Uploaded by Denis Roche

Equipment Planned Maintenance

MD501 & QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Maintenance Duties (MD) &
Qualified Maintenance Duties (QMD)
Electrical Maintenance
Potential Hazards:
Electricity
Hot Surfaces
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 1 of 29
Commercial in Confidence
MD501 & QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Maintenance Duties (MD) &
Qualified Maintenance Duties (QMD)
Contents
SECTION 1 – INTRODUCTION .............................................................................4
1. 1 BACKGROUND.................................................................................................................... 4
1.2 MANAGERS OVERVIEW ...................................................................................................... 4
1.3 ELECTRIC SHOCK ............................................................................................................... 5
1.4 IN – STORE INSPECTION ................................................................................................... 5
1.5 REPAIR OF ELECTRCAL EQUIPMENT & PLANT............................................................... 6
1.6 PROTECTION ........................................................................................................................ 6
1.7 FREQUENCY OF ELECTRICAL PLANNED MAINTENANCE INSPECTION ........................ 7
SECTION 2 - POTENTIAL HAZARDS
.........................................................8
2.1 HOT SURFACE ..................................................................................................................... 8
2.2 ELECTRIC SHOCK ............................................................................................................... 8
SECTION 3 – CONTRACTOR MANAGEMENT....................................................8
3.1 GENERAL REQUIREMENTS................................................................................................ 8
SECTION 4 - GOVERNING BODIES.....................................................................9
4.1 CONFORMING AUTHORITIES & AUSTRALIAN STANDARDS .......................................... 9
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 2 of 29
Commercial in Confidence
MD501 & QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Maintenance Duties (MD) &
Qualified Maintenance Duties (QMD)
Qualified Technician Only Tasks (QMD501)
SECTION 5 – ELECTRICAL MAINTENANCE INSPECTION AND TESTS: ..... 10
5.1 ELECTRICAL TAGS ...........................................................................................................10
5.2 REMEDIAL WORKS & ACTION ..........................................................................................10
5.3 TESTING EQUIPMENT .........................................................................................................11
5.4 FREQUENCY OF MANDATORY ELECTRICAL PLANNED MAINTENANCE
INSPECTION ...............................................................................................................................11
5.5 FREQUENCY OF BEST PRACTISE ELECTRICAL PLANNED MAINTENANCE
INSPECTION ...............................................................................................................................12
5.6 SPECIFIC MAINTAINENCE REQUIREMENTS...................................................................12
5.6.1 TESTING AND TAGGING OF EQUIPMENT ..................................................................12
5.6.2 MAIN SWITCHBOARD...................................................................................................12
5.6.3 DISTRIBUTION BOARDS (DB) [IF APPLICABLE] .........................................................14
5.6.4 TESTING OF RCD’S ......................................................................................................15
5.6.5 EMERGENCY AND EXIT LIGHTS .................................................................................15
5.6.6 GENERAL LIGHTING INSTALLATION ..........................................................................17
5.6.7 ACCESSORIES..............................................................................................................17
5.6.8 MAINS AND SUBMAINS ................................................................................................18
5.6.9 DUE DILLIGENCE .........................................................................................................19
REPORT SHEET A .....................................................................................................................21
REPORT SHEET B .....................................................................................................................21
REPORT SHEET C .....................................................................................................................23
REPORT SHEET D .....................................................................................................................24
REPORT SHEET E......................................................................................................................25
REPORT SHEET F......................................................................................................................26
REPORT SHEET G .....................................................................................................................27
REPORT SHEET K .....................................................................................................................28
NOTES: ............................................................................................................... 29
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 3 of 29
Commercial in Confidence
MD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Maintenance Duties (MD)
SECTION 1 – INTRODUCTION
1. 1 BACKGROUND
Without proper maintenance, the safety and integrity of equipment/plant can not be ensured
even if the equipment/plant has been designed and manufactured with due consideration to
health and safety.
The Occupational Health and Safety Act (the Act) and Occupational Health and Safety (Plant)
Regulations 1995 place an obligation on employers to ensure equipment/plant is maintained.
The Act also requires employers to provide and maintain, so far as is practicable, a working
environment that is safe and without risks to health for employees who undertake inspection
and maintenance work.
1.2 MANAGERS OVERVIEW
Electrical Safety is of the utmost importance in our stores. This manual describes electrical
maintenance duties in formats i.e. Maintenance Duties (MD501) which can be carried out by
Gloria Jean’s Coffees personnel and qualified technicians, and Qualified Technician
Maintenance Duties (QMD501) which can only be carried out by a qualified technician. The
document outlines the in-service electrical tasks considered necessary for both the store (MD
501) & tasks for the licensed electrical contractor (QMD 501) as minimum planned
maintenance to ensure the safety of person(s) using electrical equipment.
Electrical equipment is required to be inspected tested & tagged to Australian Electrical
Standard (AS3760) by a qualified & certified personnel on an Annual & Bi Annual basis to
detect unsafe conditions. This is to ensure we take reasonably practicable steps to ensure that
no danger results from the use of such equipment. This in effect, requires the implementation
of a systematic and regular program of maintenance, inspection and testing.
It is the Franchise Partner or Store Manager’s responsibility to co-ordinate the Electrical
Contractor to schedule this work.
All of the required inspections & checks that are outlined in this manual shall not remove the
responsibility from the personnel carrying out the works to undertake procedures in accordance
with requirements within the relevant state specific Occupational Health and Safety Legislation,
and Australian Standards for in-service safety inspection and testing of electrical equipment /
appliances / plant.
The Electrical Planned Maintenance Qualified Technician Tasks (QMD501) includes various
inspections that need to be completed by a Licensed Electrical Contractor. A licensed electrical
contractor will ensure correct diagnostic of faults & legal remedial works in store. Your electrical
contractor should already be familiar with and practising these tests & procedures that need to
be applied to our stores for the provision of a ‘safe place’. The electrical contractor should have
a current copy of the relevant Standards. The in store inspection procedures are mandatory.
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 4 of 29
Commercial in Confidence
MD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Maintenance Duties (MD)
On completion of the checks, the original signed copy of the report sheet/book must be given to
the store manager and filed in section 5 of the OH&S manual within the store premises. The
report sheet will outline inventory of all electrical equipment tested by description a list of failed
items, new repaired items log and next due date. The manager is required to record completed
tasks on completion and in accordance with the Gloria Jean’s Coffees Daily Book - Equipment
Planned Maintenance Yearly Schedule.
This manual must be stored in the Equipment Planned Maintenance Binder which forms part of
the Operations Standards Manual within the store & shared with your approved electrical
contractor for their review.
1.3 ELECTRIC SHOCK
Electric shocks caused by electrical equipment occur without warning and are often serious.
The severity of the electric shock can range from a tingling sensation to electrocution and
death, the factors which affect the severity of electric shock are the :(a) value of shock current
(b) time for which it flows
(c) the path through the body
1.4 IN – STORE INSPECTION
As a manager you are required to inspect electrical cords regularly, the things to look for when
carrying out a visual check are as follows:(a) frayed or split outer casing
(b) badly worn, perished or kinked insulation
(c) ensure that any lead is mechanically secured at termination
(d) chipped, cracked, discoloured or broken fittings
Additionally, you are required to visually inspect and detect any adverse condition to any
electrical apparatus observed to be unsafe and or faulty, such as exposed electrical
components & wiring. Examples of electrical apparatus to which this applies but not limited to
are:- power outlets, lighting & fittings, switches, equipment, plant, switchboards, computers,
monitors, air conditioner, vacuum cleaner, power tools, electric water urns / heaters, insect
traps, coffee bean grinders, ice machine, coffee, espresso machines, toasters, grillers,
microwave, hand dryers, dishwasher, refrigerated & ambient pastry display cabinets, garbage
compactor, refrigerated & freezer cabinets, beverage mixers, bean bar scale, brewer, music
hard drives & system, register, refrigerated beverage whipper dispenser.
Do not operate equipment if it has a damaged cord or plug; if it is not working properly, or if it
has been damaged or dropped. Faulty electrical equipment / plant can also lead to fires, which
may also cause death or injury to others. Report any such defect.
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 5 of 29
Commercial in Confidence
MD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Maintenance Duties (MD)
It is best practice to have your Licensed Electrical Contractor visually check all lighting
equipment, luminaires diffusers for correct position and integrity. Replace all damaged diffusers
and defective lamps. Other electrical lighting components which may require replacing will be
done by the licensed Electrical Contractor or qualified technician.
No person should attempt to repair any electrical equipment unless qualified to do so.
1.5 REPAIR OF ELECTRCAL EQUIPMENT & PLANT
If the equipment is found faulty it must be immediately disconnected from the energy source by
unplugging the power supply lead by the plug body only, isolate & withdraw from service.
Equipment is required to be labeled by the person carrying out the inspection to warn against
further use until repaired by authorised service agent or service personnel. In the event the
equipment is deemed permanently inoperable then dispose of or destroy.
At no time should you re-activate tripped Residual Circuit Breaker Device (RCD) or Earth
Leakage Circuit Breaker (ELCBs). Immediately place service call to qualified electrical service
personnel or authorised equipment service agent. Failure to do so may result in electric shock
and/or further damage to electrical components that may fail to continue to operate effectively
as per design or fail to provide protection against electric shock.
Equipment should be serviced by qualified personnel only. Contact the Supplier for
adjustment or repair.
1.6 PROTECTION
A Residual Current Device (RCD) is a device intended to isolate the circuits connected to it in
the event of a predetermined current flow to earth. RCDs are also known by other names Earth
Leakage Circuit Breaker (ELCB).
All power outlets, portable equipment and kitchen equipment must be protected by an Earth
Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD). Display RCD sign
whenever RCD is fitted in the vicinity of the distribution board / switchboard as required by local
council regulations.
It is necessary for the Electrical Contractor or authorised service personnel to verify an RCD
has operated due to an earth fault when responding to a service call. It is necessary for the
authorised service personnel to be satisfied that an earth fault does not exist and the
equipment has been serviced. Additionally, the RCD is required to be tested with the correct
equipment confirming that it still operates as designed.
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 6 of 29
Commercial in Confidence
MD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Maintenance Duties (MD)
An RCD installed at a workplace must be kept in good working condition and be tested on a
regular basis by a competent person to ensure its continued effective operation. A record
should be kept of these tests. A “competent person” is someone who is an individual who, by
way of training and/or experience, is knowledgeable of applicable equipment, is capable of
identifying workplace hazards relating to the specific operation, is designated by the employer,
and has authority to take appropriate actions.
RCDs will not protect against all electrical incidents; for example RCDs will not protect against
the serious shock situation where a person contacts both active and neutral conductors without
current flowing to earth.
RCDs are an addition to safety measures not a substitute for them.
1.7 FREQUENCY OF ELECTRICAL
CONDUCTED BY STORE
PLANNED
MAINTENANCE
INSPECTION
Monthly
•
Check the operation of each exit and emergency light by depressing the “test” pushbutton
on each fitting and checking whether the light changes to battery supply.
•
Any incorrect operation must be reported to the Store Manager and any faults remedied.
•
A monthly inspection of all lights to determine whether any lamps or fluorescent starters
have failed. Replace all readily accessible failed lamps or starters provided that they are
not damaged.
Note: Any lamp failures noticed at other times should be rectified as they occur.
•
Special note is to be taken that tungsten halogen lamps must not be touched with bare
hands as the acid from the skin will deteriorate the quartz glass envelope of the lamp.
•
Other than replacement of lamps and readily accessible starters it is recommended that all
other light fitting maintenance be carried out by fully qualified licensed electricians.
Note: Polished lighting diffusers should not be touched with bare hands as finger prints are
often difficult to remove. Cotton gloves should be utilized when cleaning or handling
polished diffusers.
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 7 of 29
Commercial in Confidence
MD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Maintenance Duties (MD)
SECTION 2 - POTENTIAL HAZARDS
2.1 HOT SURFACE
Hot Surfaces
Hot surfaces may be exposed during these checks by press toasters, grillers, coffee machines
and the like equipment in store. Hot surfaces may cause burns.
2.2 ELECTRIC SHOCK
Electricity
Potential hazards and cautions may be exposed during these procedures. Follow safe working
practices and procedures to control the hazards. If the power point is not readily accessible turn
the equipment off at the isolation switch or the circuit breaker in the switchboard.
Prior to moving any equipment in service for cleaning, moving, repairing and testing all power
must be switched off.
Note: Double adaptors & Piggy back plugs must not be used in our work place
SECTION 3 – CONTRACTOR MANAGEMENT
3.1 GENERAL REQUIREMENTS
The licensed electrical contractor, its employees and sub-contractors must be suitably qualified
and licensed for the tasks being performed.
They must have public liability insurance up to the value of $20 million. This is essential as
Gloria Jean’s Coffees own insurance or individual store Franchise Partners may be exposed in
the event of inadequate cover.
In all States and Territories a current Workers Compensation Policy must be place which
covers all contractors’ employees.
Evidence of Hazard Assessment prior to commencement of any task performed.
It is the stores responsibility and due diligence to check and confirm qualifications, licence, safe
work method statement and insurance details of all in-store approved contractors. Complete
Preferred Contractor Register filed in section 5 of the OH&S Guidelines & Workbook. File
copies of all documents and complete Contractor Service Agreement in Section 2 of the OH&S
Guidelines and work book
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 8 of 29
Commercial in Confidence
MD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Maintenance Duties (MD)
SECTION 4 - GOVERNING BODIES
4.1 CONFORMING AUTHORITIES & AUSTRALIAN STANDARDS
The Electrical Contractor shall carry out all work in accordance with relevant state specific
Occupational Health and Safety Legislation, and Australian Standards for in-service safety
inspection and testing of electrical equipment/appliances/plant, wiring regulations and any other
Authority having jurisdiction over this work. This shall include but not is limited to:
State / Territory Occupational Health & Safety Authority and relevant legislation
•
•
•
•
•
•
•
•
NSW WorkCover Authority
QLD WorkCover Authority
VIC WorkCover Authority
WA WorkCover West Australian
NT Worksafe
TAS Workplace Standards Tasmania
ACT WorkCover Authority
SA WorkCover Corporation
•
The Building Code of Australia (BCA)
•
Australian Electrical Standards as applicable
AS3760 – In Service Safety Inspection and Testing of Electrical Equipment
AS3017 – Electrical Installations – Testing and Inspection Guidelines
AS3000 – SAA Wiring Rules
AS2293 – Emergency evacuation lighting for buildings
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 9 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
SECTION 5 – ELECTRICAL MAINTENANCE INSPECTION AND
TESTS:
All Tasks Must Be Performed by Qualified Technician Only
Warning Electrical Shock Hazard
Potential hazards and cautions may be exposed during these procedures. Follow safe
working practices and procedures to control the hazards.
5.1 ELECTRICAL TAGS
On completion of each safe test / inspection, durable, non-metallic, non-reusable tags robust
enough for our environment are required to be attached to each individual piece of equipment to
verify that the equipment has been checked, tested & passed. The integrity of the tag is required to
be maintained given our aggressive environment.
Tags must contain all necessary information including due date of the next inspection. This will be
noted on the tag as well as electrical contactors details.
Where the equipment test as safe, a tag needs to be attached to the power lead within 300mm of
the plug end by way of black nylon cable tie or fastening system fit for purpose once the equipment
has passed its inspection prior being placed back in service.
5.2 REMEDIAL WORKS & ACTION
All remedial works should be completed in accordance with AS3760 & AS3000
Locking out of equipment is the most effective way of preventing it from becoming operational
during maintenance or failure. If any work is to be carried out on a particular piece of equipment
and there is a possibility of somebody inadvertently turning it on, the qualified person carrying out
the work must personally fasten a red and black "DANGER" tag or lock to the main isolating switch.
In the event that the electrical contractor shall remove from operation any equipment found to be
faulty and tag “Caution – Do not operate” on the equipment or attached to the relevant circuit
breaker if the equipment is permanently fixed wired
As a result of the electrical inspection or checks, the electrical contractor is required to record on
the report sheets any remedial work, defects and action taken. Defects require immediate action
before equipment can be placed back into service. This needs to be reported to the Store Manager
who will log the defect & arrange for the immediate action.
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 10 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
All Tasks Must Be Performed by Qualified Technician Only
Warning Electrical Shock Hazard
Potential hazards and cautions may be exposed during these procedures. Follow safe
working practices and procedures to control the hazards.
After completing works that have impacted the electrical safety of the equipment / appliance / plant,
an electrical inspection must be carried out and recorded before the equipment is returned or
placed back into service.
There could be a need for the licensed electrical contractor to work on small equipment replacing
leads and the like, in doing so, they need to maintain minimum standards with the use of the
manufactures recommended parts.
5.3 TESTING EQUIPMENT
The electrical testing device is required to comply with the relevant standard.
The use of appropriate Earth Leakage test equipment is required for testing RCD’s.
Testing equipment to be periodically tested & calibrated as per the relevant standard
5.4 FREQUENCY OF MANDATORY ELECTRICAL PLANNED MAINTENANCE INSPECTION
The following scheduled checks by Licensed Electrical Contractor:
•
12 Monthly inspection on Stationary and Portable Equipment / Appliances & associated
flexible leads as per AS3760
•
12 & 6 Monthly 90 minute discharge test of the Emergency Lumininaires and Exist lighting
system as per AS2293
•
12 Monthly Push button tests for RCD’s including operating times whilst contractor is
waiting for 90 minute emergency lighting discharge test during the above procedure
AS3760 - Table 2
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 11 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
All Tasks Must Performed by Qualified Technician Only
Warning Electrical Shock Hazard
Potential hazards and cautions may be exposed during these procedures. Follow safe
working practices and procedures to control the hazards.
5.5
FREQUENCY OF BEST PRACTICE ELECTRICAL PLANNED MAINTENANCE
INSPECTION
•
12 Monthly inspection on Main Switchboards, Distribution Switchboards, Control and
Isolation Panels (RCD’s).
•
12 Monthly Lighting Equipment visual checks of all lighting equipment, electrical
components and luminaires diffusers. Record condition of all lighting including defective
lamps, damaged fittings & diffusers. AS3760.
Follow same procedures for remedial activities to be carried out following the inspections as per
point 5.2 - Remedial Works & Action
5.6 SPECIFIC MAINTAINENCE REQUIREMENTS
5.6.1 TESTING AND TAGGING OF EQUIPMENT
•
as described in clause 5.4
5.6.2 MAIN SWITCHBOARD
The supply to the site will need to be shut down for any works on the line side busbars and
equipment. There should also be two people present if the switchboard is to be opened and live
parts exposed.
The following maintenance is to be carried out:
i)
Visual inspection of all components of the main switchboard to detect signs of
deterioration or damage. This inspection shall include, but is not limited to:
•
All equipment in the switchboard
•
Busbars
•
Supports
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 12 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
•
•
•
•
•
•
•
•
Insulating material
Panels and doors including seals
Cable and busbar connections
Markings and labeling
Contact surfaces
Switch and circuit breaker mechanisms
Earthing
Cable glands
Any deterioration must be rectified or the component replaced. Particular notice must be
taken to:
•
Signs of overheating
•
Signs of cracking or insulating materials
•
Signs of deformation of supports or any damage to these
•
Signs of corrosion or electrolysis
•
Signs of condensation
•
Any other deterioration, damage or missing components
•
Proper operation of components
•
Proper lubrication of components where required
ii)
Check the tightness of all connections. This includes:
•
Cable connections
•
Busbar connections
•
Earth connection
•
Structural components and supports
•
Bushings
iii) Operation of all components. In particular each switch and circuit breaker shall be
operated three times.
iv) Megger test the switchboard between phases and between each phase to earth. Any low
resistance reading shall be checked and the cause determined and rectified.
v) The switchboard is to be fully cleaned out of all dust and debris.
vi) All cable installations must be checked and any untidy work corrected. Also any redundant
or temporary cabling is to be removed.
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 13 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
vii) Thermal Scan of Main Switchboard(s) and associated report. This test is to be done when
the switchboard is fully loaded for at least 2 hours with all air conditioning running. Note:
This test is required only when the switchboard is heavily loaded near its capacity or
shows signs of heating problems.
viii) The recommended period for the above check - minimum annually.
ix) All maintenance is to be carried out by fully qualified licensed electricians.
x) If a fault has occurred on the switchboard or a circuit has tripped the cause of the fault
must be determined and rectified prior to re-commissioning the switchboard or re-closing
the circuit. Thorough maintenance of the switchboard will be required and the tripped
component fully checked prior to its re-commissioning. If there is any doubt as to the
condition of any component after any fault, the component is to be replaced.
xi) Whenever annual maintenance is carried out, spot load checks should be done on all
major circuits with a tong tester and the results recorded. Any circuits that are approaching
80% of the rated load should be reported to the building manager. Any circuits exceeding
80% of the rated load must be carefully checked to ensure overheating of any components
does not occur.
5.6.3 DISTRIBUTION BOARDS (DB) [IF APPLICABLE]
Maintenance
Maintenance is generally similar to the maintenance described for the main switchboard, but does
not require the shut down of the site power supply. However the supply to each distribution board
should be isolated while maintenance is being carried out. A thermal scan is only required if:
i)
ii)
iii)
iv)
There is any doubt about the condition of a DB
The DB has been subject to a fault and put back into service
The DB is rated at least 100amps and is more than 5 years old
The DB is fully utilised
Distribution Boards generally incorporate moulded case circuit breakers and residual current circuit
breakers (earth leakage circuit breakers) for circuit protection. Some DB’s also incorporate
contactors, relays and time switches for the control lighting.
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 14 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
In addition to the general maintenance of distribution boards (DB’s), the operation of residual
current circuit breakers should be tested by pressing the test button on each circuit breaker and
resetting the breaker by placing the circuit breaker switch in the ‘ON’ position. Note: it may be
necessary to first place the circuit breaker in the ‘OFF’ position, before switching to ‘ON’.
In addition to the above, check that a circuit schedule is attached to the inside of the door of the
DB, that it is accurate and typed in a neat and tidy manner. Amend and/or replace as necessary.
5.6.4 TESTING OF RCD’S
•
As described in clauses 5.4 & 5.6.3
5.6.5 EMERGENCY AND EXIT LIGHTS
Emergency and exit lights are of the single point type where each light has its own integral battery
pack and charger unit.
The battery charger for each light is fed from an un-switched active (other than the switching
provided by the emergency and exit lighting test facilities) originating at the lighting circuit feeding
the same general area of the emergency or exit light. In this way the batteries are being charged at
each fitting at all times.
The initial capacity of the battery for any newly provided emergency or exit light is 2 hours for the
first 12 months and 1 ½ hours thereafter i.e. the battery will initially operate the light for 2 hours if a
power failure occurs. After 12 months the battery capacity is expected to reduce to 1 ½ hours. This
is the minimum acceptable period after 12 months. After a total discharge it takes approximately 16
hours for the batteries to fully recharge.
The life of each battery is in excess of 2 years.
Each emergency and exit light has a ‘test’ pushbutton and a light emitting diode (LED). The LED
illuminates when the light is on normal power and the battery is charging.
An emergency and exit lighting test circuit has been provided with every distribution board
providing power to emergency and exit lights. The circuit has the following features:
•
•
•
‘Test’ pushbutton (or key switch) and ‘Test’ indicator
0-2 hour timer
‘Reset’ pushbutton
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 15 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
When the ‘test’ (or key switch) pushbutton is operated the emergency and exit lighting circuit from
that DB simulates a power failure and the emergency and exit fittings operate via the battery pack
within the fittings. The test runs until the timer automatically resets the system onto mains power
and the normal mode.
Note: The timer should be set for 2 hours (120 minutes) for the first 12 months after building
commissioning and for 1 ½ hours (90 minutes) thereafter.
Should the test need to be interrupted, the ‘reset’ button can be pushed and the system will return
to normal mode of operation.
The following maintenance should be carried out:
Bi-Annually
a)
•
Visual inspection of all lights for any signs of deterioration, damage or failures and any
faults remedied.
•
Full 2 hour discharge test in the first 12 months and 1 ½ hours thereafter of the lights by
operating the emergency and exit lights test circuit in each DB and checking whether the
batteries operate the fitting for the full 2 hours (1 ½ hours after 12 months). Any fitting that
does not provide the 2 hours (or 1 ½ hours) operation should have the batteries replaced.
•
The Emergency Lighting Log Book (as required by AS2293) should be filled in after the full
2 hour (or 1 ½ hours) discharge test. This log book is normally kept in the main switch
room/building manager’s office/security room.
Annually
b)
•
Visual inspection of all lights for any signs of deterioration, damage or failures and any
faults remedied.
•
Full 2 hour discharge test in the first 12 months and 1 ½ hours thereafter of the lights by
operating the emergency and exit lights test circuit in each DB and checking whether the
batteries operate the fitting for the full 2 hours (1 ½ hours after 12 months). Any fitting that
does not provide the 2 hours (or 1 ½ hours) operation should have the batteries replaced.
•
The Emergency Lighting Log Book (as required by AS2293) should be filled in after the full
2 hour (or 1 ½ hours) discharge test. This log book is normally kept in the main switch
room/building manager’s office/security room.
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 16 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
•
A Fire Safety Statement of Compliance for the emergency lighting should be forwarded to
the local council as required by the local council.
Notes:
1. When a test arrangement is not provided, each lighting circuit which feeds emergency and
exit lighting must be tested by opening the circuit breaker feeding that lighting circuit.
2. Any emergency lighting circuit that only feeds emergency and exit lights is incorrect as
emergency/exit lights must be fed from the local general lighting circuit and from the line
side of any light switching. Any incorrect arrangement must be corrected.
5.6.6 GENERAL LIGHTING INSTALLATION
The following maintenance is to be carried out:
a) Annually
b)
•
Cleaning of all light fittings including reflectors and diffusers.
•
All components should be checked and any defective components replaced including
damaged diffusers and noisy ballasts.
•
Check all connections and cables.
Note
•
Special note is to be taken that tungsten halogen lamps must not be touched with bare
hands as the acid from the skin will deteriorate the quartz glass envelope of the lamp.
•
Other than replacement of lamps it is recommended that all other light fitting maintenance
be carried out by fully qualified, licensed electricians.
•
Polished lighting diffusers should not be touched with bare hands as finger prints are often
difficult to remove. Cotton gloves should be utilized when cleaning or handling polished
diffusers.
5.6.7 ACCESSORIES
The following maintenance is to be carried out.
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 17 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
a)
Visual inspection as follows:
• Check all accessories for damage or deterioration.
• Check that all GPOs and switches are correctly marked with the relevant circuit number.
• Replace/repair defective components and correct or add markings as necessary.
b)
Operational check of accessories as follows:
• Check that light switches operate crisply and that there is no undue arcing during operation
• Check that GPOs and socket outlets operate
• Check that pushbuttons operate
• Check that isolating switches operate
• Repair or replace any components that are defective.
In particular, light switches controlling fluorescent lighting circuits must be checked for operation.
Unless the action is normal and crisp, damage may have occurred due to switching transients.
Replace any suspect switches. The replacement switches for fluorescent light loads should be a
type that is designed to cope with fluorescent light transients. Clipsal switch mechanisms 30FLM,
30FLM15 and 30MD20 are suitable.
5.6.8 MAINS AND SUBMAINS
a) Mains
Mains to Gloria Jean’s Coffees are reticulated from the supply authority or the building main
switchboard to the Gloria Jean’s Coffees main switchboard.
All maintenance is to be carried out by fully qualified licensed electricians.
The following maintenance is to be carried out:
Determine whether any deterioration or damage has taken place by completing a visual inspection
of the entire length of the cables. Repair any damage or if not repairable arrange to replace the
damaged cable.
Check that all cable strapping is tight and that all cable ties have been cut short. Tighten or replace
any strapping that has become loose or untidy.
Check the connections at both ends of each cable core. Tighten any that have become loose.
Isolate the supply and carry out an insulation resistance test with a suitable megger. The reading
should not be less than 3 megohm. If less than 3 megohm investigate the cause and correct.
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 18 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
As a minimum standard, the above checks are recommended to be completed annually.
b) Sub-mains
Sub-mains are run from the main switchboard to distribution boards.
All maintenance is to be carried out by fully qualified licensed electricians.
The following maintenance is to be carried out:
Determine whether any deterioration or damage has taken place by completing a visual inspection
of the entire length of the cables. Repair any damage or if not repairable arrange to replace cable.
Check that all cable strapping is tight and that all cable ties have been cut short. Tighten or replace
any strapping that has become loose or untidy. Note: MIMS and fire rated cables strapping must be
with stainless steel ties other than within switchboards.
Check the connections at both ends of each cable core. Tighten any that have become loose.
As a minimum standard, the above checks are recommended to be completed annually.
c) Final Sub-circuits
Final sub-circuits are circuits that originate at a distribution board and terminate in a piece of
equipment, general purpose outlet or light circuits etc. The circuit schedule located inside the door
of the distribution board should accurately identify each sub-circuit.
The maintenance of final sub-circuits is similar to that described for mains and sub-mains. Correct
any circuit schedules where alterations have been made to the installation.
5.6.9
DUE DILLIGENCE
All maintenance work described in this manual is to be carried out under QMD501 duties during the
bi-annual and annual maintenance works including the QMD501 duties described for Gloria Jean’s
Coffees personnel.
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 19 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
SECTION 6 - REPORT SHEETS:
The following report sheets are required:
a)
b)
c)
d)
e)
f)
g)
h)
Testing and tagging of equipment
Mains switchboard
Distribution
Testing of RCD’s
Emergency and Exit lighting
General lighting
Accessories
Cabling
Pro-forma report sheets for the above are provided in this section. These are to be copied and
used for reports.
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 20 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
Item
REPORT SHEET A
TESTING AND TAGGING OF EQUIPMENT
Passed
Made Good
Tagged
Tested Date
Yes/No
Yes/NA
Yes/No
Comments
Note: NA = Not applicable – if item has passed testing
REPORT SHEET B
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 21 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
Item
MAIN SWITCHBOARD
Inspected Date
OK/Defect
Comments
Action Taken
Visual busbars
Visual supports
Visual insulators
Visual
panels/doors
Visual
connections
Visual labels
Visual neutral
Visual earth
Visual equipment
Check cable
connections for
tightness
Check busbar
connections for
tightness
Check earth
connections
Carry out thermal
scan with switch
board fully loaded
Megger test
Clean dust debris
Notes:
• Early deterioration of any equipment to be corrected
or component replaced
• Check for signs of overloading
• Check for signs of cracking
• Check for signs of deformation or damage of supports
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
•
•
•
•
Check for signs of condensation
Check for signs of corrosion
Check operation of all components
Check operation of controls
Page 22 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
Item
REPORT SHEET C
DISTRIBUTION BOARDS
Inspected Date
OK/Defect
Comments
Action Taken
Visual busbars
Visual supports
Visual insulators
Visual
panels/doors
Visual
connections
Visual labels
Visual neutral
Visual earth
Visual equipment
Check cable
connections for
tightness
Check busbar
connections for
tightness
Check earth
connections
Carry out thermal
scan with switch
board fully loaded
Hegger test
Clean dust debris
Notes:
• Early deterioration of any equipment to be corrected
or component replaced
• Check for signs of overloading
• Check for signs of cracking
• Check for signs of deformation or damage of supports
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
•
•
•
•
Check for signs of condensation
Check for signs of corrosion
Check operation of all components
Check operation of controls
Page 23 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
Circuit
Tested Date
REPORT SHEET D
TESTING RCD’S
Passed
Yes/No
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Made Good
Yes/No
Comments
Page 24 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
REPORT SHEET E
TESTING OF EMERGENCY AND EXIT LIGHTING
Testing is to be carried out and logged in a separate log book as required by AS2293.
Notes:
1. Test to be carried out for 2 hours for an installation less than 12 months old
2. Test to be carried out for 1.5 hours for an installation more than 12 months old.
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 25 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
REPORT SHEET F
GENERAL LIGHTING
Item
Internal
Inspected Date
Comments
External
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 26 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
REPORT SHEET G
ACCESSORIES
Item
Inspected Date
Condition
Circuit Labelled
Yes/No
Comments
Note: Covers light switches, GPO’s, power outlets
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 27 of 29
Commercial in Confidence
QMD501
ELECTRICAL MAINTENANCE
Equipment Planned Maintenance System
Qualified Maintenance Duties (QMD)
Item
REPORT SHEET K
CABBLING
Inspected Date
Comments
Consumer Mains
Submains
Subcircuit Cables
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 28 of 29
Commercial in Confidence
MD501 & QMD501
Electrical Maintenance
Equipment Planned Maintenance System
Maintenance Duties (MD)
NOTES:
©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved.
MD501 & QMD501
Version 1: March 2009
Page 29 of 29
Commercial in Confidence