Omron H3DS-ML Multifunction Timer Coil: works with 24-48VDC or 24-230VAC Timing range: 0.1s to 120hr Contacts: SPDT Settings: Time Multiplier ( ) Time base (X) Mode (MODE) Timing interval is (Time Multiplier) x (Time Base) Connections: A1 and A2: coil power B1: Signal (trigger) 15: common contact terminal 16: NC contact terminal 18: NO contact terminal Modes of Operation: A: ON delay Timing: Starts when trigger is pressed (or on power-up if A1 and B1 are shorted together). Contacts: Switch when timing finishes. Release when power is lost. Further triggers: Ignored B: Flicker OFF (recycling, OFF start) Timing: Cycles start (OFF first) when trigger is pressed (or on power-up if A1 and B1 are shorted together), continue until power is lost. Contacts: Switched during ON time, released during OFF time Further triggers: Ignored B2: Flicker ON (recycling, ON start) Timing: Cycles start (ON first) when trigger is pressed (or on power-up if A1 and B1 are shorted together), continue until power is lost. Contacts: Switched during ON time, released during OFF time Further triggers: Ignored C: ON/OFF delay (type 1) Timing: ON timing starts when trigger is pressed (or on power-up if A1 and B1 are shorted together). OFF timing starts when trigger is released. Contacts: Switched during ON timing. Released when timing finishes. Switched during OFF time. Released when timing finished. Further triggers: If trigger is pressed during OFF timing, ON timing starts. Behavior continues as above. Manufacturer information does not describe behavior if trigger is released during ON time. D: OFF delay Timing: Starts when trigger is released. Contacts: Switch when trigger is pressed (or on power-up if A1 and B1 are shorted together). Release when timing finishes. Further triggers: Pressing trigger during timing will stop and reset timer. Behavior continues as above (contacts release when timing finishes) E: Interval (Interval ON) Timing: Starts when trigger is pressed (or on power-up if A1 and B1 are shorted together). Contacts: Switch when timing starts. Release when timing finishes. Further triggers: Pressing trigger when timing is not active has the above behavior. If trigger is pressed during timing, the timer resets, but does not stop. Contacts release when timing finishes. Note: holding trigger does not affect operation. This mode only registers Low-to-High triggers (leading edge, rising edge) G: ON/OFF delay (type 2) Timing: ON timing starts when trigger is pressed (or on power-up if A1 and B1 are shorted together). OFF timing starts when trigger is released. Contacts: Switch when ON timing finishes. Release when OFF timing finishes. Further triggers: Releasing trigger during ON timing will start OFF timing. Contacts switch immediately and release when OFF timing finishes. Manufacturer information does not describe behavior if trigger is pressed during OFF time. J: One-shot output ON delay Timing: Starts when trigger is pressed (or on power-up if A1 and B1 are shorted together). Contacts: Switch when timing finishes. Release after 1 (±0.6) second Further triggers: pressing trigger during timing resets timer but does not stop it. Contacts do not switch until timing finishes.