Uploaded by kgperera27

Assignment 1

advertisement
EE-4063 Power Electronic and Applications II
ASSIGNMENT 1
Name
:C.A.N. Yapa
Index No
:110651F
Power Conditioners
1. Power line disturbances are defined as any changes in power supply characteristics (voltage,
frequency, current) that would cause interferences to the normal operation of electrical equipment.
Types of power line disturbances
i.
ii.
iii.
iv.
v.
vi.
Transients
Interruptions
Undervoltages or sag
Overvoltages or swell
Waveform distortions
Voltage variations
i. Transients
This is the most damaging type of power line disturbance which can be further
categorized as impulsive transients and oscillatory transients. Impulsive transients sudden high peak
events that raise the voltage and/or current levels in either positive or negative direction. Oscillatory
transients are sudden changes in the steady state condition of a signal’s voltage, current or both at both
the positive and negative limits; oscillating at the natural system frequency. These oscillations usually
decay to zero within a cycle.
ii. Interruptions
This could be defined as the complete loss of supply voltage or load current and
depending on the duration it persists an interruption can be further categorized as given below.
Instantaneous – 0.5 to 30 cycles
Momentary – 30 cycles to 2 sec
Temporary – 2 sec to 2 min
Sustained – greater than 2 min
iii. Undervoltages or sags
Sag is defined as a reduction of AC voltage at a given frequency for the duration of 0.1
cycles to 1minute’s time whereas undervoltages are the result of long – term problems that create sags.
iv. Overvoltages or swell
Swell is having an increase in AC voltages for a duration of 0.5 cycles to 1 minute’s
time and overvoltages are the result of long – term problems that create swells.
v. Waveform distortions
Waveform distortions could be further categorized as;
DC offset – DC currents that are induced into the AC distribution system which could
transverse the AC power system and add an unwanted current component.
Harmonics – Corruption of the fundamental sine wave at frequencies that are multiples
of the fundamental.
Notching – Periodic voltage disturbances caused by electronic devices.
Noise – Unwanted voltage or current superimposed on the power system voltage or
current waveform.
vi. Voltage variation
A systematic variation of the voltage waveform or a series of random voltage changes
of small dimensions.
2. Lightning
Switching of inductive or capacitive loads
Utility fault clearing
Damages to the supply grid system due to destructive weather
Equipment failure
Starting of large loads
Sudden load reductions
Disturbances due to power electronic devices
Poor earthing systems
Electrostatic discharge
Lightning – This is the most damaging cause which basically causes impulsive transients on the
system both from direct lightning strikes as well as due to the induced current effect of the
electromagnetic field created by strikes to nearby conductive structures.
Switching of inductive or capacitive loads – Transients appear on an energized circuit when
capacitor banks are automatically switched into the system.
Starting of large loads – An induction motor draws approximately six times the nominal current
while starting up hence result in a significant voltage drop to the rest of the circuit it resides.
Sudden load reductions – This would cause an overvoltage condition in the system and typically
occurs during midnight where less loads are connected to the grid.
Disturbances due to power electronic devices – DC offsets are caused due to failure of the rectifiers
that are connected to the system and as well as notches in the voltage waveform are due to
electromagnetic interference of the power electronic drives which are extensively used in industries.
Further the advanced electronic drives inject harmonics to the grid supply at the Point of Common
Coupling (PCC) and cause noise in the voltage waveform.
Effects of the above mentioned disturbances on the sensitive equipment






Transients cause errors in results and damage the equipment such as burning of the entire
electronic control system.
Undervoltage or overvoltage situations result in errors in the equipment, shut down or damage
to sensitive equipment.
Sags can slow down the data processing systems hence resulting loss of data.
Voltage variations might result in permanent loss of data.
Harmonics affect the stability of the power supply hence cause malfunctioning of sensitive
equipment. Further harmonics alter the waveform parameters such as zero crossing and voltage
peak which are the typical quantities on which most of the modern power electronic controls
depend on thus affect the operation of the equipment adversely.
Interruptions shut off or damage the sensitive equipment.
3. Power conditioners have the ability to regulate and improve the quality of the power supplied by
delivering dynamic adjustments and removing spikes, surges, noise, sag and frequency irregularities
which affect adversely on the system performance.
A list of commonly used power conditioning techniques is as described below.
Surge protective devices
Voltage regulators
Uninterruptible Power Supplies
Isolation
Power Factor correction
i.
Surge protective devices
These devices are usually incorporated to the system with active line clamping thus
connected directly across the incoming power supply. They consist of Metal Oxide
Varistors (MOV), Transorbs, gas discharge or spark gap devices which will protect the
equipment from transients.
ii.
Voltage regulators
Voltage regulation is accomplished through several techniques including tap changing,
feroresonant transformer and double conversion methodology. In tap changing
mechanism transformer taps are switched automatically by a line voltage sensing circuit
hence to maintain the output voltage as closer as possible to the nominal voltage. A
feroresonant transformer is a non – linear transformer that is designed to provide
passive voltage regulation using magnetics. In double conversion, the incoming AC is
rectified, filtered and regulated and this regulated DC power is fed to an inverter to
obtain the regulated AC power.
iii.
Uninterruptible Power Supplies
iv.
Isolation
The power line input/output isolation is achieved through a transformer in various
configurations including simple standard core transformers and power toroidal type.
Isolation transformers provide broad band noise filtering hence reducing power line
disturbances.
v.
Power Factor correction
This is implemented either with active or passive circuits and is usually incorporated
with another power conditioning technique. Active power factor correction restores the
power waveform peak (undervoltages) which is reduced due to heavy loading of the
system whereas passive power factor correction is typically carried out by the utility
with the connection of large capacitor banks to the grid.
UPS
1. An Uninterruptible Power Supply provides protection against power outages and handles the voltage
regulation aspect as well during power line overvoltage and undervoltage situations. Further these are
used to suppress incoming line transients and harmonic disturbances.
2.
3.
i. Rectifier
The main functions of the rectifier of an UPS are to supply power to the inverter and to
maintain the battery bank charged. Different circuit arrangements can be incorporated in order to
achieve the required operation of the rectifier.
Phase controlled rectifier circuit
The control is obtained through the controlling of the firing angle of the thyristors.
Diode rectifier bridge in cascade with a step down dc – dc converter
In order to obtain a regulated dc voltage supply, the above described circuit arrangement can be
utilized. Controlling is achieved through PWM schemes that will handle the switching of the buck
converter.
DC – DC converter with electrical isolation
Output voltage is controlled using PWM schemes similar to the non – isolated arrangement of the dc –
dc converter.
ii. Battery
There are many battery systems that could be incorporated with the UPS but the most
commonly used is the lead – acid battery.
Rectifier and the separate battery charging circuit
Under normal operation with the line voltage present, a trickle charge voltage is applied across the
battery hence it draws a small amount of current and maintains itself in a fully charged state. During a
power outage the battery will supply the load. After the power has been restored the UPS is brought
back to the fully charged state which is achieved initially through a constant charging current state
until the voltage reaches the trickle voltage level and then charging in the constant voltage mode (at the
trickle voltage) with the current decreasing to the trickle charging current.
iii. Inverter
The UPS utilizes PWM dc – dc inverters giving either a single phase or three phase ac
output.
For large UPS systems, several inverter units are connected in parallel and connected through
transformers with phase shift so that the inverter could operate at a lower switching frequency. This
could be achieved through either low – frequency PWM, selective cancellation or a square – wave
switching scheme. The control of the above mentioned inverters are obtained through PWM switching
schemes.
Further it is also possible to use an inverter arrangement which incorporates resonant dc – dc
converters connect to an integral – half – cycle frequency converter through an isolation transformer.
4. A static transfer switch is used to transfer the load from the UPS to the grid supply and vice versa
and a schematic is as given below.
During the line is energized the load will be supplied through the grid supply whereas during a line
outage the load will be transferred to the UPS system.
In using a static transfer switch, the output of the inverter should be synchronized with the grid supply
therefore during the transferring process; the load will see a minimal amount of disturbance.
VAR Compensation
1. VAR compensation adjusts the reactive power that is supplied to the system hence maintain the
system voltage within a specified range around the nominal value (in Sri Lankan context +/- 5%) and
further provide dynamic voltage regulation which enhances the stability of the system. This can be
achieved through either power factor correction capacitor banks which compensates for slow changes
in reactive power whereas the Static Var Compensators provide quick control over the compensation.
Var compensation in turn reduces the current drawn by the equipment that is connected to the AC
system hence reduces the I2R losses.
2.
i. Thyristor – controlled inductors
A thyristor – controlled inductor acts as a variable inductor which is capable of
providing inductive vars to the system rapidly. Two back – to back thyristors which conduct in
alternate half cycles of the supply frequency are controlled by varying the position of the voltage
waveform at which they are gated into conduction. Both the thyristors are fired at equal delay angles.
Full conduction is obtained at a delay angle of 900 where as partial conduction is obtained between
delay angle of 900 and 1800. Increasing delay angle will reduce the fundamental component of the
current through the inductor which is equivalent to increasing of the effective inductance that is
connected to the system.
Equivalent per phase circuit is as shown below.
Variation of the inductor current with the delay angle is as shown below.
ii. Thyristor – switched capacitors
Thyristor switched capacitor is defined as a shunt – connected, thyristor switched
capacitor whose effective reactance is varied in a stepwise manner by full or zero conduction operation
of the thyristor valve. The susceptance is adjusted by controlling the number of parallel capacitors in
conduction. Each capacitor always conducts for an integral number of half – cycles. This control
mechanism is in contrast to the phase control method of thyristor – controlled inductors.
The capacitor bank will be brought to zero conduction by blocking the gate pulse to
both the thyristors. When turning on, the thyristors should be gated at the proper instant of maximum
ac voltage to limit overcurrents. The inductors are used to limit these switching overcurrents.
Incorporating a large number of thyristor – switched small capacitor banks it is possible to vary the
reactive power in small but discrete steps.
iii. Switching converter with minimum energy storage elements
The thyristor – controlled inductors and thyristor – switched capacitors incorporate
large energy storage devices in compensating vars of the system and are associated with an inherent
time lag thus unable to provide instantaneous control. Thus in order to overcome these issues, switch
mode converters that are operated in current control mode will be utilized thus the ac current could be
controlled quickly in the magnitude as well as the relationship of it to the voltage. Since the average
power drawn by these switch mode converters is zero, a DC source at the input of the converter is not
required instead a capacitor with a minimum energy storage capacity is sufficient whose voltage will
be maintained by the converter.
3.
i. Photovoltaic array interconnection
The solar cell characteristics for a given solar insolation level and temperature
comprises of two components, i.e. constant current component and the constant voltage component.
The maximum power is delivered by the PV array at the knee point of the characteristics which is the
point at which the above mentioned two components meet. In order to ensure that the array always
operates at the maximum power point, a tracking system is incorporated where the current drawn and
the resulting power output is observed and adjusted at regular intervals. In an instance where an
increase in current results in an increase in power, the current will be further increased until the power
output starts to decline and if an increase in current results in a reduction in the power output, the
current will be reduced until the power output reaches a maximum value.
The below described two interconnection methods are thus possible.

Single phase interconnection
Two alternative interconnection methods are possible in the single phase arrangement.
a. Line frequency, phase controlled converter that always operates in the inverter mode
and electrical isolation provided through a 60Hz transformer. AC side filter and var
compensators will be required since the output current has a lagging power factor,
containing harmonics.
b. Switch mode, pulse – width- modulated converter with electrical isolation provided
using a 60Hz transformer.
High frequency ac voltage is produced at the primary of the isolation transformer which
is rectified at the secondary end and interfaced with the line voltage through line – frequency, line –
voltage commutated thyristor inverter.

Three phase interconnection
As the power output exceeds several kilowatts it is required to incorporate a three phase
interconnection. This could be achieved through switching mode dc-ac inverter operating in the current
control mode where electrical isolation is provided through a 60Hz three phase transformer.
ii. Wind and small hydro interconnection
In wind power, the power output is proportional to the cube of the wind speed and in
small hydro power generation, this is proportional to the head and the flow rate. Thus in order to
harness maximum power output from these technologies it is desirable to allow the turbine speed to
vary in a wide range which is not possible with a synchronous generator which dictates a constant
speed. Thus an induction generator connected to the grid is incorporated and the efficiency of power
generation is optimized by rectifying the generator output and then interfaced with the grid supply with
the means of a switching dc – ac inverter with proper electrical isolation is provided through a 60Hz
transformer.
iii. Interconnection of energy storage systems to the utility grid
This technique could be incorporated to connect energy storage systems which could
store energy generated from efficient generating plant during low load conditions, to the utility grid
during the peak hours hence minimize the generation cost which arises due to utilization of fossil fuel
or gas fired power plants to cater the peak demand.
These energy storage devices can be batteries, fuel cells or superconductive inductors in which energy
is stored in the form of a magnetic field.
Batteries and fuel cells produce a dc output voltage thus the single phase or three phase
interconnection methods which are incorporated with the photovoltaic arrays could be utilized.
For superconductive inductors, 12 pulse line commutated converters in which the delay
angle is controlled to obtain continuously varying converter operation from full rectifier mode to full
inverter mode could be incorporated in connecting them to the utility grid.
Residential and Industrial Applications
2. Artificial lighting
High frequency fluorescent lighting is the best example for power electronic
applications in artificial lighting. The block diagram of this system is as shown below.
The high frequency electronic ballast converts the low frequency input (typically 50Hz)
to a high frequency output in the range of 25 – 40 kHz. The schematic of the high frequency electronic
ballast is given below.
High frequency ac is obtained by a dc – high frequency ac inverter which could be either a resonant
converter or a switch mode converter such as the half bridge topology.
Further a dimming circuit could be incorporated with these gas discharge lamps which
also involve power electronic controls.
By varying the firing angle of the triac which is fired by the means of a diac and a RC triggering
circuit, the intensity of the light could be varied. Less firing angle will result in more voltage across the
lamp hence more intensity of illumination and vice versa. During the operation in each half cycle,
depending on the value of VR1 the voltage across the capacitor C1 will vary hence if it reaches a value
greater than the breakover voltage of the diac the gate of the triac will be triggered.
Utility Interface
1.
Harmonics are of two variations, voltage harmonics and current harmonics. The main
causes for these harmonic types are the static power converters that are used for various purposes in
the industry such as adjustable speed drives, Switch – Mode Power Supplies (SMPS) and
Uninterruptible Power Supplies (UPS). These converters utilize semiconductor devices for power
conversion from ac to dc, dc to dc, dc to ac and ac to ac and draw nonlinear currents hence distort the
supply voltage waveform at the Point of Common Coupling (PCC). The nonlinear currents contain
high amplitude short pulses which are rich in harmonics and produce voltage drop across system
impedance.
Below described are certain sources of harmonics.






Phase controlled rectifiers (thyristor rectifiers) – These converters inject voltage notches
and draw power at a very low displacement power factor. This is mainly due to the fact
that the power through the converter is reversible although the current is unidirectional
which is not the case with uncontrolled rectifiers (diode rectifiers) where both the
current and power flow are unidirectional
Welding equipment
Variable speed drives
Periodic switching of voltages and currents
AC generators due to non-sinusoidal air gap and flux distribution
Switching devices like SMPS, UPS and CFL
Effects of harmonics on the utility








Increase the generator heating due to increased iron losses and copper losses which both are
proportional to the frequency hence increase due to increase of harmonics in the voltage and
current waveforms
Due to the effect of the harmonics, the transformers are affected by the increase of the core
losses due to eddy current and hysteresis and copper losses and stray flux losses which
contributes to the overheating of the windings and insulation. Further resonance between the
winding inductance and supply capacitance might occur, causing additional losses in the
transformer
Nonlinear load being connected to the distribution transformers, due to the triplen harmonics in
the phase currents not getting cancelled off results in a high current in the neutral conductor
overheating it and burning off
Cable losses, dissipated as heat, are substantially increased when carrying harmonic currents
due to elevated I2R losses
Circuit breakers of the system might trip prematurely and the operating time of the fuses will be
reduced due to the increased heating effect of the harmonic currents
Power cables carrying harmonic loads act to introduce EMI (electromagnetic interference) in
adjacent signal or control cables via conducted and radiated emissions
Any telemetry, protection or other equipment which relies on conventional measurement
techniques or the heating effect of current will not operate correctly in the presence of
nonlinear loads
Conventional meters are normally designed to read sinusoidal-based quantities. Nonlinear
voltages and currents impressed on these types of meters introduce errors into the measurement
circuits which result in false readings
2.
With the intention improving the power quality, standards and guidelines have been
imposed which specify the limits on the magnitude of the harmonic currents that could be inject to the
system by the consumers.





EN 50 006, Limitation of Disturbances in Electricity Supply Networks caused by Domestic
Appliances Equipped with Electronic Devices”, European Standard prepared by Comitè
Europèen de Normalisation Electro technique, CENELEC
IEC Norm 555 – 3, prepared by International Electrical Commission
West German Standards VDE 0838 for household appliances, VDE 0160 for converters and
VDE 0712 for fluorescent lamp ballasts
IEEE Guide for Harmonic Control and Reactive Compensation of Static Power Converters,
ANSI/IEEE Std. 519-1981, revised in 1992 to 512-1992
The revised IEEE – 519 specifies requirements on the user as well as on the utility
The table below defines the levels of harmonic currents that an industrial user can inject onto the utility
distribution system (120V through 69kV).
The below given table specifies the voltage distortion limits that can be reflected back onto the utility
distribution system.
3.
i. Passive Harmonic Filters (Line Harmonic Filters)
Passive or Line Harmonic Filters (LHF) are also referred to as harmonic trap filters and
are used to eliminate or control lower order harmonics which are more dominant specifically 5th, 7th,
11th and 13th. It is used either as a standalone part integral to a large nonlinear load such as 6 – pulse
drive or it can be used for a multiple small single – phase nonlinear load by connecting it to a
switchboard. LHF comprises of a passive L – C circuit which is tuned to a specific harmonic frequency
which is needed to be eliminated. The operation of this filter relies on the resonance principle that
occurs due to the variation in frequency in the inductor and the capacitor. These filters are susceptible
to the changes in source and load impedances and attract harmonics from other sources thus proper
design consideration should be given taking these into account.
ii. Active filters
Active filters are commonly used in industrial applications for both harmonic mitigation
and reactive power compensation. Unlike passive L–C filters, active filters do not present potential
resonance to the network and does not depend on the source impedance. The commonest configuration
is the shunt – connected active filters consisting of an IGBT bridge and DC bus architecture.
When rated correctly in terms of harmonic compensation current, the active filters provide
the nonlinear load current with the harmonic component that is required for its proper functioning
while the source will have to provide only the fundamental component thus minimizing waveform
distortions.
4. Electro Magnetic Interference (EMI) is generated in switching converters and power electronic
devices due to rapid changes in voltage and currents, in their operation with other equipment as well as
with its own proper operation. EMI is transmitted in two forms, radiated and conducted. Conducted
interferences are further divided into two forms namely, differential mode and common mode.
EMI standards
Various CISPR, IEC, VDE, FCC standards specify the maximum limit on the
conducted EMI.
The conducted noise will be measured by mean of the Line Impedance Stabilization Network (LISN)
which is specified impedance network and compared against the set standards.
EMI filters
An EMI filter is an electronic passive device which is used in order to suppress
conducted interference that is present on the power line. EMI filters can be used to suppress
interference that is generated by the device or by other equipment in order make a device more
immune to electromagnetic interference signals present in the environment. Most EMI filters consist of
components that suppress differential and common mode interference.
In either power supplies or electronic equipment, it is the function of the EMI filter to keep any
internally generated noise contained within the device and to prevent any external ac line noise from
entering the device. The inductive part of the EMI filter is designed to act as a low-frequency pass
device for the AC line frequencies and a high-frequency blocking device. Other parts of the EMI filter
use capacitors to bypass or shunt unwanted high-frequency noise away from the sensitive circuits. The
net result is that the EMI filter significantly reduces or attenuates any unwanted noise signals from
entering or leaving the protected electronic device.
Download