Desiccant dehumidification Desiccant dehumidification describes the use of a moistureattracting material (solid or liquid) in the air stream. As Figure 4–1 suggests, desiccant dehumidification requires a process air stream and a regeneration air stream. In this example, the moisture in the process (outdoor) air stream is absorbed by the desiccant wheel, which then releases the collected moisture in the regeneration (exhaust) air stream. Figure 4–1 Air-distribution system with desiccant dehumidification Continued operation of the desiccant requires a regeneration process. Regeneration is usually accomplished by applying heat to the regeneration air stream before it reaches the desiccant. Consideration of desiccant dehumidification is warranted whenever one or more of the following conditions is true of a prospective application: ■ The latent load is significantly larger than the sensible load ■ The cost to regenerate the desiccant is low when compared to the cost associated with overcooling the space ■ The humidity-control level in the space would require chilling the supply air to subfreezing dew points when vapor-compression refrigeration alone is used 4–2 System Design Options Desiccant dehumidification TRACE 700 User’s Manual • CDS-PRM001-EN Typical applications for desiccant dehumidification include ice rinks, supermarkets, retail clothing stores, and clean rooms, as well as installations in humid southern climates. In each instance, desiccant dehumidification provides independent control of sensible and latent heat without the need for reheat. It also dehumidifies the supply air stream without lowering the dry-bulb temperature. Application considerations ■ Desiccant regeneration commonly requires high temperatures, which incurs a significant energy cost. ■ Exposure to contaminants, clogging, and thermal stress causes desiccants to degrade over time. ■ One should consider space requirements, cost, and added pressure drop when evaluating whether desiccant dehumidification is practical for a particular application. Related reading ■ Dehumidification in HVAC Systems Applications Engineering Manual (Trane literature number SYS-APM004-EN) Sample scenario The ventilation deck of the air-distribution system for a building includes a solid-desiccant wheel with an integral run-around coil loop. The wheel only operates from 6 a.m. until 6 p.m. To model desiccant dehumidification, which is a means of removing latent heat from an air stream, begin by modeling the airdistribution system. 1 Choose the desired system type from the categories listed. For this example, select Series Fan-Powered VAV from the Variable Volume category. CDS-PRM001-EN • TRACE 700 User’s Manual System Design Options Desiccant dehumidification 4–3 2 Specify the type of air-toair energy recovery / transfer and the location of the process air stream. This example uses a solid desiccant located on the ventilation deck. Click Yes to activate or include the desiccant device for design and energy analysis. Click No to ignore the desiccant device during the design calculation and include it only during the energy-analysis simulation. Note: This message will only appear whenever an energy-transfer device is added and Allow energy recovery / transfer during design calculations is turned off. 3 A message will appear that asks whether the user wants to account for energy recovery / transfer during the design and energy analysis simulations or only during the energy analysis simulation. Select Yes for this example. ■ Select Ventilation upstream if the device is located in the outdoor air stream and upstream of the optional ventilation coil. ■ Select Ventilation downstream if the device is located in the outdoor air stream and downstream of the optional ventilation cooling coil. ■ Select Return / outdoor air downstream if the device is located after the mixed air stream, downstream of the main cooling coil. ■ Select Return / outdoor air upstream if the device is located after the mixed air stream, upstream of the main cooling coil. 4 Select the appropriate supply-side deck for the device. For this example, Ventilation upstream will be selected as the supply-side deck. The desiccant device will be used to dehumidify the outdoor air stream. Note: If no optional ventilation system has been input, then Ventilation upstream and Ventilation downstream will function identically. If the main cooling coil has been deleted, or if the ventilation-deck location on the Advanced window in Create Systems is not Return/Outdoor deck, then Return / outdoor air upstream and Return / outdoor air downstream will function identically. 4–4 System Design Options Desiccant dehumidification TRACE 700 User’s Manual • CDS-PRM001-EN 5 Select the exhaust-side deck for the device. This will determine which airflow will be used as the regeneration air stream. The airstreams typically used are building exhaust air, outdoor air, or a mixture of the two. Note: In this case, the airflow that is being exhausted from the building at the system level will be used as the regeneration airstream for the desiccant device. Because of this, System Exhaust will be used. ■ Select Outdoor & room exhaust mix if the regenerator will first try to use room exhaust as the sole source of regeneration airflow. If the room exhaust airflow is insufficient, the rest of the regeneration airflow will be made up of outdoor air. ■ Select Outdoor & system exhaust mix if the regenerator will first try to use system exhaust as the sole source of regeneration airflow. If the system exhaust airflow is insufficient, the rest of the regeneration airflow will be made up of outdoor air. ■ Select Outdoor if outdoor air is used exclusively as the regeneration airstream. ■ Select System Exhaust if main system exhaust is used exclusively as the regeneration airstream. If a liquid desiccant is used and the system exhaust varies in volume (due to varying ventilation rates), do not use this input for the exhaust-side deck— use Outdoor & system exhaust mix to get the required constant regeneration airflow. ■ Select Room Exhaust if the room exhaust airflow is used exclusively as the regeneration airstream. Room exhaust airflows are input on the Airflows tab of Create Rooms. If no room exhaust is input, then all exhaust air will be at the system level. Also, if a liquid desiccant is used and the room exhaust varies in volume (due to varying ventilation rates or room exhaust schedules), do not use this input for the exhaust-side deck—use Outdoor & room exhaust mix to get the required constant regeneration airflow. Note: If the proper airstreams are not selected for the energy recovery / transfer device, then the device will not function correctly or may not function at all. The Airflows section of the System Checksums report can be used to verify that sufficient airflow is available to be used for energy recovery / transfer. Room Exhaust = Rm Exh on the System Checksums report and System Exhaust = Exhaust on the System Checksums report. CDS-PRM001-EN • TRACE 700 User’s Manual System Design Options Desiccant dehumidification 4–5 6 Choose the schedule that describes when the desiccant device is permitted to operate. For this example, a custom schedule was created that allows the desiccant device to operate only from 6 a.m. to 6 p.m. 7 Now that the desiccant subsystem has been input, the coil loop needs to be added as the second stage of energy recovery. The coil loop will preheat the regeneration airstream, reducing the amount of energy required to regenerate the desiccant and cool the outdoor air after it leaves the desiccant device, therefore reducing the amount of cooling energy required. Refer to “Coil loop for exhaust-air energy recovery” on page 4–8 for step-by-step instructions on how to input a coil loop. The default schedule Available 100% will allow the energy recovery / transfer device to operate year-round. Liquid-desiccant systems should typically only be made available to operate during occupied hours, because the liquid-desiccant system will try to maintain the ERD (energy-recovery device) leaving-air humidity ratio at its design value. (This is auto-calculated, based on the design conditions, unless overridden by the user on the Desiccant Dehumidification Options screen that appears when the Options button is clicked.) Note: For instructions on how to create custom schedules, refer to “Creating schedules” on page 6–137. Within the custom schedule, 0 percent would indicate that the desiccant device is deactivated, and 100 percent would indicate that it is available to operate. Note: If both stage 1 and stage 2 energy recovery/ transfer devices are given the same exhaust-side deck, then stage 1 will be upstream of stage 2. 4–6 System Design Options Desiccant dehumidification TRACE 700 User’s Manual • CDS-PRM001-EN Note: To further refine the model of the desiccant dehumidification device, the Options button on the Options tab of Create Systems can be used to define such items as parasitic energy consumers, supplyside design air conditions, coolant types, approach temperatures, heatsource temperatures, economizer lockout, and so on. Next, define the heating plant that serves the airside heating loads. 8 Add a gas-fired, hot-water boiler to serve the main heating load. To provide the heat needed to regenerate the desiccant, add a gas-fired heat exchanger. Not shown: Specify equipment types, capacities, schedules, and the full-load consumption of the hotwater pump on the Heating Equipment tab. 9 Unassigned systems and associated coils appear in this pane. To assign a load and/or system, drag the relevant icon to the appropriate cooling or heating plant at right. Assign the heating coil loads to the heating plants. The Stage 1 desiccant regenerator regenerates the solid desiccant. Additional item 1 When adding a desiccant subsystem to an airside system, it is recommended that the minimum and maximum cooling supplyair dry bulbs be set equal to each other to fix the value for the cooling supply-air dry bulb. This is suggested because TRACE 700 cannot psychrometrically solve for the cooling supplyair dry bulb when an energy recovery / transfer device is attached to the Return/Outdoor deck. Refer to “Frequently asked questions” on page 6–20 for the ramifications of inputting a cooling supply-air dry bulb. CDS-PRM001-EN • TRACE 700 User’s Manual System Design Options Desiccant dehumidification 4–7