HVAC Heat Transfer Heat is a form of energy. Every object on earth has some heat energy. Cooling in the process of transferring heat from one object to another. When an air-conditioning system cools, it is actually removing heat and transferring its somewhere else. There are two forms of heat energy: i. ii. Sensible heat Latent heat Sensible heat is the form of heat energy which is most commonly understood because it in sensed by touch on measured directly with a thermometer. When weather reporters say it will be 90 degrees, they are referring to sensible heat. Latent heat can’t be sensed by touch or measured with a thermometer. Latent heat causes an object to change its properties. When enough latent heat is removed from water vapor (steam in humidity), it condenses into water (liquid). If enough latent heat is removed from water (liquid) it will freeze, this process is reversed when latent heat is added. Air Conditioning: Air conditioning is the process of treating air to control its temperature, humidity, quality, movement and pressure simultaneously to meet the requirements of the conditional space. Refrigeration system: If we take a liquid refrigerant, confine it in a container and place this near a warm object, the liquid will absorb heat from the warm object. If enough heat is absorbed by the liquid refrigerant, it will boil and vaporize. If the vaporized refrigerant gas is sufficiently Compressed, it will give up the heat that absorbed from the warm object and the gas will condense back to liquid. •The process of alternatively vaporizing and condensing a refrigerant is called a refrigeration cycle. •When the cycle accomplished continuously through the use of machinery, it is called mechanical refrigeration and also called vapor compression cycle. 1 Vapor Compression cycle The basic components required to make up a refrigeration system are: I. II. III. IV. An evaporator the cooling coil A pump the compressor A Condenser the heat disposer A liquid metering device - expansion valve or capillary tube. General Provisions Air Conditioning, Heating and Ventilation (HVAC) system is a combined process that performs many functions simultaneously and provide comfortable conditions within and enclosed space without complaining on health and safely of occupants or for the purpose of the product processing. HVAC system controls and optimizes the following factors in the building a) b) c) d) e) f) g) Temperature Relative humidify Air quality Air movement Noise and vibration Energy efficiency and Fire safety. HVAC system shall be designed, constructed, installed, operated and maintained in accordance with good engineering practice such as described in the ASHRAE Handbooks, HI manuals and relevant chapters of latest BNBC. General Design Aspect of Air-Conditioning System 7.5.1 2 Select internal conditions required, temperature and humidity, whether for comfort or for process or for equipment/ storage area. 7.5.2 Calculate cooling load required, floor wise/zone wise based on Design-criteria given in ASHRAE Hand Book/ Carrier’s Hand Book/ Trane’s Hand Book. Design parameters like natural heat gain, occupancy, room orientation, smoking/ no smoking zones and corridor space should be taken into account. Add ventilation load to the cooling load. Consider use of Air-Curtains at certain areas to reduce load requirement. 7.5.3 Select the system of Air-conditioning depending on the type of Building and its use. By system, we mean All-Air, All-Water and Air/ Water mixed. 7.5.4 Once the system is selected, the duct/ pipe layout must be carefully designed to have required air flow/ water flow in conditioned area and return air/ water system. Short circulating between supply air outlets and return air outlets should be avoided. 7.5.5 While designing Air-conditioning system in Bangladesh, the comfort temperature/ humidity for people, the dust and moisture content of local air must be getting in mind. Also fresh airrequirement of the local occupants must seriously be taken into account. Since higher fresh air requirement increases the cost of the system, a compromise should be done with the inside temperature/ humidity to maintain fresh air requirement. Lesser the fresh air, greater is the chance of fungus growth in the air-conditioned area from which persons working in the air-conditioned area is attacked with Fungus Allergy. Once the cooling load is determined, equipment selection made, the next important point to be considered is the machine room layout. It is a hard task to extract enough space from the building for a comfortable layout of the plant-room requirement. No compromise should be made on space requirement which is very vital for equipment operation maintenance. 7.5.6 In air-conditioning system be it in the plant room or in the conditioned area sound level should be kept at as minimum as possible- especially for the office areas. Special consideration is to be given to Heat shock i.e. movement from cold area to normal area (in the summer season specially) would cause the persons to catch cold and therefore, the temperature between air-conditioning area, corridor and outside condition to be carefully considered for health reason. In designing air-conditioning system for this country, one must remember that we live in a natural moderate temperature excepting for a short period of high temperature. So what is comfort to a person in cold countries or very hot countries is not applicable to Bangladesh. Room temperature should be so selected that a local person can use the room without coat and tie. Should certain areas/ rooms are to be so maintained that use of coat and tie is a must those areas should be designed specially and that would keep the cost of the system own. 7.5.7 7.5.8 7.5.9 In order to have a long life of the Central plants, due consideration should be given to water treatment, in case of water-cooled chillers. Living in air-conditioned area is hazardous if enough fresh-air is not introduced. In residence, where rooms are full of pot plants, fresh air requirement is to be increased. In room air cooler, the fresh air inlet should always be kept open. 3 7.5.10 The split-air coolers do not have any provision for fresh air-inlet and the rooms polluted air full of carbon-dioxide and human odor is being circulated. In case use of split-air coolers is a must, extra arrangement must be made to introduce fresh air of adequate quantity. 7.6 INSIDE DESIGN CONDITIONS 7.6.1 For comfort air-conditioning the inside design conditions shall be selected with an objective to reduce energy consumption in the operation of the air-conditioning system. Acceptable values of inside design conditions for summer is provided in Table-A unless otherwise specially required the design calculations shall be based on the normal practice value of Table-A 7.6.2 To avoid thermal shock, the difference between the dry bulb temperatures of outdoor air and indoor air shall not exceed 11oC. If it is absolutely necessary to have a difference more than 11oC, there shall have adequate provision for ante-room to reduce the effect of thermal shock. 7.6.3 For air-conditioning systems other than comfort air-conditioning, design conditions required by the specific processes involved or applications may be adopted. When required, proper protective measures shall be taken for persons working therein. 7.6.4 Velocity of air in an air-conditioned space, in the zone between the floor level and the 1.5 m level, shall be within 0.12 m/s and 0.25 m/s for comfort applications for commercial buildings, and for other applications it shall not exceed 0.5 m/s. 7.7 OUTSIDE DESIGN CONDITIONS 7.7.1 The outside design conditions for summer months for different cities are provided in Table-B. Selection of outside design conditions from this table shall be based on requirements of the application and the percent of time the outside air temperature is allowed to exceed the outside design conditions. 7.7.2 In case of stringent design conditions a meteorologist with experience in applied climatology may be consulted to evaluate conditions such as; the formation of heat sinks in urban areas; the duration of extreme temperatures; project sites located remotely from reporting stations. 7.8 VENTILATION AIR 7.8.1 Every space served by the air-conditioning system shall be provided with outside fresh air not less than the minimum amount mentioned in Table-C. If adequate temperature regulation along with efficient filtration of air and absorption of odour and gas are provided, the amount of fresh air requirement may be reduced. However, in no case the outdoor air quantity shall be lower than 2.5 l/s per person. 7.8.2 In hospital operation theaters, a large quantity of outdoor air supply is recommended to overcome explosion hazard of anesthetics and to maintain sterile conditions. However, if adequate filtration with efficient absorption of anesthetics and laminar flow of supply air is provided, outside air requirement may be substantially reduced 4 Table -A Inside Design Conditions of Some of Applications for Summer a Indoor Design Conditions SI No Use Category of Space Dry Bulb Temperature (ºC) 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. Relative Humidity (%) Restaurants, Cafeteria and Dining Hall 23 ~ 26 Kitchens 28 ~ 31 -- Office buildings 23 ~ 26 50 ~ 60 Bank/Insurance/ Commercial building 23 ~ 26 45 ~ 55 Hotel guest rooms 23~ 26 55 ~ 60 50 ~ 60 Ball room/meeting room 23 ~ 26 40 ~ 60 Class rooms 23 ~ 26 50 ~ 60 Auditoriums 23 ~ 26 50 ~ 60 Recovery rooms 24 ~ 26 45 ~ 55 Patient rooms 24 ~ 26 45 ~ 55 Operation theatres 17 ~ 27 45 ~ 55 Delivery room ICU/CCU New born Intensive care Treatment room Trauma room Endoscopy / Bronchoscopy 20~ 23 45 ~ 55 20~ 23 30 ~ 60 22.5~ 25.5 30 ~ 60 23~ 25 30 ~ 60 17 ~ 27 45 ~ 55 20~ 23 30 ~ 60 X-ray (diagnostic & treatment) 25.5 ~ 27 40 ~ 50 X-ray (surgery/critical area and 21~ 24 30 ~ 60 22.5~ 24.5 30 ~ 60 Art Galleries/Museums 17~ 22 40 ~ 55 Libraries 20~ 22 45 ~ 55 Laboratory (diagnostics) Note: a The room design dry bulb temperature should be reduced when hot radiant panels are adjacent to the occupant and increased when cold panels are adjacent, to compensate for the increase or decrease in radiant heat exchange from the body. A hot or cold panel may be un‐shaded glass or glass block windows (hot in summer, cold in winter) and thin partitions with hot or cold spaces adjacent. Hot tanks, furnaces, or machines are hot panels. 5 Table: Outside design Conditions of Different Stationsa Cooling, DB /MWBb 0.4% Station Evaporator, DB /MWBc 1% 2% 0.4% 1% Range of 2% DB MWB DB MWB DB MWB WB MDB WB MDB WB MDB DBd (2) (3) (4) (5) (6) (7) (8) (9) (10) (11) (12) (13) (14) Barishal 35.5 28.5 34.5 28.5 34.0 28.0 30.0 33.0 29.5 33.0 29.0 32.0 5.0 Bogura 36.5 28.5 35.5 28.5 34.5 28.0 31.5 33.5 30.0 33.0 29.0 33.0 5.5 Chandpur 35.5 28.5 34.5 28.5 34.0 28.0 29.5 33.0 29.5 33.0 29.0 32.5 5.0 Chattogram 34.0 28.5 33.5 28.5 33.0 28.0 29.5 32.5 29.0 32.5 28.5 32.0 4.5 Comilla 35.0 27.5 34.5 27.5 34.0 27.5 29.0 33.0 28.5 32.5 28.0 32.0 5.5 Cox’s Bazar 34.0 27.5 33.5 27.5 33.0 27.5 29.0 31.0 29.0 30.0 29.0 30.0 5.0 Dhaka 35.55 27.5 35.0 27.00 34.0 27.0 29.0 33.0 28.5 29.0 28.5 29.0 5.0 Dinajpur 36.0 28.5 35.5 28.0 34.5 28.0 30.0 32.5 29.0 33.0 29.0 33.0 5.5 Faridpur 36.5 28.5 35.5 28.0 34.5 28.0 29.5 33.0 29.0 33.0 29.0 33.0 5.0 Ishurdi 37.5 27.0 36.5 27.0 35.5 28.0 30.0 34.5 29.0 33.5 29.0 33.5 6.0 Jashore 38.0 28.5 37.0 28.5 36.0 28.0 30.0 35.0 30.0 35.0 29.5 34.0 6.5 Khulna 36.5 29.0 36.0 28.0 35.5 28.0 30.0 34.0 30.0 34.0 29.5 33.5 5.0 Mongla 37.0 31.0 36.0 30.5 35.0 30.0 33.0 34.0 32.5 34.0 32.0 33.5 5.0 Mymensingh 35.0 28.0 34.0 28.0 33.5 27.5 29.5 33.0 29.0 32.56 28.5 32.0 4.5 Patuakhali 35.5 28.5 35.0 28.5 34.5 28.5 30.0 33.0 30.0 33.0 29.5 32.5 5.0 Rajshahi 35.5 296.0 34.5 28.5 34.0 29.0 31.5 33.0 31.0 32.5 30.0 31.5 5.0 Rangamati 35.5 26.0 34.5 27.0 34.0 27.5 28.5 33.5 28.0 32.5 28.0 32.5 6.0 Rangpur 35.5 28.5 34.5 28.0 34.0 28.0 29.5 30.5 29.5 30.0 29.5 30.5 5.0 Sylhet 35.5 27.0 34.5 27.0 34.0 26.5 28.5 32.5 28.0 32.5 28.0 32.5 5.5 Tangail 36.0 27.5 35.5 27.5 34.5 27.5 29.0 33.5 28.5 33.0 28.5 33.0 5.5 (1) Notes: a) This table has been prepared by statistical analysis of weather data of ten years, recorded three hourly by trained observers of Bangladesh Meteorological Department b) The dry bulb (DB) temperatures presented in column‐2, 4 & 6 represent values which have equaled or exceeded by 0.4%, 1%, and 2% of the total hours during the summer months of May through September. The coincident mean wet bulb temperatures (MWB) listed in columns 3, 5 & 7 are the mean of all wet bulb temperatures occurring at the specific design dry bulb temperatures. These values shall be used for cooling load calculation. c) Wet bulb (WB) temperatures presented in column‐8, 10 & 12 represent values which have been equaled or exceeded by 0.4%, 1% and 2% of the total hours during the summer months of May through September. The coincident mean dry bulb temperatures (MDB) listed in columns 9, 11 & 13 are the mean of all dry bulb temperatures occurring at the specific design wet bulb temperatures. These values shall be used for selection of Cooling Tower, evaporative cooling equipment, fresh air cooling and other similar equipment. d) Mean daily range temperatures presented in column‐14 are the difference between the average daily maximum and average daily minimum temperatures during the warmest months at each station 6 Table: Required Minimum Air Circulation Rate for Mechanical Ventilation of Non-AirConditioned Space Sl Application Air Change Sl Application Air Change No. per Hour No. per Hour 1 Assembly Rooms 4-8 28 Hospitals-sterilizing 15-25 2 Bakeries 20-30 29 Hospitals-Wards 6-8 3 Bank/Building societies 4-8 30 Hospitals Domestic 15-20 4 Bathrooms 6-10 31 Laboratories 6-15 5 Bedrooms 2-4 32 Launderettes 10-15 6 Billiard Rooms 6-8 33 Laundries 10-30 7 Boiler Rooms 15-30 34 Lavatories 6-15 8 Cafes and Coffee Bars 10-12 35 Lecture Theatres 5-8 9 Canteens 8-12 36 Libraries 3-5 10 Cellars 3-10 37 Living Rooms 3-6 11 Churches 1-3 38 Mushroom House 6-10 12 Cinemas and Theaters 10-15 39 Offices 6-10 13 Club Rooms 12, min 40 Paint Shops (not cellulose) 10-20 14 Compressor Rooms 10-12 41 Photo and X-Ray Darkroom 10-15 15 Conference Rooms 8-12 42 Public House Bars 12, min 16 Dairies 8-12 43 Recording Control Rooms 15-25 17 Dance Halls 12, min 44 Recording Studios 10-12 18 Dye Works 20-30 45 Restaurants 8-12 19 Electroplating Shops 10-12 46 School Rooms 5-7 20 Engine Rooms 15-30 47 Shops and Supermarkets 8-15 21 Entrance Halls 3-5 48 Shower Baths 15-20 22 Factories and Work Shops 8-10 49 Stores and Warehouses 3-6 23 Foundries 15-30 50 Squash Courts 4, min 24 Garages 6-8a 51 Swimming Baths 10-15 25 Glass Houses 25-60 52 Toilets 6-10 26 Gymnasium 6, min 53 Utility Rooms 15-20 27 Hair Dressing Saloon 10-15 54 Welding Shops 15-30 Note: The Ventilation Rates may be increased by 50 percent where heavy smoking occurs or if the room is below ground. a Only outdoor air and no recirculation shall be done. 7 Design Considerations for cooling load calculation To Calculate the space cooling load; detailed building information, location, site and weather data, internal design information and operating schedules are required. Information regarding the outdoor the outdoor design conditions and desired indoor condition are the standing point for the load calculation. Building Characteristics To calculate space heat gain, the following information on building envelope is required. a) Architecture plans, sections and elevations for estimating building dimensions/ area/ volume. b) Building orientation (N, S, E, W, NE, SE, SQ, BW etc.) location etc. c) External/ Internal shading, ground reflectance etc. d) Material of construction for external walls, roofs, windows, doors, internal walls, partitions, ceiling, insulating materials and thickness, external wall and roof colors select and/ or compute u-vastness for walls, roof, windows, doors, partitions etc. e) Amount of glass, type and shading on window. Internal load and operating nature i. ii. iii. iv. Number of occupants, duration of occupancy & nature of activity. Lighting total wattage at peak and duration of operators. Appliances rated power input or heat generator data. Nature of operation continuous or intermittent. Others ▪ ▪ Infiltration: Movement of air into indoor space from the outside. Exfiltration: Movement of air escaping outside the building, The air conditioner’s efficiency, performance, durability and cost depend on metering its size to the above factors. 7.9 NOISE AND VIBRATION 7.9.1 General: Air-conditioning, heating and ventilation system design and installations shall consider all the aspects of noise and vibration control related to the system. Selection and installation of equipment for air-conditioning, heating and ventilation system shall be such that 8 noise and vibration transmitted to the space served by the system shall not exceed the recommended value for the space served. 7.9.2 Equipment room: Equipment room for installation of air handling units, refrigeration machinery, pumps, boilers, blowers and other equipment, which produce noise and vibration, shall not preferably be located adjacent to any acoustically sensitive area. Location of the equipment room shall be such that direct transmission of noise and vibration from the equipment room to acoustically sensitive areas do not occur. Appropriately designed sound barriers shall be used to restrict transmission of noise from equipment room to any acoustically sensitive areas, wherever necessary. Similarly, adequate measures shall be taken to restrict transmission of vibration from equipment room to other rooms. 7.9.3 Selection of equipment: Where possible, the equipment shall be selected which produce low sound power level consistent with the required performance and ensuring operation at maximum efficiency. Noise levels shall be reduced by appropriate shrouding of the equipment, if necessary. Equipment shall be so oriented that the noise will be radiated away from the likely areas of complaint. 7.9.4 Noise control: 7.9.4.1 Air Ducts: Air ducts shall be so designed and installed to avoid any transmission of noise and vibration which may be picked up by the duct system from equipment room or adjoining rooms. Duct system shall not allow cross talk or noise transfer from one occupied space to another. Duct system shall be appropriately designed, constructed and installed to obtain adequate attenuation of noise required to maintain recommended noise level in the airconditioned space. Duct construction and installation shall be such that drumming effect of duct walls and noise transmission through the duct walls can be minimized to the approved level. 7.9.4.2 Plenum Chamber: If required, properly designed plenum chamber, lined with approved sound absorbed material, and/or sound attenuators shall be used for attenuation of noise. 7.9.4.3 Flow Control Devices: Air dampers and other flow control devices shall be so selected that noise generation does not exceed approved levels. 7.9.4.4 Air Terminals: Air terminals shall be selected for the approved noise generation characteristics. 7.9.4.5 Piping: Velocity of fluids in piping shall be so selected that noise generation does not exceed approved levels. 7.9.4.6 Chiller and Refrigeration Equipment: Chiller(s) and refrigeration equipment(s) shall be so selected and installed that the combined effect of noise level does not exceed 65 dBA or approved levels at the property boundary line. Where ever possible refrigerant compressors may be encased in acoustically treated enclosures to reduce noise transmission. Similarly, low speed condenser fans may be used to have reduced noise generation. Fan cylinders may be acoustically treated to reduce noise transmission. 9 7.9.4.7 Cooling Tower: Cooling Towers(s) shall be so selected and installed that the combined effect of noise generation does not exceed 65 dBA or approved levels at the proper boundary level. Where ever possible, fan cylinders shall be acoustically treated to reduce noise transmission. Floating mats may also be used to reduce water droplet noise. 7.9.5 Vibration Control: 7.9.5.1 Appropriately designed vibration isolators shall be installed under the machinery to restrict vibration transmission to structures. Similarly vibration isolators shall also be used between machinery and all pipe work and duct work including the supports when applicable. 7.9.5.2 Where ever necessary “Inertia Block” with spring vibration isolators shall be used to restrict vibration transmission to structures. 7.9.5.3 Spring vibration isolators shall be earthquake restraint type. 7.10. FIRE DAMPER Fire damper shall be provided at locations where air distribution systems penetrate assemblies that are required to be fire resistance rated by the latest Bangladesh National Building Code. Types of Air Conditioning system Air Conditioning effect can be achieved with various types of air conditioning units and system. The common of them are listed below. i) Room air-conditioning unit ii) Split air-conditioning unit iii) Single package air-conditioning unit iv) DX or Direct Expansion air-conditioning unit v) Central air-conditioning system vi) Variable refrigerant flow (VRF) air-conditioning system Window (Unitary) Air Conditioner A window air conditioner is a packaged unit controlling of a compressor, condenser, evaporator, expansion valve, fan, filter appropriate control and a housing. It is generally and for cooling and general dehumidification. 10 Installation Window (unitary) air conditioner is suitable for bedroom, office cabin, general office area, hotel room and similar applications, where normal comfort conditions are required to be maintained. It is also not suitable for areas that require close control of both the indoor temperature and relative humidity. Application Window (unitary) air conditioner should be mounted preferably at the window sill level on an external wall, where hot air from air-cooled condenser can be discharged without causing nuisance. There should not be any obstruction for the inlet air to, and discharge air from, the condenser. While deciding location of the window air conditioner, care shall be taken to ensure that the condensate drain water is piped to the ground level and does not drip, causing nuisance Split Air Conditioner A split system is an air conditioning system that has separate cabinets for the evaporator and the condenser. The cabinets are connected by refrigerant lines, plumbing and electrical conductors. The evaporator of a split system is located inside a building, called indoor unit and the condenser in located outdoor, caller outdoor unit. The indoor unit may be , mounted on wall or ceiling or floor. It also may be exposed type or concealed type. Installation Wall mounted unit and similar exposed indoor unit are provided with installation plate for ease in installation. Care shall be taken to ensure that enough clearance space is available below the ceiling in order to have free intake of return air.Outdoor unit is mounted on an epoxy-coated steel frame in an open area so that the fan of the air cooled condenser can discharge hot air to the atmosphere, without any obstruction. Application Split air conditioner is suitable for wide range of applications including residences, small office, club, restaurant, showroom, departmental store, and others. Variable Refrigerant Flow (VRF) Variable Refrigerant flow (VRF) is an air-conditioning system where There is a one outdoor condensing unit and multiple indoor units. VRF can be explained as a multiple Split Airconditioning system wing Principle of control of flow/quality of Refrigerant through the indoor unit to control cooling and heating medium. This Refrigerant in compressed and liquefied by a single Outdoor Condensing Unit (ODU) and is circulated within the building through copper refrigerant pipes to multiple Fan Coil Units (FCU’s) called Indoor Unit (IU’s). VRF outdoor units are typically provided with rectifier-inverter power system, which provided a Variable Voltage & Variable Frequency (VVVF) supply to compressor motor, in order to support variable speed. This in turn provided variable Refrigerant flow though the Refrigerant lines meeting the demand of cooling/heating. The speed of motor is controlled through a feedback system sensing the refrigeration demand from the indoor units. 11 Applications VRF systems are typically distributed system the outdoor unit is kept at a far-off location like the top of the building of remotely at grade level and all the evaporator units are installed at various location inside the building. There system is basically extension of split type air conditioners and much less efficient as compared to central air conditioning plant. It is suitable for the existing building, requiring central AC but the space for providing AC plant, height of ceiling for during, water supply for skilled water lines is unavailable. Such system is normally suitable where high diversity in demand is available include small officers, small hotels, great houses, art galleries etc. Prohibition of application: Operation theatres where provisions for 100 percent fresh air and high-quality filtration of air are required. System Selection Criteria There are various types of air conditioning system. Suitability of system cannot be generalized, It needs to be building specific decision consideration, initial cost, efficiency, maintenance, effect on building aesthetics, noise, service life and other factors. When low initial cost and simplicity are primary concern, designers may select some-bysome distributed system. This approach tends to be used for smaller buildings as well as for larger building with multiple tenancy and sufficient loop area distributed system includes unitary air-conditioners (window & split air-conditioners), packed roof top air conditioners & VRF. When indoor air quality humidity, lower operating cost, central maintenance and control are primary concerns, designers may select centralized systems that may be DX (Direct Expansion) type central plant or chilled water type central plant. These systems often require a greater initial cost than distributed systems but often result in annual energy savings because additional benefits also include the ability to reduce installed capacity by using load diversity. Centralized cooling systems usually prove to be more cost effective when the building load is large, depending on climate and patterns of occupancy use. Comparative advantages, disadvantages and constraints of is option should be carefully evaluated before final HVAC system selection. 12 Packaged Air Conditioner It is a self-contained unit suitable for floor mounting, designed to provide conditioned air to moderate rise conditioned spaces. It includes prime source of refrigeration for cooling and dehumidification, facility for drawing fresh air and mixing with return and fresh air and generally provision for external air distribution ducting for uniform air distribution in the conditioned spaces. There are two types of packaged air condition i) Single packaged unit ii) Split packaged unit When the machine is equipped with compressor, evaporator, expansion device and condenser in a single housing it is called single packaged unit. When the machine is equipped with compressor, evaporate & expansion device in a one cabinet/housing and remote condenser in a separated housing and two are interconnected with copper refrigerate pricing, it is called split packaged unit. Installation Packaged unit is normally mounted on resilient pads which prevent vibration of the unit from being transmitted to the floor. Application Packaged unit is suitable for wide range of applications including office, club, community hall, banquet hall, showroom, departmental store other. Central Air Conditioning System Central Air Conditioning System are generally deviated into three basic types, classified by the methods by which final spaces cooling in affined. These are as follows: i) All Air System ii) All Water System iii) Air Water System All Air System The refrigeration unit (chiller) is located in a remote plant room from which secondary refrigerant (chilled water) is supplied to the air-handling units Air handling units also remotely located in separate room/places from the conditioned spaces. Only the final cooling or heating medium (air) is brought and distributed into the conditioned spaces through duct network and air outlets. Application Single purpose occupancies, office buildings, place of assembly, Industries, large departmental store, special requirement etc. 13 Benefits Quiet operation, central operational control, centralized maintenance & better environment control. All Water System The refrigeration unit (chiller) is located in a remote plant room. The secondary refrigerant (i.e. chilled water) in supplied from a remote refrigeration unit and circulated through coil of air circulating unit (FCU) installed within the conditioned spaces. Outdoor unit is supplied directly from the outside into the remote air plenum fitted with the unit. Application Multi-room building with separate central such as hotel, hostel etc. building where adequate space for installation of AHU and space for ductwork not available building where inside air quality is not of prime importance. Benefits Flexibility of operation, room wise operational control, unit wise (FCU) maintenance etc. Air Water System The refrigeration unit and air handling unit (AHU) are located in separate places from the conditioned spaces. Cooling or heating is done partly by air brought through the duct work from separate AHU/after filtering and cooling. The remaining cooling or heating is done by cooled water or worm heater circulated through a coil of fan coil unit (FCU) installed within conditioned space. Application Multi-room building with separate control such as hotel, hostel etc. & building where adequate space for installation AHU and space for ductwork not available everywhere. Benefits Same as those of all water system. In addition, this provides filtered and clean outdoor air from central AHU. Chillers Chiller are the heart of the chilled-water central air conditioning system. They serve the pivotal faction of creating the cooling effect required to maintain comfort conditions. Chillers utilize the vapor compression (mechanical) or absorption refrigeration cycle to produce chilled water. Chillers use a refrigerant gas to move the unwanted heat between the evaporator and the condenser. The chilled water is generated in evaporator and this is sent around the building by a pump to collect the unwanted heat and bring it back to the evaporator to be cooled down. The refrigerant collects this heat and moves it to the condenser. The condenser parts this unwanted heat into another loop which is sent by a pump to the cooling towers to sent it into atmosphere or it will send it to a cooling cool where a fan blower the heat away into the atmosphere. There are generally two different types of chillers in central air conditioning system: i) Air Cooled ii) Water Cooled 14 Air Cooled Chiller Air Cooled condensers are used in this system. Air-cooled condensers employ ambient air as the condensing medium and use a fan to move the air over the coil. Water Cooled Chiller Water cooled condenser are used in this chiller. Water cooled condenser employ water as the condensing medium and uses a pump to circulate the water through the condenser and out to a cooling tower that rejects the heat to the atmosphere. 15 Table: HVAC system Analysis and Selection Matrix (1) i) (2) Temperature Fixed Speed Unitary Systems (Window ACs/Split ACs/Package ACs) (3) No uniform and effective control ii) Capacity requirements Capacity to suit zone peak, no diversity iii) Special requirements No plant/equipment room required. Compromise building elevation iv) Electric supply Distributed electric supply required v) Initial cost Minimum initial cost Moderate initial cost but marginally higher than variable speed unitary product vi) Operating cost Strategic scheduling of equipment can save operating cost better than unitary product, but higher peak energy requirement vii) Maintenance cost Higher operating cost. Strategic scheduling of multiple pieces of equipment can save marginal operating cost, but equipment is less efficient Comparatively less maintenance cost vii) Reliability Reliable equipment but low service life Reliable equipment but moderate service life ix) Flexibility Has to be placed at fixed locations Can be placed at distributed locations x) Noise and vibration Noise and vibration within/adjacent to occupied spaces for unitary window type air conditioners which is substantially reduced in case of split system Noise and vibration on roof terrace or ground, away from occupied spaces; however, the same can be reduced with good installation practices SL No. System Characteristic 16 Variable Refrigerant Flow Systems (VRF) (4) Reasonably uniform and effective control possible Capacity to suit zone peak, limited diversity can be considered No plant/equipment room required, Outside units can be located on roof or on adjacent ground. Very small shaft desirable for refrigerant piping Zone-wise distributed electric supply required Maintenance cost higher than both fixed and variable speed unitary system but less than central system Central Systems (5) Uniform and effective control possible Allows the design engineer to consider HVAC load diversity factors, accordingly reduce installed equipment capacity Equipment rooms/spaces and accessible shaft required for chilled water piping Minimal distribution cost by centralized supply near the substation Even the HVAC diversity, a central system may not be less costly than decentralized HVAC systems More energy-efficient primary equipment and multiple pieces of HVAC equipment allow staging of operation to match building loads while maximizing operational efficiency Comparatively higher since centralized equipment room requires operator with no access to occupant workspace, but with fewer pieces of HVAC equipment to service Reliable equipment with much longer service life Flexibility available in terms of alternative locations Noise and vibration away from occupied spaces 17