1 Frequency Dynamics with Grid Forming Inverters: A New Stability Paradigm arXiv:2102.12332v1 [eess.SY] 24 Feb 2021 R. W. Kenyon, Student Member, IEEE, A. Sajadi, Senior Member, IEEE, B. M. Hodge, Senior Member, IEEE Abstract—Traditional power system frequency dynamics are driven by Newtonian physics, where a synchronous generator (SG), the historical primary source of power, follows a deceleration frequency trajectory upon power imbalances according to the swing equation. Subsequent to a disturbance, an SG will modify pre-converter, mechanical power as a function of frequency; these are reactive, second order devices. The integration of renewable energies is primarily accomplished with inverters that convert DC power into AC power, and which hitherto have employed grid-following control strategies that require other devices, typically SGs, to establish a voltage waveform and elicit power imbalance frequency dynamics. A 100% integration of this particular control strategy is untenable and attention has recently shifted to grid-forming (GFM) control, where the inverter directly regulates frequency; direct frequency control implies that a GFM can serve power proactively by simply not changing frequency. With analysis and electromagnetic transient domain simulations, it is shown that GFM pre-converter power has a first order relation to electrical power as compared to SGs. It is shown that the traditional frequency dynamics are dramatically altered with GFM control, and traditional second-order frequency trajectories transition to first-order, with an accompanying decoupling of the nadir and rate of change of frequency. Index Terms—synchronous generators, grid forming inverters, frequency response, nadir, rate of change of frequency I. I NTRODUCTION Frequency dynamics in AC power systems have forever been govnerned by Newtonian physics, where a synchronous generator (SG), the conventional primary source of power, follows a deceleration frequency trajectory upon mechanical– electrical power imbalances. The integration of variable renewable energy generation into power systems is primarily accomplished with inverters (i.e., inverter based resources (IBRs)), which hitherto have employed grid-following (GFL) control strategies that rely on other devices to establish the voltage profile [1]. As renewable shares continue to grow at an accelerating pace, small to medium sized power systems with significant instantaneous penetrations of IBRs have become commonplace in many systems across the globe [2]–[4]. As the penetration of GFL devices increases, overall system inertia decreases due to the supplanting of SGs [5]; it is R. W. Kenyon and B. M. Hodge are with the Electrical Computer and Energy Engineering (ECEE) and the Renewable and Sustainable Energy Institute (RASEI) at the University of Colorado Boulder, Boulder, CO 80309, USA, and the Power Systems Engineering Center, National Renewable Energy Laboratory (NREL), Golden, CO 80401, USA, email: {richard.kenyonjr,BriMathias.Hodge}@colorado.edu, {richard.kenyon,Bri-Mathias.Hodge}@nrel.gov A. Sajadi is with the Renewable and Sustainable Energy Institute (RASEI) at the University of Colorado Boulder, Boulder, CO 80309, USA, email: Amir.Sajadi@colorado.edu well documented that instability can occur for high/complete penetrations of GFL inverters (i.e., low–zero inertia systems) [5]–[8]. As a result, attention has shifted to grid-forming (GFM) control, where instead of regulating to active power set points as a current source, the IBR establishes a voltage and frequency at the point of interconnection to the grid. A primary challenge concerning the operation of these lowinertia power systems is the maintenance of system stability, in particular the frequency response when SGs are displaced by GFL IBRs; recent work has pointed towards the potential of GFM inverters to mitigate these stability challenges [9]–[16]. The authors of [9]–[12] have extensively studied the smallsignal stability of power systems with integrated GFMs by developing high-fidelity differential-algebraic models; often, non-zero, minimum SG quantities are declared in order to preserve system stability. Conversely, the feasibility of operating bulk power systems with 100% GFM-based generation has been computationally demonstrated in the electromagnetic transient domain [13], and positive sequence [14]. [13] investigated the dynamic interactions between GFMs and SGs and have identified that the integration of GFMs improves the system frequency response; however, these studies fail to link the fundamental shift in power conversion order to these improved dynamics. Other studies have started to identify the damping-like contribution of droop controlled GFM inverters to frequency dynamics [13]–[15], but cast these conclusions on the basis of similar frequency trajectories across an entire system. This paper investigates the power conversion dynamics of SGs and GFMs (i.e., converters) and the associated frequency dynamics in bulk electric power systems along a shifting generation trajectory; namely, from a 100% SG, standard inertia system, to a 100% GFM, inertia-free system. The main conclusions of this paper are summarized: • It is analytically derived that, with respect to preconverter power, the primary frequency dynamics of a GFM are first order, and second order for an SG. Frequency-power portrait analyses of test system load step responses with varied GFM and SG quantities confirm these lower order dynamics. • The standard assertion of the fast frequency response of IBRs, as applicable to pre-converter power of a GFM, is refuted. A GFM serves power simply by not changing the local frequency. • Common average frequency metrics, typically used to approximate an overall system frequency response, are demonstrated as inadequate with GFM devices, and the decoupling of traditional nadir and rate of change of 2 frequency relations with GFMs is demonstrated. II. M ATHEMATICAL M ODELS OF C ONVERTERS This section focuses on the mathematical models that describe the power converter devices of interest; namely, the mechanics and associated time scales in which a converter can modulate the power throughput. To facilitate the comparison of frequency dynamics between GFMs and SGs, the notation relating the flow of power through either device is first summarized in Fig. 1. As shown, both devices have a pre-converter power (pm ) flowing into the device, which is analogous to the mechanical torque applied to the shaft of an SG, or the power supplied by an energy storage system to the GFM1 . Each type of converter stores a quantity of 2 energy, either as kinetic energy for the SG Eint,G = 21 Iωmech with I and ω being the moment of inertia and shaft rotation rotational speed, respectively, or within the GFM primarily 2 , with as electrical capacitive storage, Eint,I = 12 CDC VDC CDC and VDC being the DC link capacitance and capacitor voltage, respectively. Generally, Eint,G >> Eint,I [17], [18]. Electrical power is delivered to the grid by the converter, represented as pe . The distinction between GFM pre-converter power, pm,I , and electrical power, pe,I , is made to create the comparison analogy; these values are only distinguished by a low-pass filter in this particular GFM control design (pm,I is often referred to as filtered power, pavg , in the literature [10], [19]). Here, it is assumed that pm,I is readily available within the low-pass filter rise time on account of standard energy storage/inverter response times [20], [21]. Neglecting losses, conservation of energy requires that Ė 6= 0 if pm 6= pe 2 . export relationship. For this work, we focus on the frequency dynamics of the multi-loop droop control GFM, with the simplified control block diagram shown in Fig. 2. Henceforth, GFM implies this particular control strategy. In this diagram, from the left, pm is injected into the converter via the DC voltage source, where it is modified with a pulse width modulation (PWM) controller that outputs a series of modified amplitude square waves that are filtered and interfaced with the power system. The LC output filter meets with a coupling inductor to create the LCL topology shown in Fig. 2. The current (if ) and capacitor voltage (EI ) are regulated by proportional-integral (PI) controllers operated in the directquadrature reference frame. Additional detail on the controller design and implementation can be found in [25]. Lf LI RI io [vo , ωI] vo EI vi + - if Rf Cf PWM Current Controller Voltage Controller e[v , ω] +- [vset ,ωset] Fig. 2: Control scheme of multi-loop droop grid-forming inverter. In this paper, where the interest is in frequency dynamics, the voltage can be assumed to be stiffly regulated and therefore constant within the subsequent mathematical formulations. This complements the SG model approximation to be discussed in Section II-B. The low pass filter dynamical relation between pm,I and pe,I is provided in (1). 2π (pe,I − pm,I ) (1) τI where τI,f il is the filter time constant; as cutoff frequency, ωI,f il = 2π/τI . The work in [10] found a limit of 5ωI,f il > ωn , which indicates that ωI,f il should be greater than 75 rad/s in a 60 Hz system, and therefore τI ≤ 0.08 s; i.e., on the order of rapid energy system response times. By (1), pm,I has a first order relation to pe,I . The active power–frequency governing equations, which are the control basis of the multi-loop droop relation, are shown in (2) and (3): ṗm,I = Fig. 1: Converter topology showing the relation between the device internal energy (Eint ), pre-converter power (pm ), and electrical power (pe ). A. Grid Forming Inverter Although a variety of GFM control strategies have been presented in the literature, such as the droop [22], multiloop droop [15], virtual synchronous machine [23], and virtual oscillator control [24], they all approximate a similar objective; namely, the construction of a voltage and frequency at the point of interconnection with dynamics associated via a power 1 other sources of power exist for the GFM, such as curtailed photovoltaic output, although here an energy storage system with available energy is assumed for simplicity 2 dot notation indicates time derivative; ẋ = d x dt δ̇I = MP (pm,I,o − pm,I ) (2) 2πMP (pm,I − pe,I ) ω̇I = (3) τI where δI is the GFM phase angle, MP is the droop gain, pm,I,O is the pre-converter power set point, pm,I is the preconverter power, ωI is the GFM frequency, and pe,I is the power transferred to the grid; (3) is formulated by combining (2) and (1). Note that (2) is expressed in relative form (i.e., the steady state value is zero). Based on (1), the pm,I evolves based only on pe,I . Following, δI evolves according to (2). It can therefore be stated that the GFM frequency is a function of the pre-converter power; the device meets the increase in power demand (pe,I ), and then 3 adjusts the frequency according to the droop relation. This distinction indicates that a GFM does not require frequency deviations in order for pm,I to evolve. In this control scheme, frequency is changed to accomplish power sharing, but the underlying throughput power mechanics indicate an entirely different, and inverted, relationship with power differentials as compared to the SG. B. Synchronous Generator The SG is a well understood and documented device; see [17], [26] for in-depth discussions. Here, ideal voltage regulation is assumed and the machine/voltage dynamics are neglected. While governor models are generally non-linear with higher order filtering, deadbands, and saturation, a valid approximation for frequency dynamics can be made with a first order system [17]. The result is a 3rd order dynamical system consisting of the swing equation (shown in (4) and (5)) and the first order governor dynamics (6). The swing equation, i.e., Newton’s second law in rotational form, relates the SG rotation speed with pm,G – pe,G power imbalance. δ̇G = ωG − ωs 1 pm,G − pe,G − Dδ̇G ω̇G = M (4) (5) where δG is the SG phase angle, ωG is the SG rotor speed, ωs is the synchronous speed (equivalent to ω0 for a two pole machine), M = 2H ωs where H is the inertia of the machine, pm,G is the pre-converter power, pe,G is the electrical power, and D is the damper winding component. The governor dynamics of the SG can be approximated by the slowest action as: RD −1 (ωo − ωG ) − (pm,G − pm,G,o ) ṗm,G = (6) τG where RD is the droop setting of the device (it includes a factor of 2π), pm,G,o is the pre-converter power set point, and τG is the governor response time. The value of τG can vary substantially depending on type and model, but is generally not less than 0.5 s [17]. Taking (5) within the derivative of (6), it can be concluded that pm,G has a second order relation to pe,G : p̈m,G −RD −1 ω̇G − ṗm,G = τG −1 −(RD M ) (pm,G − pe,G ) − ṗm,G = τG (7) (8) Therefore, pm,G has a second order relation to pe,G , as compared to the first order relation seen with the GFM device. Furthermore, it can be stated that pm,G is a function of frequency, the inverse of the GFM pre-converter–frequency relationship. More simply, it can be said that whereas the SG is a reactive device, the GFM is a proactive device, with respect to frequency. III. S INGULAR P ERTURBATION A NALYSIS A common practice in the mathematical formulation and analysis of power systems is the utility of singular perturbation theory, wherein dynamical equations are reduced to algebraic expressions because the associated dynamics are too fast to be of interest [27]. Within the context of power system dynamics analysis, this is most transparent in the algebraic treatment of the transmission system. Here, we apply this tool to the frequency dynamic analysis of the GFM and SG. Note that both (1) and (6) are first order differential equations, with time constants τI and τG . There is, in general, an order of magnitude of separation between these values; i.e. τI << τG . Therefore, where the time scale of interest is the settling of frequency dynamics associated with the SG, using the foundations of singular perturbation analysis, ṗm,I can be assumed 0; thus, according to (1), pm,I ≈ pe,I . Due to the relatively slower response of the SG governor, immediately following a disturbance the difference between pm,G,o and pm,G is negligible; i.e., pm,G,o ≈ pm,G . Applying these approximations, the frequency dynamics relevant before substantial SG governor action of the GFM ((2) and (3)) and SG ((4) and (5)) can be reformulated. The approximated GFM frequency dynamics are given in (9): δ̇I = MP (pm,I,o − pe,I ) ∝ −MP pe,I (9) The SG dynamics are given in (10) and (11): δ̇G = ωG − ωo (10) 1 (pm,G,o − pe,G ) ω̇G = M (11) pe,G ∝− M From (9), it can be concluded that GFM frequency is algebraically related to pe,I ; therefore, considering the first order relation of pe,I and pm,I in (1), GFM frequency has a first order relation with pre-converter power. From (10) and (11), with respect to pe,G the frequency dynamics of the SG follow a first order response; therefore, with (6), the frequency dynamics of the SG have a second order relation with preconverter power. A. Device Step Response The conclusion that the SG manifests a second-order frequency dynamic is extensively studied and well understood [17], [26]. However, our analytical model suggests that the GFM exhibits a first order response. For verification, we simulate the frequency response of the SG and GFM following a load. All simulations are performed in the power system computer aided design (PSCAD) [28] simulation platform. Frequency, rate of change of frequency (ROCOF), and inertia metrics are defined as in the Appendix. The GFM model is a full order, averaged model that was created based on the state of the art [10], [29] and is made available open-source at [30]. A full text on the model implementation is available at [25], with all default parameters listed. Parameters of note are MP = 0.05(Hz, pu/S, pu) 4 and τI = 0.05s. The SG model uses the standard PSCAD machine model with default prime–double prime reactance and time constants, two damper windings sans saturation and resistive windage losses. The exciter is an AC7B model with default parameters. All instances of SGs share a common set of parameters; for all 9 and 39 bus system simulations, RD = 0.05(Hz/Sbase ), H = 4s (inertia seconds), and τG = 0.5s. The single device tests examine varied H values to exhibit the traditional nadir (lowest frequency excursion) and rate of change of frequency relationship. The frequency and power step response of each device for a 10% load step are presented in Figs. 3 and 4. In this model, each device is operated in standalone fashion, dispatched at 50% with a constant power load connected directly to the terminals. The SG frequency trace in Fig. 3 shows the second order negative step response following the load step with overshoot and subsequent damped oscillations that settle to the droop determined steady state. The GFM frequency traces follows a standard first order response; steady state is achieved with no overshoot and a far smaller response time as compared to the SG. A summary of the nadir, and ROCOF are presented in Table I. Note the inverse proportionality between inertia and ROCOF and the correlation between a lower nadir and reduced inertia. Conversely, note the larger ROCOF of the GFM device but a resultant higher nadir. TABLE I: Single Device Step Response Results Device SG (H = 4s) SG (H = 3s) SG (H = 2s) SG (H = 1s) GFM ROCOF (Hz/s) 0.48 0.63 0.95 1.90 1.50 Nadir (Hz) 59.77 59.73 59.67 59.52 59.85 Settling Frequency (Hz) 59.85 59.85 59.85 59.85 59.85 singular perturbation application. The pm,G follows a second order response complete with overshoot and oscillations, as well as the initial acceleration and inflection change. Fig. 4: Power response of isolated GFM and SG devices to a 10% load step at a 50% initial loading. pe is identical for each device. The acceleration period of pm,G , a second order characteristic, is evident in the magnified window. The results of two standard benchmarks, the IEEE 9 and 39 bus test systems, that were used to validate our analysis are presented in the next two sections. IV. T EST C ASE I: IEEE 9 B US S YSTEM Simulations on the IEEE 9 bus test system were performed in the PSCAD simulation environment. The network and all associated dynamic elements are available open source at [30], [31]. Buses 4-9 are 230 kV, buses 1-3 are 16.5 kV, 18.0 kV, and 13.8 kV, respectively. All SG or GFM devices are rated at 200 MVA, with other pertinent parameters as established in Section III. The load is modelled as constant power with no frequency or voltage dependence. A 10% load step (31.5 MW, 11.5 MVar) occurs at bus 6. Prior to the perturbation, the system is brought to steady state by initiating all devices as ideal sources, and then systematically releasing the associated dynamics in a manner conducive to maintaining steady state stability. Greater detail on this startup process can be found in [32]. Different interconnection scenarios of SG and GFMs into the system are created by systematically supplanting an SG with a GFM, as shown in Table II. TABLE II: 9 Bus Configuration and Results Fig. 3: Frequency response of isolated GFM and SG devices to a 10% load step at a 50% initial loading. The pe and pm responses of each device are presented in Fig. 4. Note that the pe response is identical for each device; because the voltage dynamics are near ideal, the electrical power is primarily determined by network changes and not the device dynamics. The slight pe overshoot is a relic of the constant power load modeling in PSCAD load impedance values are modulated every half cycle. The first order relation of pm,I and pe,G is obvious in the GFM traces, and at a much faster rate than the SG response, which corroborates the Scenario A B C D Device at Bus 1 2 3 SG SG SG GFM SG SG GFM GFM SG GFM GFM GFM Inertia (s) 4.0 2.6 1.3 0.0 ROCOF (Hz/s) 0.50 0.73 1.12 1.61 Nadir (Hz) 59.72 59.76 59.79 59.83 The results in Fig. 5 show the results for four simulations (scenarios A, B, C, and D - explained in Table II) where the the SGs are systematically replaced by the GFMs, resulting in a incremental decrease in H. These reduced values are captured in Table II, along with the the resultant nadir and ROCOF statistics for each scenario. It is evident that as the mechanical inertia is decreased, the nadir increases, which is indicative of the dominant first order response of the additional GFMs. Additionally, although the ROCOF increases as inertia 5 is reduced, it does not correlate with a lower nadir, as would be expected in a second order system. trajectories [15], [17]; these results show this assumption is no longer valid with GFM devices. The Scenario C frequency exhibits overshoot, but a smoother recovery; i.e. the concavity in the green trace from t = 1.5–2.5s is the inverse of the expected second order recovery. This system frequency trace is not representative of an overdamped second order system, nor a critically damped system which would follow a far more gradual trajectory to the settling frequency. The GFM devices are acting too quickly for all of the devices to remain synchronized during the first 0.5 s following the perturbation. In Scenario D, with all GFM devices, the system frequency follows a typical first order response where overshoot and similar frequency oscillations are absent. The device frequencies show that with all GFM, the devices maintain a general synchronization throughout the recovery. Fig. 5: Average system frequency response for varied quantities of GFM/SGs. Although the peak ROCOF grows with fewer online SGs, the nadir is simultaneously reduced. The system frequency oscillation period with all SGs (Scenario A) matches the single machine step response; i.e., 0.4 Hz oscillations. Individual device frequencies for each Scenario are presented in Fig. 6, where it is evident that for Scenario A, all three SGs have similar frequency trajectories; the three devices maintain broad synchronization following the perturbation. Herein lies the motivation for center of inertia and average frequency metrics. Fig. 7: Comparison of pre-converter and electrical powers of each device for the four 9 bus simulation scenarios. Note that Pe and GFM Pm are overlapped at these resolutions. Fig. 6: Initial frequency response of each device for the four simulated scenarios on the 9 bus system. Note the contrary motion present with mixed systems (scenario B and C), indicating an initial lack of broad synchronization. The Scenario B system frequency follows a standard second order step response with a damping value around 50%, with a brief inversion between 0.5–0.75s; this corroborates the assertion that droop controlled GFMs add to the damping of the system [15]. From Fig. 6, it is obvious that the three devices are not broadly synchronized immediately following the disturbance. The large GFM frequency changes are the cause of the average frequency inversion (Fig. 5) just after the perturbation. The bedrock assumption of average system frequency metrics is that all devices have similar frequency The pe and pm response for each scenario are presented in Fig. 7. The electrical powers show inter-area oscillations (f = 1.6Hz) between SG 1 and SG 2 in Scenario A. Note the time separation between these pe,G oscillations and pm,G . Scenario B shows the very rapid changes in pm,I –pe,I (these are indistinguishable at this resolution) of GFM 1, which exacerbates a larger peak pe,G of SG 2 and 3, while the subsequent oscillations are more damped. The peak pe,G output of SG 3 in Scenario C is further increased, although there are no oscillations following this overshoot. The conclusion is that the rapid frequency changes of the GFMs, evident in Fig. 6, cause the network conditions to change rapidly, while the SG frequency follows the slower second order response and resulting in a larger pe,G extraction. Therefore, the fast frequency change of the GFM forces the SG into larger oscillations because of its slow response and exacerbates the dynamic excursions. Scenario D power outputs show a 6 large reduction in power oscillations (including interarea), with minimal overshoot and a relatively rapid arrival to settling outputs. Frequency–power portraits are omitted for the 9 bus, due to strong similarities with the 39 bus results subsequently presented (Fig. 9). These 9 bus system results depict that the presence of GFM inverters reduces the average system frequency nadir, while increasing ROCOF. In a second order system, these two directional changes would not be correlated; the cause is due to the first order response of the GFM devices. The traditional average frequency determination methods therefore do not produce an appropriate metric with GFMs because the rapid changes of the GFM frequency result in device frequencies that are at times contrary and divergent to adjacent SGs, negating the fundamental assumption of these metrics. of the 39 bus test system in PSCAD with only inverters is a significant testament to the viability of zero inertia systems. V. T EST C ASE II: IEEE 39 B US S YSTEM Fig. 8: Average frequency response of 39 bus system for varied quantities of GFMs and SGs and a 10% load step at bus 15. The IEEE 39 bus test system [33] is also presented as a larger case study, with the entire system as simulated in PSCAD and supporting Python code available open-source at [30]. The network has been partitioned into 6 subsystems using the Bergeron parallelization components; a valuable contribution to future research. The network elements are unchanged. All buses operate at 230 kV, with a 230/18 kV generator step–up unit installed to connect all generation elements at 18 kV. All generation elements are rated at 1000 MVA. Dispatch and voltage set points are unchanged from the test system configuration. All ten initial SG devices are systematically replaced by GFMs, with a scenario defining each iteration; i.e. scenarios 0–10 in Table III. The 10% load step (600 MW/141 Mvar) occurs at bus 15. TABLE III: 39 Bus Configuration and Results Scenario 0 1 2 3 4 5 6 7 8 9 10 GFMs at Buses n/a 30 30–31 30–32 30–33 30–34 30–35 30–36 30–37 30–38 All GFM Inertia (s) 4.0 3.6 3.2 2.8 2.4 2.0 1.6 1.2 0.8 0.4 0.0 ROCOF (Hz/s) 0.567 0.587 0.669 0.808 0.930 1.071 1.225 1.396 1.525 1.648 1.852 The f –pm,I portraits for a selection of 39 bus system simulations are presented in Fig. 9, where the subtitles correspond with the Table III entry. With no GFMs, the SGs follow the trajectory of an initial frequency deviation prior to preconverter changes. Prior to convergence on the steady state values, the trajectories exhibit oscillations in the form of converging spirals. With half GFMs in scenario 5, the first order relation between frequency and pre-converter power is evident, while the SG trajectories are shortened with less overshoot. With only a single SG online in scenario 9, the SG exhibits no pre-converter power overshoot. This is due to the faster frequency oscillations, where the large governor response time does not permit a reaction. Scenario 10, with only GFMs online, exhibits the first order/quasi linear relationship between frequency and pm,I . Nadir (Hz) 59.690 59.712 59.717 59.724 59.730 59.738 59.748 59.748 59.756 59.772 59.808 Figure 8 shows the average frequency for each of the 11 scenarios simulated on the 39 bus system. Along with the frequency statistics presented in Table III, it is concluded that while ROCOF increases with larger quantities of GFMs and a resultant decrease in system mechanical inertia, the nadir is raised. Additionally, the the nadir occurs sooner after the load step. The damping of the frequency oscillations increases with a larger quantity of GFMs. The average frequency shows more variance immediately following the disturbance with larger quantities of GFM. These unusual frequency traces are the result of the at times contrary GFM frequency as compared to the SG units, further diminishing the bedrock assumptions of average frequency metrics. Here, it is noted that the simulation Fig. 9: Frequency–power portraits of each device for scenario 0, 5, 9, and 10 for the 10% load step on the 39 bus test system. VI. D ISCUSSION With only reactive devices such as SGs (see Section II-B) matching system aggregate pm to pe and the associated slow 7 governor response (6), a larger ROCOF generally yields a deeper nadir for the same magnitude power imbalance [34]. Consider the following approximating equation: ∆fprior = αROCOF × tresponse (12) where ∆fprior is the frequency deviation prior to substantive pm,G changes, αROCOF is the ROCOF for a particular system, and tresponse is the pre-converter power response time (as used in (1) and (6)). Evidently, a relatively larger ROCOF for the same tresponse (such as τG , in (6)), yields a larger ∆fprior before substantial pm changes take place. This is the wellknown inertial response period when rotational kinetic energy (Eint,G ) is extracted from the SGs; for SG frequency response dominated systems, less inertia yields larger αROCOF values, which are susceptible to lower nadirs potentially triggering frequency load shedding [35]. This is corroborated by the simulation results presented in Table I for a single device. A defining feature in this relationship is the reactive nature of SGs to frequency; the frequency must change prior to a change in pm,G . This relation is inverted with a GFM device; when pe,I changes due to varying network conditions, pm,G is directly impacted prior to any change in frequency. However a GFM changing frequency is a control response, ostensibly designed to achieve some type of load sharing, and not the result of a necessary chain of events to match pe,I and pm,I as for an SG. Therefore and as derived in Section III, the preconverter–frequency relationship is of lower order with GFMs. Resulting from this lower order relationship is a reduction in frequency dynamics in the presence of GFMs as presented in the simulation results of Sections IV and V, where it is evident that the standard inertial frequency response of SG dominated systems is no longer to be expected with GFM devices. Fig. 10: Nadir and ROCOF as a function of mechanical inertia for the single device, 9 bus, and 39 bus systems following a 10% load step. Figure 10 summarizes the relation between ROCOF and Nadir of the single SG device, 9 bus, and 39 bus test systems as a function of mechanical inertia. The data presented is from Tables I II and III. Evident is the standard anti-correlation between larger ROCOF and lower nadirs in the traditional, SG dominated power systems; these are approximated with the single device system, which is de facto the center of inertia response. In the presence of GFM devices, this relation is no longer present, as shown by the now correlated nadir and ROCOF data for the 9 and 39 bus systems. Here, it is noted that there are potential broader issues due to larger ROCOFs such as relay tripping, device disconnection, and machine shaft strain, but the analysis of these considerations is beyond the scope of this work. However, the ability to greatly reduced the severity in nadirs with GFM may out weigh these other potential issues. VII. C ONCLUSION This work investigated the power transfer dynamics of synchronous generators and grid forming inverters and the driving factors associated with these dynamics. It was shown analytically that grid forming devices have a lower order relation between electrical and pre-converter power as compared to the synchronous generator, which results in a reduction in device frequency dynamics. From these relations, it was demonstrated that the multi-loop droop grid forming inverter is a proactive device with respect to frequency and pre-converter power, contrasting with the reactive nature of the synchronous generator. As implemented in the 9 and 39 bus test systems, it was shown that the traditional frequency metric relations of larger rate of change of frequency and nadir are decoupled in the presence of these grid forming devices. R EFERENCES [1] R. W. Kenyon, M. Bossart, M. Marković, K. Doubleday, R. MatsudaDunn, S. Mitova, S. A. Julien, E. T. Hale, and B.-M. Hodge, “Stability and control of power systems with high penetrations of inverter-based resources: An accessible review of current knowledge and open questions,” Solar Energy, Jun. 2020. [Online]. Available: http://www.sciencedirect.com/science/article/pii/S0038092X20305442 [2] B. Kroposki, B. Johnson, Y. Zhang, V. Gevorgian, P. Denholm, B. Hodge, and B. Hannegan, “Achieving a 100% Renewable Grid: Operating Electric Power Systems with Extremely High Levels of Variable Renewable Energy,” IEEE Power and Energy Magazine, vol. 15, no. 2, pp. 61–73, Mar. 2017. [3] F. Milano, F. Dörfler, G. Hug, D. J. Hill, and G. Verbič, “Foundations and Challenges of Low-Inertia Systems,” in 2018 Power Systems Computation Conference (PSCC), Jun. 2018, pp. 1–25. [4] A. Sajadi, L. Strezoski, V. Strezoski, M. Prica, and K. A. Loparo, “Integration of renewable energy systems and challenges for dynamics, control, and automation of electrical power systems,” WIREs Energy and Environment, vol. 8, no. 1, p. e321, 2019, eprint: https://onlinelibrary.wiley.com/doi/pdf/10.1002/wene.321. [Online]. Available: https://onlinelibrary.wiley.com/doi/abs/10.1002/ wene.321 [5] A. Ulbig, T. S. Borsche, and G. Andersson, “Impact of Low Rotational Inertia on Power System Stability and Operation,” IFAC Proceedings Volumes, vol. 47, no. 3, pp. 7290–7297, Jan. 2014. [6] NERC, “Integrating Inverter Based Resources into Low Short Circuit Strength Systems,” North American Electric Reliability Corporation, Atlanta, GA, NERC Reliability Guideline, Dec. 2017. [7] W. Wang, G. M. Huang, P. Kansal, L. E. Anderson, R. J. O’Keefe, D. Ramasubramanian, P. Mitra, and E. Farantatos, “Instability of PLLSynchronized Converter-Based Generators in Low Short-Circuit Systems and the Limitations of Positive Sequence Modeling,” in 2018 North American Power Symposium (NAPS), Sep. 2018, pp. 1–6. [8] N. Hatziargyriou, J. V. Milanovic, C. Rahmann, V. Ajjarapu, C. Canizares, I. Erlich, D. Hill, I. Hiskens, I. Kamwa, B. Pal, P. Pourbeik, J. J. Sanchez-Gasca, A. Stankovic, T. Van Cutsem, and C. Vournas, “Stability definitions and characterization of dynamic behavior in systems with high penetration of power electronic interfaced technologies,” IEEE Power and Energy Society, Tech. Rep. PES-TR77, Apr. 2020. 8 [9] J. Matevosyan, B. Badrzadeh, T. Prevost, E. Quitmann, D. Ramasubramanian, H. Urdal, S. Achilles, J. MacDowell, S. H. Huang, V. Vital, J. O’Sullivan, and R. Quint, “Grid-Forming Inverters: Are They the Key for High Renewable Penetration?” IEEE Power and Energy Magazine, vol. 17, no. 6, pp. 89–98, Nov. 2019, conference Name: IEEE Power and Energy Magazine. [10] T. Qoria, Q. Cossart, C. Li, X. Guillaud, F. Gruson, and X. Kestelyn, Deliverable 3.2: Local Control and Simulation Tools for Large Transmission Systems. MIGRATE, Dec. 2018. [11] U. Markovic, O. Stanojev, E. Vrettos, P. Aristidou, and G. Hug, “Understanding Stability of Low-Inertia Systems,” Feb. 2019. [Online]. Available: https://doi.org/10.31224/osf.io/jwzrq [12] M. M. S. Khan, Y. Lin, B. Johnson, V. Purba, M. Sinha, and S. Dhople, “A Reduced-order Aggregated Model for Parallel Inverter Systems with Virtual Oscillator Control,” in 2018 IEEE 19th Workshop on Control and Modeling for Power Electronics (COMPEL). Padua: IEEE, Jun. 2018, pp. 1–6. [Online]. Available: https://ieeexplore.ieee.org/document/8458494/ [13] A. Tayyebi, D. Groß, A. Anta, F. Kupzog, and F. Dörfler, “Frequency Stability of Synchronous Machines and Grid-Forming Power Converters,” arXiv:2003.04715 [cs, eess, math], Mar. 2020, arXiv: 2003.04715. [Online]. Available: http://arxiv.org/abs/2003.04715 [14] M. E. Elkhatib, W. Du, and R. H. Lasseter, “Evaluation of Inverterbased Grid Frequency Support using Frequency-Watt and Grid-Forming PV Inverters,” in 2018 IEEE Power Energy Society General Meeting (PESGM), Aug. 2018, pp. 1–5, iSSN: 1944-9925. [15] R. H. Lasseter, Z. Chen, and D. Pattabiraman, “Grid-Forming Inverters: A Critical Asset for the Power Grid,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 8, no. 2, pp. 925–935, Jun. 2020. [16] Y. Lin, J. H. Eto, B. B. Johnson, J. D. Flicker, R. H. Lasseter, H. N. V. Pico, G.-S. Seo, B. J. Pierre, and A. Ellis, “Research Roadmap on GridForming Inverters,” National Renewable Energy Lab. (NREL), Golden, CO, Tech. Rep. NREL/TP-5D00-73476, 2020. [17] P. W. Sauer, M. A. Pai, and Chow, J. H., Power System Dynamics and Stability: With Synchrophasor Measurement and Power System Toolbox, 2nd ed. Wiley-IEEE Press, 2017. [18] A. Yazdani and R. Iravani, Voltage-Sourced Converters in Power Systems: Modeling, Control, and Applications. John Wiley & Sons, 2010. [19] Y. Lin, B. Johnson, V. Gevorgian, V. Purba, and S. Dhople, “Stability Assessment of a System Comprising a Single Machine and Inverter with Scalable Ratings,” in 2017 North American Power Symposium (NAPS), Sep. 2017, pp. 1–6. [20] Q. Zhu, A. Bolzoni, A. Forsyth, and R. Todd, “Impact of Energy Storage System Response Speed on Enhanced Frequency Response Services,” in 2019 IEEE Energy Conversion Congress and Exposition (ECCE), Sep. 2019, pp. 2523–2529, iSSN: 2329-3748. [21] R. W. Kenyon, A. Hoke, J. Tan, and B. Hodge, “Grid-Following Inverters and Synchronous Condensers: A Grid-Forming Pair?” in 2020 Clemson University Power Systems Conference (PSC), Mar. 2020, pp. 1–7. [22] P. Piagi and R. H. Lasseter, “Autonomous control of microgrids,” in 2006 IEEE Power Engineering Society General Meeting, Jun. 2006, p. 8. [23] H. Beck and R. Hesse, “Virtual Synchronous Machine,” in 2007 9th International Conference on Electrical Power Quality and Utilisation, Oct. 2007, pp. 1–6. [24] B. B. Johnson, M. Sinha, N. G. Ainsworth, F. Dörfler, and S. V. Dhople, “Synthesizing Virtual Oscillators to Control Islanded Inverters,” IEEE Transactions on Power Electronics, vol. 31, no. 8, pp. 6002–6015, Aug. 2016. [25] R. W. Kenyon, A. Sajadi, A. Hoke, and B.-M. Hodge, “Open-Source PSCAD Grid-Following and Grid-Fomring Inverters and A Benchmark for Zero-Inertia Power System Simulations.” [26] J. Machowski, J. Bialek, and J. Bumby, Power System Dynamics: Stability and Control, 2nd ed. Wiley, 2008. [27] J. H. Chow, J. R. Winkelman, M. A. Pai, and P. W. Sauer, “Singular perturbation analysis of large-scale power systems,” International Journal of Electrical Power & Energy Systems, vol. 12, no. 2, pp. 117–126, Apr. 1990. [Online]. Available: http://www.sciencedirect.com/ science/article/pii/014206159090007X [28] Manitoba Hydro International Ltd, “PSCAD.” [Online]. Available: https://www.mhi.ca/products/pscad [29] W. Du, Z. Chen, K. P. Schneider, R. H. Lasseter, S. Pushpak, F. K. Tuffner, and S. Kundu, “A Comparative Study of Two Widely Used GridForming Droop Controls on Microgrid Small Signal Stability,” IEEE Journal of Emerging and Selected Topics in Power Electronics, pp. 1–1, 2019. [30] R. W. Kenyon, “PyPSCAD,” Golden, CO, Nov. 2020, original-date: 2020-11-09T20:50:43Z. [Online]. Available: https://github.com/NREL/ PyPSCAD [31] Manitoba Hydro International Ltd, “IEEE 9 Bus System.” [Online]. Available: https://www.pscad.com/knowledge-base/article/25 [32] R. W. Kenyon, B. Wang, A. Hoke, J. Tan, C. Antonio, and B.-M. Hodge, “Validation of Maui PSCAD Model: Motivation, Methodology, and Lessons Learned: Preprint,” in Renewable Energy, 2021, p. 9. [Online]. Available: https://www.nrel.gov/docs/fy21osti/76808.pdf [33] Manitoba Hydro International Ltd, “IEEE 39 Bus System.” [Online]. Available: https://www.pscad.com/knowledge-base/article/28 [34] Inverter-Based Resource Performance Task Force, “Fast Frequency Response Concepts and Bulk Power System Reliability Needs,” NERC, Atlanta, GA, Tech. Rep., Mar. 2020. [35] North American Electric Reliability Corporation, Standard PRC-006-2 Automatic Underfrequency Load Shedding. Atlanta, GA: NERC, Aug. 2017. A PPENDIX A. Average System Frequency The frequency at a generation bus is defined as the shaft rotation speed for an SG, or the control system derived frequency for a GFM. The center of inertia system frequency formulation, where an aggregate system frequency response can be derived based on the summation of SG parameters system wide [15], [17], is not used because the method will not capture the frequency regulation of the zero inertia GFMs; i.e. this metric lacks applicability to these zero inertia devices. To arrive at a system average frequency, f (t), each device frequency is weighted according to the device rating, as shown in (13): Pn (M V Ai ∗ fi (t)) Pn f (t) = i=1 (13) i=1 M V Ai where fi (t) is the frequency of device i at time t, M V Ai is the device i rating, and n is the number of devices. B. Rate of Change of Frequency ROCOF, with respect to the rotation speed of a SG, is a continuous function; however, for practical purposes such as device action (i.e., protection, inverter response, etc.) it is calculated with a sliding window averaging method, as shown in (14): f (t + TR ) − f (t) f˙(t) := (14) TR where f is the frequency, and TR is the size, in seconds, of the sliding window. A TR = 100 ms window is used, in accordance with [34]. The largest absolute ROCOF value during a particular event is the result presented. C. Mechanical Inertia An aggregate mechanical inertia value is calculated as: (15). This serves the purpose of quantifying the changeover from inertial devices, SGs, to non-inertial devices, GFMs. Lower inertia here implies a greater quantity of generation supplanted by GFMs. Pn i=1 Hi SB,i H= P (15) n i=1 SB,i where Hi is the inertia rating (in s) of device i, SB,i is the MVA rating of device i, and n is the number of devices.