TRANSFORMERS Transformer Tests The transformer tests are performed to determine the circuit constants, efficiency and voltage regulation We distinguish between two typical tests: - Open Circuit Test (O.C test / No load test) - Short Circuit Test (S.C test/Impedance test) These tests are economical and convenient These tests furnish the result without actually loading the transformer CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 2 Open-circuit test secondary winding(usually the high voltage side) is open-circuited, and its primary winding is connected to a full-rated line voltage at rated frequency. A voltmeter V, an ammeter A and a wattmeter W are connected in the low voltage (LV) side Since the secondary is open circuited, a very small current I0 (usually 2 to 5% of rated current) called noload current, flows in the primary. CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 3 Open-circuit test Power loss in the transformer is due to core loss and negligible copper loss, I2R in the primary winding There is no I2R loss in the secondary since it is open and Is = 0. The readings of the instruments are as follows: Ammeter reading = no-load current I0 Voltmeter reading = primary rated voltage Vs Wattmeter reading = iron or core loss Pi From these measured values components of the no-load equivalent circuit can be determined as follows: CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 4 Open-circuit test (b) No-load power factor (a) Core loss (c) Active component of I0 (e) Core loss resistance R0 (d) Reactive component of I0 (f) Magnetising reactance X0 CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 5 Short-circuit Test secondary terminals (usually the low voltage side) are short circuited by a thick conductor or through an ammeter. An ammeter, a voltmeter and a wattmeter are connected on the high-voltage side. The input voltage is gradually adjusted until full load flows. CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 6 Short-circuit Test The readings of the instruments in the short-circuit test are as follows: Ammeter reading = full-load primary current,Isc Voltmeter reading = short circuit voltage,Vsc Wattmeter reading = full-load copper losses, Pcfl The output voltage Vs is zero because of the short circuit. Consequently, the whole primary voltage is used to supply the voltage drop in the total impedance Z1e referred to the CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 7 Short-circuit Test If cosΦsc = power factor at short circuit then: Pc = V1scI1sccosΦsc Psc I sc2 Re Equivalent resistance referred to the primary: Psc Re 2 I sc Vsc Ze I sc :Equivalent impedance referred to the primary Equivalent reactance referred to the primary: X e Z e2 Re2 Re cossc Ze CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 8 Transformer Ratings Transformers are rated to supply a given output in Volt Amps or VA at a specified frequency and terminal voltage. They are NOT RATED in Watts because CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 9 Transformer losses The transformer losses are classified into electrical losses (copper losses) and Magnetic losses (Iron losses). Copper losses occur in both the primary and secondary windings. Pcu I R1 I R2 2 1 2 2 Magnetic losses are divided into eddy current losses and hysteresis losses. Pcore Peddy Physterises CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 10 Copper losses (Pcu) Varies with load current, Pcu=I2R Produces HEAT. Created by resistance of windings. Short Circuit Test supplies copper losses. CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 11 Cu Losses (W) Copper Losses 150 140 130 120 110 100 90 80 70 60 50 40 30 20 10 0 0 10 20 30 40 50 60 70 80 90 100 110 % Load CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 12 Core loss or iron loss They are independent of the load i.e. remain constant with loading of the transformer. Produces HEAT. They are determined by Open Circuit Test. Eddy current loss is minimised by using laminations. Hysteresis loss minimised by using silicon steel. CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 13 Transformer efficiency Power In Some Power is used to: Power Out Overcome Copper Losses Overcome Iron Losses CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 14 Efficiency Ratio between Input power and Output Power η Output Power Input Power Input Output Losses Output Power η Output Power Losses Input Power Losses η Input Power CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 15 Efficiency Efficiency is normally expressed as a percentage: Output Power η% 100 Input Power VS I S cos x100% PCu Pcore VS I S cos CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 16 Behavior of magnetic losses and efficiency with loading 1.4 Losses (W) 1.2 1.0 η% Cu Losses Fe Losses 97.00 0.8 0.6 η% 0.4 0.2 0.0 96.00 0 10 20 30 40 50 60 70 80 90 100 110 % Load Fe = Cu =Max η CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 17 Condition for maximum efficiency It is observed that the efficiency is low at small loads and reaches a maximum value for a certain load. The efficiency then decreases as the load is increased. The efficiency of the transformer for a given power factor is always maximum when the variable copper loss is equal to the constant iron(core) loss: PFe = PCu =Max η CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 18 All Day Efficiency The primary of a distribution transformer is connected to the line for 24 hours a day. Thus the core losses occur for the whole day whereas copper losses occur only when the transformer is on load. Distribution transformers operate well below the rated power output for most of the time. Performance of the distribution transformer is more appropriately represented by all day efficiency. The all-day efficiency of a transformer is defined as the ratio of total energy output for a certain period to the total energy input for the same period. CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 19 All day efficiency The energy efficiency can be calculated for a specified period. When the energy efficiency is calculated for a 24 hours it is called the all-day efficiency. out put in watts Ordinary commercial efficiency input in watts output in kWh All day efficiency :all day ( for 24 hours) Input in kWh All day efficiency is always less than the commercial efficiency CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 20 Autotransformer CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 21 Autotransformer Sometimes it is desirable to change voltage level only by a small amount. This may be due to small increase in voltage drop that occur in a power system with long lines. In such cases it is very expensive to hire a two full winding transformer, however a special transformer called: ”auto-transformer” can be used. Auto transformers are a special type, since they have no electrical isolation between the primary and secondary windings. CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 22 Autotransformer The voltage across the common winding is called the common voltage VC, and the current through this coil is called the common current IC. The voltage across the series winding is called a series voltage VSE, and the current through that coil is called a series current ISE. -The A Series winding following can be B deduced for an Common Autotransformer: winding C Circuit diagram of Autotransformer CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 23 Types of Autotransformers CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 24 Types of Autotransformers If the output from the auto transformer can be varied via a moveable tapping, as shown below, it is also known as a variac (variable ac supply) CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 25 Autotransformers CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 26 Advantages of autotransformer Uses less winding material than two winding transformer. Smaller in size and cheaper than two winding transformer of the same output. Has higher efficiency. Has better voltage regulation. Can deliver variable voltage, if a sliding contact is used. CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 27 Disadvantages of autotransformer There is no electrical isolation between the high-voltage and low-voltage sides. In case of open circuit in the common winding, the full primary voltage would be applied on the secondary side. This high voltage would damage equipment connected to the secondary. Effective impedance of a autotransformer is smaller compared to two winding transformer. The reduced internal CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 28 Application of auto-transformer Interconnection of power systems of different voltages Boosting of supply voltage by a small amount in distribution systems to compensate the for voltage drop. For starting induction and synchronous motors , if equipped with a number of tappings. Used as a VARIAC (variable a.c.) in laboratory. CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 29~aq Three phase Transformers CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 30 Construction The majority of the power generation/distribution systems in the world are 3phase systems. The transformers for such circuits can be constructed either as a 3-phase bank of independent identical transformers (can be replaced independently) or as a single transformer wound on a single 3-legged core (lighter, cheaper, more efficient). Three -phase transformer bank Three phase transformer wound on single 3 legged core Three-phase transformer cores CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 32 Three-Phase Transformers C D E B F F A Three-phase transformer. CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 33 Primary and Secondary Connections The primary (input) side of a three-phase transformer can be connected in a wye or delta configuration. The secondary (output) side of a three-phase transformer can also be connected in a wye or delta configuration. CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 34 Primary and Secondary Connections This allows four basic connection patterns: Wye-Wye Delta-Delta Wye-Delta Delta-Wye CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 35 Wye-wye connection Wye – wye (Y – Y) CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 36 Wye-delta connection Wye-delta three-phase connection schematic. CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 37 Delta-wye connection Delta-wye three-phase connection schematic. CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 38 Delta-delta connection Delta – delta (Δ – Δ) CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 39 Winding identification Winding identification. CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 40 Special transformers Two types of special purpose transformers used in power systems for taking measurements. – Potential Transformer – Current Transformer CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 41 Standard symbols for instrument transformers. The standard secondary values for full-scale meter readings are also shown CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 42 Instrument transformers (a) Voltage transformer (b) Current transformer CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 43 APPLICATION OF TRANSFORMERS CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 44 Electrical Power System CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 45 Distribution transformers Single phase transformer Three phase transformer CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 46 Step up Transformer Step up transformer at power plant CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 47 END OF TOPIC!! CHINHOYI UNIVERSITY OF TECHNOLOGY ELECTRICAL MACHINES CUAE 211 48