LOAD SCHEDULE
LEGEND
GENERAL NOTES
1. ALL ELECTRICAL WORKS SHALL COMPLY IN ACCORDANCE WITH
DESCRIPTION
SYMBOL
THESE PLANS AND
SPECIFICATIONS. THE APPLICABLE PROVISIONS OF THE LATEST EDITION OF THE
PANELBOARD:
-
CEILING LIGHT OUTLET
PHILIPPINE ELECTRICAL CODE (PEC). THE RULES AND REGULATION OF THE LOCAL
2
-
2 x 40 WATTS FLUORESCENT LAMP
ENFORCING AUTHORITY AND THE REQUIREMENTS OF THE LOCAL POWER COMPANY. THE

-
CEILING FAN OUTLET
ELECTRICAL WORKS SHALL BE DONE UNDER THE IMMEDIATE
SUPERVISION OF A DULY
REGISTERED ELECTRICAL ENGINEER.
2. THE ELECTRICAL SERVICE POWER IS 1-PHASE, 2-WIRE,
230 V AC, 60 Hz.
3. WIRING METHOD SHALL BE AS FOLLOWS :
a. FEEDERS AND RISERS -
INTERMEDIATE METALLIC CONDUIT
b. LIGHTING, POWER RECEPTACLE -
CONVENIENCE OUTLET - 9x180w
1860
230
2
20
50
3.35mm² THW IN 15mmØ C
S cde
-
THREE GANG DEVICE SWITCH
2
CONVENIENCE OUTLET - 9x180w
1860
230
2
20
50
3.35mm² THW IN 15mmØ C
S 3W
-
THREE WAY DEVICE SWITCH
3
CONVENIENCE OUTLET - 6x180w
1080
230
2
20
50
3.35mm² THW IN 15mmØ C
Sf
-
FAN CONTROL SWITCH
4
LIGHTING OUTLET
1460
230
2
20
50
3.35mm² THW IN 15mmØ C
S EF
-
EXHAUST FAN SWITCH
5
LIGHTING OUTLET
1500
230
2
20
50
3.35mm² THW IN 15mmØ C
-
RACEWAY CONDUIT CONCEALED IN CEILING
6
LIGHTING OUTLET
1200
230
2
20
50
3.35mm² THW IN 15mmØ C
-
RACEWAY CONDUIT CONCEALED UNDER FLOOR
7
LIGHTING OUTLET
1000
230
2
20
50
3.35mm² THW IN 15mmØ C
8
LIGHTING OUTLET
1100
230
2
20
50
3.35mm² THW IN 15mmØ C
9
LIGHTING OUTLET
1100
230
2
20
50
3.35mm² THW IN 15mmØ C
10
SPARE
1500
230
2
20
50
11
SPARE
1500
230
2
20
50
5. ALL OUTLET BOXES SHALL BE GALVANIZED GAGE NO. 16 DEEP TYPE WITH FACTORY
EF
KNOCKOUTS.
LP
-
PANELBOARD
-
CKT. BREAKER, RATING AS INDICATED
-
DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE
-
EXHAUST FAN OUTLET, SINGLE, GROUNDING TYPE
10 AMPS, 250 VOLT WITH MODERN PLATE COVER
-
HOMERUN DIRECT TO PANELBOARD
-
PUSH BUTTON
-
ENCLOSED AIR CIRCUIT BREAKER
FA
-
FIRE ALARM CONTROL PANEL
F
-
FIRE ALARM STATION OUTLET
-
VIBRATING BELL OUTLET
PARTICULAR LOCATION AND PURPOSE OF USAGE.
7. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL LIGHTING AND POWER CIRCUIT AS
PER PHILIPPINE ELECTRICAL CODE REQUIREMENT.
B
b. CONVENIENCE OUTLET
-
0.30 M ABOVE FINISH FLOOR.
B
-
FIRE ALARM BELL
c. PANELBOARD
-
1.50 M ABOVE FINISH FLOOR
M
-
SERVICE METER
d. FIRE ALARM STATION OUTLET
-
1.50 M. ABOVE FINISH FLOOR
-
SERVICE ENTRANCE
e. PUSH BUTTON OUTLET
-
1.20 M ABOVE FINISH FLOOR
f. FIRE ALARM & VIBRATING BELL
-
TOTAL
14680
OVERHEAD SERVICE ENTRANCE
CONNECTED TO 220V AC, 1Ø, 2
WIRE, 60 Hz FITTED WITH
32mmØ TYPE "F" CONDULET
BUILDING WALL
TO SIMILAR OUTLET
@ SECOND FLOOR
& THIRD FLOOR
2ND FLOOR LINE
150AT, 225AF, 2P, 230V AC
1
TO LINE SIDE OF LP
2
3
20
20
20
20
20
20
20
20
20
20
5
7
F
4
METERING CONDUIT
3-3.5mm² THW
IN 15mmØ RSC
KWHR METER
6
FA
8
10
20
13
15
20
20
20
20
20
14
16
GROUND TERMINAL
#14mm² BARE COOPER WIRE
16MMO x 240MM LENGTH
GROUNDING ROD COPPERWELD
N ITO R I NG
RI N
G , A S SE S S
MO
ME
THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT
TO
APPROVED FOR ACCREDITATION :
SCALE
CONCURRED :
PROJECT TITLE :
FE M. BARRIENTOS
SOFIA T. SANTIAGO
GILBERTO S. REYES
RAMON C. BACANI
OIC, DIRECTOR III
BUREAU OF DESIGN, DPWH
OIC, DIRECTOR IV
BUREAU OF DESIGN, DPWH
UNDERSECRETARY



N
MERALCO AVENUE, PASIG CITY
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE
OF THE SAME DUE TO FAULTY DESIGN.
NOT
RECOMMENDING APPROVAL :
&
MCMXCIX
EE
SCALE
RISER DIAGRAM
T
IO
T
IN
G
R
A
EN
PA
TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING
ENGINEER III
PRC NO. :
TIN :
PTR NO. :
DATE :
CHIEF, ELECTRICAL DIVISION
BUREAU OF DESIGN, DPWH
VIBRATING BELL
2
VENERANDO D. SAHAGUN
A
F O RC E
N
NES
DE
TM
UC
EN
T O F ED
DEPARTMENT OF EDUCATION (DepED)
E
F
T
TA
SK
I
PP
REP
UB
L
REPUBLIC OF THE PHILIPPINES
LI
M
t he PH
I
FIRE ALARM
1-8.0mm BARE COPPER WIRE
IN 15mmO C
SINGLE LINE DIAGRAM
REVIEWED BY:
TO NEAREST C.O.
FIN. GRADE LINE
16mmØx2400mm
COPPERWELD
GROUND ROD
TO
2-3.5mm² THW
IN 15mmØ RSC
ELECTRICAL
GROUND FLOOR LINE
NOT
2-3.5mm² THW
IN 15mmØ RSC
ENCLOSED ACB
RATING: 20AT, 50AF,
230V, 2P
12
1500 mm
11
1800 mm
9
B
B
2-32mm²THW
IN 32mmØ RSC
of
PROTECTION: 150 AT, 225 AF, 2P, 230 V
230 V
PANEL LP
IC
2-30mm² THW IN 32mmØ C
FEEDER:
IL @ 80% D.F. = 14680x 80% x 1.25 = 63.8 A
0.30 M BELOW CEILING LINE
CONSULTANT / DESIGNER
WIRE & CONDUIT SIZE
AF
AT
1
10 AMPS, 250 VOLT WITH MODERN PLATE COVER
1.20 M ABOVE FINISH FLOOR
POLE
TWO GANG DEVICE SWITCH
BE 15mmØ TRADE/NOMINAL SIZE. I
-
VOLT
-
LIGHTING CIRCUIT HOMERUN SHALL BE 3.5mm² AND INSULATED FOR 600 VOLTS.
8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS :
CIRCUIT BREAKER
Sab
OTHERWISE INDICATED IN THE PLAN. THE MINIMUM SIZE OF WIRE FOR POWER AND
TYPE FOR THE
VA
LOAD
ONE GANG DEVICE SWITCH
4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THW" UNLESS
a. LIGHT SWITCH
CKT.
NO. DESCRIPTION
-
POLYVINYL CHLORIDE CONDUIT SCH. 40
6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED
MAIN : 100AT, 100AF, 2P, 230V
S/S a
BRANCH CKT., & AUXILIARY
SMALLEST RACEWAY SHALL
LP
DEPATMENT OF EDUCATION (DepED)
LOCATION :
PROJECT NO: 01-002
OWNER :
DEPARTMENT OF EDUCATION
DESIGNED BY: RDS
DepED
ENCODED BY: Max C
SHEET CONTENTS :
CHECKED BY:
DATE :
SHEET NO:
6-23-03
NOTE:
LOAD SCHEDULE
GENERAL NOTES
LEGEND
SINGLE LINE DIAGRAM RISER DIAGRAM
E-1
3
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.
REP. ACT 545










CLASSROOM
CLASSROOM
CLASSROOM
DN

DN
UP
UP


1 : 100
SCALE :



METERS







URINAL
UD
SD

CLASSROOM
CLASSROOM
SINK COUNTER
SINK COUNTER
CLASSROOM
STO.
UP
UP

RAMP
UP
RAMP
UP

1 : 100
SCALE :
REPUBLIC OF THE PHILIPPINES
N ITO R I NG
ELECTRICAL
ENGINEER
ENGINEER
III
MO
IO
IN
G
T
EN
R
A
F O RC E
PA
TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING
MCMXCIX
EE
RI N
G , A S SE S S
ME
THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT
CONCURRED :
PROJECT TITLE :
FE M. BARRIENTOS
SOFIA T. SANTIAGO
GILBERTO S. REYES
RAMON C. BACANI
OIC, DIRECTOR III
BUREAU OF DESIGN, DPWH
OIC, DIRECTOR IV
BUREAU OF DESIGN, DPWH
UNDERSECRETARY



N
MERALCO AVENUE, PASIG CITY
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE
OF THE SAME DUE TO FAULTY DESIGN.
APPROVED FOR ACCREDITATION :
VENERANDO D.D.
SAHAGUN
VENERANDO
SAHAGUN
A
TA
SK
NES
DE
TM
UC
EN
T O F ED
DEPARTMENT OF EDUCATION (DepED)
E
F
T
RECOMMENDING APPROVAL :
&
LI
REVIEWED BY:
T
t he PH
I
N
of
M
IC
I
PP
REP
UB
L
CONSULTANT / DESIGNER
METERS
PRC NO. :
TIN :
PTR NO. :
DATE :
CHIEF, ELECTRICAL DIVISION
BUREAU OF DESIGN, DPWH
DEPATMENT OF EDUCATION (DepED)
LOCATION :
PROJECT NO: 01-002
OWNER :
SHEET NO:
DEPARTMENT OF EDUCATION
DESIGNED BY: RDS
DepED
ENCODED BY: Max C
SHEET CONTENTS :
CHECKED BY:
DATE :
01 03
NOTE:
E-2
3
LIGHTING LAYOUT
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.
REP. ACT 545










2
a
b
2
DN
d
2
e
2
f
2
2
2
S
b
2
a
a
2
b
2
c
2
c
2
d
2
2
d
LP
9
e
2
e
2
f
2
f
2
Sabc

DN
S
a

c
2
2
f
2
2
LP
8
S def

1 : 100
SCALE :

METERS









DN
DN

LP
3


SCALE :
1 : 100
REPUBLIC OF THE PHILIPPINES
N ITO R I NG
MCMXCIX
EE
ENGINEER III
MO
IO
IN
G
T
EN
R
A
F O RC E
PA
TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING
RI N
G , A S SE S S
ME
THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT
CONCURRED :
PROJECT TITLE :
FE M. BARRIENTOS
SOFIA T. SANTIAGO
GILBERTO S. REYES
RAMON C. BACANI
OIC, DIRECTOR III
BUREAU OF DESIGN, DPWH
OIC, DIRECTOR IV
BUREAU OF DESIGN, DPWH
UNDERSECRETARY



N
MERALCO AVENUE, PASIG CITY
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE
OF THE SAME DUE TO FAULTY DESIGN.
APPROVED FOR ACCREDITATION :
VENERANDO D. SAHAGUN
A
TA
SK
NES
DE
TM
UC
EN
T O F ED
DEPARTMENT OF EDUCATION (DepED)
E
F
T
RECOMMENDING APPROVAL :
&
LI
REVIEWED BY:
T
t he PH
I
N
of
M
IC
I
PP
REP
UB
L
CONSULTANT / DESIGNER
METERS
PRC NO. :
TIN :
PTR NO. :
DATE :
CHIEF, ELECTRICAL DIVISION
BUREAU OF DESIGN, DPWH
DEPATMENT OF EDUCATION (DepED)
LOCATION :
PROJECT NO: 01-002
OWNER :
SHEET NO:
DEPARTMENT OF EDUCATION
DESIGNED BY: RDS
DepED
ENCODED BY: Max C
SHEET CONTENTS :
CHECKED BY:
DATE :
01 03
NOTE:
POWER LAYOUT
E-3
3
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.
REP. ACT 545










CLASSROOM
DN

CLASSROOM
CLASSROOM
DN
UP
UP


1 : 100
SCALE :

METERS








URINAL
UD
SD
CLASSROOM
CLASSROOM
CLASSROOM
SINK COUNTER
SINK COUNTER


UP
STO.
UP

RAMP
UP
RAMP
UP

1 : 100
SCALE :
REPUBLIC OF THE PHILIPPINES
N ITO R I NG
ELECTRICAL
ENGINEER
ENGINEER
III
MO
IO
IN
G
T
EN
R
A
F O RC E
PA
TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING
MCMXCIX
EE
RI N
G , A S SE S S
ME
THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT
CONCURRED :
PROJECT TITLE :
FE M. BARRIENTOS
SOFIA T. SANTIAGO
GILBERTO S. REYES
RAMON C. BACANI
OIC, DIRECTOR III
BUREAU OF DESIGN, DPWH
OIC, DIRECTOR IV
BUREAU OF DESIGN, DPWH
UNDERSECRETARY



N
MERALCO AVENUE, PASIG CITY
FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE
OF THE SAME DUE TO FAULTY DESIGN.
APPROVED FOR ACCREDITATION :
VENERANDO D. D.
SAHAGUN
VENERANDO
SAHAGUN
A
TA
SK
NES
DE
TM
UC
EN
T O F ED
DEPARTMENT OF EDUCATION (DepED)
E
F
T
RECOMMENDING APPROVAL :
&
LI
REVIEWED BY:
T
t he PH
I
N
of
M
IC
I
PP
REP
UB
L
CONSULTANT / DESIGNER
METERS
PRC NO. :
TIN :
PTR NO. :
DATE :
CHIEF, ELECTRICAL DIVISION
BUREAU OF DESIGN, DPWH
DEPATMENT OF EDUCATION (DepED)
LOCATION :
PROJECT NO:
PROJECT
NO: 01-002
01-002
OWNER :
SHEET NO:
DEPARTMENT OF EDUCATION
DESIGNED BY:
BY: RDS
RDS
DESIGNED
DepED
ENCODED BY: Max
RDS C
SHEET CONTENTS :
CHECKED BY:
DATE ::6-23-0301 03
DATE
NOTE:
POWER LAYOUT
E-3
3
THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND
MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION,
ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE.
REP. ACT 545
Related documents
Download
Study collections