Classification of Excitation System | Power Plants Home Upload & Share Privacy Policy Contact Us Classification of Excitation System | Power Plants Article shared by : ADVERTISEMENTS: The excitation systems can be broadly classified as: 1. DC Excitation System 2. AC Excitation System 3. Static Excitation System. 1. DC Excitation System: In dc excitation system, the system has two exciters—the main exciter (a separately excited dc generator providing the field current to the alternator) and a pilot exciter (a compound wound self-excited dc generator providing the field current to the main exciter). The exciter output is regulated by an automatic voltage regulator (AVR) for controlling the output terminal voltage of the alternator. The current transformer input to the AVR ensures limiting of alternator current during fault. With the opening of field breaker, the field discharge resistor is connected across the field winding so as to dissipate the stored energy in the field winding which is highly inductive. The main and pilot exciters can be either driven by the main shaft (directly or through gearing) or separately driven by a motor. ADVERTISEMENTS: Direct driven exciters are usually preferred as these preserve the unit system of operation and the excitation is not affected by external disturbances. Exciters for small sized turbo-alternators are usually directly coupled to the shaft whereas for medium and large size turbo-alternators, the exciters are coupled to the main shaft through gear and are usually driven at 1,000 rpm. The voltage rating of the main exciter is about 400 V and its capacity is about 0.5% of the capacity of the alternator. Troubles in the exciters of turbo-alternators are quite frequent because of their high speeds and as such separate motor driven exciters are provided as standby exciters. In some cases the dc excitation system is equipped with amplidyne controller. The amplidyne is a high response cross-field dc generator, which has a very high amplification factor and requires very small control power. It is supplied from an automatic voltage regulator (AVR). The main shortcomings of dc excitation system are large time constant (around 3 seconds) and commutation difficulties. As such the dc excitation systems have been superseded by ac excitation systems and static systems. http://www.engineeringenotes.com/power-plants-2/equipment/classification-of-excitation-system-power-plants/29729[01-Dec-19 9:46:43 PM] Classification of Excitation System | Power Plants 2. AC Excitation System: This system consists of an alternator and thyristor rectifier bridge directly connected to the main alternator shaft. The main exciter may either be self-excited or separately excited. A rotating thyristor excitation system employs self-excited main exciter whereas the brushless excitation system employs a separately excited main exciter. ADVERTISEMENTS: i. Rotating Thyristor Excitation System: Block diagram of a rotating thyristor excitation system is depicted in Fig. 17.2, the rotating portion being shown enclosed by dashed line rectangle. This system comprises of an ac exciter having a stationary field and a rotating armature. The exciter output, rectified by a full-wave thyristor bridge rectifier circuit, is supplied to the main alternator field winding. The alternator field winding is also supplied from the exciter output through another rectifier circuit. Exciter voltage can be built up using its residual flux. For convenience and to shorten the buildup time, stationary battery supply is also incorporated. http://www.engineeringenotes.com/power-plants-2/equipment/classification-of-excitation-system-power-plants/29729[01-Dec-19 9:46:43 PM] Classification of Excitation System | Power Plants The power supply and rectifier control, incorporated as a part of rotating portion, generates the required phase controlled triggering signals in response to a dc control level fed by the voltage regulator. ADVERTISEMENTS: An automatic voltage regulator (AVR) is also incorporated in the system. The alternator voltage signal (from the PT) is averaged and compared directly with the operator’s voltage adjustment (voltage reference) in the auto mode of operation. In the manual mode of operation the excitation current of the alternator is compared with a separate manual voltage adjustment (reference) and supplied to the rotating thyristor bridge through separate regulating elements. For maintaining the terminal voltage of the exciter at the desired level, the exciter voltage is averaged, compared with the exciter voltage reference and applied to the rectifier control and rectifier in a suitable manner. The system also incorporates additional features like overvoltage protection, overcurrent protection in the exciter field control, lead-lag compensation for stabilization of voltage control, watt and VAR signals for regulating the voltage and field discharge resistor, which are not shown in the block diagram. ADVERTISEMENTS: ii. Brushless Excitation System: With the increase in rating of alternators, the problem of brush maintenance gets more and more complicated, so the brushless excitation systems are becoming more and more popular. The advent of silicon diodes and http://www.engineeringenotes.com/power-plants-2/equipment/classification-of-excitation-system-power-plants/29729[01-Dec-19 9:46:43 PM] Classification of Excitation System | Power Plants thyristors made it possible to have compact rectified system converting ac to dc at higher power levels. This system is depicted in Fig. 17.3, the rotating portion being shown enclosed by a dashed line rectangle. The excitation system comprises of an alternator rectifier main exciter and a permanent magnet generator (PMG) pilot exciter. Both of the main and pilot exciter is driven directly from the main shaft. The main exciter has a stationary field and a rotating armature directly connected, through silicon rectifiers, to the field of the main alternator. The pilot exciter is a shaft driven permanent magnet generator having rotating permanent magnets attached to the shaft and a 3-phase stationary armature, which feeds the main exciter’s field through 3-phase full-wave phase controlled thyristor bridges. ADVERTISEMENTS: This system eliminates the use of commutator, collectors and brushes and has a short time constant and a response time of less than 0.1 second. The short time constant has the advantage in improved small signal dynamic performance and facilitates the application of supplementary power system stabilizing signals. 3. Static Excitation System: Figure 17.4 depicts the static excitation system using SCRs. http://www.engineeringenotes.com/power-plants-2/equipment/classification-of-excitation-system-power-plants/29729[01-Dec-19 9:46:43 PM] Classification of Excitation System | Power Plants In static excitation system, the excitation supply is taken from the alternator itself through a 3-phase star/delta connected, oil immersed, forced air cooled, indoor type step- down transformer and a rectifier system employing mercury- arc rectifiers or silicon controlled rectifiers. The star- connected primary is connected to the alternator bus, the delta-connected secondary supplies power to the rectifier system and the delta-connected tertiary feeds power to grid control circuits and other auxiliary equipment. The rectifiers are connected in parallel to give sufficient current carrying capacity. Each leg of rectifier is protected with series fuse, surge protection and fault indicating light. The rectifiers are forced air cooled. This system has a very small response time (about 20 milliseconds) and provides excellent dynamic performance. SCRs are ideally suited for a static excitation system because they have high speed of response, high power gain and can be easily paralleled. The advantages of the static excitation system are elimination of exciter windage loss and commutator wearing and winding maintenance resulting in reduced operating costs and electronic speed response. The fact that in static excitation the voltage is proportional to the speed, affords a major advantage in load rejection. http://www.engineeringenotes.com/power-plants-2/equipment/classification-of-excitation-system-power-plants/29729[01-Dec-19 9:46:43 PM] Classification of Excitation System | Power Plants Home ›› Electrical Engineering ›› Power Plants ›› Equipments ›› Excitation System Related Articles: 1. 2. 3. 4. Types of Static Voltage Regulators | Power Plants Types of Electromechanical Voltage Regulators | Power Plants Electrical Equipment Used in Power Plants Power Supply for Electrolytic Process | Industrial Engineering Before uploading and sharing your knowledge on this site, please read the following pages: 1. Content Guidelines 2. Prohibited Content 3. Image Guidelines 4. Plagiarism Prevention 5. Content Filtration 6. Terms of Service 7. Disclaimer 8. Privacy Policy 9. Copyright 10. Report a Violation 11. Account Disable 12. Uploader Agreement. Title Your Name Your Email ID Drop files here or Select files http://www.engineeringenotes.com/power-plants-2/equipment/classification-of-excitation-system-power-plants/29729[01-Dec-19 9:46:43 PM] Classification of Excitation System | Power Plants Upload and Share LATEST Unconventional Machining Processes: AJM, EBM, LBM & PAM | Manufacturing Material Properties: Alloying, Heat Treatment, Mechanical Working and Recrystallization Design of Gating System | Casting | Manufacturing Science Forming Process: Forming Operations of Materials | Manufacturing Science Generative Manufacturing Process and its Types | Manufacturing Science GUIDELINES Home Privacy Policy Upload & Share Contact Us SUGGESTION Report Spelling and Grammatical Errors Suggest Us http://www.engineeringenotes.com/power-plants-2/equipment/classification-of-excitation-system-power-plants/29729[01-Dec-19 9:46:43 PM]