirements for
Machinery-Room Design

Ventilation

Refrigerating system placement

Doors, passageways, access

Refrigerant monitoring

Open-flame devices

Pressure-relief piping

General
32
machinery-room design requirements
Ventilation


Natural (gravity-driven)

Minimum cross-section of opening

Opening location
Mechanical (powered) ventilation

Normal rate for human occupancy

Alarm rate if a leak is detected
33
machinery-room design requirements
Natural Ventilation
Permissible if:
occupied
building
occupied
building
> 20 ft
refrigerating
system
lean-to or
other ventilated
structure
34
machinery-room design requirements
Natural Ventilation
Minimum free-aperture cross section for
ventilation opening:
F = G0.5
where:
F = free opening area, ft²
G = mass of refrigerant, lb
35
machinery-room design requirements
Mechanical Ventilation
Normal rate:

Provide minimum ventilation during
occupancy: 0.5 cfm/ft² or 20 cfm/person

Maintain comfort by not exceeding the
higher of:
inlet air + 18°F
or
122°F room air (maximum)
36
machinery-room design requirements
Mechanical Ventilation
Alarm rate:
Exhaust accumulated refrigerant resulting
from a leak or rupture
Q = 100 × G0.5
where:
Q = airflow (ft³/min)
G = mass of refrigerant (lb)
37
machinery-room design requirements
Mechanical Ventilation



Vent to outdoors

Cause no nuisance or danger

Provide for makeup air

Position to avoid recirculation
Provide separate supply/return ducts
Use multiple or multispeed fans to obtain
reduced airflow for normal ventilation
38
Suggested
Exhaust-Fan Location
exhaust fan
breathing zone: 5 ft
39
end view
exhaust
airflow
plan view
ventilation
airflow
Dual-Purpose
Mechanical Ventilation
40
section 8.11 requirements for
Machinery-Room Design

Ventilation

Refrigerating system (chiller) placement

Doors, passageways, access

Refrigerant monitoring

Open-flame devices

Pressure-relief piping

General
41
machinery-room design requirements
Chiller Placement

Provide unobstructed space for service,
maintenance, inspection, and operation
Comply with applicable safety standards and
requirements of presiding regulatory agency

If mounted overhead, provide ≥ 7.25 ft of
clear head room below
42
machinery-room design suggestions
Multiple-Chiller Layouts
chillers
air
inlets
arrangement A
IDEAL
exhaust
fans
arrangement B
ADEQUATE
43
section 8.11 requirements for
Machinery-Room Design

Ventilation

Refrigerating system (chiller) placement

Doors, passageways, access

Refrigerant monitoring

Open-flame devices

Pressure-relief piping

General
44
machinery-room design requirements
Doors, Passages, Access



Limit entry to authorized personnel
Provide adequate number and type
of doors
Prevent openings to other parts of
building

No “shared” air-handling systems

No open raceways or tunnels
45
section 8.11 requirements for
Machinery-Room Design

Ventilation

Refrigerating system (chiller) placement

Doors, passageways, access

Refrigerant monitoring

Open-flame devices

Pressure-relief piping

General
46
machinery-room design requirements
Refrigerant Monitoring


Select a “detector” that activates at or
below TLV®–TWA

Broadcasts an alarm

Initiates mechanical ventilation
Place sensor where refrigerant will
concentrate
47
machinery-room design requirements
Refrigerant Monitoring
2004 standard alarm requirements

Audible and visual signals

Alarms inside machinery room and outside
each entry

Advisory signage at each entry

Manual reset inside machinery room
… and permits additional alarm levels
(if TLV-TWA actions are met)
48
machinery-room design suggestions
Refrigerant Monitoring

Position sensor 12-18 inches above floor

Arrange sensor site based on ventilation
Continuous:
Between chiller
and exhaust fan
exhaust fan
sensor
chiller
Intermittent:
Between entry and
chiller (within 50 ft)
exhaust fan
sensor
chiller
49
machinery-room design suggestions
Refrigerant Monitoring
roof or floor
occupied space
machinery room
refrigerant
monitor
5 ft
sample-in
tubing
particle filter
12–18 in.
chiller
50
Suggested Sensor Placement
for Intermittent Ventilation
sensor
chillers
sensor
51
Multichannel Scanner
for Multiple Chillers
and/or Floor Levels
sensor
monitor/
multichannel
scanner
pit
52
section 8.11 requirements for
Machinery-Room Design

Ventilation

Refrigerating system (chiller) placement

Doors, passageways, access

Refrigerant monitoring

Open-flame devices

Pressure-relief piping

General
53
machinery-room design requirements
Open-Flame Devices
“No open flames that use combustion air
from the machinery room shall be installed
where any refrigerant is used.”
Exceptions:

Sealed duct brings air into combustion
chamber, preventing leaked refrigerant
from entering

Refrigerant detector automatically shuts
down combustion if a refrigerant leak
occurs
54
section 8.11 requirements for
Machinery-Room Design

Ventilation

Refrigerating system (chiller) placement

Doors, passageways, access

Refrigerant monitoring

Open-flame devices

Pressure-relief piping

General
55
machinery-room design requirements
Pressure-Relief Piping


Route vent-line piping to discharge
outdoors
Position vent-line discharge:

≥ 15 ft above grade level

≥ 20 ft from any building opening
56
roof
Refrigerant Vent-Line
purge-discharge
vented to atmosphere
relief device
(alternate
arrangement)
exterior wall
Prevent discharge
from contacting
personnel
15 ft above
ground level,
20 ft from building
openings
57
machinery-room design requirements
Pressure-Relief Piping



Ensure that relief-line size exceeds outlet
diameter of relief device
Use Appendix H equations to determine
maximum vent-line run
If manifolding multiple relief devices:

Consider effect of back pressure

Ensure that manifold area exceeds sum of
relief-device areas
58
section 8.11 requirements for
Machinery-Room Design

Ventilation

Refrigerating system (chiller) placement

Doors, passageways, access

Refrigerant monitoring

Open-flame devices

Pressure-relief piping

General
59
machinery-room design requirements
General


Changing refrigerants:

Obtain owner’s permission

Notify presiding authority

Update/add appropriate signage
Storing refrigerant in machinery room:

Limit to 330 lbs in approved storage
containers

Comply with Section 9.7 to store more
60
machinery-room design requirements
General
Signage:

Identify installer, refrigerant, lubricant, field
test pressure

Identify controls, switches, and piping

Limit access to authorized personnel

Prevent access during alarm (except with
protective gear and proper training)
61
machinery-room design requirements
General
Emergency shutdown procedure:

Post conspicuously where convenient to
operators

Include service contact information

Provide instructions and contacts for
reportable incidents

Forbid entry if refrigerant alarm
(per 8.11.2.1) activates
62
machinery-room design requirements
General
Self-contained
breathing apparatus (SCBA):

Locate manual reset for alarm inside
machinery room

Provide signage forbidding entry without an
SCBA during an alarm condition

Review Appendix I, “Emergencies in
Refrigerating Machinery Rooms,” for further
guidance
63
machinery-room design requirements
Summary


Ascertain need for a machinery room

Building occupancy

Refrigerant safety

Refrigerating system
Machinery room requirements
Same for all quantities of A1 and B1
refrigerants

Primary goal: SAFETY
64
Refrigerating Systems
and Machinery Rooms
Applying ASHRAE Standard 15
Questions?
Download