MD501 & QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Maintenance Duties (MD) & Qualified Maintenance Duties (QMD) Electrical Maintenance Potential Hazards: Electricity Hot Surfaces ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 1 of 29 Commercial in Confidence MD501 & QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Maintenance Duties (MD) & Qualified Maintenance Duties (QMD) Contents SECTION 1 – INTRODUCTION .............................................................................4 1. 1 BACKGROUND.................................................................................................................... 4 1.2 MANAGERS OVERVIEW ...................................................................................................... 4 1.3 ELECTRIC SHOCK ............................................................................................................... 5 1.4 IN – STORE INSPECTION ................................................................................................... 5 1.5 REPAIR OF ELECTRCAL EQUIPMENT & PLANT............................................................... 6 1.6 PROTECTION ........................................................................................................................ 6 1.7 FREQUENCY OF ELECTRICAL PLANNED MAINTENANCE INSPECTION ........................ 7 SECTION 2 - POTENTIAL HAZARDS .........................................................8 2.1 HOT SURFACE ..................................................................................................................... 8 2.2 ELECTRIC SHOCK ............................................................................................................... 8 SECTION 3 – CONTRACTOR MANAGEMENT....................................................8 3.1 GENERAL REQUIREMENTS................................................................................................ 8 SECTION 4 - GOVERNING BODIES.....................................................................9 4.1 CONFORMING AUTHORITIES & AUSTRALIAN STANDARDS .......................................... 9 ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 2 of 29 Commercial in Confidence MD501 & QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Maintenance Duties (MD) & Qualified Maintenance Duties (QMD) Qualified Technician Only Tasks (QMD501) SECTION 5 – ELECTRICAL MAINTENANCE INSPECTION AND TESTS: ..... 10 5.1 ELECTRICAL TAGS ...........................................................................................................10 5.2 REMEDIAL WORKS & ACTION ..........................................................................................10 5.3 TESTING EQUIPMENT .........................................................................................................11 5.4 FREQUENCY OF MANDATORY ELECTRICAL PLANNED MAINTENANCE INSPECTION ...............................................................................................................................11 5.5 FREQUENCY OF BEST PRACTISE ELECTRICAL PLANNED MAINTENANCE INSPECTION ...............................................................................................................................12 5.6 SPECIFIC MAINTAINENCE REQUIREMENTS...................................................................12 5.6.1 TESTING AND TAGGING OF EQUIPMENT ..................................................................12 5.6.2 MAIN SWITCHBOARD...................................................................................................12 5.6.3 DISTRIBUTION BOARDS (DB) [IF APPLICABLE] .........................................................14 5.6.4 TESTING OF RCD’S ......................................................................................................15 5.6.5 EMERGENCY AND EXIT LIGHTS .................................................................................15 5.6.6 GENERAL LIGHTING INSTALLATION ..........................................................................17 5.6.7 ACCESSORIES..............................................................................................................17 5.6.8 MAINS AND SUBMAINS ................................................................................................18 5.6.9 DUE DILLIGENCE .........................................................................................................19 REPORT SHEET A .....................................................................................................................21 REPORT SHEET B .....................................................................................................................21 REPORT SHEET C .....................................................................................................................23 REPORT SHEET D .....................................................................................................................24 REPORT SHEET E......................................................................................................................25 REPORT SHEET F......................................................................................................................26 REPORT SHEET G .....................................................................................................................27 REPORT SHEET K .....................................................................................................................28 NOTES: ............................................................................................................... 29 ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 3 of 29 Commercial in Confidence MD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Maintenance Duties (MD) SECTION 1 – INTRODUCTION 1. 1 BACKGROUND Without proper maintenance, the safety and integrity of equipment/plant can not be ensured even if the equipment/plant has been designed and manufactured with due consideration to health and safety. The Occupational Health and Safety Act (the Act) and Occupational Health and Safety (Plant) Regulations 1995 place an obligation on employers to ensure equipment/plant is maintained. The Act also requires employers to provide and maintain, so far as is practicable, a working environment that is safe and without risks to health for employees who undertake inspection and maintenance work. 1.2 MANAGERS OVERVIEW Electrical Safety is of the utmost importance in our stores. This manual describes electrical maintenance duties in formats i.e. Maintenance Duties (MD501) which can be carried out by Gloria Jean’s Coffees personnel and qualified technicians, and Qualified Technician Maintenance Duties (QMD501) which can only be carried out by a qualified technician. The document outlines the in-service electrical tasks considered necessary for both the store (MD 501) & tasks for the licensed electrical contractor (QMD 501) as minimum planned maintenance to ensure the safety of person(s) using electrical equipment. Electrical equipment is required to be inspected tested & tagged to Australian Electrical Standard (AS3760) by a qualified & certified personnel on an Annual & Bi Annual basis to detect unsafe conditions. This is to ensure we take reasonably practicable steps to ensure that no danger results from the use of such equipment. This in effect, requires the implementation of a systematic and regular program of maintenance, inspection and testing. It is the Franchise Partner or Store Manager’s responsibility to co-ordinate the Electrical Contractor to schedule this work. All of the required inspections & checks that are outlined in this manual shall not remove the responsibility from the personnel carrying out the works to undertake procedures in accordance with requirements within the relevant state specific Occupational Health and Safety Legislation, and Australian Standards for in-service safety inspection and testing of electrical equipment / appliances / plant. The Electrical Planned Maintenance Qualified Technician Tasks (QMD501) includes various inspections that need to be completed by a Licensed Electrical Contractor. A licensed electrical contractor will ensure correct diagnostic of faults & legal remedial works in store. Your electrical contractor should already be familiar with and practising these tests & procedures that need to be applied to our stores for the provision of a ‘safe place’. The electrical contractor should have a current copy of the relevant Standards. The in store inspection procedures are mandatory. ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 4 of 29 Commercial in Confidence MD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Maintenance Duties (MD) On completion of the checks, the original signed copy of the report sheet/book must be given to the store manager and filed in section 5 of the OH&S manual within the store premises. The report sheet will outline inventory of all electrical equipment tested by description a list of failed items, new repaired items log and next due date. The manager is required to record completed tasks on completion and in accordance with the Gloria Jean’s Coffees Daily Book - Equipment Planned Maintenance Yearly Schedule. This manual must be stored in the Equipment Planned Maintenance Binder which forms part of the Operations Standards Manual within the store & shared with your approved electrical contractor for their review. 1.3 ELECTRIC SHOCK Electric shocks caused by electrical equipment occur without warning and are often serious. The severity of the electric shock can range from a tingling sensation to electrocution and death, the factors which affect the severity of electric shock are the :(a) value of shock current (b) time for which it flows (c) the path through the body 1.4 IN – STORE INSPECTION As a manager you are required to inspect electrical cords regularly, the things to look for when carrying out a visual check are as follows:(a) frayed or split outer casing (b) badly worn, perished or kinked insulation (c) ensure that any lead is mechanically secured at termination (d) chipped, cracked, discoloured or broken fittings Additionally, you are required to visually inspect and detect any adverse condition to any electrical apparatus observed to be unsafe and or faulty, such as exposed electrical components & wiring. Examples of electrical apparatus to which this applies but not limited to are:- power outlets, lighting & fittings, switches, equipment, plant, switchboards, computers, monitors, air conditioner, vacuum cleaner, power tools, electric water urns / heaters, insect traps, coffee bean grinders, ice machine, coffee, espresso machines, toasters, grillers, microwave, hand dryers, dishwasher, refrigerated & ambient pastry display cabinets, garbage compactor, refrigerated & freezer cabinets, beverage mixers, bean bar scale, brewer, music hard drives & system, register, refrigerated beverage whipper dispenser. Do not operate equipment if it has a damaged cord or plug; if it is not working properly, or if it has been damaged or dropped. Faulty electrical equipment / plant can also lead to fires, which may also cause death or injury to others. Report any such defect. ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 5 of 29 Commercial in Confidence MD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Maintenance Duties (MD) It is best practice to have your Licensed Electrical Contractor visually check all lighting equipment, luminaires diffusers for correct position and integrity. Replace all damaged diffusers and defective lamps. Other electrical lighting components which may require replacing will be done by the licensed Electrical Contractor or qualified technician. No person should attempt to repair any electrical equipment unless qualified to do so. 1.5 REPAIR OF ELECTRCAL EQUIPMENT & PLANT If the equipment is found faulty it must be immediately disconnected from the energy source by unplugging the power supply lead by the plug body only, isolate & withdraw from service. Equipment is required to be labeled by the person carrying out the inspection to warn against further use until repaired by authorised service agent or service personnel. In the event the equipment is deemed permanently inoperable then dispose of or destroy. At no time should you re-activate tripped Residual Circuit Breaker Device (RCD) or Earth Leakage Circuit Breaker (ELCBs). Immediately place service call to qualified electrical service personnel or authorised equipment service agent. Failure to do so may result in electric shock and/or further damage to electrical components that may fail to continue to operate effectively as per design or fail to provide protection against electric shock. Equipment should be serviced by qualified personnel only. Contact the Supplier for adjustment or repair. 1.6 PROTECTION A Residual Current Device (RCD) is a device intended to isolate the circuits connected to it in the event of a predetermined current flow to earth. RCDs are also known by other names Earth Leakage Circuit Breaker (ELCB). All power outlets, portable equipment and kitchen equipment must be protected by an Earth Leakage Circuit Breaker (ELCB) or Residual Current Device (RCD). Display RCD sign whenever RCD is fitted in the vicinity of the distribution board / switchboard as required by local council regulations. It is necessary for the Electrical Contractor or authorised service personnel to verify an RCD has operated due to an earth fault when responding to a service call. It is necessary for the authorised service personnel to be satisfied that an earth fault does not exist and the equipment has been serviced. Additionally, the RCD is required to be tested with the correct equipment confirming that it still operates as designed. ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 6 of 29 Commercial in Confidence MD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Maintenance Duties (MD) An RCD installed at a workplace must be kept in good working condition and be tested on a regular basis by a competent person to ensure its continued effective operation. A record should be kept of these tests. A “competent person” is someone who is an individual who, by way of training and/or experience, is knowledgeable of applicable equipment, is capable of identifying workplace hazards relating to the specific operation, is designated by the employer, and has authority to take appropriate actions. RCDs will not protect against all electrical incidents; for example RCDs will not protect against the serious shock situation where a person contacts both active and neutral conductors without current flowing to earth. RCDs are an addition to safety measures not a substitute for them. 1.7 FREQUENCY OF ELECTRICAL CONDUCTED BY STORE PLANNED MAINTENANCE INSPECTION Monthly • Check the operation of each exit and emergency light by depressing the “test” pushbutton on each fitting and checking whether the light changes to battery supply. • Any incorrect operation must be reported to the Store Manager and any faults remedied. • A monthly inspection of all lights to determine whether any lamps or fluorescent starters have failed. Replace all readily accessible failed lamps or starters provided that they are not damaged. Note: Any lamp failures noticed at other times should be rectified as they occur. • Special note is to be taken that tungsten halogen lamps must not be touched with bare hands as the acid from the skin will deteriorate the quartz glass envelope of the lamp. • Other than replacement of lamps and readily accessible starters it is recommended that all other light fitting maintenance be carried out by fully qualified licensed electricians. Note: Polished lighting diffusers should not be touched with bare hands as finger prints are often difficult to remove. Cotton gloves should be utilized when cleaning or handling polished diffusers. ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 7 of 29 Commercial in Confidence MD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Maintenance Duties (MD) SECTION 2 - POTENTIAL HAZARDS 2.1 HOT SURFACE Hot Surfaces Hot surfaces may be exposed during these checks by press toasters, grillers, coffee machines and the like equipment in store. Hot surfaces may cause burns. 2.2 ELECTRIC SHOCK Electricity Potential hazards and cautions may be exposed during these procedures. Follow safe working practices and procedures to control the hazards. If the power point is not readily accessible turn the equipment off at the isolation switch or the circuit breaker in the switchboard. Prior to moving any equipment in service for cleaning, moving, repairing and testing all power must be switched off. Note: Double adaptors & Piggy back plugs must not be used in our work place SECTION 3 – CONTRACTOR MANAGEMENT 3.1 GENERAL REQUIREMENTS The licensed electrical contractor, its employees and sub-contractors must be suitably qualified and licensed for the tasks being performed. They must have public liability insurance up to the value of $20 million. This is essential as Gloria Jean’s Coffees own insurance or individual store Franchise Partners may be exposed in the event of inadequate cover. In all States and Territories a current Workers Compensation Policy must be place which covers all contractors’ employees. Evidence of Hazard Assessment prior to commencement of any task performed. It is the stores responsibility and due diligence to check and confirm qualifications, licence, safe work method statement and insurance details of all in-store approved contractors. Complete Preferred Contractor Register filed in section 5 of the OH&S Guidelines & Workbook. File copies of all documents and complete Contractor Service Agreement in Section 2 of the OH&S Guidelines and work book ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 8 of 29 Commercial in Confidence MD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Maintenance Duties (MD) SECTION 4 - GOVERNING BODIES 4.1 CONFORMING AUTHORITIES & AUSTRALIAN STANDARDS The Electrical Contractor shall carry out all work in accordance with relevant state specific Occupational Health and Safety Legislation, and Australian Standards for in-service safety inspection and testing of electrical equipment/appliances/plant, wiring regulations and any other Authority having jurisdiction over this work. This shall include but not is limited to: State / Territory Occupational Health & Safety Authority and relevant legislation • • • • • • • • NSW WorkCover Authority QLD WorkCover Authority VIC WorkCover Authority WA WorkCover West Australian NT Worksafe TAS Workplace Standards Tasmania ACT WorkCover Authority SA WorkCover Corporation • The Building Code of Australia (BCA) • Australian Electrical Standards as applicable AS3760 – In Service Safety Inspection and Testing of Electrical Equipment AS3017 – Electrical Installations – Testing and Inspection Guidelines AS3000 – SAA Wiring Rules AS2293 – Emergency evacuation lighting for buildings ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 9 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) SECTION 5 – ELECTRICAL MAINTENANCE INSPECTION AND TESTS: All Tasks Must Be Performed by Qualified Technician Only Warning Electrical Shock Hazard Potential hazards and cautions may be exposed during these procedures. Follow safe working practices and procedures to control the hazards. 5.1 ELECTRICAL TAGS On completion of each safe test / inspection, durable, non-metallic, non-reusable tags robust enough for our environment are required to be attached to each individual piece of equipment to verify that the equipment has been checked, tested & passed. The integrity of the tag is required to be maintained given our aggressive environment. Tags must contain all necessary information including due date of the next inspection. This will be noted on the tag as well as electrical contactors details. Where the equipment test as safe, a tag needs to be attached to the power lead within 300mm of the plug end by way of black nylon cable tie or fastening system fit for purpose once the equipment has passed its inspection prior being placed back in service. 5.2 REMEDIAL WORKS & ACTION All remedial works should be completed in accordance with AS3760 & AS3000 Locking out of equipment is the most effective way of preventing it from becoming operational during maintenance or failure. If any work is to be carried out on a particular piece of equipment and there is a possibility of somebody inadvertently turning it on, the qualified person carrying out the work must personally fasten a red and black "DANGER" tag or lock to the main isolating switch. In the event that the electrical contractor shall remove from operation any equipment found to be faulty and tag “Caution – Do not operate” on the equipment or attached to the relevant circuit breaker if the equipment is permanently fixed wired As a result of the electrical inspection or checks, the electrical contractor is required to record on the report sheets any remedial work, defects and action taken. Defects require immediate action before equipment can be placed back into service. This needs to be reported to the Store Manager who will log the defect & arrange for the immediate action. ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 10 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) All Tasks Must Be Performed by Qualified Technician Only Warning Electrical Shock Hazard Potential hazards and cautions may be exposed during these procedures. Follow safe working practices and procedures to control the hazards. After completing works that have impacted the electrical safety of the equipment / appliance / plant, an electrical inspection must be carried out and recorded before the equipment is returned or placed back into service. There could be a need for the licensed electrical contractor to work on small equipment replacing leads and the like, in doing so, they need to maintain minimum standards with the use of the manufactures recommended parts. 5.3 TESTING EQUIPMENT The electrical testing device is required to comply with the relevant standard. The use of appropriate Earth Leakage test equipment is required for testing RCD’s. Testing equipment to be periodically tested & calibrated as per the relevant standard 5.4 FREQUENCY OF MANDATORY ELECTRICAL PLANNED MAINTENANCE INSPECTION The following scheduled checks by Licensed Electrical Contractor: • 12 Monthly inspection on Stationary and Portable Equipment / Appliances & associated flexible leads as per AS3760 • 12 & 6 Monthly 90 minute discharge test of the Emergency Lumininaires and Exist lighting system as per AS2293 • 12 Monthly Push button tests for RCD’s including operating times whilst contractor is waiting for 90 minute emergency lighting discharge test during the above procedure AS3760 - Table 2 ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 11 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) All Tasks Must Performed by Qualified Technician Only Warning Electrical Shock Hazard Potential hazards and cautions may be exposed during these procedures. Follow safe working practices and procedures to control the hazards. 5.5 FREQUENCY OF BEST PRACTICE ELECTRICAL PLANNED MAINTENANCE INSPECTION • 12 Monthly inspection on Main Switchboards, Distribution Switchboards, Control and Isolation Panels (RCD’s). • 12 Monthly Lighting Equipment visual checks of all lighting equipment, electrical components and luminaires diffusers. Record condition of all lighting including defective lamps, damaged fittings & diffusers. AS3760. Follow same procedures for remedial activities to be carried out following the inspections as per point 5.2 - Remedial Works & Action 5.6 SPECIFIC MAINTAINENCE REQUIREMENTS 5.6.1 TESTING AND TAGGING OF EQUIPMENT • as described in clause 5.4 5.6.2 MAIN SWITCHBOARD The supply to the site will need to be shut down for any works on the line side busbars and equipment. There should also be two people present if the switchboard is to be opened and live parts exposed. The following maintenance is to be carried out: i) Visual inspection of all components of the main switchboard to detect signs of deterioration or damage. This inspection shall include, but is not limited to: • All equipment in the switchboard • Busbars • Supports ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 12 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) • • • • • • • • Insulating material Panels and doors including seals Cable and busbar connections Markings and labeling Contact surfaces Switch and circuit breaker mechanisms Earthing Cable glands Any deterioration must be rectified or the component replaced. Particular notice must be taken to: • Signs of overheating • Signs of cracking or insulating materials • Signs of deformation of supports or any damage to these • Signs of corrosion or electrolysis • Signs of condensation • Any other deterioration, damage or missing components • Proper operation of components • Proper lubrication of components where required ii) Check the tightness of all connections. This includes: • Cable connections • Busbar connections • Earth connection • Structural components and supports • Bushings iii) Operation of all components. In particular each switch and circuit breaker shall be operated three times. iv) Megger test the switchboard between phases and between each phase to earth. Any low resistance reading shall be checked and the cause determined and rectified. v) The switchboard is to be fully cleaned out of all dust and debris. vi) All cable installations must be checked and any untidy work corrected. Also any redundant or temporary cabling is to be removed. ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 13 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) vii) Thermal Scan of Main Switchboard(s) and associated report. This test is to be done when the switchboard is fully loaded for at least 2 hours with all air conditioning running. Note: This test is required only when the switchboard is heavily loaded near its capacity or shows signs of heating problems. viii) The recommended period for the above check - minimum annually. ix) All maintenance is to be carried out by fully qualified licensed electricians. x) If a fault has occurred on the switchboard or a circuit has tripped the cause of the fault must be determined and rectified prior to re-commissioning the switchboard or re-closing the circuit. Thorough maintenance of the switchboard will be required and the tripped component fully checked prior to its re-commissioning. If there is any doubt as to the condition of any component after any fault, the component is to be replaced. xi) Whenever annual maintenance is carried out, spot load checks should be done on all major circuits with a tong tester and the results recorded. Any circuits that are approaching 80% of the rated load should be reported to the building manager. Any circuits exceeding 80% of the rated load must be carefully checked to ensure overheating of any components does not occur. 5.6.3 DISTRIBUTION BOARDS (DB) [IF APPLICABLE] Maintenance Maintenance is generally similar to the maintenance described for the main switchboard, but does not require the shut down of the site power supply. However the supply to each distribution board should be isolated while maintenance is being carried out. A thermal scan is only required if: i) ii) iii) iv) There is any doubt about the condition of a DB The DB has been subject to a fault and put back into service The DB is rated at least 100amps and is more than 5 years old The DB is fully utilised Distribution Boards generally incorporate moulded case circuit breakers and residual current circuit breakers (earth leakage circuit breakers) for circuit protection. Some DB’s also incorporate contactors, relays and time switches for the control lighting. ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 14 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) In addition to the general maintenance of distribution boards (DB’s), the operation of residual current circuit breakers should be tested by pressing the test button on each circuit breaker and resetting the breaker by placing the circuit breaker switch in the ‘ON’ position. Note: it may be necessary to first place the circuit breaker in the ‘OFF’ position, before switching to ‘ON’. In addition to the above, check that a circuit schedule is attached to the inside of the door of the DB, that it is accurate and typed in a neat and tidy manner. Amend and/or replace as necessary. 5.6.4 TESTING OF RCD’S • As described in clauses 5.4 & 5.6.3 5.6.5 EMERGENCY AND EXIT LIGHTS Emergency and exit lights are of the single point type where each light has its own integral battery pack and charger unit. The battery charger for each light is fed from an un-switched active (other than the switching provided by the emergency and exit lighting test facilities) originating at the lighting circuit feeding the same general area of the emergency or exit light. In this way the batteries are being charged at each fitting at all times. The initial capacity of the battery for any newly provided emergency or exit light is 2 hours for the first 12 months and 1 ½ hours thereafter i.e. the battery will initially operate the light for 2 hours if a power failure occurs. After 12 months the battery capacity is expected to reduce to 1 ½ hours. This is the minimum acceptable period after 12 months. After a total discharge it takes approximately 16 hours for the batteries to fully recharge. The life of each battery is in excess of 2 years. Each emergency and exit light has a ‘test’ pushbutton and a light emitting diode (LED). The LED illuminates when the light is on normal power and the battery is charging. An emergency and exit lighting test circuit has been provided with every distribution board providing power to emergency and exit lights. The circuit has the following features: • • • ‘Test’ pushbutton (or key switch) and ‘Test’ indicator 0-2 hour timer ‘Reset’ pushbutton ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 15 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) When the ‘test’ (or key switch) pushbutton is operated the emergency and exit lighting circuit from that DB simulates a power failure and the emergency and exit fittings operate via the battery pack within the fittings. The test runs until the timer automatically resets the system onto mains power and the normal mode. Note: The timer should be set for 2 hours (120 minutes) for the first 12 months after building commissioning and for 1 ½ hours (90 minutes) thereafter. Should the test need to be interrupted, the ‘reset’ button can be pushed and the system will return to normal mode of operation. The following maintenance should be carried out: Bi-Annually a) • Visual inspection of all lights for any signs of deterioration, damage or failures and any faults remedied. • Full 2 hour discharge test in the first 12 months and 1 ½ hours thereafter of the lights by operating the emergency and exit lights test circuit in each DB and checking whether the batteries operate the fitting for the full 2 hours (1 ½ hours after 12 months). Any fitting that does not provide the 2 hours (or 1 ½ hours) operation should have the batteries replaced. • The Emergency Lighting Log Book (as required by AS2293) should be filled in after the full 2 hour (or 1 ½ hours) discharge test. This log book is normally kept in the main switch room/building manager’s office/security room. Annually b) • Visual inspection of all lights for any signs of deterioration, damage or failures and any faults remedied. • Full 2 hour discharge test in the first 12 months and 1 ½ hours thereafter of the lights by operating the emergency and exit lights test circuit in each DB and checking whether the batteries operate the fitting for the full 2 hours (1 ½ hours after 12 months). Any fitting that does not provide the 2 hours (or 1 ½ hours) operation should have the batteries replaced. • The Emergency Lighting Log Book (as required by AS2293) should be filled in after the full 2 hour (or 1 ½ hours) discharge test. This log book is normally kept in the main switch room/building manager’s office/security room. ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 16 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) • A Fire Safety Statement of Compliance for the emergency lighting should be forwarded to the local council as required by the local council. Notes: 1. When a test arrangement is not provided, each lighting circuit which feeds emergency and exit lighting must be tested by opening the circuit breaker feeding that lighting circuit. 2. Any emergency lighting circuit that only feeds emergency and exit lights is incorrect as emergency/exit lights must be fed from the local general lighting circuit and from the line side of any light switching. Any incorrect arrangement must be corrected. 5.6.6 GENERAL LIGHTING INSTALLATION The following maintenance is to be carried out: a) Annually b) • Cleaning of all light fittings including reflectors and diffusers. • All components should be checked and any defective components replaced including damaged diffusers and noisy ballasts. • Check all connections and cables. Note • Special note is to be taken that tungsten halogen lamps must not be touched with bare hands as the acid from the skin will deteriorate the quartz glass envelope of the lamp. • Other than replacement of lamps it is recommended that all other light fitting maintenance be carried out by fully qualified, licensed electricians. • Polished lighting diffusers should not be touched with bare hands as finger prints are often difficult to remove. Cotton gloves should be utilized when cleaning or handling polished diffusers. 5.6.7 ACCESSORIES The following maintenance is to be carried out. ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 17 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) a) Visual inspection as follows: • Check all accessories for damage or deterioration. • Check that all GPOs and switches are correctly marked with the relevant circuit number. • Replace/repair defective components and correct or add markings as necessary. b) Operational check of accessories as follows: • Check that light switches operate crisply and that there is no undue arcing during operation • Check that GPOs and socket outlets operate • Check that pushbuttons operate • Check that isolating switches operate • Repair or replace any components that are defective. In particular, light switches controlling fluorescent lighting circuits must be checked for operation. Unless the action is normal and crisp, damage may have occurred due to switching transients. Replace any suspect switches. The replacement switches for fluorescent light loads should be a type that is designed to cope with fluorescent light transients. Clipsal switch mechanisms 30FLM, 30FLM15 and 30MD20 are suitable. 5.6.8 MAINS AND SUBMAINS a) Mains Mains to Gloria Jean’s Coffees are reticulated from the supply authority or the building main switchboard to the Gloria Jean’s Coffees main switchboard. All maintenance is to be carried out by fully qualified licensed electricians. The following maintenance is to be carried out: Determine whether any deterioration or damage has taken place by completing a visual inspection of the entire length of the cables. Repair any damage or if not repairable arrange to replace the damaged cable. Check that all cable strapping is tight and that all cable ties have been cut short. Tighten or replace any strapping that has become loose or untidy. Check the connections at both ends of each cable core. Tighten any that have become loose. Isolate the supply and carry out an insulation resistance test with a suitable megger. The reading should not be less than 3 megohm. If less than 3 megohm investigate the cause and correct. ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 18 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) As a minimum standard, the above checks are recommended to be completed annually. b) Sub-mains Sub-mains are run from the main switchboard to distribution boards. All maintenance is to be carried out by fully qualified licensed electricians. The following maintenance is to be carried out: Determine whether any deterioration or damage has taken place by completing a visual inspection of the entire length of the cables. Repair any damage or if not repairable arrange to replace cable. Check that all cable strapping is tight and that all cable ties have been cut short. Tighten or replace any strapping that has become loose or untidy. Note: MIMS and fire rated cables strapping must be with stainless steel ties other than within switchboards. Check the connections at both ends of each cable core. Tighten any that have become loose. As a minimum standard, the above checks are recommended to be completed annually. c) Final Sub-circuits Final sub-circuits are circuits that originate at a distribution board and terminate in a piece of equipment, general purpose outlet or light circuits etc. The circuit schedule located inside the door of the distribution board should accurately identify each sub-circuit. The maintenance of final sub-circuits is similar to that described for mains and sub-mains. Correct any circuit schedules where alterations have been made to the installation. 5.6.9 DUE DILLIGENCE All maintenance work described in this manual is to be carried out under QMD501 duties during the bi-annual and annual maintenance works including the QMD501 duties described for Gloria Jean’s Coffees personnel. ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 19 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) SECTION 6 - REPORT SHEETS: The following report sheets are required: a) b) c) d) e) f) g) h) Testing and tagging of equipment Mains switchboard Distribution Testing of RCD’s Emergency and Exit lighting General lighting Accessories Cabling Pro-forma report sheets for the above are provided in this section. These are to be copied and used for reports. ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 20 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) Item REPORT SHEET A TESTING AND TAGGING OF EQUIPMENT Passed Made Good Tagged Tested Date Yes/No Yes/NA Yes/No Comments Note: NA = Not applicable – if item has passed testing REPORT SHEET B ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 21 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) Item MAIN SWITCHBOARD Inspected Date OK/Defect Comments Action Taken Visual busbars Visual supports Visual insulators Visual panels/doors Visual connections Visual labels Visual neutral Visual earth Visual equipment Check cable connections for tightness Check busbar connections for tightness Check earth connections Carry out thermal scan with switch board fully loaded Megger test Clean dust debris Notes: • Early deterioration of any equipment to be corrected or component replaced • Check for signs of overloading • Check for signs of cracking • Check for signs of deformation or damage of supports ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 • • • • Check for signs of condensation Check for signs of corrosion Check operation of all components Check operation of controls Page 22 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) Item REPORT SHEET C DISTRIBUTION BOARDS Inspected Date OK/Defect Comments Action Taken Visual busbars Visual supports Visual insulators Visual panels/doors Visual connections Visual labels Visual neutral Visual earth Visual equipment Check cable connections for tightness Check busbar connections for tightness Check earth connections Carry out thermal scan with switch board fully loaded Hegger test Clean dust debris Notes: • Early deterioration of any equipment to be corrected or component replaced • Check for signs of overloading • Check for signs of cracking • Check for signs of deformation or damage of supports ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 • • • • Check for signs of condensation Check for signs of corrosion Check operation of all components Check operation of controls Page 23 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) Circuit Tested Date REPORT SHEET D TESTING RCD’S Passed Yes/No ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Made Good Yes/No Comments Page 24 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) REPORT SHEET E TESTING OF EMERGENCY AND EXIT LIGHTING Testing is to be carried out and logged in a separate log book as required by AS2293. Notes: 1. Test to be carried out for 2 hours for an installation less than 12 months old 2. Test to be carried out for 1.5 hours for an installation more than 12 months old. ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 25 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) REPORT SHEET F GENERAL LIGHTING Item Internal Inspected Date Comments External ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 26 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) REPORT SHEET G ACCESSORIES Item Inspected Date Condition Circuit Labelled Yes/No Comments Note: Covers light switches, GPO’s, power outlets ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 27 of 29 Commercial in Confidence QMD501 ELECTRICAL MAINTENANCE Equipment Planned Maintenance System Qualified Maintenance Duties (QMD) Item REPORT SHEET K CABBLING Inspected Date Comments Consumer Mains Submains Subcircuit Cables ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 28 of 29 Commercial in Confidence MD501 & QMD501 Electrical Maintenance Equipment Planned Maintenance System Maintenance Duties (MD) NOTES: ©Copyright 2008/2009 Jireh International Pty Ltd. All rights reserved. MD501 & QMD501 Version 1: March 2009 Page 29 of 29 Commercial in Confidence