L-100D LOAD BANK MANUAL CONTAINS OPERATING INSTRUCTIONS PARTS LIST WIRING DIAGRAMS SERVICE INSTRUCTIONS CANNON LOAD BANKS, INC. 502 PARK STREET PALMETTO, GA. 30268 770 - 463 - 0504 This load bank is manufactured and protected under U. S. Patent number 4,445,047 CAUTION THIS LOAD BANK IS DESIGNED FOR THE TESTING AND SERVICING 115/200V 400HZ GROUND POWER UNITS. THESE GENERATORS HAVE THE POTENTIAL OF DELIVERING A LETHAL SHOCK. THIS LOAD BANK SHOULD BE USED ONLY BY TRAINED AND QUALIFIED PERSONNEL. THIS LOAD BANK IS DESIGNED FOR TEMPORARY USE ONLY. THE LOAD RESISTORS ARE ENERGIZED WHEN THE RATE SWITCH IS OFF, THEREFORE DO NOT INSERT ANY OBJECTS IN THE GRILL ASSEMBLY. DO NOT BLOCK THE AIR FLOW OR USE IF THE AIR FLOW IS REVERSED. CANNON LOAD BANKS, INC. MANUAL FOR L-100D LOAD BANK TABLE OF CONTENTS SUBJECT SECTION PAGE DESCRIPTION PURPOSE OF LOAD BANK RATING OF LOAD BANK LOAD BANK DESCRIPTION CONTROL PANEL LAYOUT CONTROL DESCRIPTION 1-1 1-2 1-3 1 1-4 1 1 1 2 3 2-1 2-2 2-3 2-4 2-5 1 1 1 1 1 3 3 3 3 3 3 3 3 1 2 3 4 5 6 7 8 FIGURE 1 - 1 FIGURE 1 - 2 OPERATION SETTING UP LOAD BANK APPLYING POWER CHECKING INPUT APPLYING LOAD SHUTTING DOWN PARTS PARTS INFORMATION CONTROL PANEL PARTS LAYOUT CONTROL PANEL PARTS LIST INTERIOR PARTS LAYOUT INTERIOR PARTS LIST FAN PANEL PARTS LAYOUT FAN PANEL PARTS LIST VENDOR LIST FIGURE 3 - 1 FIGURE 3 - 2 FIGURE 3 - 3 SERVICING GENERAL SERVICING REPLACING FAN FIGURE 4 - 1 4-1 4-2 1 2 WIRING DIAGRAMS INTERIOR W IRING FAN PANEL WIRING SCHEMATIC DIAGRAM FIGURE 5 - 1 FIGURE 5 - 2 FIGURE 5 - 3 5 5 5 1 3 5 CANNON LOAD BANKS, INC. DESCRIPTION 1-1 PURPOSE OF LOAD BANK: The L-100D is a portable load bank designed to be used for field servicing and testing aircraft ground power units. It can be used for checking cables after they have been replaced or repaired. On diesel generator sets it is helpful to run the generators at full load periodically to prevent wet stacking (carbon build-up in the engine). The load bank can also be shipped to different locations using the carrying case. 1-2 RATING OF LOAD BANK: The L-100D is rated at 109KW at full load. The load steps are 10KW, 19KW, 28KW, 37KW, 46KW, 55KW, 64KW, 73KW, 82KW, 91KW, 100KW, 109KW, The load bank will run continuously at any load step. 1-3 LOAD BANK DESCRIPTION: The load bank is completely self-contained and needs no power source to operate other than the power unit. The different sides of the load bank are shown in fig. 1-1. The air enters the right side (fan side) and exits the left side. <<<< AIR FLOW <<<< LEFT SIDE------------------------ ------------RIGHT SIDE (FAN SIDE) FIGURE 1-1 LENGTH WIDTH HEIGHT WEIGHT 22 IN. 8 IN. 16 IN. 45 LBS. CANNON LOAD BANKS, INC. PAGE 1 SECTION 1 CONTROL PANEL LAYOUT 1 1 5.0 L2 1 1 5.0 L3 1 1 5.0 L1 L-100 D FUSE MULTIMETER .5A CONTROL FUSES E& F SWITCH 2A 46KW 55KW 64KW 37KW ON 28KW E & F 73KW 19KW 82KW 10KW 100KW 109KW OFF A B B C C ABC N RATE SWITCH 91KW OFF A POWER INDICATOR LIGHTS FUSE RATE CBA E&F E F E& F INDICATOR PHASE ROTATION LIGHTS METER TEST JACKS POWER RECEPTACLE FIGURE 1 - 2 CANNON LOAD BANKS, INC. PAGE 2 SECTION 1 1-4 CONTROL DESCRIPTION: The following is a description of the controls on the control panel (see figure 1-2 on page 2. DIGITAL MULTIMETER - A three phase meter used to measure, Phase Voltage (V),Phase to Neutral (V), Frequency (Hz),Phase Current (I),Neutral Current (I),Active Power (W),Reactive Power (Var), Apparent Power (VA), Power Factor ( P.F.), Active Energy (W.h), Reactive Energy Var.h), Instantaneous Demand Amp, Instantaneous Demand Active Power, Instantaneous Demand Apparent Power, Maximum Demand Amps, Maximum Demand Active Power, Maximum Demand Apparent Power. The meter should read approximately 115 volts line to neutral or 200 volts line to line. A 200V line to neutral reading would indicate a line and neutral cable reversed. CONTROL FUSE - A .5A and 1A fuse used in the control circuit and E & F interlock circuit. E & F SWITCH - Switch is used to turn off or on the 28V power supply that powers the E & F circuit, fans and the control circuit in the load bank. RATE SWITCHES - Switches used to select the desired rate on the load bank. The rates are as follows: RATE SWITCH 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 10KW 19KW 28KW 37KW 46KW 55KW 64KW 73KW 82KW 91KW 100KW 109KW balanced load balanced load balanced load balanced load balanced load balanced load balanced load balanced load balanced load balanced load balanced load balanced load POWER INDICATOR LIGHTS - These lights will light to indicate power on A, B, and C phase. All three lights should be on. PHASE ROTATION LIGHTS - These lights indicate ABC or CBA phase rotation. The ABC light will be on when the phase rotation is correct. Do not operate if the red CBA light is on. E & F CABLE INTERLOCKS INDICATOR - The light will be on when the interlock circuit between the E & F in the cable is complete. METER TEST JACKS - This provides a place to connect an external meter. There is a test jack for each cable pin. POWER RECEPTACLE - The power cable from the ground power unit is plugged into the load bank through this receptacle. This is a standard aircraft receptacle. CANNON LOAD BANKS, INC. PAGE 3 SECTION 1 BLANK OPERATION 2-1 SETTING UP THE LOAD BANK - Place the load bank in an area free from fuel, oil, or any other flammable substance. The load bank should be positioned so that any strong wind or air currents will flow with the air flow of the load bank. 2-2 APPLYING POWER - The load bank should be connected to a ground power unit with an output of 115 / 200V (115V line to neutral / 200V line to line). Make sure that the power unit is off before connecting the cable to the load bank. Plug the power cable plug in to the load bank. The load bank may be tilted on the back feet in order to make it easier to plug the cable in. Return the load bank to the bottom feet before applying power. Turn on the E & F switch, turn the rate switches to OFF on the load bank. If the ground power unit has a test bank / aircraft switch, leave it in the aircraft position. Turn on the output of the ground power unit. 2-3 CHECKING THE POWER - check the following: A. The air flow should be as indicated by the air flow arrow. B. the 3 amber A, B, C lights should be on. C. The voltmeter should read 115V line to neutral or 200V line to line on A,B,and C phase A 200V line to neutral reading would indicate a line and neutral cable reversed. D. The amber ABC light should be on. A red CBA light would indicate reversed phase rotation.DO NOT OPERATE if the phase rotation is reversed. E. The E & F light should be on. If the light is not on; this would indicate a lose or broken interlock cable. F. The frequency meter should read approximately 400HZ. G. The ammeter should read 0A. 2-4 APPLYING THE LOAD - If the above steps checked OK, the load steps listed below may be turned on as needed to select up to 109KW. MAIN RATE SWITCH A. Step 1 is B. Step 2 is C. Step 3 is D. Step 4 is E. Step 5 is F. Step 6 is 10KW balanced load 19KW balanced load 28KW balanced load 37KW balanced load 46KW balanced load 55KW balanced load G. Step 7 is H. Step 8 is I. Step 9 Is J. Step 10 is K. Step 11 is L. Step 12 is 64KW balanced load 73KW balanced load 82KW balanced load 91KW balanced load 100KW balanced load 109KW balanced load Check to see that the voltage and frequency does not drop beyond acceptable limits under load. Return the rate switch to the off position. 2-5 SHUTTING DOWN - After turning the rate switches off, allow the load bank to cool down before turning the power unit off. Turn the power unit off and disconnect the power cable plug. CANNON LOAD BANKS, INC. PAGE 1 SECTION 2 METER OPERATION Each screen is displayed by pressing one of the four front panel buttons: ‘I’ for Current ‘V/Hz’ for Voltage and Frequency ‘P’ for Power and ‘E’ for Energy Display Screens of the M850 ‐ MP1 Press the ‘I’ button to access measurements on Current. One press of the button displays line currents; two presses of the button displays neutral current; three presses displays current demand; four presses of the ‘I’ button displays current maximum demand; five presses of the button brings the user back the to top of the category listing. Each press of the button steps the user to the next measurement. CANNON LOAD BANKS, INC. PAGE 2 SECTION 2 PARTS INFORMATION The following pages list the parts used in the load bank. All of the major parts are shown. Wire, screws, bolts, and small miscellaneous hardware are not listed. Parts that are purchased from a vendor will show a vendor name. These names refer to the vendor list is on page 8. Parts manufactured for or by Cannon Load Banks will not show a vendor name. A part number can be found by first locating the part on a drawing. After finding the part use the number to refer to the parts list on the opposite page. Each part will have a drawing number, Cannon Load Banks part number, description and the number used for each load bank. Parts should be ordered from the address below giving the machine model number, part number and the description. CANNON LOAD BANKS, INC. 502 PARK STREET PALMETTO, GA. 30268 PHONE 770 - 463 - 0504 FAX 770 - 463 - 2717 CANNON LOAD BANKS, INC. PAGE 1 SECTION 3 CONTROL PANEL PARTS 1 1 5.0 L2 1 1 5.0 L3 1 1 5.0 L1 L-100 D 2 1 FUSE FUSE .5A 2A 2 46KW 55KW 64KW 37KW 4,5,6 ON 28KW 19KW E & F 3 B 7,8 82KW 10KW 91KW 100KW 109KW OFF OFF A 73KW RATE C ABC CBA E&F 10 11 9 A B C N E F 12 FIGURE 3 - 1 CANNON LOAD BANKS, INC. 14 PAGE 2 SECTION 3 CONTROL PANEL PARTS FIGURE 3-1 DRAWING NUMBER PART NUMBER DESCRIPTION VENDOR NO. NUMBER USED 1 MR-D400 DIGITAL MULTIMETER 1 2 HD-25 HANDLE V-VEMALINE PRODUCTS (LR 185-32) 2 3 SW-22 TOGGLE SWITCH DPST V-NEWARK ELECTRONICS 1 4 FH-10 FUSE HOLDER V-BUSMANN (HKP-HH) 2 5 FS-05 .5A GLASS FUSE V-BUSMANN 1 6 FS-02 2A GLASS FUSE V-BUSMANN 1 7 KN-11 POINTER KNOB 1 8 SW-18 ROTARY SWITCH 18POS 4POLE 1 9 LT-10 115V AMBER LIGHT 4 10 LT-28 28V GREEN LIGHT 1 11 LT-15 115V RED LIGHT 1 12 TP-10 METER TEST JACKS 6 13 RP-40 RECEPTACLE 6PIN V-ANDERSON (4631B) 1 CANNON LOAD BANKS, INC. PAGE 3 SECTION 3 INTERIOR PARTS LAYOUT 9 1 2 8 5 6 7 3 10 12 9 4 11 FIGURE 3 - 2 CANNON LOAD BANKS, INC. PAGE 4 SECTION 3 L-100D INTERIOR PARTS FIGURE 3-2 DRAWING NUMBER PART NUMBER DESCRIPTION VENDOR NO. NUMBER USED 1 HD-10 FOLDING HANDLES V- VEMALINE PRODUCTS (EM 155-32) 1 2 BX-57 20" X 16" X 8" ALUM BOX 1 3 CT-35 350:5 CURRENT TRANSFORMER 3 4 SW-11 AIR FLOW SWITCH 1 5 TM-07 TERMINAL STRIP 2 6 RC-19 180KΩ RESISTOR 2 7 CP-47 .0047 MFD 600V CAPACITOR 2 8 RC-57 56KΩ RESISTOR 4 9 RY-25 24VDC 2P RELAY 25A , FLANGE MOUNT 12 10 FT-10 GLIDES 8 11 LR-45 4.2Ω RESISTOR 36 12 TR-26 28V POWER SUPPLY 1.5A 400HZ 1 * GL-24 RESISTOR GRILL 1.5 CANNON LOAD BANKS, INC. PAGE 5 SECTION 3 FAN PANEL PARTS LAYOUT 1 2 3 4 5 6 7 FIGURE 3 - 3 CANNON LOAD BANKS, INC. PAGE 6 SECTION 3 FAN PANEL PARTS FIGURE 3-3 DRAWING NUMBER PART NUMBER DESCRIPTION VENDOR NO. NUMBER USED 1 TM-20 8 POSITION TERMINAL STRIP V- NEWARK ELECTRONICS 1 2 SW-12 TILT SWITCH 1 3 GL-10 FAN GRILL 9 4 FN-40 200V 400HZ 3P FAN 9 5 TS-17 THERMAL SWITCH V-GEMLINE (L-175) 1 6 TS-15 THERMAL SWITCH V-GEMLINE (L-155) 1 7 FP-100D ALUM. FAN PANEL 1 CANNON LOAD BANKS, INC. PAGE 7 SECTION 3 VENDOR LIST The following is a list of vendors for parts shown in the parts list. VENDOR Anderson Power Products 145 Newton St. Boston MA. 02135 Allied Electronics, Inc. 3425 Corporate Way, Suite A Duluth, Ga. 30136 Bussmann Manufacturing Distributed by Allied Control Design Supply 1939-F Parker CT Stone Mountain, GA. 30087 Cutler-Hammer Distributed by Peerless EBM Industries, Inc. Distributed by Peerless E.F. Johnson Distributed by Peerless Electric Supply Co. 433 Bishop St. Atlanta, Ga. 30325 Gemline Products, Inc. 12472 Edison Way Garden Grove, Ca. 92641 Merrill Manufacturing Corpation 236 South Genesee Street Merrill, WI. 54452 Peerless Radio Corporation 3101 towercreek Pkwy, Suite 590 Atlanta, GA. 30339 SSAC, Inc. Electronics Corp. Distributed by Control Design Vemaline Products 333 Strawberry Field Rd. Warwick, RI. 02887 CANNON LOAD BANKS, INC. PAGE 8 SECTION 3 GENERAL SERVICE There is no regular maintenance required on the load bank. There are no adjustments inside the load bank. It should however be checked periodically for defective fans, burned out light bulbs, and defective meters. To remove the fan panel, remove the screws around the outer edge. The fan grills should be kept free of any trash. Do not place any objects in the fan or resistor grill. CANNON LOAD BANKS, INC. PAGE 1 SECTION 4 FAN REPLACEMENT The following are steps to take to replace a defective fan. 1. Remove the screws holding the fan panel to the load bank. 2. Remove the wires on the terminal strip coming from the load bank. 3. Drill out the rivets holding the fan (four on each side). 4. Lift up the fan and unplug the wires to the fan. Connect the plug to the new fan. 5. Rivet the new fan back to the fan panel and install the fan guard. 6. Install the wires back on the terminal strip and place the fan panel back on the load bank. Make sure that the wires are on the proper terminals. WHITE WHITE BLACK GREEN YELLOW YELLOW BLUE RED FIGURE 4 - 1 CANNON LOAD BANKS, INC. BLUE RED WIRES TO LOAD BANK PAGE 2 SECTION 4 L-100D INTERIOR WIRING FRONT PANEL RELAY PANEL 14 9 W-VLT LR2 LR1 LR3 LR4 LR5 LR6 K3 13 8,1 40 BL K 10 GRY 12 GRY 55 YEL 54 R ED 14 5,1 47 W-VLT 7- BRN 3- BLU 9- BRN 10 -GRY 11- BLU 12 -GRY 2- WH T 13 -VLT 8- BLU 4- WH T 14 -BL U 15 -VLT K6 14 4,1 46 BL K 19 WHT 21 WHT 60 R ED 61 YEL 17 4,1 76 W- OR G LR7 LR8 LR9 LR10 LR11 LR12 LR13 LR14 LR15 LR16 LR17 LR18 K9 17 6 W-OR G 15 0,1 52 BL K 14 8,1 50 BL K 39 BR N 37 BR N 73 YEL 72 R ED K8 28 VLT 30 VLT 66 R ED 67 YEL 16 3 W-YEL 16 -ORG 17 -BL U 18 -ORG 23 -BL U 24 -BR N 19 -WHT 20 -BL U 21 -WHT L1 13 4 25 -GRY 26 -BL U 27 -GRY LR19 LR20 LR21 LR22 LR23 LR24 LR25 LR26 LR27 LR28 LR29 LR30 15 6,1 58 BL K L2 13 2 22 -BR N K1 2 L3 13 0 15 4,1 56 BL K L4 12 4-1 29 13 1-1 33 L5 K11 13 3 17 3,1 74 W-ORG 13 1 36 WHT 34 WHT 70 R ED 71 YEL 12 9 15 2,1 54 BL K 12 5 12 6 12 7 12 8 K1 0 SW1D 13 7,1 73 W-ORG 116 BAR E 114 VLT 31 ORG 33 ORG 68 R ED 69 YEL SW1C L6 RESISTOR PANEL RESISTOR WIRE ARE ALL 12GA 114 115 VLT W-VLT SW1B 116 BAR E 12 3 14 6,1 48 BL K 116 BAR E K7 SW2 13 5 W-VLT SW1A 1 70 V LT 18 1 W-VLT 13 9,1 63 W-YEL 13 7 W-ORG 22 BR N 24 BR N 63 YEL 62 R ED 18 0 VLT 14 1 W-GRY 13 9 W-YEL 14 2,1 44 BLK K BL 16 9 R ED K5 97 R ED 27 GRY 25 GRY 64 R ED 65 YEL 12 0 WHT 118 WHT 14 0,1 42 BL K FS2 14 3,1 45 W-VLT 172 RED FS1 K4 101 BLU 13 6,1 38 BL K 105 YEL K2 108 GRN 14 7,1 49 W-VLT 15 5 BL K AUX N 13 6 BL K L3 L2 16 ORG 18 ORG 58 R ED 59 YEL re d ju mpe r L1 7 BRN 9 BRN 52 -RED 53 -YEL 95 ,111,12 1 WHT M1 13 5,1 43 W-VLT CT WIRES I I I 12 1 111 95 1 41 K1 W-GRY 12 2 112 96 K K K 13 VLT 15 VLT 56 R ED 57 YEL 96 ,112 ,1 22 B LK 2-WHT 4-WHT 5-YEL 1-R ED TR1 97 RED 109 119 GRN WHT 120 WHT 180 VLT 181 W-VLT 12 4 TP6 TP5 113 VLT TP4 10 7 GRN E 99 , 1 00 BL U 113 VLT A F R P1 GRN 10 6 10 7,1 08 ,1 09 110 C N TP1 TP2 10 3, 10 4 YEL 117 WH T 117 WH T TP3 B Y EL 5,53 ,5 5,5 7,59 ,6 1,6 3,65 ,6 7,6 9 71 ,73 ,7 5,77 ,79 ,8 1,10 2,1 03 ,1 05 16 8, 17 1 RED 28 -VLT 29 -BL U 30 -VLT 1,5 2,54 ,56,5 8 60 ,62 ,6 4,66 68 ,70 ,7 2,74 76 ,78 ,8 0,16 7 16 8,1 69 ,1 72 R ED 34 -WHT 35 -BL U 36 -WHT 3,8 ,11 ,14 ,1 7,20 23 ,26 ,2 9,32 ,35 38 ,41 ,4 4,47 50 ,98 ,9 9,10 1 BL U LR32 LR31 GROU ND 110 GRN 12 2 BL K 12 1 WH T 98 B LU E 2 10 6 GRN 5 3 10 2 YEL 112 BLK 111 WH T 6 15 8 BL K 118 WHT 119 WHT TO T5 ON FAN PANE L 7 C T2 BLU 3,8,11,1 4,17 20 ,23 ,2 6,29 ,32 ,3 5 38 ,98 C2 12 7 BL K 10 0 BL U 12 6,1 28 -BLK R1 96 BLK R2 95 WHT R6 LR34 32 -BL U 33 -ORG 38 -BL U 39 -BR N LR35 C T3 YEL 5 ,5 3,5 5,57 ,5 9 61 ,63 ,6 5,67 ,69 ,7 1 73 ,10 2 C 1,C2 C T1 -3 FS1 FS2 K1 -12 L1 -5 L6 LR 1- 36 M1 R 1-4 R 5-6 R P1 SW1 SW2 SW6 TP1- 6 TR1 C APA CITOR , .00 47 MFD C UR REN T TRAN SFORME R 35 0:5 FUSE , 2 A FUSE , .5A R ELAY, 24 VDC 2 P 25 A, FL ANGE LIGH T, N EON 115 V LIGH T, 2 8V LOAD RES ISTOR 4 .2 Ω METER , D IGITA L 3 PHA SE R ESISTOR , 5 6KΩ R ESISTOR , 1 80 KΩ R ECEPTACL E, 6 POLE SWITCH ,R OTAR Y 1 8 POS 4POL E SWITCH , TOGGL E DPST SWITCH , AIR FLOW TEST PIN S POWER SU PPLY 28 VD C R5 12 5 BL K R3 17 1 R ED R4 T2 C1 17 0 VLT 115 W- VLT T1 NO COM NC SW6 FIGURE 5-1 SIDE PANEL CANNON LOAD BANKS, INC. BOTTOM PANEL PAGE 1 LR36 LEGEND RED 1,52 ,5 4,5 6 58 ,60 ,6 2,64 ,66 ,6 8 70 ,72 ,1 67 8 10 4 YEL 37 -BR N C T1 1 16 7 RE D LR33 31 -ORG SECTION 5 BLANK FAN PANEL WIRING FAN WIRES ARE INCLUDED WITH FANS. 1 9 RED 2 9 BLUE 3 9 YEL 4 5 80 GRN 6 81 BLK 7 82 WHT 8 SW5 T5 83 WHT SW6 83 WHT 82 WHT SW7 81 BLK 80 GRN FIGURE 5 - 2 CANNON LOAD BANKS, INC. PAGE 3 SECTION 5 BLANK L-100D SCHEMATIC RP1 A B C E F N L1 L2 L3 L6 L4 L5 R5 R6 CT1 TP4 CT2 LR 4 9K W TP6 TP1 TP2 TP3 TP5 R3 R2 K1a CT3 LR 5 LR 6 K1b LR 1 K2a F1-12 R1 C2 C1 R4 LR 2 LR 3 LR 7 K2b FS2 K3a 1AC LR 8 LR 9 K3b LR 10 K4a 2C OM 3 DC5 DC+ 4 DC+ FS1 SW5 SW3 TR-1 M1 MULTIMETER k l k l k l LR 11 45 KW LR 12 K4b SW2 L1 L2 L3 N LR 13 AUX K5a LR 14 SW6 LR 15 K5b LR 16 K6 1 LR 17 LR 18 LR 19 LEGEND K6b SW4 K1 LR 20 LR 21 SW1A K7a 12 K7b 1 18 KW LR 22 K8a LR 23 LR 24 K8b K7 LR 25 K9a K8 SW1B 12 LR 26 LR 27 K9b K9 1 K10 LR 28 K10 a K11 LR 29 LR 30 SW1C C1 ,C 2 CT1-3 FN1-1 2 FS1 FS2 K1-1 2 L1 -5 L6 LR 1-48 M1 R1 -4 R5 -6 RP1 SW1 SW2 SW3 SW4 SW5 SW6 TP1-6 TR1 CAPACITOR , .004 7MFD CU RREN T TRANSFORMER 3 50:5 FAN 2 00 V 4 00H Z FUSE, 2 A FUSE, .5 A REL AY,2 4VDC 2 P 2 5A FL ANGE LIGHT, N EON 115V LIGHT, 2 8V LOAD RE SISTOR 4.2 Ω METER, D IGITAL 3 PHASE RESISTOR , 56 KΩ RESISTOR , 18 0KΩ REC EPTACL E, 6 POLE SWITCH , R OTA RY 1 8POS 4 POL E SWITCH , TOGGLE DPST SWITCH , THER MAL17 5° SWITCH , THER MAL 1 55° SWITCH ,TILT SWITCH , AIR FLOW TEST PINS,BLU E POWER S UPPLY 2 8VD C K10 b K12 12 36 KW LR 31 K11a K2 1 LR 32 LR 33 K11b LR 34 K12 a K4 SW1D K5 LR 35 LR 36 K3 K12 b CANNON LOAD BANKS, INC. 12 K6 PAGE 5 FIGURE 5-3 SECTION 5 BLANK