TUGAS TRAFO TRANSFORMATOR 1. A-150 kVA transformer has 400 turns on the primary and 80 turns on the secondary. The primary and secondary resistances are 0.25 Ω and 0.013 Ω respectively and the corresponding leakage reactances are 1.1 and 0.036 Ω respectively. The supply voltage is 2200 V. Calculate (a) equivalent impedance referred to primary and (b) the voltage regulation and secondary terminal voltage for full power of 0.8 leading. 2. the A short-circuit test when performed onload the having h.v. sidea of a 10factor kVA, 2000/400 V single phase transformer, gave the following data ; 60 V, 4 A, 100 W. If the 1.v. side is delivering full load current at 0.8 p.f. lag and at 400 V, find the voltage applied to h.v. side. 3. Trafo tenaga 60 kVA : 2300/230 V, 50 Hz digunakan sebagai trafo distribusi. Pada arus sekunder beban penuh dengan factor daya tertinggal 0,8. Tentukan : a. Besar impedansi beban trafo tersebut b. Arus primer, jika arus trafo tanpa beban sebesar 5 A dengan factor daya tertinggal 0,37 4. 5. A 20-kVA, 2200/220-V, 50-Hz distribution transformer is tested for efficiency and regulation as follows : O.C test : 220 V ; 4.2 A ; 150 W - l.v. side S.C. test : 85 V ; 10 A ; 360 W - l.v. side Determine (a) core loss (b) equivalent resistance referred to primary (c) equivalent resistance referred to secondary (d) equivalent reactance referred to primary (e) equivalent reactance referred to secondary (f) regulation of transformer at 0.8 p.f. lagging current (g) efficiency at fullload andof 1000 kVA at 0.86 p.f. lagging is supplied by two 3 phase transformers of A load half full-load at 0.8 p.f. lagging current Ratio of transformation is same : 6400/400 800the kVA capacity operating in parallel. V, delta/ star. If the equivalent impedances referred to secondary are (0.005 + j.015) ohm and (0.012 + j 0.030) ohm per phase respectively. Calculate load and power factor of each transformer.