LOAD SCHEDULE LEGEND GENERAL NOTES 1. ALL ELECTRICAL WORKS SHALL COMPLY IN ACCORDANCE WITH DESCRIPTION SYMBOL THESE PLANS AND SPECIFICATIONS. THE APPLICABLE PROVISIONS OF THE LATEST EDITION OF THE PANELBOARD: - CEILING LIGHT OUTLET PHILIPPINE ELECTRICAL CODE (PEC). THE RULES AND REGULATION OF THE LOCAL 2 - 2 x 40 WATTS FLUORESCENT LAMP ENFORCING AUTHORITY AND THE REQUIREMENTS OF THE LOCAL POWER COMPANY. THE - CEILING FAN OUTLET ELECTRICAL WORKS SHALL BE DONE UNDER THE IMMEDIATE SUPERVISION OF A DULY REGISTERED ELECTRICAL ENGINEER. 2. THE ELECTRICAL SERVICE POWER IS 1-PHASE, 2-WIRE, 230 V AC, 60 Hz. 3. WIRING METHOD SHALL BE AS FOLLOWS : a. FEEDERS AND RISERS - INTERMEDIATE METALLIC CONDUIT b. LIGHTING, POWER RECEPTACLE - CONVENIENCE OUTLET - 9x180w 1860 230 2 20 50 3.35mm² THW IN 15mmØ C S cde - THREE GANG DEVICE SWITCH 2 CONVENIENCE OUTLET - 9x180w 1860 230 2 20 50 3.35mm² THW IN 15mmØ C S 3W - THREE WAY DEVICE SWITCH 3 CONVENIENCE OUTLET - 6x180w 1080 230 2 20 50 3.35mm² THW IN 15mmØ C Sf - FAN CONTROL SWITCH 4 LIGHTING OUTLET 1460 230 2 20 50 3.35mm² THW IN 15mmØ C S EF - EXHAUST FAN SWITCH 5 LIGHTING OUTLET 1500 230 2 20 50 3.35mm² THW IN 15mmØ C - RACEWAY CONDUIT CONCEALED IN CEILING 6 LIGHTING OUTLET 1200 230 2 20 50 3.35mm² THW IN 15mmØ C - RACEWAY CONDUIT CONCEALED UNDER FLOOR 7 LIGHTING OUTLET 1000 230 2 20 50 3.35mm² THW IN 15mmØ C 8 LIGHTING OUTLET 1100 230 2 20 50 3.35mm² THW IN 15mmØ C 9 LIGHTING OUTLET 1100 230 2 20 50 3.35mm² THW IN 15mmØ C 10 SPARE 1500 230 2 20 50 11 SPARE 1500 230 2 20 50 5. ALL OUTLET BOXES SHALL BE GALVANIZED GAGE NO. 16 DEEP TYPE WITH FACTORY EF KNOCKOUTS. LP - PANELBOARD - CKT. BREAKER, RATING AS INDICATED - DUPLEX CONVENIENCE OUTLET, GROUNDING TYPE - EXHAUST FAN OUTLET, SINGLE, GROUNDING TYPE 10 AMPS, 250 VOLT WITH MODERN PLATE COVER - HOMERUN DIRECT TO PANELBOARD - PUSH BUTTON - ENCLOSED AIR CIRCUIT BREAKER FA - FIRE ALARM CONTROL PANEL F - FIRE ALARM STATION OUTLET - VIBRATING BELL OUTLET PARTICULAR LOCATION AND PURPOSE OF USAGE. 7. GROUNDING SYSTEM SHALL BE PROVIDED TO ALL LIGHTING AND POWER CIRCUIT AS PER PHILIPPINE ELECTRICAL CODE REQUIREMENT. B b. CONVENIENCE OUTLET - 0.30 M ABOVE FINISH FLOOR. B - FIRE ALARM BELL c. PANELBOARD - 1.50 M ABOVE FINISH FLOOR M - SERVICE METER d. FIRE ALARM STATION OUTLET - 1.50 M. ABOVE FINISH FLOOR - SERVICE ENTRANCE e. PUSH BUTTON OUTLET - 1.20 M ABOVE FINISH FLOOR f. FIRE ALARM & VIBRATING BELL - TOTAL 14680 OVERHEAD SERVICE ENTRANCE CONNECTED TO 220V AC, 1Ø, 2 WIRE, 60 Hz FITTED WITH 32mmØ TYPE "F" CONDULET BUILDING WALL TO SIMILAR OUTLET @ SECOND FLOOR & THIRD FLOOR 2ND FLOOR LINE 150AT, 225AF, 2P, 230V AC 1 TO LINE SIDE OF LP 2 3 20 20 20 20 20 20 20 20 20 20 5 7 F 4 METERING CONDUIT 3-3.5mm² THW IN 15mmØ RSC KWHR METER 6 FA 8 10 20 13 15 20 20 20 20 20 14 16 GROUND TERMINAL #14mm² BARE COOPER WIRE 16MMO x 240MM LENGTH GROUNDING ROD COPPERWELD N ITO R I NG RI N G , A S SE S S MO ME THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT TO APPROVED FOR ACCREDITATION : SCALE CONCURRED : PROJECT TITLE : FE M. BARRIENTOS SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI OIC, DIRECTOR III BUREAU OF DESIGN, DPWH OIC, DIRECTOR IV BUREAU OF DESIGN, DPWH UNDERSECRETARY N MERALCO AVENUE, PASIG CITY FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE OF THE SAME DUE TO FAULTY DESIGN. NOT RECOMMENDING APPROVAL : & MCMXCIX EE SCALE RISER DIAGRAM T IO T IN G R A EN PA TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING ENGINEER III PRC NO. : TIN : PTR NO. : DATE : CHIEF, ELECTRICAL DIVISION BUREAU OF DESIGN, DPWH VIBRATING BELL 2 VENERANDO D. SAHAGUN A F O RC E N NES DE TM UC EN T O F ED DEPARTMENT OF EDUCATION (DepED) E F T TA SK I PP REP UB L REPUBLIC OF THE PHILIPPINES LI M t he PH I FIRE ALARM 1-8.0mm BARE COPPER WIRE IN 15mmO C SINGLE LINE DIAGRAM REVIEWED BY: TO NEAREST C.O. FIN. GRADE LINE 16mmØx2400mm COPPERWELD GROUND ROD TO 2-3.5mm² THW IN 15mmØ RSC ELECTRICAL GROUND FLOOR LINE NOT 2-3.5mm² THW IN 15mmØ RSC ENCLOSED ACB RATING: 20AT, 50AF, 230V, 2P 12 1500 mm 11 1800 mm 9 B B 2-32mm²THW IN 32mmØ RSC of PROTECTION: 150 AT, 225 AF, 2P, 230 V 230 V PANEL LP IC 2-30mm² THW IN 32mmØ C FEEDER: IL @ 80% D.F. = 14680x 80% x 1.25 = 63.8 A 0.30 M BELOW CEILING LINE CONSULTANT / DESIGNER WIRE & CONDUIT SIZE AF AT 1 10 AMPS, 250 VOLT WITH MODERN PLATE COVER 1.20 M ABOVE FINISH FLOOR POLE TWO GANG DEVICE SWITCH BE 15mmØ TRADE/NOMINAL SIZE. I - VOLT - LIGHTING CIRCUIT HOMERUN SHALL BE 3.5mm² AND INSULATED FOR 600 VOLTS. 8. MOUNTING HEIGHT OF WIRING DEVICES SHALL BE AS FOLLOWS : CIRCUIT BREAKER Sab OTHERWISE INDICATED IN THE PLAN. THE MINIMUM SIZE OF WIRE FOR POWER AND TYPE FOR THE VA LOAD ONE GANG DEVICE SWITCH 4. ALL WIRES SHALL BE COPPER AND THERMOPLASTIC INSULATED TYPE "THW" UNLESS a. LIGHT SWITCH CKT. NO. DESCRIPTION - POLYVINYL CHLORIDE CONDUIT SCH. 40 6. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND APPROVED MAIN : 100AT, 100AF, 2P, 230V S/S a BRANCH CKT., & AUXILIARY SMALLEST RACEWAY SHALL LP DEPATMENT OF EDUCATION (DepED) LOCATION : PROJECT NO: 01-002 OWNER : DEPARTMENT OF EDUCATION DESIGNED BY: RDS DepED ENCODED BY: Max C SHEET CONTENTS : CHECKED BY: DATE : SHEET NO: 6-23-03 NOTE: LOAD SCHEDULE GENERAL NOTES LEGEND SINGLE LINE DIAGRAM RISER DIAGRAM E-1 3 THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION, ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE. REP. ACT 545 CLASSROOM CLASSROOM CLASSROOM DN DN UP UP 1 : 100 SCALE : METERS URINAL UD SD CLASSROOM CLASSROOM SINK COUNTER SINK COUNTER CLASSROOM STO. UP UP RAMP UP RAMP UP 1 : 100 SCALE : REPUBLIC OF THE PHILIPPINES N ITO R I NG ELECTRICAL ENGINEER ENGINEER III MO IO IN G T EN R A F O RC E PA TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING MCMXCIX EE RI N G , A S SE S S ME THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT CONCURRED : PROJECT TITLE : FE M. BARRIENTOS SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI OIC, DIRECTOR III BUREAU OF DESIGN, DPWH OIC, DIRECTOR IV BUREAU OF DESIGN, DPWH UNDERSECRETARY N MERALCO AVENUE, PASIG CITY FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE OF THE SAME DUE TO FAULTY DESIGN. APPROVED FOR ACCREDITATION : VENERANDO D.D. SAHAGUN VENERANDO SAHAGUN A TA SK NES DE TM UC EN T O F ED DEPARTMENT OF EDUCATION (DepED) E F T RECOMMENDING APPROVAL : & LI REVIEWED BY: T t he PH I N of M IC I PP REP UB L CONSULTANT / DESIGNER METERS PRC NO. : TIN : PTR NO. : DATE : CHIEF, ELECTRICAL DIVISION BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) LOCATION : PROJECT NO: 01-002 OWNER : SHEET NO: DEPARTMENT OF EDUCATION DESIGNED BY: RDS DepED ENCODED BY: Max C SHEET CONTENTS : CHECKED BY: DATE : 01 03 NOTE: E-2 3 LIGHTING LAYOUT THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION, ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE. REP. ACT 545 2 a b 2 DN d 2 e 2 f 2 2 2 S b 2 a a 2 b 2 c 2 c 2 d 2 2 d LP 9 e 2 e 2 f 2 f 2 Sabc DN S a c 2 2 f 2 2 LP 8 S def 1 : 100 SCALE : METERS DN DN LP 3 SCALE : 1 : 100 REPUBLIC OF THE PHILIPPINES N ITO R I NG MCMXCIX EE ENGINEER III MO IO IN G T EN R A F O RC E PA TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING RI N G , A S SE S S ME THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT CONCURRED : PROJECT TITLE : FE M. BARRIENTOS SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI OIC, DIRECTOR III BUREAU OF DESIGN, DPWH OIC, DIRECTOR IV BUREAU OF DESIGN, DPWH UNDERSECRETARY N MERALCO AVENUE, PASIG CITY FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE OF THE SAME DUE TO FAULTY DESIGN. APPROVED FOR ACCREDITATION : VENERANDO D. SAHAGUN A TA SK NES DE TM UC EN T O F ED DEPARTMENT OF EDUCATION (DepED) E F T RECOMMENDING APPROVAL : & LI REVIEWED BY: T t he PH I N of M IC I PP REP UB L CONSULTANT / DESIGNER METERS PRC NO. : TIN : PTR NO. : DATE : CHIEF, ELECTRICAL DIVISION BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) LOCATION : PROJECT NO: 01-002 OWNER : SHEET NO: DEPARTMENT OF EDUCATION DESIGNED BY: RDS DepED ENCODED BY: Max C SHEET CONTENTS : CHECKED BY: DATE : 01 03 NOTE: POWER LAYOUT E-3 3 THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION, ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE. REP. ACT 545 CLASSROOM DN CLASSROOM CLASSROOM DN UP UP 1 : 100 SCALE : METERS URINAL UD SD CLASSROOM CLASSROOM CLASSROOM SINK COUNTER SINK COUNTER UP STO. UP RAMP UP RAMP UP 1 : 100 SCALE : REPUBLIC OF THE PHILIPPINES N ITO R I NG ELECTRICAL ENGINEER ENGINEER III MO IO IN G T EN R A F O RC E PA TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING MCMXCIX EE RI N G , A S SE S S ME THE REVIEW & APPROVAL OF THIS PLANS BY THE DPWH DOES NOT RELIEVE THE DESIGNER/CONSULTANT CONCURRED : PROJECT TITLE : FE M. BARRIENTOS SOFIA T. SANTIAGO GILBERTO S. REYES RAMON C. BACANI OIC, DIRECTOR III BUREAU OF DESIGN, DPWH OIC, DIRECTOR IV BUREAU OF DESIGN, DPWH UNDERSECRETARY N MERALCO AVENUE, PASIG CITY FROM RESPONSIBILTY FOR THE SAFETY OF THE COMPLETED FACILITIES AS WELL AS FOR THE FAILURE OF THE SAME DUE TO FAULTY DESIGN. APPROVED FOR ACCREDITATION : VENERANDO D. D. SAHAGUN VENERANDO SAHAGUN A TA SK NES DE TM UC EN T O F ED DEPARTMENT OF EDUCATION (DepED) E F T RECOMMENDING APPROVAL : & LI REVIEWED BY: T t he PH I N of M IC I PP REP UB L CONSULTANT / DESIGNER METERS PRC NO. : TIN : PTR NO. : DATE : CHIEF, ELECTRICAL DIVISION BUREAU OF DESIGN, DPWH DEPATMENT OF EDUCATION (DepED) LOCATION : PROJECT NO: PROJECT NO: 01-002 01-002 OWNER : SHEET NO: DEPARTMENT OF EDUCATION DESIGNED BY: BY: RDS RDS DESIGNED DepED ENCODED BY: Max RDS C SHEET CONTENTS : CHECKED BY: DATE ::6-23-0301 03 DATE NOTE: POWER LAYOUT E-3 3 THIS DRAWING, AS AN INSTRUMENT OF SERVICE IS THE PROPERTY OF TASK FORCE ENGINEERING, ASSESSMENT AND MONITORING AND AS SUCH MUST NOT BE REPRODUCED OR COPIED IN PART OR IN WHOLE WITHOUT THEIR PERMISSION, ALL DRAWINGS ARE TO BE RETURNED WHEN NO LONGER IN USE. REP. ACT 545