Uploaded by Lynnet Lucy

Introduction to transformers

advertisement
INTRODUCTION TO TRANSFORMERS
Introduction
A transformer is a device which uses the phenomenon of mutual induction to change the
values of alternating voltages and currents. In fact, one of the main advantages of a.c.
transmission and distribution is the ease with which an alternating voltage can be
increased or decreased by transformers.
Losses in transformers are generally low and thus efficiency is high. Being static, they
have a long life and are very stable. Transformers range in size from the miniature units
used in electronic applications to the large power transformers used in power stations.
The principle of operation is the same for each. A transformer is represented in Figure
1(a) as consisting of two electrical circuits linked by a common ferromagnetic core. One
coil is termed the primary winding, which is connected to the supply of electricity, and
the other the secondary winding, which may be connected to a load. A circuit diagram
symbol for a transformer is shown in Figure 1(b)
S1
I1
+
+
E1
-
E2
-
N1
a
t
=
N
N
S2
I2
N2
1
(b)20.2 Transformer principle
Figure 1: A Basic single-phase two-winding transformer and
its schematic equivalent circuit
2
Transformer principle of operation
When the secondary is an open-circuit and an alternating voltage V1 is applied to the primary
winding, a small current called the no-load current I0 – flows, which sets up a magnetic flux
in the core. This alternating flux links with both primary and secondary coils and induces in
them e.m.f.s of E1 and E2, respectively, by mutual induction. The induced e.m.f. E in a coil of
N turns is given by
where dΦ/dt is the rate of change of flux. In an ideal transformer, the rate of change of flux is
the same for both primary and secondary and thus E1/N1=E2/N2, i.e. the induced e.m.f. per
turn is constant.
Assuming no losses, E1=V1 and E2=V2. Hence
V1/V2 is called the voltage ratio and N1/N2 the turns ratio, or the ‘transformation ratio’ of the
transformer. If N2 is less than N1 then V2 is less than V1 and the device is termed a step-down transformer.
If N2 is greater, then N1 then V2 is greater than V1 and the device is termed a step-up transformer. When a
load is connected across the secondary winding, a current I2 flows. In an ideal transformer losses are
neglected and a transformer is considered to be 100% efficient.
Hence input power = output power, or V1 I1 = V2 I2, i.e. in an ideal transformer, the primary and secondary
volt-amperes are equal.
𝑉𝑉
𝐼𝐼
Thus, 1 = 2
(2)
𝑉𝑉2
𝐼𝐼1
Combining equations (1) and (2) gives:
𝑉𝑉1
𝑁𝑁1
𝐼𝐼2
=
=
3
𝑉𝑉2
𝑁𝑁2
𝐼𝐼1
The rating of a transformer is stated in terms of the volt-amperes that it can transform without overheating.
With reference to 1(a), the transformer rating is either V1I1 or V2I2, where I2 is the full load secondary current.
Problem 1. A transformer has 500 primary turns and 3000 secondary turns. If the primary voltage is
240 V, determine the secondary voltage, assuming an ideal transformer.
Solution
For an ideal transformer, voltage ratio = turns ratio, i.e
𝑉𝑉1
𝑁𝑁1
240
500
=
, β„Žπ‘’π‘’π‘’π‘’π‘’π‘’π‘’π‘’
=
𝑉𝑉2
3000
𝑉𝑉2
𝑁𝑁2
Thus secondary voltage 𝑉𝑉2 =
3000 240
500
= 1440 V or 1.44 kV
Problem 2. An ideal transformer with a turns ratio of 2:7 is fed from a 240 V supply. Determine its
output voltage.
Solution
A turns ratio of 2:7 means that the transformer has 2 turns on the primary for every 7 turns on the
secondary (i.e. a step-up transformer). Thus,
𝑁𝑁1
2
=
7
𝑁𝑁2
𝑉𝑉
𝑁𝑁
2
240
For an ideal transformer, 1 = 1 ; β„Žπ‘’π‘’π‘’π‘’π‘’π‘’π‘’π‘’ =
𝑉𝑉2
𝑁𝑁2
Thus the secondary voltage 𝑉𝑉2 =
7 240
2
7
= 840 V
𝑉𝑉2
Problem 3. An ideal transformer has a turns ratio of 8:1 and the primary current is 3A when it is
supplied at 240 V. Calculate the secondary voltage and current.
Solution
𝑁𝑁
8
A turns ratio of 8:1 means, 1 = , i.e. a step-down transformer.
𝑁𝑁2
Also,
𝑁𝑁1
𝑁𝑁2
=
1
𝑉𝑉1
𝑁𝑁1
𝑁𝑁2
=
π‘œπ‘œπ‘œπ‘œ 𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣 𝑉𝑉2 = 𝑉𝑉1
𝑉𝑉2
𝑁𝑁2
𝑁𝑁1
𝐼𝐼2
; β„Žπ‘’π‘’π‘’π‘’π‘’π‘’π‘’π‘’
𝐼𝐼1
𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐𝑐 𝐼𝐼2 = 𝐼𝐼1
𝑁𝑁1
𝑁𝑁2
= 3
8
1
1
= 240
8
= 𝟐𝟐𝟐𝟐 𝑨𝑨
= 30 𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉𝑉
Problem 4. An ideal transformer, connected to a 240 V mains, supplies a 12 V, 150 W lamp. Calculate
the transformer turns ratio and the current taken from the supply.
Solution
𝑃𝑃
150
= 12.5 𝐴𝐴
𝑉𝑉1 = 240 𝑉𝑉, 𝑉𝑉2 = 12 𝑉𝑉, 𝐼𝐼2 =
=
𝑉𝑉2
12
𝑉𝑉1
𝑁𝑁1
240
= 𝟐𝟐𝟐𝟐
𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇 π‘Ÿπ‘Ÿπ‘Ÿπ‘Ÿπ‘Ÿπ‘Ÿπ‘Ÿπ‘Ÿπ‘Ÿπ‘Ÿ =
=
=
12
𝑉𝑉2
𝑁𝑁2
𝑉𝑉1
𝐼𝐼2
𝑉𝑉2
12
=
, 𝑓𝑓𝑓𝑓𝑓𝑓𝑓𝑓 𝑀𝑀𝑀𝑀𝑀𝑀𝑀𝑀,
𝐼𝐼1 = 𝐼𝐼2
= 12.5
240
𝑉𝑉2
𝐼𝐼1
𝑉𝑉1
Hence, current taken from the supply, 𝐼𝐼1 =
12.5
20
= 𝟎𝟎. πŸ”πŸ”πŸ”πŸ”πŸ”πŸ” 𝑨𝑨
Problem 5. A 5 kVA single-phase transformer has a turns ratio of 10:1 and is fed
from a 2.5 kV supply. Neglecting losses, determine (a) the full load secondary
current, (b) the minimum load resistance which can be connected across the
secondary winding to give full load kVA and (c) the primary current at full load kVA
Solution
𝑁𝑁1
10
(a)
=
π‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Ž 𝑉𝑉1 = 2.5 π‘˜π‘˜π‘˜π‘˜ = 2500 𝑉𝑉
𝑁𝑁2
1
𝑉𝑉1
𝑁𝑁1
𝑁𝑁2
1
= 250 𝑉𝑉
=
, 𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠 𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣𝑣 𝑉𝑉2 = 𝑉𝑉1
= 2500
10
𝑉𝑉2
𝑁𝑁2
𝑁𝑁1
The transformer rating in volt-amperes = V2 I2 (at full load), i.e. 5000 = 250 I2
500
Hence full load secondary current 𝐼𝐼2 =
= 𝟐𝟐𝟐𝟐𝟐𝟐
𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆𝑆
(b) Minimum value of load resistance,
(c)
𝑁𝑁1
𝑁𝑁2
=
𝐼𝐼2
, from
𝐼𝐼1
250
𝑉𝑉
RL = 2
𝐼𝐼2
=
which primary current, 𝐼𝐼1 =
250
= 𝟏𝟏𝟏𝟏. πŸ“πŸ“ 𝛀𝛀
20
𝑁𝑁
1
𝐼𝐼2 2 = 20
𝑁𝑁1
10
= 𝟐𝟐 𝑨𝑨
Transformer no-load phasor diagram
The core flux is common to both primary and secondary windings in a transformer and is thus taken as the reference phasor in a
phasor diagram. On no-load the primary winding takes a small no- load current I0 and since, with losses neglected, the primary
winding is a pure inductor, this current lags the applied voltage V1 by 90β—¦. In the phasor diagram, assuming no losses, shown in
Figure 2(a), current I0 produces the flux and is drawn in phase with the flux. The primary induced e.m.f. E1 is in phase opposition
to V1 (by Lenz’s law) and is shown 180β—¦ out of phase with V1 and equal in magnitude. The secondary induced e.m.f. is shown for
a 2:1 turns ratio transformer.
Figure 2
(ii) A no-load phasor diagram for a practical transformer is shown in Figure 2(b). If current flows then losses will occur. When
losses are considered then the no-load current I0 is the phasor sum of two components – (a) IM, the magnetizing component, in
phase with the flux, and (b) IC, the core loss component (supplying the hysteresis and eddy current losses).
From Figure 2(b): No-load current,𝐼𝐼0 =
2
𝐼𝐼𝑀𝑀
+ 𝐼𝐼𝐢𝐢2 , where
𝑰𝑰𝑴𝑴 = π‘°π‘°πŸŽπŸŽ 𝐒𝐒𝐒𝐒𝐒𝐒 π“π“πŸŽπŸŽ 𝒂𝒂𝒂𝒂𝒂𝒂 𝑰𝑰π‘ͺπ‘ͺ = π‘°π‘°πŸŽπŸŽ 𝐂𝐂𝐂𝐂𝐂𝐂 π“π“πŸŽπŸŽ
Power factor on no-load = 𝐂𝐂𝐂𝐂𝐂𝐂 π“π“πŸŽπŸŽ =
𝑰𝑰π‘ͺπ‘ͺ
π‘°π‘°πŸŽπŸŽ
The total core losses (i.e. iron losses) = 𝑉𝑉1 π‘°π‘°πŸŽπŸŽ 𝐂𝐂𝐂𝐂𝐂𝐂 π“π“πŸŽπŸŽ
Problem 6. A 2400V/400V single-phase transformer takes a no-load current of 0.5A and the core loss is 400W.
Determine the values of the magnetizing and core loss components of the no-load current. Draw to scale the noload phasor diagram for the transformer.
Solution
V1 = 2400 V, V2 = 400 V, I0 = 0.5A
Core loss (i.e. iron loss) = 400 = V1 I0 𝐂𝐂𝐂𝐂𝐂𝐂 π“π“πŸŽπŸŽ = (2400)(0.5) 𝐂𝐂𝐂𝐂𝐂𝐂 π“π“πŸŽπŸŽ
400
Hence 𝐢𝐢𝐢𝐢𝐢𝐢∅0 =
= 0.3333
2400 0.5
∅0 = Cos −1 0.3333 = 70.530
The no-load phasor diagram is shown in Figure 3.
Magnetizing component, IM = I0 Sinφ0 = 0.5Sin70.53β—¦ = 0.471A
Core loss component, IC = I0 Cosφ0 = 0.5Cos70.53β—¦ = 0.167A
Figure 3: Phasor diagram
Problem 7. A transformer takes a current of 0.8A when its primary is connected to
a 240 volt, 50 Hz supply, the secondary being on open circuit. If the power
absorbed is 72 watts, determine (a) the iron loss current, (b) the power factor on noload and (c) the magnetizing current.
Solution
I0 = 0.8 A, V1 = 240 V
(a) Power absorbed = total core loss = 72 = V1 I0 cosφ0
Hence 72 = 240 I0 Cosφ0 and iron loss current, IC = I0 cosφ0 = 72/240 = 0.30A
(b) Power factor at no load, cosφ0= IC/I0 = 0.30/0.80 = 0.375
(c) From the right-angled triangle in Figure 2(b) and using Pythagoras’ theorem,
from which magnetizing current
𝐼𝐼0 =
2
𝐼𝐼𝑀𝑀
+ 𝐼𝐼𝐢𝐢2 , 𝐼𝐼𝑀𝑀 =
𝐼𝐼02 − 𝐼𝐼𝐢𝐢2
=
0.802 + 0.302
= 0.74A
E.m.f. equation of a transformer
The magnetic flux πœ™πœ™ set up in the core of a transformer when an alternating voltage is applied to its primary
winding is also alternating and is sinusoidal.
Let πœ™πœ™m be the maximum value of the flux and f be the frequency of the supply. The time for 1 cycle of the
alternating flux is the periodic time T, where T =1/f seconds. The flux rises sinusoidally from zero to its
maximum value in 1/4 cycle, and the time for 1/4 cycle is 1/4 f seconds.
πœ™πœ™
Hence the average rate of change of flux = π‘šπ‘š = 4π‘“π‘“πœ™πœ™π‘šπ‘š , and since 1Wb/s = 1 volt, the average e.m.f.
1/4𝑓𝑓
induced in each turn = 4π‘“π‘“πœ™πœ™π‘šπ‘š volts.
As the flux varies sinusoidally, then a sinusoidal e.m.f. will be induced in each turn of both primary and
secondary windings.
For a sine wave, form factor = r.m.s. value average value = 1.11
Hence r.m.s. value = form factor × average value = 1.11×average value
Thus r.m.s. e.m.f. induced in each turn = 1.11×4 f _m volts = 4.44 f πœ™πœ™π‘šπ‘š volts
Therefore, r.m.s. value of e.m.f. induced in primary,
E1 = 4.44 fπ“π“π’Žπ’Ž N1 volts
(4)
and r.m.s. value of e.m.f. induced in secondary,
E2 = 4.44 fπ“π“π’Žπ’Ž N2 volts
(5)
Dividing equation (4) by equation (5) gives:
𝐸𝐸1
𝑁𝑁1
=
, π‘Žπ‘Žπ‘Žπ‘Ž 𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝 π‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œ
𝐸𝐸2
𝑁𝑁2
Problem 8. A 100 kVA, 4000 V/200 V, 50 Hz single-phase transformer has 100 secondary turns. Determine (a) the primary
and secondary current, (b) the number of primary turns and (c) the maximum value of the flux.
Solution
V1 = 4000 V, V2 = 200 V, f = 50 Hz, N2 = 100 turns
(a) Transformer rating= V1 I1 = V2 I2 = 100 000 VA
Hence primary current, I1 = 100000/V1 = 100000/4000 = 25A and
Secondary current, I2 = 100000/V2 = 100000/200 = 500 A
(b) From
𝑉𝑉1
𝑉𝑉2
=
𝑁𝑁1
,
𝑁𝑁2
primary turns 𝑁𝑁1 = 𝑁𝑁2
𝑉𝑉1
𝑉𝑉2
(c) From equation (5), E2 = 4.44 f πœ™πœ™π‘šπ‘š N2,
𝐸𝐸
200
maximum flux πœ™πœ™π‘šπ‘š = 4.44 2𝑓𝑓𝑁𝑁 =
πŸ“πŸ“πŸ“πŸ“ 𝟏𝟏𝟏𝟏𝟏𝟏
1
= 100
πŸ’πŸ’.πŸ’πŸ’πŸ’πŸ’
4000
200
= 𝟐𝟐𝟐𝟐𝟐𝟐𝟐𝟐 𝒕𝒕𝒕𝒕𝒕𝒕𝒕𝒕𝒕𝒕
π‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Žπ‘Ž 𝐸𝐸1 = 𝐸𝐸2
= 9.01×10−3 Wb or 9.01 mWb
Problem 9. A single-phase, 50 Hz transformer has 25 primary turns and 300 secondary turns. The cross-sectional area of
the core is 300 cm2. When the primary winding is connected to a 250 V supply, determine (a) the maximum value of the flux
density in the core, and (b) the voltage induced in the secondary winding.
Solution
(a) From equation (4), e.m.f. E1 = 4.44 f πœ™πœ™π‘šπ‘š N1 volts. This implies 250 = 4.44(50) πœ™πœ™π‘šπ‘š (25)
Hence, maximum flux density, πœ™πœ™π‘šπ‘š =
250
(4.44)(50)(25)
π‘Šπ‘Šπ‘Šπ‘Š = 0.04505 π‘Šπ‘Šπ‘Šπ‘Š
However, πœ™πœ™π‘šπ‘š = Bm × A, where Bm = maximum flux density in the core and A = cross-sectional area of the core. Hence Bm ×
300 × 10−4 = 0.04505
from which, maximum flux density, π΅π΅π‘šπ‘š =
0.04505
300 ∗10−4
= 1.50𝑇𝑇
(b)
𝑉𝑉1
𝑉𝑉2
=
𝑁𝑁1
,
𝑁𝑁2
from which, voltage induced in the secondary winding 𝑉𝑉2 =
𝑉𝑉1
𝑁𝑁2
𝑁𝑁1
300
𝑉𝑉2 = 250
= πŸ‘πŸ‘πŸ‘πŸ‘πŸ‘πŸ‘πŸ‘πŸ‘ 𝑽𝑽 𝒐𝒐𝒐𝒐 πŸ‘πŸ‘πŸ‘πŸ‘πŸ‘πŸ‘
25
Problem 10. A single-phase 500 V/100 V, 50 Hz transformer has a maximum core flux density of 1.5 T and an effective core
cross-sectional area of 50 cm2. Determine the number of primary and secondary turns
Solution
The e.m.f. equation for a transformer is E =4.44 f πœ™πœ™π‘šπ‘š N
and maximum flux, πœ™πœ™π‘šπ‘š = B × A = (1.5)(50 ×10−4) = 75 × 10−4 Wb
Since E1 = 4.44 f πœ™πœ™π‘šπ‘š N1
Problem 11. A 4500 V/225 V, 50 Hz single-phase transformer is to have an approximate e.m.f. per turn of 15 V and
operate with a maximum flux density of 1.4 T. Calculate (a) the number of primary and secondary turns and (b) the crosssectional area of the core.
Solution
Transformer on-load phasor diagram
If the voltage drop in the windings of a transformer are assumed negligible, then the terminal
voltage V2 is the same as the induced e.m.f. E2 in the secondary. Similarly, V1 = E1.
Assuming an equal number of turns on primary and secondary windings, then E1 E2, and let
the load have a lagging phase angle φ2.
In the phasor diagram of Figure 4, current I2 lags V2 by angle φ2. When a load is connected
across the secondary winding a current I2 flows in the secondary winding. The resulting
secondary e.m.f. acts so as to tend to reduce the core flux. However this does not hap- pen
since reduction of the core flux reduces E1, hence a reflected increase in primary current I1÷
occurs which provides a restoring mmf. Hence at all loads, primary and secondary mmfs are
equal, but in opposition, and the core flux remains constant. I1÷ is sometimes called the
‘balancing’ current and is equal, but in the opposite direction, to current I2, as shown in
Figure 4. I0, shown at a phase angle φ0 to V1, is the no-load current of the transformer. The
phasor sum of I1÷ and I0 gives the supply current I1, and the phase angle between V1 and I1
is shown as φ1
Figure 4
Problem 12. A single-phase transformer has 2000 turns on the primary and
800 turns on the secondary. Its no-load current is 5 A at a power factor of 0.20
lagging. Assuming the volt drop in the windings is negligible, determine the
primary current and power factor when the secondary current is 100 A at a
power factor of 0.85 lagging.
Solution
Let 𝐼𝐼1′ be the component of the primary current which provides the restoring
mmf. Then
In the phasor diagram shown in Figure 5, I2=100 A is shown at an angle of φ2=31.8β—¦ to V2 and 𝐼𝐼1′ = 40A is
shown in anti-phase to I2
Figure 5
Transformer construction
There are broadly two types of single-phase double-wound transformer constructions – the core type and the shell type, as
shown in Figure 6. The low- and high-voltage windings are wound as shown to reduce leakage flux
Figure 6
(i) For power transformers, rated possibly at several MVA and operating at a frequency of 50 Hz, the core material
used is usually laminated silicon steel or stalloy, the laminations reducing eddy currents and the silicon steel keeping
hysteresis loss to a minimum.
(ii) Large power transformers are used in the main distribution system and in industrial supply circuits.
Small power transformers have many applications, examples including welding and rectifier supplies,
domestic bell circuits, imported washing machines, and so on.
(iii) For audio frequency (a.f.) transformers, rated from a few mVA to no more than 20 VA, and
operating at frequencies up to about 15 kHz, the small core is also made of laminated silicon steel. A
typical application of a.f. transformers is in an audio amplifier system.
(vi) Radio frequency (r.f.) transformers, operating in the MHz frequency region, have either an air
core, a ferrite core or a dust core. Ferrite is a ceramic material having magnetic properties similar to
silicon steel with a high resistivity. Dust cores consist of fine particles of carbonyl iron or permalloy
(i.e. nickel and iron), each particle of which is insulated from its neighbour. Radio frequency
transformers are used in radio and television receivers.
(vi) Transformer windings are usually of enamel-insulated copper or aluminium.
(vii) Cooling is achieved by air in small transformers and oil in large transformers.
Equivalent circuit of a Transformer
Figure 7 shows an equivalent circuit of a transformer. R1 and R2 represent the resistances of the primary and secondary
windings and X1 and X2 represent the reactances of the primary and secondary windings, due to leakage flux.
The core losses due to hysteresis and eddy currents are allowed for by resistance R which takes a current IC, the core loss
component of the primary current. Reactance X takes the magnetizing component IM.
In a simplified equivalent circuit shown in Figure 8, R and X are omitted since the no-load current I0 is normally only about
3–5% of the full load primary current.
It is often convenient to assume that all of the resistance and reactance is on one side of the transformer.
Resistance R2 in Figure 8 can be replaced by inserting an additional resistance 𝑅𝑅2′ in the primary circuit such that the
power absorbed in 𝑅𝑅2′ when carrying the primary current is equal to that in R2 due to the secondary current, i.e.
𝐼𝐼12 𝑅𝑅2′ = 𝐼𝐼22 𝑅𝑅2′ .
Thus,
𝑅𝑅2′
=
𝐼𝐼22
𝑅𝑅2 𝐼𝐼2
1
2
=
𝑉𝑉12
𝑅𝑅2 𝑉𝑉 2
2
2
Then the total equivalent resistance in the primary circuit Re is equal to the primary and secondary resistances of the actual
transformer. Hence
2 2
𝑉𝑉
1
𝑅𝑅𝑒𝑒 = 𝑅𝑅1 + 𝑅𝑅2′ = 𝑅𝑅1 + 𝑅𝑅2 2
𝑉𝑉2
Figure 8
By similar reasoning, the equivalent reactance in the primary circuit is given by
𝑋𝑋𝑒𝑒 = 𝑋𝑋1 +
2
′ 𝑉𝑉1
𝑋𝑋2 𝑉𝑉 2
2
2
(7)
The equivalent impedance Ze of the primary and secondary windings referred to the primary is given by:
𝑅𝑅𝑒𝑒2 + 𝑋𝑋𝑒𝑒2
(8)
𝑍𝑍𝑒𝑒 =
If φe is the phase angle between I1 and the volt drop I1 Ze then
𝑅𝑅
𝐢𝐢𝐢𝐢𝐢𝐢𝐢𝐢𝑒𝑒 = 𝑒𝑒
𝑍𝑍𝑒𝑒
(9)
The simplified equivalent circuit of a transformer is shown in Figure 9.
Figure 9
Problem 13. A transformer has 600 primary turns and 150 secondary turns. The primary and secondary
resistances are 0.25 Ω and 0.01Ω, respectively, and the corresponding leakage reactances are 1.0 Ω and 0.04 Ω,
respectively. Determine (a) the equivalent resistance referred to the primary winding, (b) the equivalent
reactance referred to the primary winding, (c) the equivalent impedance referred to the primary winding and (d)
the phase angle of the impedance.
Solution
Regulation of a transformer
When the secondary of a transformer is loaded, the secondary terminal voltage, V2, falls. As the power
factor decreases, this voltage drop increases. This is called the regulation of the transformer and it is
usually expressed as a percentage of the secondary no-load voltage, E2. For full-load conditions.
𝐸𝐸2 − 𝑉𝑉2
𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅𝑅 =
π‘₯π‘₯ 100%
10
𝐸𝐸2
The fall in voltage, (E2−V2), is caused by the resistance and reactance of the windings.
Typical values of voltage regulation are about 3% in small transformers and about 1% in large
transformers.
Problem 14. A 5kVA, 200V/400V, single-phase transformer has a secondary terminal voltage of
387.6 volts when loaded. Determine the regulation of the transformer.
Solution
Problem 15. The open-circuit voltage of a transformer is 240V. A tap-changing device is set to operate when
the percentage regulation drops below 2.5%. Determine the load voltage at which the mechanism operates.
Solution
Transformer losses and efficiency
There are broadly two sources of losses in transformers on load, viz: copper losses and iron losses.
(A) Copper losses are variable and result in a heating of the conductors, due to the fact that they possess resistance.
If R1 and R2 are the primary and secondary winding resistances then the total copper loss is I 2 R1 + I 2 R2
(B) Iron losses are constant for a given value of frequency and flux density and are of two types – hysteresis loss
and eddy current loss.
(i) Hysteresis loss is the heating of the core as a result of the internal molecular structure reversals which occur as
the magnetic flux alternates. The loss is proportional to the area of the hysteresis loop and thus low loss nickel iron
alloys are used for the core since their hysteresis loops have small areas.
(ii) Eddy current loss is the heating of the core due to e.m.f.s being induced not only in the transformer windings
but also in the core. These induced e.m.f.s set up circulating currents, called eddy currents. Owing to the low
resistance of the core, eddy currents can be quite considerable and can cause a large power loss and excessive
heating of the core. Eddy current losses can be reduced by increasing the resistivity of the core material or, more
usually, by laminating the core (i.e. splitting it into layers or leaves) when very thin layers of insulating material
can be inserted between each pair of laminations. This increases the resistance of the eddy cur- rent path, and
reduces the value of the eddy current.m
π‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œπ‘œ 𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝
𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖 𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝 − 𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙
=
𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇𝑇 𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸𝐸, πœ‚πœ‚ % =
𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖 𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝
𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖 𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝
𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙𝑙
11
= 1 −
𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖𝑖 𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝𝑝
It is not uncommon for power transformers to have efficiencies of between 95% and 98%.
Output power= V2 I2 cosφ2
total losses = copper loss + iron losses and input power = output power + losses
Problem 16. A 200 kVA rated transformer has a full-load copper loss of 1.5 kW and an iron loss of 1kW. Determine the
transformer efficiency at full load and 0.85 power factor.
Solution
Problem 17. Determine the efficiency of the transformer in worked Problem 16 at half full load and 0.85 power factor.
Solution
Problem 18. A 400 kVA transformer has a primary winding resistance of 0.5 K and a secondary winding
resistance of 0.001 K. The iron loss is 2.5 kW and the primary and secondary voltages are 5 kV and 320 V,
respectively. If the power factor of the load is 0.85, determine the efficiency of the transformer (a) on full
load, and (b) on half load.
Solution
Maximum efficiency
It may be shown that the efficiency of a transformer is a maximum when the variable copper loss (i.e. I 2 R1 + I 2 R2) is equal
to the constant iron losses.
Problem 19. A 500 kVA transformer has a full load copper loss of 4 kW and an iron loss of 2.5 kW. Determine (a) the output
kVA at which the efficiency of the transformer is a maximum, and (b) the maximum efficiency, assuming the power factor of
the load is 0.75
Solution
Autotransformers
An auto transformer is a transformer which has part of its winding common to the primary and secondary
circuits. Figure 14(a) shows the circuit for a double- wound transformer and Figure 14(b) that for an auto
transformer. The latter shows that the secondary is actually part of the primary, the current in the secondary
being (I2 – I1). Since the current is less in this section, the cross-sectional area of the winding can be reduced,
which reduces the amount of material necessary.
Figure 14
Figure 15 shows the circuit diagram symbol for an auto transformer.
Figure 15: Circuit diagram symbol for an auto transformer
Advantages of auto transformers
The advantages of auto transformers over double-wound transformers include:
1. A saving in cost since less copper is needed (see above)
2. Less volume, hence less weight
3. A higher efficiency, resulting from lower I 2 R losses
4. A continuously variable output voltage is achievable if a sliding contact is used
5. A smaller percentage voltage regulation
Disadvantages of auto transformers
The primary and secondary windings are not electrically separate, hence if an open-circuit occurs in the
secondary winding the full primary voltage appears across the secondary.
Uses of auto transformers
Auto transformers are used for reducing the voltage when starting induction motors and for
interconnecting systems that are operating at approximately the same voltage
Problem 20. A single-phase auto transformer has a voltage ratio 320 V: 250 V and supplies a load of 20 kVA at
250 V. Assuming an ideal transformer, determine the current in each section of the winding.
Solution
The current flowing in each section of the transformer is shown in Figure 16.
Figure 16
Three-phase transformers
Transformers not only enable current or voltage to be transformed to some different magnitude,
but provide a means of isolating electrically one part of a circuit from another when there is no
electrical connection between primary and secondary windings. An isolating trans- former is a
1:1 ratio transformer with several important applications such as bathroom shaver-sockets,
portable electric tools and model railways.
Three-phase transformers
Three-phase, double-wound transformers are mainly used in power transmission and are usually
of the core type. They basically consist of three pairs of single- phase windings mounted on one
core, as shown in Figure 17, which gives a considerable saving in the amount of iron used. The
primary and secondary wind- ings in Figure 17 are wound on top of each other in the form of
concentric cylinders, similar to that shown in Figure 6(a). The windings may be with the primary
delta-connected and the secondary star-connected, or star–delta, star–star or delta–delta, depending
on its use.
Figure 20.17
A delta connection is shown in Figure 18(a) and a star connection in Figure 18(b)
Problem 21. A three-phase transformer has 500 primary turns and 50 secondary turns. If the supply voltage is 2.4 kV,
find the secondary line voltage on no-load when the windings are connected (a) star–delta, (b) delta–star.
Solution
(a) For a star connection, VL = 3Vp
Current transformers
For measuring currents in excess of about 100 A, a current transformer is normally used. With a d.c. movingcoil ammeter the current required to give full-scale deflection is very small – typically a few milli-amperes.
When larger currents are to be measured a shunt resistor is added to the circuit. However, even with shunt
resistors added it is not possible to measure very large currents. When a.c. is being measured a shunt cannot be
used since the proportion of the current which flows in the meter will depend on its impedance, which varies
with frequency.
In current transformers, the primary usually consists of one or two turns whilst the secondary can have several
hundred turns. A typical arrangement is shown in Figure 19.
Figure 19
For example, if the primary has 2 turns and the secondary 200 turns, then if the
primary current is 500A,
Current transformers isolate the ammeter from the main circuit and allow the use of a standard range of
ammeters giving full-scale deflections of 1A, 2A or 5A. For very large currents the transformer core can be
mounted around the conductor or bus-bar. Thus the primary then has just one turn. It is very important to shortcircuit the secondary winding before removing the ammeter. This is because if current is flowing in the
primary, dangerously high voltages could be induced in the secondary should it be open-circuited. Current
transformer circuit diagram symbols are shown in Figure 20.
Figure 20
Problem 22. A current transformer has a single turn on the primary winding and a secondary winding of 60 turns. The
secondary winding is connected to an ammeter with a resistance of 0.15 K. The resistance of the secondary winding is
0.25 K. If the current in the primary winding is 300 A, determine
(a) the reading on the ammeter,
(b)
the potential difference across the ammeter and
(c)
the total load (in VA) on the secondary.
Solution
Voltage transformers
For measuring voltages in excess of about 500 V it is often safer to use a voltage
transformer. These are normal double-wound transformers with a large number of
turns on the primary, which is connected to a high voltage supply, and a small
number of turns on the secondary. A typical arrangement is shown in Figure 21.
Figure 21
Thus, if the arrangement in Figure 21 has 4000 primary turns and 20 secondary turns then for a
voltage of 22 kV on the primary, the voltage on the secondary.
Download