See discussions, stats, and author profiles for this publication at: https://www.researchgate.net/publication/318695051 Fault current limiter versus series reactor Conference Paper · June 2017 DOI: 10.1109/EEEIC.2017.7977495 CITATIONS READS 3 1,210 7 authors, including: Teymoor Ghanbari Mohammad Amin Jarrahi Shiraz University Shiraz University 126 PUBLICATIONS 1,216 CITATIONS 19 PUBLICATIONS 76 CITATIONS SEE PROFILE Some of the authors of this publication are also working on these related projects: Integrated Battery Charger with Charge Equalization Circuit View project State Estimation in Advanced Electric Vehicles View project All content following this page was uploaded by Mohammad Amin Jarrahi on 06 February 2018. The user has requested enhancement of the downloaded file. SEE PROFILE Fault Current Limiter versus Series Reactor Haidar Samet, Teymoor Ghanbari, Mohammad Amin Jarrahi Abdorasoul Ahmadi Beni, Bahram Kolkian, Arash Ebtia, Mohammad Reza Banaeian Mofrad Shiraz University Shiraz, Iran samet@shirazu.ac.ir, ghanbarih@shirazu.ac.ir, mohammadamin.jarrahi@gmail.com Mobarakeh Steel Company Isfahan, Iran a.ahmadibeni@msc.ir, b.kolkian@msc.ir, a.ebtia@msc.ir, m.banaeianmofrad@msc.ir Abstract— Mobarakeh Steel Company (MSC) in Isfahan/Iran is one of the largest industrial complexes operating in Middle East. In a development program in 10 kV feeder of MSC distribution network, the short circuit capacity of the network has been increased. Limitation of fault current in this network is relegated to some series reactors in the tie feeders. Fault current limiter (FCL) is an efficient alternative for the series reactors in this application. In this paper, it is confirmed that using some FCLs in suitable locations of network, the problems can be resolved. Keywords— FCL; series reactor; MSC; tie feeder. I. INTRODUCTION A. Motication and Literature review The increasing development, growing electricity petition, and rising complexity in industrial networks result in higher fault currents. Thus, there is a significant interest in devices which are capable of limiting fault currents [1]. Fault current limiter (FCL) is an ideal option for limiting high fault currents. An FCL is a device with low impedance at normal operation, large impedance during fault and quick response characteristics [2-4]. Utilization of FCL permits equipment to stay in use even if their fault current exceeds the permissible value and shorttime withstand. In fact, capability of the increased fault current interruption is provided by the FCLs for the power system circuit breakers [5]. Using FCLs, replacement of over-rated equipment can be avoided or at least moved to later [6-8]. In case of newly planned systems, FCLs allow the usage of equipment with lower ratings which results in possible considerable cost saving [9]. FCLs have different types such as sold-state types and superconductor types which among them, the superconductor types have been more employed in industries. Using unique quench characteristics of superconductor elements, the superconducting FCL (SFCL) could suppress fault currents, efficiently [2]. An SFCL has various merits such as automatic excessive current detecting, automatic recovering, and faster excessive current limiting actions. Furthermore, due to the lowloss nature in the superconducting state during normal operation, they could be installed in the system to control excessive current levels without any considerable losses and nuisances [9]. FCLs can be placed in different locations of network for different purposes as shown in Fig. 1 [10]. FCL in location A is utilized to reduce the negative effects of upstream network on downstream network in fault situations. Utilizing FCL in location B is used for decreasing the interactions between two adjacent networks. FCL in location C is aimed to decrease effects of load R3 (which is in a feeder with high fault probability) on network. FCL can be placed in location D for protection of generator G from faults occurrence in the upstream network. As mentioned, one of the most suitable locations for utilization of FCLs in industrial networks is in their tie feeders [11]. The results of an analysis carried out by the CIGRE Working Group regarding the preferred locations for installing FCL is presented in Fig. 2 [12]. It can be observed that the majority of FCLs have been installed in tie feeders. A FCL FCL B A FCL FCL D FCL C G R1 R2 Fig. 1. Suitable locations of FCL [2] Incoming generator 15% Incoming transformer 18% Tie feeder 52% Feeder 15% Fig. 2. Preferred locations for installing FCLs [12] 978-1-5386-3917-7/17/$31.00 ©2017 IEEE R3 B. Aim and Contribution Mobarakeh Steel Company (MSC) is one of the biggest steel producers in Middle East. Some problems have been reported in MSC’s 10 kV distribution network development program because of already installed series reactors in their tie feeder locations. Some of series reactors reported shortcomings are considerable conduction losses in normal condition, remarkable voltage drop in case of heavy load start-up, and low response time. FCLs can be a competent substitute for the series reactors in this claim. In this paper, it is confirmed that the suitable proposed solution for resolving MSC’s 10 kV distribution network is replacing some FCLs with already installed series reactors. For showing the performance of proposed solution, the network with series reactors and FCLs is simulated and analyzed in different conditions. The results validate the proposed solution to overcome the network problems. C. Paper Organization The rest of the paper is organized as follows: Section II provides the operating principle of the FCL. In Section III, the problem in MSC’s 10 kV distribution network and the proposed solution are described. In Section IV, results and discussions are presented. Design consideration of the utilized FCL and its specifications are addressed in Section V. Concluding remarks are provided in Section VI. II. OPERATING PRINCIPLE OF FCL Fig. 3 shows a simple equivalent circuit for discussing the problem associated with fault current limitation in power systems [13]. Regardless the load current passing through the feeder prior to the fault, short-circuit current builds up with a certain rate-of-rise depending on the parameters of the circuit (source voltage U0 and source impedance ZS) and incipient angle of the fault. When no limiting action takes place, a fault current waveform denoted by i1 in Fig. 4 appears. This current will be interrupted by a conventional circuit-breaker at t3. The simplest way to limit the short-circuit current would be the use of a source impedance ZS with an appropriate value. The drawback of this solution is that it obviously also influences the system during normal operation, i.e. it results in considerable voltage drops at high load currents. In order to be able to limit the first peak Î1 of the short circuit current i1, it is necessary for the fault current limiting device to operate within the time interval t1 and to cause a zero or negative rate-of-rise of the current. This can be achieved by inserting a voltage or an impedance with high enough value into the circuit. Such an action requires the use of non-linear elements and leads to currents of the shape i2 or i3, respectively, depending on whether the current is only limited (i2) or limited and interrupted (i3). Along with this current limitation an overvoltage appears, which is proportional to the superimposed di/dt. Zs U0 is CB Fault Fig. 3. Equivalent circuit representing a fault condition Fig. 4. Typical current waveforms due to a fault [13] III. PROBLEM DESCRIPTION AND PROPOSED SOLUTION 10 kV feeder of MSC distribution network has three 63kV/10kV 40 MVA transformers which are shown in Fig. 5. Each transformer feed its downstream busbar loads which they work in parallel for applying power to each busbar. Connections of busbars are already by a series reactor which a bus tie is in its parallel position. Maximum tolerable current of series reactors is about 600 A. Problems that have been reported for this feeder are related to start-up of compressors with 10 to 15 MW power consumption. These compressors draw a huge inrush current at start-up time from its supplying network which even with soft starters, the current is about 3 or 4 times bigger than nominal current of the network. Presence of series reactors in tie feeders can be a problem in this situation because of their considerable voltage drop. Also the inrush current subsequent from heavy load start-up can overload the series reactor and result in tripping it. The transformer of each busbar should supplies its loads on its own because of series reactor tripping. Consequently, transformer draws a huge current from network because of this event and therefore, an enormous voltage drop will be happened. Also in this condition, voltage sensitive loads will be tripped. The solution for solving this problem is replacing series reactors with FCLs. With utilization of FCLs in place of series reactors as shown in Fig. 6, feeder transformer contributions for heavy loads start-up can be done without any problem. In this situation, high inrush current is divided between three transformers and mentioned problem won’t happen. FCLs act as low impedance in heavy loads start-up situation and doesn’t produce a considerable voltage drop. In fact, FCL’s effect on network in normal situation and heavy load start-up situation is insignificant. Although FCLs can have a better performance in current limiting condition toward already installed series reactors. FCLs can limit fault currents to an acceptable amount that circuit breakers can properly perform. Upstream network Upstream network Upstream network TR1 63kv/10kv 40 MVA Bus1 Bus2 Bus3 Bus tie1 Other loads Heavy loads TR3 63kv/10kv 40 MVA TR2 63kv/10kv 40 MVA B. Scenario II Bus tie2 Reactor1 Reactor2 Loads2 Loads3 Fig. 5. Single line diagram of 10 kV feeder of MSC’s distribution network Upstream network Upstream network Upstream network TR1 63kv/10kv 40 MVA TR2 63kv/10kv 40 MVA TR3 63kv/10kv 40 MVA Bus1 Other loads Heavy loads Bus2 FCL Bus3 FCL Loads2 MW compressor with a soft starter in Bus1 is simulated. At first, the drawn inrush current is so enormous that a large voltage drop is happened over series reactor1. After a few moments, the series reactor1 is tripped because the inrush current is much more than its tolerable current. After that event, the other loads (voltage sensitive loads) are also tripped as a result of voltage drop. The one phase voltage and current waveform for Bus1 in this condition are shown in Fig. 7. and Fig. 8. Loads3 Fig. 6. Single line diagram of 10 kV feeder of MSC’s distribution network with FCLs IV. RESULTS AND DISCUSSIONS For showing the proposed solution for MSC’s 10 kV distribution network problem, the system is simulated in PSCAD which four scenarios are considered: Scenario I: Simulating the reported problems of network with already installed series reactors. Scenario II: Simulating the proposed solution by installing FCLs in tie feeder locations. Scenario III: Simulating the system with series reactors and FCLs to compare their effects on voltage drop. Scenario IV: Simulating the fault current limiting capability of series reactors and FCLs. The results for mentioned scenarios are described and shown in following: A. Scenario I As mentioned in section II, heavy loads start-up is the reason of network problems. For showing the problems, a 15 In this scenario, series reactors are replaced with FCLs to overcome the network problems. In the heavy loads start-up condition, FCLs performs as a low impedance and large inrush current shared between three transformers capacities. Hence the Voltage is increased in this scenario in compared to the previous scenario. FCLs can handle the large current in this situation and voltage sensitive load are still remain connected. It should be noted that the current threshold that is selected for FCL to act as large impedance is much more than maximum inrush current which starting-up of heavy loads is drawn from network. The one-phase voltage and current RMS waveform for Bus1 in this condition are shown in Fig. 9. and Fig. 10. C. Scenario III In this scenario it is assumed that series reactor1 can operate in heavy load start-up situation and don’t trip. A considerable voltage drop will be occurred in this case due to its large impedance. Presence of FCL in tie feeder can be a perfect solution for this condition. FCL doesn’t produce voltage drop because of it low impedance. Figure 11 compares the voltage of Bus1 in presence of series reactor and FCL during a start-up of the compressor. D. Scenario IV Comparing the fault current capability of series reactor and FCL is done in this scenario. To fulfill this task, a three phase fault is simulated on bus1 in system with series reactor and FCL in bus tie location. In this scenario, FCL enters considerable high impedance to system and limit the current to an amount which the circuit breakers can cut the faulty section. The one phase current RMS waveform for Bus2 in this condition is shown in Fig. 12. V. DESIGN CONSIDERATION OF FCL Resistive and inductive types of SFCL are common structures, which have been employed in industries. Nowadays, the resistive type is more being attractive due to some advantages addressed in [14-16]. Hence, the utilized FCL in this application is selected as resistive type SFCL. A well designed resistive FCL should meet the following basic requirements: 1) limitation of the first peak of a fault current (transient current); 2) limitation of the steady-state fault current; 3) low impedance under normal operation conditions of the protected circuit; 4) low power loss under normal conditions 5) quick return to the low impedance state after the limitation of fault currents; 6) high reliability and long lifetime similar to a conventional power transformer; 7) no overvoltage related to the FCL operation Based on the simulations, the main specifications for the SFCL can be listed in Table I. Considering the system conditions and the FCL specifications, following design considerations should be taken into account: Fig. 9. Voltage RMS waveform for Bus1of 10 kV feeder of MSC’s distribution network with FCL The device should be designed for normal voltage and normal current of system which is in order 10 kV and 1.5 kA. Permissible voltage drop of the designed device should not be more than 5% of nominal system voltage. In this situation, the value of resistance in normal state can be calculated which is 0.11 Ω for MSC’s 10 kV distribution network. The designed FCL should operate in time interval of quarter cycle after inception of fault. Knowing this fact, FCL’s activation current should fulfill this condition. Activation current for designed FCL is considered 3.5 kA. Designed FCL should limit the current to at least 50% of maximum short circuit current. Resistance of device must follow the mentioned subject. In this system, Resistance of designed FCL is considered 1.8 Ω. Fig. 10. Current RMS waveform for Bus1of 10 kV feeder of MSC’s distribution network with FCL Fig. 11. Voltage RMS waveform for Bus1of 10 kV feeder of MSC’s distribution network with FCL and with series reactor Fig. 7. Voltage waveform for Bus1of 10 kV feeder of MSC’s distribution network Fig. 12. Current RMS waveform for Bus2 of 10 kV feeder of MSC’s distribution network with and without FC Fig. 8. Current waveform for Bus1of 10 kV feeder of MSC’s distribution network TABLE I. SPECIFICATIONS OF THE DESIRED FCL device Specifications Electrical characteristics Normal voltage (kV) Normal current (kA) Number of phases Resistance in normal state (Ω) Activation current (kA) Resistance in fault state (Ω) Maximum tolerable short circuit current (kA) Maximum tolerable time for current limiting (ms) Limiting Speed (ms) Time for return to normal state after limiting (ms) Voltage drop in normal state (% of rated voltage) Insulation class Mechanical characteristics Height (m) Length (m) Width (m) Weight (tonnes) Cryogenic characteristics Superconductor element Cooling liquid temperature in normal state (K) Cooling liquid pressure in normal state (bar) Cooling liquid level in normal state (%) [3] amount 10 1.5 3 0.11 3.5 1.8 12 120 2 10 5 H [4] 1.1 0.9 0.9 3 to 5 [9] [5] [6] [7] [8] [10] YBCO 77 3 90 VI. CONCLUSION The paper presents a solution for problems of MSC’s 10 kV distribution network. The proposed solution is replacing some FCLs with already installed series reactors in tie feeder location. By installing FCL in the MSC 10 kV distribution network, system interconnection is possible without the need to raise the capacity of the circuit breakers, and facilities can be configured for efficiency, among other benefits [11] [12] [13] [14] ACKNOWLEDGMENT The authors wish to thank the staff from MSC who have contributed to the data and information contained herein. This work was fully supported by Mobarakeh Steel Company under grant number 48379316-2. [15] [16] REFERENCES [1] [2] T. Ghanbari and E. Farjah, "Unidirectional fault current limiter: An Efficient Interface Between the Microgrid and Main Network", IEEE Transactions on Power Systems, vol. 28, no. 2, pp. 1591-1598, 2013. A. Morandi, "State of the art of superconducting fault current limiters and their application to the electric power system", Physica C: Superconductivity, vol. 484, pp. 242-247, 2013. View publication stats [17] M. Sadi and M. Ali, "A fuzzy logic controlled bridge type fault current limiter for transient stability augmentation of multi-machine power system", IEEE Transactions on Power Systems, vol. 31, no. 1, pp. 602611, 2016. H. Radmanesh, H. Fathi and G. Gharehpetian, "Series transformer-based solid state fault current limiter", IEEE Transactions on Smart Grid, vol. 6, no. 4, pp. 1983-1991, 2015. W. Guo, L. Xiao, S. Dai, Z. Zhang, T. Ma, Y. Li and X. Xu, "Multicell fault current limiter", IEEE Transactions on Industrial Electronics, vol. 61, no. 4, pp. 2071-2080, 2014. H. Yousefi, F. Aminifar and M. Mirzaie, "Reliability assessment of HV substations equipped with fault current limiter considering changes of failure rate of components", IET Generation, Transmission & Distribution, vol. 10, no. 7, pp. 1504-1509, 2016. T. Ghanbari and E. Farjah, "Development of an rfficient solid-state fault current limiter for microgrid", IEEE Transactions on Power Delivery, vol. 27, no. 4, pp. 1829-1834, 2012. A. Sahebi, H. Samet and T. Ghanbari, "Evaluation of power transformer inrush currents and internal faults discrimination methods in presence of fault current limiter", Renewable and Sustainable Energy Reviews, vol. 68, pp. 102-112, 2017. R. Dommerque, S. Krämer, A. Hobl, R. Böhm, M. Bludau, J. Bock, D. Klaus, H. Piereder, A. Wilson, T. Krüger, G. Pfeiffer, K. Pfeiffer and S. Elschner, "First commercial medium voltage superconducting faultcurrent limiters: production, test and installation", Superconductor Science and Technology, vol. 23, no. 3, p. 034020, 2010. T. Ghanbari and E. Farjah, "A multiagent-based fault-current limiting scheme for the microgrids", IEEE Transactions on Power Delivery, vol. 29, no. 2, pp. 525-533, 2014. B. Lee, J. Sim, K. Park and I. Oh, "Practical application issues of superconducting fault current limiters for electric power systems", IEEE Transactions on Applied Superconductivity, vol. 18, no. 2, pp. 620-623, 2008. Hye-Rim Kim, Seong-Eun Yang, Seung-Duck Yu, Heesun Kim, WooSeok Kim, Kijun Park, Ok-Bae Hyun, Byeong-Mo Yang, Jungwook Sim and Young-Geun Kim, "Installation and testing of SFCLs", IEEE Transactions on Applied Superconductivity, vol. 22, no. 3, pp. 56027045602704, 2012. T. Ghanbari, A. Zandnia and E. Farjah, "Development of a highperformance bridge-type fault current limiter", IET Generation, Transmission & Distribution, 2013.57272 T. Ghanbari, E. Farjah and N. Tashakor, "Thyristor based bridge-type fault current limiter for fault current limiting capability enhancement", IET Generation, Transmission & Distribution, vol. 10, no. 9, pp. 2202-2215, 2016. A. Hobl, W. Goldacker, B. Dutoit, L. Martini, A. Petermann and P. Tixador, "Design and production of the ECCOFLOW resistive fault current limiter", IEEE Transactions on Applied Superconductivity, vol. 23, no. 3, pp. 5601804-5601804, 2013. G. Mafra, G. Sotelo, M. Fortes and W. de Sousa, "Application of resistive superconducting fault current limiters in offshore oil production platforms", Electric Power Systems Research, vol. 144, pp. 107-114, 2017. M. Vojenciak, B. Dutoit, J. Souc and F. Gomory, "Can resistive-type fault current limiter operate in cryogen-free environment?", IEEE Transactions on Applied Superconductivity, vol. 26, no. 3, pp. 1-4, 2016