DEHN protects. © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 1 Lightning Protection Standard © 2014 DEHN + SÖHNE / protected by ISO 16016 International Electrotechnical Commission (IEC) Common Ground for International Trade © 2014 DEHN + SÖHNE / protected by ISO 16016 Lightning protection standard IEC 62305:2010 “Protection against lightning" IEC 62305 Part 1 General principles Part 2 Risk management Part 3 Physical damage to structures and life hazard Part 4 Electrical and electronic systems within structures SS 555 : 2018 Part 1: 85 pages Part 2: 101 pages Part 3: 179 pages Part 4: 99 pages © 2014 DEHN + SÖHNE / protected by ISO 16016 20.02.13 / 6004_E_1 IEC 62561 Standard for LPS Components IEC 62561 deals with the requirements and tests for lightning protection system components (LPSC) used for the installation of a lightning protection system (LPS) designed and implemented according to IEC 62305 series of standards. IEC 62561 consists of the following parts, under the general title Lightning protection system components (LPSC): IEC 62561-1: Requirements for connection components IEC 62561-2: Requirements for conductors and earth electrodes IEC 62561-3: Requirements for isolating spark gaps (ISG) IEC 62561-4: Requirements for fasteners IEC 62561-5: Requirements for earth electrode inspection housings and earth electrode seals IEC 62561-6: Requirements for lightning strike counters (LSC) IEC 62561-7: Requirements for earth enhancing compounds © 2014 DEHN + SÖHNE / protected by ISO 16016 BCA Circular Ref : APPBCA-2018-09 (31 Oct 2018) © 2014 DEHN + SÖHNE / protected by ISO 16016 IEC 62305 / SS 555-3 © 2014 DEHN + SÖHNE / protected by ISO 16016 IEC 61643 Standard for SPD and SPD Application IEC 61643-11:2011 (EN 61643-11:2012) Surge protective devices connected to low-voltage power distribution system. Part 1: Performance requirements and testing methods IEC 61643-12 Surge protective devices connected to low-voltage power distribution system. Part 12: Selection and application principles IEC 61643-21 Surge protective devices connected to telecommunications and signalling networks. Part 21: Performance requirements and testing methods IEC 61643-22 Surge protective devices connected to telecommunications and signalling networks. Part 22: Selection and application principles © 2014 DEHN + SÖHNE / protected by ISO 16016 8 IEC 616430-1 : 2005 Withdrawn © 2014 DEHN + SÖHNE / protected by ISO 16016 9 IEC 62305 / SS 555-4 © 2014 DEHN + SÖHNE / protected by ISO 16016 External Lightning Protection System (LPS) SS 555-1 : Foreword Ref.: AS/NZS 1768:2007 © 2014 DEHN + SÖHNE / protected by ISO 16016 11 External Lightning Protection System (LPS) SS 555-1 : Foreword ESE = methods for artificially increase the range DAS = methods capable of modifying the natural weather phenomena In the National Foreword, there is an important paragraph that gives directive that ESE and DAS cannot be used as primary design. For primary design, always stick to the three methods described in IEC 62305-3. © 2014 DEHN + SÖHNE / protected by ISO 16016 IEC 62305-3:2010 5. External lightning protection system 5.2 Air-termination systems 5.2.2 Positioning Air-termination components installed on a structure shall be located at corners, exposed points and edges (especially on the upper level of any facades) in accordance with one or more of the following methods. Acceptable methods to be used in determining the position of the airtermination system include: ➢ the protection angle method; ➢ the rolling sphere method; ➢ the mesh method. The rolling sphere method is suitable in all cases. The protection angle method is suitable for simple-shaped buildings but it is subject to limits of air-termination height indicated in Table 2. The mesh method is a suitable form of protection where plane surfaces are to be protected. © 2014 DEHN + SÖHNE / protected by ISO 16016 16.03.13 / 6020_E_1 Not recognise Non-conventional LPS (ESE2, CTS3 ,DAS4) ESE “Early Streamer Emitter” or CTS “Charge Transfer Systems” or DAS “Dissipation Arrays” © 2014 DEHN + SÖHNE / protected by ISO 16016 Not recognise non-conventional LPS Source: http://www.ground.co.kr/PGS_forum/forum_20090818.html, 13-11-14 © 2014 DEHN + SÖHNE / protected by ISO 16016 Charge Transfer System - Principle Idea: Discharging the thunderstorm cloud before even a lightning strike could happen. © 2014 DEHN + SÖHNE / protected by ISO 16016 Early Streamer Emission (ESE) Devices (I) Picture: Cirprotec Idea: Launching an upward leader earlier than conventional systems. This „time advantage“ can be then converted to an extended virtual height of the physical length of the air termination rod. © 2014 DEHN + SÖHNE / protected by ISO 16016 Picture: Erico Damage to buildings with ESE air terminations Kuala Lumpur, (byHartono and Robiah) © 2014 DEHN + SÖHNE / protected by ISO 16016 Damage to buildings with ESE air terminations Kuala Lumpur, (by Hartono and Robiah) © 2014 DEHN + SÖHNE / protected by ISO 16016 Damage to buildings with ESE air terminations Kuala Lumpur, (by Hartono and Robiah) © 2014 DEHN + SÖHNE / protected by ISO 16016 Damage to buildings with ESE air terminations Kuala Lumpur, (by Hartono and Robiah) © 2014 DEHN + SÖHNE / protected by ISO 16016 Damage to buildings with ESE air terminations Kuala Lumpur, (by Hartono and Robiah) © 2014 DEHN + SÖHNE / protected by ISO 16016 SS 555 Part 1 & 2 © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 23 Introduction © 2014 DEHN + SÖHNE / protected by ISO 16016 24 Lightning Flash Density © 2014 DEHN + SÖHNE / protected by ISO 16016 25 Overview of the risk components RX RB RA RC S1 RZ Rx S4 S2 RM S3 RW © 2014 DEHN + SÖHNE / protected by ISO 16016 RV RU DEHNsupport – Risk analysis 19.07.13 / 5762_E_1 DEHN Concept Risk Management Risk management for structures and buildings according to IEC/EN 62305-2* Four different categories are distinguished in a risk analysis: • Risk R1 : Loss of human life • Risk R2 : Loss of service to the public • Risk R3 : Loss of cultural heritage • Risk R4 : Loss of economic value © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Concept 15.06.2016 / 5604_E_1 Risk Assessment Zoning © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 28 Risk Assessment Zoning © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 29 Risk Assesment Type of Loss 10 -1 (0.1) : Hospital , Hotel , School , Civic Building • • • • • • • Civic Building = Public Building Gymnasiums , Sports Stadiums , Swimming Pools Shopping Centres, departments Stores Railway Stations , airports , Bus Station High-rise building Blocks of flats (multi story) Police Stations , fire departments, ambulances 5 x 10 -2 (0.05) : Public Entertainment , Church Museum • • • • Agriculture buildings Shelters, carparks Single family house Two-family houses (one or 2 story) 2 x 10 -2 (0.02) : Industrial , commercial • © 2014 DEHN + SÖHNE / protected by ISO 16016 Industrial (non-explosive) DEHN Asia Lightning protection 30 Risk Assessment Reduction Factor Whole Building/Structure : • Low Risk: Semi – D* , Town House* , Open Space Car Park , Shelters , Bus Stops • High Risk: Library , Multi Story Car Park , Library By Zones : • High Risk : Kitchen , Hallway (if it is carpeted – eg : Hotel) • Low Risk : Dining Area Reference made from reports from Canada , Europe & New Zealand © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection 31 Risk Assesment Implementation - SPD From the RA Requirement of SPD requirement is reflected in : • pEB: Lightning equipotential bonding : Equipotential bonding for LPL – o By implementation Refers to the Mainboard • Surge Protection LPL o By implementation usually refer to the respective Zone (Sub Board) – eg : Guard house , server room , residential etc… © 2014 DEHN + SÖHNE / protected by ISO 16016 32 Risk Assessment Result © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection 33 SS 555 Part 3 © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 34 Thickness of Bonding Material © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection 35 Annex E © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 36 © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 37 IEC 62305:2010-2012, Part 3 Physical Damage and Life Hazard Lightning Protection System © 2014 DEHN + SÖHNE / protected by ISO 16016 lightning equipotential bonding separation distances earth-termination system down-conductor system air-termination system as per IEC 62305-3 38 IEC 62305-3:2010 6.3 Electrical insulation of the external LPS 6.3.1 General Electrical insulation between the air-termination or the down-conductor and the structural metal parts, the metal installations and the internal systems can be achieved by providing a separation distance, s, between the parts. The general equation for the calculation of s is given by: ki depends on the selected class of LPS (see Table 10); km depends on the electrical insulation material (see Table 11); kc s = ki • ⎯ • l km kc depends on the (partial) lightning current flowing on the airtermination and the down-conductor (see Table 12 and Annex C); l is the length, in metres, along the air-termination and the down conductor from the point, where the separation distance is to be considered, to the nearest equipotential bonding point or the earth termination (see E.6.3 of Annex E). NOTE The length l along the air-termination can be disregarded in structures with continuous metal roof acting as natural air-termination system. © 2014 DEHN + SÖHNE / protected by ISO 16016 International Workshop 2015-07 04.08.14 / 6045_E_1 Demonstration test „Proximity“ Down conductor (copper) Video (slow motion) © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 40 Lightning current distribution at the cell tower Solution with spacer and HVI®Conductor air-termination rod GRP supporting tube spacer aluminium supporting tube air-termination rod HVI®Conductor © 2014 DEHN + SÖHNE / protected by ISO 16016 Lightning effects on cell sites 12.06.15 [20150612] / 9925_E_10 Demonstration test „Proximity“ High voltage-resistant, isolated down conductor Video (slow motion) © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 42 Technical Trend of External LPS Japan • Conventional – non-isolated LPS • Reinforcement suffer flash over , causes concrete chipping • Higher probability for high rise building • Reinforcement system as part down conductor is recommended Japan Science and Technology Agency (JST) 嶋田章 - ㈱村田電機製作所 Murata Electric Manufacturing Co., Ltd. (1913) Ref.: Insert text © 2014 DEHN + SÖHNE / protected by ISO 16016 Flash Over Incident Hilton , Kuala Lumpur , Malaysia Hartono’s Respond to ILPA Posting Z. A. Hartono and I. Robiah (Malaysia) Senior Members IEEE (USA) , Ref.: Insert text © 2014 DEHN + SÖHNE / protected by ISO 16016 IEC 62305:2010-2012, Part 3 Physical Damage and Life Hazard Lightning Protection System © 2014 DEHN + SÖHNE / protected by ISO 16016 lightning equipotential bonding separation distances earth-termination system down-conductor system air-termination system as per IEC 62305-3 45 Minimum Thickness Air Termination *Special attention to be paid for combustible or flammable material – ensuring temperature rise of inner surface does not constitute a danger © 2014 DEHN + SÖHNE / protected by ISO 16016 46 Air Termination • Height of Person 2.5m must take into consideration • To be Separated/Insulated from touch Potential ❖ Attention to be paid for accessible Air Termination • Side Flash @ 45m • Corners , edges & Parapet walls - Metal Capping © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 47 Methods for positioning of air termination systems mesh size M h2 air termination rod radius of rolling sphere 1 2 down conductor h1 earth-termination system protection class radius of rolling sphere maximum building height © 2014 DEHN + SÖHNE / protected by ISO 16016 mesh size I 20 m 5×5m II 30 m 10 × 10 m III 45 m 15 × 15 m IV 60 m 20 × 20 m 06.11.14 / 660_D_1 3D concept development / Project schedule - Protected volume © 2014 DEHN + SÖHNE / protected by ISO 16016 19./20.01.15 / MKN Protection in Open Space Type A , B & C Type A : Small defined open space full protection can be provided Type B : Open habitable roof space where people regularly present and where full protection can be provided . Examples: • Penthouse open terrace • Roof Gardens • Roof Level Multi-story car parks • Roof Amenities – café Sport facility , swimming pools Type C : Large open spaces where full protection is not practicable : • School fields • Public parks • Beaches • Golf Course • Vacant land for ad-hoc activities – trade fairs , fun fairs etc. © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 50 Rolling Sphere Example © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 51 Rolling Sphere Sag © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 52 © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 53 Air Termination & Down conductor + Separation Distance © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 54 Air Termination Avoiding Touch & Separation Distance © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 55 Air Termination + Separation Distance © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 56 Direct connection of roof-mounted structures Partial lightning currents inside the structure ventilation / air-conditioning system floor distributor PC PC floor distributor PC PC server MEB: Main Earthing Busbar; EB: Earthing Busbar © 2014 DEHN + SÖHNE / protected by ISO 16016 International Workshop 2015-07 EB EB MEB 24.06.13 / 1535_E_1 Protection of roof-mounted structures with isolated air-termination system Lightning current discharged from the outside ventilation system/air conditioning FDB PC PC FDB PC PC Server EB EB MEB FDB: Floor Distribution Board; MEB: Main Equipotential Bonding; EB: Equipotential Bonding © 2014 DEHN + SÖHNE / protected by ISO 16016 International Workshop 2015-07 06.11.13 / 8371_E_1 Air-termination system for small-sized electric roof installations αo s Protection of the roof-mounted fan by means of an air-termination rod according to: IEC 62305-3 Subsection 5.2.2 Protective angle α according to Table 2 Connection of the roof-mounted fan via a spark gap according to DIN VDE 0185 T1 Direct connection of a roof-mounted fan according to ABB 8th edition © 2014 DEHN + SÖHNE / protected by ISO 16016 HVI Standard Presentation; TDL 16.09.13 / 369_E_1 Conductor Holder Roof Tile © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 60 Conductor Holder Roof Tile © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 61 Down conductor No Aluminum to Concrete © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 62 Conductor Holder © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 63 Test Joints Test Joints : • Type 1 : Expose down conductor ❖ 2.5m @ Every down conductor [ j] – i : 0.3m – k : 0.5m © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 64 Touch Voltage © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 65 Step Voltages © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 66 Protection measures against touch and step voltage No life hazard if... “There are no persons within 3 m from the down conductors.” “The contact resistance of the surface layer of the soil is not less than 100 kΩ.“ “A layer of insulating material, e. g. asphalt, of 5 cm thickness (or a layer of gravel 15 cm thick)” 3m Ref.: IEC 62305-3:2010, 8.1 © 2014 DEHN + SÖHNE / protected by ISO 16016 3m External LPS Presentation 67 23.02.13 / 2934_E_1 Protection measures against touch voltage down conductor insulated to a value of 100 kV (1.2/50 µs) insulation of 3 m If none of these conditions is fulfilled, protection measures shall be adopted against injury to living beings due to touch voltages as follows: ▪ insulation of the exposed down-conductor is provided giving a 100 kV, 1,2/50 μs impulse withstand voltage, e.g. at least 3 mm crosslinked polyethylene ▪ physical restrictions and/or warning notices to minimize the probability of down-conductors being touched clamp Ref: IEC 62305-3 :2010; 8.1 © 2014 DEHN + SÖHNE / protected by ISO 16016 External LPS Presentation 68 05.02.13 / 2934_E_2 CUI Conductor Protection against touch voltage at down conductors CUI Conductor Technical data Impulse withstand voltage 100 kV (1.2/50 µs) Conductor material copper Insulation material cross-linked PE Outer diameter (conductor) 20 mm Cross-section 50 mm² (Ø 8 mm) Protective coating of the skin PE, light grey Length of 3.5 m Length of 5 m Part No. 830 208 Part No. 830 218 ▪ Eliminates the risk of touch voltage for living beings according to IEC 62305-3 © 2014 DEHN + SÖHNE / protected by ISO 16016 External LPS Presentation 69 04.02.13 / 4499_E_2 © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 70 Joints conforming to IEC 62305 Suitable for Lightning & EMC Recommended • • • • • • • © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar No Power Source Require No Life Hazard No Health Hazard • Chemical release from welding • 3 – 5x faster Installation by torque wrench Inspection by torque wrench Faster installation Completion Lower Level of skill requirement compare to Welding & Bound Joints 71 SS 555, Part 3 Reinforcement & Natural Down Conductor © 2014 DEHN + SÖHNE / protected by ISO 16016 SS 555, Part 3 Reinforcement & Natural Down Conductor © 2014 DEHN + SÖHNE / protected by ISO 16016 Simulation of the current distribution Using the reinforcement as natural down conductor © 2014 DEHN + SÖHNE / protected by ISO 16016 Compact Lightning Protection Seminar – Separation distance 27.09.12 / 5857_E_2 IEC 62305-3:2010 6.3 Electrical insulation of the external LPS 6.3.1 General In structures with metallic or electrically continuous connected reinforced concrete framework a separation distance is not required. Note DEHN: Only applies to the separation distance inside the building! © 2014 DEHN + SÖHNE / protected by ISO 16016 Compact Lightning Protection Seminar – Separation distance 24.06.13 / 6148_E_1 High Rise Building Separation Distance – Conventional Design LPL III @ 200kA Building Profile : Height : 60 Width : 25 Length : 25 Details of Simulation Selected class of LPS : III Current intensity : 200 kA Insulation coefficient km: 0.5 Potential level : -10 m © 2014 DEHN + SÖHNE / protected by ISO 16016 Furthest 3m 18m 35m 45m 55m 2.06 m 29cm 66cm 1.03m 1.23m 1.5m High Rise Building Separation Distance – Reinforcement Design LPL III @ 200kA Building Profile : Height : 60 Width : 25 Length : 25 Details of Simulation Selected class of LPS : III Current intensity : 200 kA Insulation coefficient km: 0.5 Potential level : 58 m Furthest 56cm © 2014 DEHN + SÖHNE / protected by ISO 16016 3m 18m 35m 45m Equipotential 55m High Rise Building Separation Distance – Reinforcement Design LPL I @ 200kA Building Profile : Height : 60 Width : 25 Length : 25 Details of Simulation Selected class of LPS : I Current intensity : 200 kA Insulation coefficient km: 0.5 Potential level : 58 m Furthest 41cm © 2014 DEHN + SÖHNE / protected by ISO 16016 3m 18m 35m 45m Equipotential 55m BS 7430:2011 / SS 551 Code of practice for protective earthing of electrical installations 9.5.8.5 Structural steelwork Foundation metalwork in concrete may be used as a ready made and effective earth electrode. The total electrode area formed by the underground metalwork of large structure may often be used to provide an earth resistance lower then that obtainable by other methods; overall values well below 1 Ω are obtainable. © 2014 DEHN + SÖHNE / protected by ISO 16016 Ring earth electrode in case of perimeter insulation Installation in the blinding layer Ref.: Fritz Mauermann GmbH + Co. KG, Paderborn © 2014 DEHN + SÖHNE / protected by ISO 16016 ring earth electrode material: StSt (V4A) mesh size of 10x10 m, if a lightning protection systems is installed Compact Lightning Protection Seminar – Basics of dimensioning 07.01.13 / 5523_E_1 DIN 18014: Earth-termination system in case of foundations with increased earth contact resistance © 2014 DEHN + SÖHNE / protected by ISO 16016 Compact Lightning Protection Seminar – Basics of dimensioning 13.11.13 / 6608_E_2 DIN 18014: Earth-termination system in case of foundations with increased earth contact resistance functional ring earth electrode, mesh size bonding conductor, - 10 m x 10to m the with LPSmesh size ≤ 20 m x 20 m connection - 20 m x 20 m at without LPS reinforcement intervals of 2 m © 2014 DEHN + SÖHNE / protected by ISO 16016 DIN 18014: Earth-termination system in case of foundations with increased earth contact resistance ring earth electrode, pressure-water-tight mesh size - 10 m x 10 m with LPS wall bushing - 20 m x 20 m without LPS Connection of the ring earth electrode to the functional bonding conductor ▪ per down conductor of the lightning protection system or ▪ at intervals of 20 m / circumference of the building © 2014 DEHN + SÖHNE / protected by ISO 16016 Compact Lightning Protection Seminar – Basics of dimensioning 13.11.13 / 6608_E_7 DIN 18014: Earth-termination system in case of foundations with increased earth contact resistance ground surface highest ground water level foundation slab pressurewater-tight wall bushing blinding layer terminal lug connection to the reinforcement connecting clamp © 2014 DEHN + SÖHNE / protected by ISO 16016 equipotential bonding conductor Compact Lightning Protection Seminar – Basics of dimensioning ring earth electrode 13.11.13 / 6608_E_11 Lightning protection zones concept Detail: Earth-termination system Earth-termination system Connection to the reinforcement mesh © 2014 DEHN + SÖHNE / protected by ISO 16016 Lightning protection zones concept Detail: Down-conductor system Connection of the down-conductor system to the foundation earth electrode © 2014 DEHN + SÖHNE / protected by ISO 16016 86 15.11.12 / 8080_E_16 Test Joints • Type 2 : Natural down conductor and flushed mounted ❖ 1.5m min 2 Connection of the downconductor system to the foundation earth electrode ❖ No Earth Pit Require © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 87 Establishing a “lightning equipotential bonding level“ for a new building based on IEC 62305-4 a 8 1 b 3 7 5 4 2 direct connection to the intermeshing in the reinforcement 6 5 1 Connection between the air-termination system and the down conductors 2 Horizontal connecting conductor 3 Reinforcing bars 4 Down conductor and ring conductor 5 Equipotential bonding bar of the internal lightning protection system 6 Test clamp 7 Current carrying connection 8 Air-termination rod Typical distances a = about 5 m b = about 5 m NOTE: Such a lightning protection system is ideally suited for new buildings where a low-impedance structure should be created to be able to neglect separation distances from the inside of the structure up to the roof level. Ref.: EN 62305-4:2010, Figure 7 04.01.2017 [20160502] / 9207_E_1 © 2014 DEHN + SÖHNE / protected by ISO 16016 Metal facade used as a natural down conductor b 2 3 1 2 4 4 c 6 6 5 Typical distances a/b = 5 m; c = 1 m (not common practice for curtain walling) a 6 7 connection to the earthtermination system 7 5 8 1 Metal capping of the roof parapet 2 Connection between the facade cladding and the air-termination system 3 Horizontal air-termination system 4 Metal facade cladding 5 Equipotential bonding bar Connection between the plates of the facade cladding 6 Connection between the facade elements and the load bearing construction 7 Test joint 8 Steel reinforcement embedded in concrete Ref.: EN 62305-3:2010, Figure E.8a 04.01.17 [20161213] / 2979_E_1 © 2014 DEHN + SÖHNE / protected by ISO 16016 Multi-storey building with utilisation of the reinforcement Structure of the building 1 Mesh size of the ring earth electrode acc. DIN 18014 - max. 10 x 10 m (each down conductor must be connected to the ring earth electrode) 2 Mesh size of the functional bonding conductor acc. DIN 18014 - max. 20 x 20 m 3 5m 5m 1m 3 1m 3 Lightning equipotential bonding Lightning current arrester Local equipotential bonding Surge arrester Functional earthing 2 10 m 1 Air-termination system Equipotential bonding Fixed earthing point 20 m Note: Building is not shielded according IEC 62305-4 Low-voltage supply system 3 Equipotential surface Lightning Protection Zone 14.12.16 [20160503] / 10289_E_1 © 2014 DEHN + SÖHNE / protected by ISO 16016 Multi-storey building with utilisation of the reinforcement Isolated lightning protection system on the roof Curtain-wall metal facing "s" is kept 1 Equipotential surface 1 1 1 Note: Building is not shielded according to IEC 62305-4 Lightning equipotential bonding Lightning current arrester Local equipotential bonding Surge arrester Functional earthing Low-voltage supply system LPL D+S recommend: SPDs Type 2 based on VDE 0100-534, Table 534.3B D+S recommend: SPDs LPL I Nominal discharge current In 20 kA (8/20µs) / pole Nominal discharge current In 10 kA (8/20µs) / wire LPL II Nominal discharge current In 15 kA (8/20µs) / pole Nominal discharge current In 10 kA (8/20µs) / wire LPL III / IV Nominal discharge current In 10 kA (8/20µs) / pole Nominal discharge current In 10 kA (8/20µs) / wire © 2014 DEHN + SÖHNE / protected by ISO 16016 Air-termination system Equipotential bonding Fixed earthing point Lightning Protection Zone 11.01.17 [20160503] / 10289_E_5 Lightning protection zones concept Detail: Down-conductor system Down conductor in the supporting structure Connection of the down conductor to the reinforcement of the supporting structure © 2014 DEHN + SÖHNE / protected by ISO 16016 92 15.11.12 / 8080_E_15 Example: Two-storey building (according to IEC 62305-3) c= 10 m h1 = h2 = h3 = 3.0 m c s h1 l s s h2 s h3 l Lightning equipotential bonding Lighning current arrester Local equipotential bonding Surge arrester Functional earthing Low-voltage supply system Air-termination system Equipotential bonding Fixed earthing point Lightning Protection Zone 02.05.17 [20160504] / 10316_E_1 © 2014 DEHN + SÖHNE / protected by ISO 16016 Lightning protection zones concept Detail: Equipotential bonding Equipotential bonding of metal installations © 2014 DEHN + SÖHNE / protected by ISO 16016 94 15.11.12 / 8080_E_21 Lightning protection zones concept Detail: Structural Metal components e. g. cable trays e. g. railings e. g. lifts systems © 2014 DEHN + SÖHNE / protected by ISO 16016 95 15.11.12 / 8080_E_22 Reinforcement as Down conductor Separation Distance , Down Conductor & Bonding Advantage: • Solved : • Separation Requirement (Except Roof Top) • Touch (Except Roof Top) & Step Voltage Hazard • Shielding Effect • Ease of Bonding Point Introduction ( Omits Long cable for Bonding) • < 1Ω Earthing Value (Foundation/Structure Steel Work Being Use) • Anti Theft • Long Term – Maintenance Free / Negligible replacement requirement • No need earth pit • Only 2 earth test point diagonally installed • Ease Architectural Design • Cost & Time Savings Ref.: Insert text © 2014 DEHN + SÖHNE / protected by ISO 16016 Continuity Test © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 97 SS 555 Part 4 © 2014 DEHN + SÖHNE / protected by ISO 16016 DEHN Asia Lightning protection seminar 98 Comparison of test currents Video 2 1 wave form [µs] i [kA] 100 imax [kA] 10/350 8/20 40 40 80 60 50 40 1 20 2 0 20 200 Ref.: IEC 61643-11 © 2014 DEHN + SÖHNE / protected by ISO 16016 400 600 800 1000 t [µs] 30.07.13 / 916_E_1 Comparison of test currents Video: Impact on the electrical installation © 2014 DEHN + SÖHNE / protected by ISO 16016 11.02.13 / 916_E_4 Laboratory test with simulated lightning currents according to IEC 61643-11 GSM customer panel 50 kA (10/350 µs) © 2014 DEHN + SÖHNE / protected by ISO 16016 Application Surge protection for power supply systems Type 3 Type 2 SDB > 10 m DEHNguard M 10 m terminal DEHNsafe device Type 3 Type 2 SDB > 10 m DEHNrail DEHNguard M > 10 m MDB DEHNventil M terminal device Type 3 Type 1+2 power network terminal device 10 m terminal device DEHNflex terminal device MDB Main Distribution Board SDB Sub Distribution Board © 2014 DEHN + SÖHNE / protected by ISO 16016 30.07.14 / 8350_E_1 Lightning Current Distribution LPL I = 200 kA (10/350µs) Building Service Transformer External Lightning Protection 200 kA 25 kA per Line 25 kA each 100 kA 100 kA 100 kA © 2014 DEHN + SÖHNE / protected by ISO 16016 Sizing & Configuration according to LPL (lightning protection level) First positive impulse Lightning protection level (LPL) I II III-IV Peak current I (kA) 200 150 100 Iimp N-PE (kA) 100 75 50 Iimp L-N (kA) 25 18.75 12.5 Time parameters T1/T2 (µs/µs) 10/350 Ref.: IEC 62305-1:2010, Table 3 (extract) © 2014 DEHN + SÖHNE / protected by ISO 16016 Compact Surge Protection Seminar – Causes 16.07.14 / 6006_E_1 Application of SPD in ACPD (AC Power Distribution) AC Power Distribution Board • • • 230/400 V • • • I • • • • • In accordance with IEC 61643-11 Combined SPD (Type 1+2), Voltage Protection ≤ 1.5kV Lightning Impulse Current (10/350us) - 25kA per channel, 100kA total (LPL1) - 12.5kA per channel, 50kA total (LPL3) Differential mode or 3+1 configuration Ensure energy coordination of SPD Follow Current (If) shall be less than current rating of the incoming breaker to avoid nuisance tripping Follow Current Interrupt Rating (Ifi) & Short-Circuit Rating of SPD (Isccr) ≥ Prospective short circuit rating of System (Ip) Backup fuse rating in accordance with IEC 61643-12 Metal encapsulated spark-gap to ensure no plasma jet TOV, 440V, min 2 hrs Status indicator to show the serviceability of the SPD including N-PE channel © 2014 DEHN + SÖHNE / protected by ISO 16016 Internal surge protection Thank You © 2014 DEHN + SÖHNE / protected by ISO 16016