CENTRAL AIR-CONDITIONING SYSTEM A comprehensive report on: Central Air-Conditioning System Presented to: Dr. Atef Khalil Presented by: Alaa Saif Elnasr Ibrahim Sec:1 BN:11 Aya Mohamed Abdulazzaq Sec:1 BN:20 Rania Atef Omar Sec: 1 BN:31 Radwa Said Mohamady Sec: 1 BN:33 Table of Contents INTRODUCTION .................................................................................................................................... 2 CLASSIFICATIONS OF CENTRAL AIR CONDITIONING SYSTEMS ........................... 2 DIRECT EXPANSION (DX) SYSTEMS .................................................................................................... 2 CHILLED WATER SYSTEMS ................................................................................................................. 3 THE PARTS OF A CENTRAL AIR CONDITIONING UNIT ................................................ 5 CHOOSING OR UPGRADING YOUR CENTRAL AIR CONDITIONER ....................... 6 OVERVIEW OF HEALTH CARE HVAC SYSTEMS................................................................ 7 INTRODUCTION .................................................................................................................................... 7 VENTILATION AND ENVIRONMENTAL CONTROL FOR SPECIAL FUNCTIONS ...................................... 7 ROLE OF THE BUILDING ENVELOPE ................................................................................................... 7 DESIGN CRITERIA ............................................................................................................................... 7 HVAC SYSTEM HYGIENE ................................................................................................................... 8 INFECTION CONTROL ...................................................................................................................... 9 HOSPITAL ROOM DESIGN ............................................................................................................ 10 POSITIVE AND NEGATIVE PRESSURE ROOMS .................................................................................... 10 CONDITIONS IN EACH ROOM ............................................................................................................. 11 ISOLATION ROOMS .......................................................................................................................... 12 AII ROOMS ........................................................................................................................................ 12 PE ROOMS ......................................................................................................................................... 13 COVID-19 AND HVAC SYSTEMS ................................................................................................ 13 DISADVANTAGES ............................................................................................................................... 14 CONCLUSION AND RECOMMENDATIONS ......................................................................... 15 1 1-Introduction -In central air conditioning, air, water, or both are used as working fluids to produce the required heating and/or cooling, and therefore based on working fluids, central air conditioning systems can be classified into three groups:1-All-air systems: in these systems air is used as working fluid for heating and/or cooling purposes. 2-All-water (hydronic) systems: in these systems water is used as working fluid for heating and/or cooling purposes. 3-Air-water systems: in these systems both air and water are used as working fluids for producing heating and cooling purposes. -It is may be of interest to note that each type of the central air conditioning systems has several systems of sometimes different configurations, and the use of 1 any system depends on its advantages and disadvantages. -The following sections will provide descriptions of all types of central air conditioning systems. 2. Classifications of central air conditioning systems Direct Expansion (DX) systems: -In DX systems, the air is cooled with refrigerant passing through the tubes of the finned cooling coil. The Figure-1 below provides a conceptual view of a DX air-conditioning system. In this figure, the heat is extracted from the space and expelled to the outdoors (left to right) through 3 loops of heat transfer. • In the leftmost loop, a supply air fan drives the indoor air across the evaporator, where it transfers its heat to the liquid refrigerant. The resultant cooled air is thrown back to the indoor space. The liquid refrigerant is vaporized in the tubes of the evaporator. • In the middle loop, a refrigeration compressor drives the vapor refrigerant from evaporator to the condenser and back to the evaporator as a liquid refrigerant. The cycle continues in a closed loop copper tubing.• In the rightmost loop, a condenser air fan drives the ambient air across the condenser, where it transfers heat of refrigerant to the outdoors. The refrigerant is cooled and liquefied after expanding it through an expansion valve located between condenser and the evaporator. 2 Window air-conditioners, package units and split systems are typical examples of DX systems. These comprise of a hermetic sealed compressor/s, evaporator (cooling coil fabricated out of copper tubes and aluminum fins), a supply air fan, filter and a condensing unit. DX systems are essentially the factory assembled self-contained units and are also known as local systems. The application and unit capacity ranges are as follows: • Room air conditioner (capacity range of 0.5 to 3 TR per unit, suitable for an area of not more than 1000 square feet) • Packaged unit integral air-cooled condenser (capacity range of 3 to 50 TR, suitable for a maximum an area of 1000 – 10000 square feet) • Split system with outdoor air-cooled condenser (capacity range of 0.5 to 50 TR, suitable for an area of 100 – 10000 square feet) -Note: Each building is different and the design conditions differ greatly between regions to region. On hotter & humid regions the cooling requirement may be as high as 150 sqft/TR and in cooler places it could be as low as 500 sqft/TR. For comfort applications, it is reasonable to assume a figure of 200 sqft/TR as a rule of thumb for a preliminary estimation in absence of heat load calculations. Chilled Water Systems: -In chilled water system the air is cooled with chilled water passing through the tubes of a finned coil (cooling coil). Chilled water systems are further categorized as air-cooled or water cooled system depending on how the heat is rejected out of the system. The Figure-2 below provides a conceptual view of chilled water air-conditioning system with air-cooled condenser. The figure below depicts that heat is extracted from the space and expelled to the outdoors (left to right) through 4 loops of heat transfer. The chilled water is produced in the evaporator of the refrigeration cycle and is pumped to a single or multiple air-handling units containing cooling coils. The heat is rejected through an aircooled condensing unit in the rightmost loop. 3 The Figure-3 below provides a conceptual view of chilled water airconditioning system with water-cooled condenser. Here the heat is extracted from the space and expelled to the outdoors (left to right) through 5 loops of heat transfer. The chilled water is produced in the evaporator of the refrigeration cycle and is passed through a single or multiple cooling coils. The heat is rejected through a water-cooled condenser and the condenser water pump sends it to the cooling tower. The cooling tower’s fan drives air across an open flow of hot condenser water, transferring the heat to the outdoors. The main equipment used in the chilled water system is a chiller package that includes • A refrigeration compressor (reciprocating, scroll, screw or centrifugal type) • Shell and tube heat exchanger (evaporator) for chilled water production • Shell and tube heat exchanger (condenser) for heat rejection in water cooled configuration • Copper tube/Aluminum finned condenser coil and fan (condensing unit) for air cooled configuration • An expansion valve between condenser and the evaporator -The middle refrigerant loop is connected through a copper piping forming a closed loop. The water circuit on the chilled waterside is connected through an insulated carbon steel pipe and is a closed loop. The condenser water connected through a carbon steel piping is an open loop and requires 2 to 3 % make up water as a result of evaporation, drift and blow down losses from the cooling tower. The chilled water system is also called central air conditioning system. This is because the chilled water system can be networked to have multiple cooling coils distributed through out a large or distributed buildings with the refrigeration equipment (chiller) placed at one base central location. 4 -Chilled water systems are typically applied to the large and/or distributed areas. (Capacity range of 20- 2000 TR, suitable for an area of 3000 square feet and above) 3-The Parts of a Central Air Conditioning Unit -the main parts of your air conditioning system:Condenser: is a very essential part of your system and the outside unit of your air conditioning system, It sits outside on the ground and is typically round or square-shaped, it’s responsible for releasing the heat that your refrigerant has absorbed into the atmosphere, Refrigerant enters the condenser as a vapor but turns into a liquid as it cools while flowing through the condenser and condenser coils. Compressor: The compressor is a large AC component located inside of the condenser and isn’t visible, it helps the condenser by increasing the refrigerant’s pressure enough for the condenser to change the high pressure vapor into a liquid. Lineset: Lineset is the term that refers to the copper lines that run between the outdoor and indoor portions of your unit, these linesets are used to transport either liquid or gas refrigerant from one component to the next in the cycle. Evaporator: it serves essentially the opposite purpose of the condenser and is typically located inside the top of your air conditioning system. -Cooler, liquid refrigerant enters the evaporator from the condenser (via the lineset) and is met with lower pressure when this happens, the liquid refrigerant turns back into a gas and absorbs heat from the air around it, cooling the inside of your home, After this takes place, the gas refrigerant makes its way back to the condenser and the cycle repeats itself until your home is at a comfortable temperature. Expansion Valve: Just as the compressor assists the condenser by adjusting the pressure of the refrigerant, assists the evaporator and serves to lessen the pressure of the liquid refrigerant so that it can turn back into a gas inside of the evaporator. 5 Other Components: Besides the parts mentioned above, there are a few other components of your air conditioning system worth mentioning: thermostat that monitors the temperature in your home and either sustains from or sets the cooling process in motion according to your settings. When your air conditioning system pulls in air for cooling, the air filter helps trap any pollen, pet dander, dust or other particles from being recirculated. 4- Choosing or Upgrading Your Central Air Conditioner -Central air conditioners are more efficient than room air conditioners, quiet and convenient to operate. - When buying an air conditioner, look for a model with a high efficiency. Central air conditioners are rated according to their seasonal energy efficiency ratio (SEER), SEER indicates the relative amount of energy needed to provide a specific cooling output. Many older systems have SEER ratings of 6 or less. -Proper sizing and installation are key elements in determining air conditioner efficiency. Too large a unit will not adequately remove humidity. Too small a unit will not be able to attain a comfortable temperature on the hottest days. Improper unit location, lack of insulation, and improper duct installation can greatly diminish efficiency. -The standards do not require you to change your existing central air conditioning units, and replacement parts and services should still be available for your home's systems. -Other features to look for when buying an air conditioner include: A thermal expansion valve and a high-temperature rating (EER) greater than 11.6, for high-efficiency operation when the weather is at its hottest A variable speed air handler for new ventilation systems A unit that operates quietly A fan-only switch, so you can use the unit for nighttime ventilation to substantially reduce air-conditioning costs A filter check light to remind you to check the filter after a predetermined number of operating hours 6 An automatic-delay fan switch to turn off the fan a few minutes after the compressor turns off. 5- Overview of health care HVAC systems 5.1-introduction -In support of the health care process, HVAC systems are called upon to perform several vital functions that affect environmental conditions, infection and hazard control building life safety to Staff and patient comfort, the provision of therapeutic space conditions and facilitate optimum patient treatment outcomes. -Certain medical functions, treatments or healing processes demand controlled environmental temperature and/or relative humidity conditions that deviate from the requirements for personal comfort (i.e Operating rooms and nursery units) often require a range of room temperatures spanning several degrees, regardless of the season, to best facilitate a given procedure or patient condition, Burnpatient treatment rooms and bedrooms may require elevated temperature and relative humidity (RH) conditions. 5.1-Ventilation and Environmental Control for Special Functions -That include Many medical facilities functions or processes in which chemical fumes, aerosols, or harmful gases are stored and generated, posing health or safety hazards. Examples include laboratories where aerosolizing chemicals are used to fix slide specimens, preserve tissues or perform other processes orthopedic appliance and artificial limb shops involving adhesives and other aerosolizing agents, In such applications, HVAC equipment operates in conjunction with primary containment equipment. 5.2-Role of the Building Envelope -That include the integrity of the building envelope is essential to minimize the introduction of unconditioned, unfiltered air into a building, as well as to effectively exclude moisture. 5.3-Design Criteria -Typical criteria for HVAC design include indoor and outdoor environmental design conditions:1-outdoor air and total air change requirements. 2- economic considerations for equipment selection. 3-requirements for redundancy or backup equipment capacity. 4-room pressure relationships. 7 5- required filtration, and other benchmarks for systems and equipment selection and sizing. -Other criteria that influence the HVAC design may involve:1-envelope configuration and thermal performance. 2-environmental requirements for special equipment and processes. 3- operation and maintenance considerations. 4-clearance and conditioning requirements for electrical and electronic equipment. 5-equipment Redundancy and Service Continuity. - major HVAC service does not jeopardize life or health, it may lead to inability to continue medical functions and unacceptable economic impact to the building owner. Designers should also recognize that routine maintenance requirements will, at least on an annual or seasonal basis 5.4- HVAC system hygiene -In addition to the general topic of infection cause and control discussed previously, the designer must be aware of the potential for infection risks that can arise through poor design or maintenance of HVAC equipment, infections acquired within the health care facility Any location where moisture and nutrient matter come together can become a reservoir for growth of harmful microorganisms. Generally, hard surfaces (such as sheet metal) require the presence of liquid water to support microbe growth, whereas growth in porous materials may require only high relative humidity. -The task of the HVAC designers to minimize the opportunity for moisture and nutrients to collect in the system, through proper design of equipment, including adequate provisions for inspection and maintenance. - Potential high-risk conditions in an HVAC system include the following:1-outdoor air intakes located too close to collected organic debris, such as wet leaves, animal nests, trash, wet soil, grass clippings, or low areas where dust and moisture collect; this is a particular concern with low-level intakes and a primary reason for code-mandated separation requirements between intake and ground, or intake and roof. 2-Outdoor air intakes not properly designed to exclude precipitation; examples are intakes without intake louvers (or with improperly designed louvers) and intakes located where snow can form drifts or splashing rain can enter. 3-Improperly designed or installed outdoor air intake opening ledges where the collected droppings of roosting birds carry or support the growth of microorganisms. 8 4-Improperly designed or installed cooling-coil drain pans or drainage traps that prevent adequate condensate drainage. 5-Air-handling unit or duct-mounted humidifiers not properly designed or installed to provide complete evaporation before impingement on downstream equipment or fitting. 6-Filters and permeable linings, which collect dust, located too close to a moisture source, such as a cooling coil or humidifier. 7-Improper attention to maintenance during design, resulting in air-handling components that cannot be adequately accessed for inspection or cleaning. 6-Infection control Protection population -Positive pressure environment (PPE) rooms are designed for patients with severely compromised immune systems, such as bone marrow transplant and HIV patients. The HVAC systems for PPE rooms are designed to preclude airborne pathogens through the use of high-quality filtration, high air exchange rates, anterooms, and pressurization. -The emergency waiting room is an area of particular risk because both immune-compromised and undiagnosed contagious patient populations often coexist there, this type of space has high air exchange rates and all air is exhausted directly outside. Filtration -The efficacy of air filters is determined primarily by particle size but can be affected by the relative electrical charges of particles and filters. Bacteria typically are quite small, requiring filters that remove particles below 1 μm in size. ANSI/ASHRAE Standard) specifies a test procedure for evaluating the performance of air-cleaning devices as a function of particle size, resulting in a minimum efficiency reporting value (MERV) for a given device. -from ANSI/ASHRAE/ASHE Standard 170-2008, gives requirements for prefiltration and final filtration in different areas as indicated in Table 2-4 9 Effect of infection control on HVAC design -the figure below shows how the infection control measures affect the design of HVAC systems by influencing the following HVAC design parameters:•Outdoor air quantity, including natural ventilation. • Type and location of filters. • Humidification. • UV radiation. • Chilled-water temperature. • Supply air conditions. • Supply air change rates in individual rooms. • Air distribution and velocity. • Locations of return air grilles. • Balance of supply and return/exhaust air for pressurization. 7-Hospital Room Design -Many rooms in hospitals require special design considerations because of heightened infection concerns, high internal loads, special equipment, unique processes, and unique patients. -Many spaces in hospitals require maintenance of a differential pressure relative to adjacent spaces. For example, ORs, protective isolation, and sterile supply require positive pressure, whereas airborne infectious isolation, toilet, soiled, bronchoscopy, and decontamination rooms require negative pressure. 7.1-Positive and Negative Pressure Rooms -Positive pressure rooms maintain a higher pressure inside the treated area than that of the surrounding environment, this means air can leave the room without circulating back in, In this way, any airborne particle that originates in the room will be filtered out. Germs, particles, and other potential contaminants in the surrounding environment will not enter the room. In medical settings, a positive pressure room allows staff to keep vulnerable patients safe from infections and disease. -negative pressure room uses lower air pressure to allow outside air into the segregated environment, these traps and keeps potentially harmful particles within the negative pressure room by preventing internal air from leaving the space, Negative pressure rooms in medical facilities isolate patients with infectious conditions and protect people outside the room from exposure. 10 7.2-conditions in each room Operating rooms - The purposes of the HVAC system in an operating room (OR) are to minimize infection, maintain staff comfort, and maintain patient comfort. - According to ASHRAE standard 170-2008 ORs requirements are:•air change per hour (ACH) value has been 25 ach supply air including 5 ach of outdoor air. • designed for a positive pressure differential is 2.5 Pa, 35-47 L/s. • most standard operating rooms require MERV 7/8- 14/15-17 filtration. • air velocity is 0.25-0.45 m/s. • relative humidity 30-60%. • temp. 18-26 °C. • air distribution is laminar. • Outdoor Air intakes: The location of outdoor air intake for an AHU must not be located near potential contaminated sources like DG exhaust hoods, lab exhaust vents, and vehicle parking area. • Preventive Maintenance of the system: It is recommended that periodic preventive maintenance be carried out in terms of cleaning of pre filters, micro vee filters at the interval of 30 days ICU - The level of care and electronic monitoring of patients in these rooms are greatly increased compared to conventional patient rooms. - According to ASHRAE Standard 170-2008 requirements are:• variable-range temperature capability 21.1-23.9°C. • relative humidity of 30- 60%. • ACH value has been 6 ach as minimum, of which a minimum of 2 ach must be outdoor air. • air velocity is 1.5 to 2.5 m/s • It is recommended that all air should be filtered to 99% efficiency down to 5 microns. • Central HVAC with HIFA filter Emergency department -The emergency department is generally the point of entry to a hospital for undiagnosed patients, some of whom may be carriers of dangerous infectious diseases so it need good air conditioning system to avoid them. - According to ASHRAE Standard 170-2008 requirements are:• relative humidity is max 65% • variable-range temperature capability 21-24°C. • ACH value has been 12 ach as minimum, of which a minimum of 2 ach must be outdoor air. 11 • there are basically two filtration methods: particulate and ultraviolet germicidal irradiation (UVGI) Because each contaminant has a different level of urgency, filtration methods can vary. Burn unit (WIC) -This room type requires careful humidity control and, normally, the ability to achieve elevated temperature, Regimens of patient treatment vary between providers, and some institutions use radiant-heating equipment to supplement ambient heating. - According to ASHRAE Standard 170-2008 requirements are:• variable-range temperature capability 21-24°C. • with HEPA-filtered (MERV 17). • air velocity is 0.25 m/s. • relative humidity is 40- 60%. • ACH value has been 12 ach as minimum, of which a minimum of 2 ach must be outdoor air. • maintain the room under positive pressurization at all times. Cardiac and Interventional Lab -In “cath” and interventional labs, stents, balloons, and valves are placed in the body, the device placed inside the artery is then guided using fluoroscopy. -Because there is continuous X-ray exposure for considerable time, good shielding is a necessity and requires:• ACH value has been 20 ach as minimum, of which a minimum of 4ach must be outdoor air. • laminar flow ceiling with laminar flow diffusers •maintain the room under positive pressurization at all times. • relative humidity heating 30-60%, relative humidity cooling 20-60%. •noise criteria 35-45 • variable-range temperature capability 20-24°C. 8-Isolation rooms -Airborne infectious isolation (AII) rooms are for patients having an airbornecommunicable disease. For an AII room, the HVAC system functions as one of multiple levels of infection control designed to contain patient-generated infectious microbials within the room, to prevent the spread of infection to other patients and staff. .9.1-AII Rooms -AII rooms have two major ventilation design criteria:1- negative air pressure relative to all adjoining spaces 12 2- an air distribution pattern within the room designed to reduce airborne infection. 3-The recommended design approach favors creating maximized air mixing, pressurization, and airflow, thereby minimizing exposure. 9.2-PE Rooms -Protective environment (PE) rooms include those for bone marrow transplant, oncology, hematology, and similar rooms for any condition that leaves a patient immunocompromised. -A PE room seeks to protect the patient from all potential airborne infectious organisms, some of which may be benign to those with normal immune systems. Combined AII/PE rooms are for patients suffering from a weakened immune system who also have an airborne communicable disease. In this type of room, HVAC issues involve a combination of both AII room and PE room considerations. - According to ASHRAE Standard 170-2008 requirements for isolation room are:• variable-range temperature capability 21-24°C. • most standard isolation rooms require MERV 8-17 filtration. • air velocity 0.5 m/s. • air distribution is laminar. • pressure difference is 2.5 pa. • ACH value has been 12 ach supply air including 2 ach of outdoor air. 9- Coronavirus covid-19 and HVAC systems -According to the CDC (Centers for Disease Control and Prevention) and ASHRAE (The American Society of Heating, Refrigerating and AirConditioning Engineers), hospital HVAC systems play a critical role in mitigating the spread of diseases like COVID-19, MERS, SARS, and tuberculosis ,When an infected person coughs or sneezes, respiratory droplets can travel through the air and be inhaled by people nearby. Room pressurization, air change rates, humidity, and temperature all play an integral role in mitigating airborne contaminants to provide a healing space for patients while protecting healthcare providers. 13 - AIIRs constantly provide clean air to patients and help protect staff from infection. AIIRs contain, dilute, and exhaust contaminated air through a high-efficiency particulate air (HEPA) filter, and then vent it outdoors. - The negative pressure prevents contaminated droplets from traveling to other areas of the hospital when the doors are opened. Room doors should be kept closed except when personnel are entering and exiting. Entry and exits should be minimized as air currents from personnel traffic can disrupt proper airflow, so AIIR HVAC equipment must be fastacting, adjusting immediately to changing conditions. Facilities should monitor and document AIIR negative pressure function, and there should be a constant visual indication from the room pressure controller or monitor. Droplet suspension: illustration of the aerobiology of droplets and small airborne particles produced by an infected patient. 10-Disadvantages of air conditioners -Air conditioners use a lot of electricity. - financial disadvantage. -spending too much time in an air-conditioned environment can contribute to health problems such as asthma, tightness in the chest and other respiratory ailments. -Low temperatures will lead to a sharp contraction of blood vessels, poor blood flow and joint pain. -the temperature difference between indoor and outdoor, people often will feel hot and cold, this will result in the body conditioning system disorders. 14 11-CONCLUSIONS AND RECOMMENDATIONS -The air is not just a medium but it can be regarded as a guard in the critical health applications. -The proper direction of the airflow increases the possibilities of successful pollutant scavenging from healthcare applications. -The numerical tool, used here, was found to be so effective to predict the airflow pattern in the healthcare facilities at reasonable costs and acceptable accuracy. -Good architectural design allows the HVAC system designers to properly locate the supply outlets and extraction ports in the optimum locations. -The hospitals/medical institution deals with life of the clientele, the lives saved by providing appropriate therapeutic, diagnostic and treatment facilities justify that the investment for air conditioning is a small cost for better quality care to the patients. References - ANSI/ASHRAE (American Society of Heating, Refrigerating and Air Conditioning Engineers) /ASHE standards 170-2017 -HVAC design manual for hospitals and clinics book - https://www.health.ny.gov/facilities/cons/docs/ashrae_table_7-1.pdf - https://www.energy.gov/energysaver/central-air-conditioning - https://www.hometips.com/how-it-works/central-air-conditioners.html - https://www.intechopen.com/online-first/central-air-conditioning-systems-and-applications - https://www.richmondsair.com/hvac-guide/equipment-101/parts-central-air-conditioning-unit 15