Housing Accessibility Regulation In Canada Prepared for: Canadian Home Builders’ Association By: Rowena Moyes June, 2011 Table of Contents Executive Summary ........................................................................................................................ 3 Accessibility Requirements for Housing in Canada ....................................................................... 1 Introduction ................................................................................................................................. 1 Background ................................................................................................................................. 1 Codes are only one part of the answer ........................................................................................ 3 Provincial status in brief ............................................................................................................. 4 Requirements in the National Building Code, 2010 ....................................................................... 6 Recognized Goal ......................................................................................................................... 6 Requirements in Part Nine .......................................................................................................... 6 Requirements in Part Three – Section 3.8 .................................................................................. 7 Design Assumption ................................................................................................................. 7 Occupancies affected by Section 3.8 ...................................................................................... 7 Requirement for Washroom Doors ......................................................................................... 8 Requirement for Barrier-Free Path of Travel.......................................................................... 8 Requirements and exemptions affecting accessing the building and travelling to the units .. 9 Requirements and exemptions affecting designated units themselves ................................. 13 Comparison with Provincial Requirements for Residential Suites: .............................................. 17 BRITISH COLUMBIA ......................................................................................................... 17 ALBERTA ............................................................................................................................ 20 SASKATCHEWAN ............................................................................................................. 24 MANITOBA ......................................................................................................................... 26 ONTARIO............................................................................................................................. 30 QUEBEC............................................................................................................................... 33 NEW BRUNSWICK ............................................................................................................ 34 NOVA SCOTIA.................................................................................................................... 35 PRINCE EDWARD ISLAND .............................................................................................. 40 NEWFOUNDLAND............................................................................................................. 41 Executive Summary 1. Building codes currently do not require barrier-free/accessibility for all residential units. The national model building code (NBC) has been amended over the years to include requirements for a barrier-free path of travel and access to services/facilities; this has concentrated primarily on “public” areas, services and workplaces. Private residences have generally been exempted from the requirements, including all single-detached, semi-detached, duplex, triplex, row and town houses up to three storeys in building height. At least one entrance and public areas of apartment buildings on floors served by an elevator have generally been required to be accessible, while the units themselves were not. The NBC includes requirements for at least one washroom doorway in suites of residential occupancy to allow passage of a manual wheelchair. The NBC contains requirements for residential units which apply where units have been designated by an authority having jurisdiction to be barrier-free units. Several provinces already require that a percentage of units in apartment buildings be constructed as barrier-free or accessible units, and have included specific requirements in their codes or interpretations for the units themselves. i. In some cases, this only applies to government-funded units. For example, in Alberta a percentage of all government-funded housing units must be barrier-free (details provided in a Standata interpretation document); projects funded under Manitoba’s Affordable Housing Initiative must also provide accessible units. ii. In others, it applies as well to privately funded units. In Ontario 10% of all apartment units must meet accessibility requirements in the province’s building code; in Nova Scotia one in 20 of all multi-family units must meet Nova Scotia code accessibility requirements; in Saskatchewan, it is 5 %; and in Newfoundland all apartment buildings with more than 15 units must provide barrier-free access to all floors and meet provincial accessibility standards. Several more provinces are in process of introducing similar “number or percentage of apartment units” requirements or widening the scope of current programs aimed at government-funded units only so they include privately funded units as well (Quebec, Manitoba, Alberta, New Brunswick). British Columbia has passed a code section for “adaptable” units in multi-unit buildings, and given municipalities the right to require these standards by passing a bylaw. 2. A few municipalities have begun to pursue accessibility requirements beyond the requirements of provincial codes. (These are sometimes referred to as adaptability, visitability, aging-in-place or universal design policies.) In a number of provinces municipalities are not prohibited by provincial law from imposing requirements beyond the building code, although scope differs substantially (BC, SK, MB, QC, NB, PE, NF1). Even where they do not have power to require more than the code, municipalities can use their power over rezoning and subdivision approval to negotiate “voluntary” agreements on design elements for accessibility. Municipalities can use zoning to encourage accessible housing – creating zones where projects that meet certain accessibility requirements may be allowed to build more storeys, smaller units, fewer parking spaces, etc. 3. Discussions are under way or anticipated in some provinces to encompass additional residential units and housing types. Manitoba and Nova Scotia code representatives say they expect to be discussing some form of accessibility requirements that would apply to more units, including those small low rise housing types currently exempted from barrier-free requirements, within the next two years. Alberta building code branch staff is currently reviewing code change requests which may result in proposed Alberta-specific changes later this year or in 2012; if not, they expect a form of adaptability or visitability to be discussed for the next round of changes. In 2010, the Ontario Ministry of Community and Social Services’ advisory Accessible Built Environment standard development committee proposed wideranging changes to requirements affecting the built environment from roads and transit to buildings. The provincial government has deferred these from the 20102011 round of code change discussions, but identified accessibility as an area for future research. 4. Renovations could be affected. The impact on renovation projects appears mixed. It depends on the wording of the provincial code and how the province designates units required to be accessible/adaptable/barrier-free. In general, major rebuilding and additions would probably be captured in current requirements. In provinces with specific accommodation in their codes for renovation, impacts could be muted. 5. More study is required. For example, as mentioned above, the Ontario provincial government has deferred consideration of wide ranging additional code requirements for accessibility in this round of code changes, in order to research them further. The Ministries of Municipal Affairs and Housing and Community and Social Services have said that they want to make sure that any requirements that become law are clear, consistent, enforceable and build on current accessibility requirements. 1 However, in Newfoundland, designation of and requirements for barrier-free apartments is handled differently. It is not imposed through a building code, but by the province under a separate provincial statute. Accessibility Requirements for Housing in Canada Introduction This paper contains a survey of current/proposed requirements and policy directions in the national and provincial building codes, with regard to scope and requirements for accessibility in residential buildings. It focuses primarily on current or proposed moves to include in-suite requirements for “adaptability” or “visitability” in apartments in private market multi-unit buildings. Definition of “Small Housing” The National Building Code specifically exempts detached houses, semi-detached houses, houses with a secondary suite, duplexes, triplexes, townhouses, row houses and boarding houses from requirements in its barrier-free design sections. This exemption is also found in provincial building codes. While the precise definition varies, visitability involves wheelchair This paper uses the term “small housing” to refer to access from the exterior to the main these housing types. living spaces and to a washroom in every new dwelling unit. Adaptability can include design for future adaptation, such as how to provide access from the street and/or to expand a washroom to accommodate a wheel-in shower. The paper also identifies a growing interest in requiring more residential units to be visitable or adaptable, including the small housing types currently exempt. Background It is important to realize that up until the 1960s and 70s, it was taken for granted that disabled persons would generally be housed in some form of institution. Perhaps ‘warehoused’ is a more accurate term. Perceptions of disabilities and disabled persons’ rights and role in society and the workforce have changed significantly since then. This has been aided by some significant medical and technological advances in mobility devices, communications, etc. 1. Design guidelines in the 1960s In the 1960s, a number of bodies were working on ways to increase accessibility for people in wheelchairs or other restrictions on their strength/mobility to buildings and spaces open to the public. In 1965, for example, the National Research Council published a Supplement to the National Building Code titled Building Standards for the Handicapped. It contained guidelines (not model regulations) for incorporating provisions for the physically handicapped into the design and construction of “buildings used by the public”, including facility planning, site development, and building equipment, plus specifications for such things as toilets, utilities, ramps, stairs, parking and storage. 1 2. National Building Code section published in 1985 Requirements from the Supplement relating specifically to buildings were incorporated into the 1985 edition of the National Building Code (NBC) as model regulations. As well as a new section 3.7 on Barrier-Free Design2, Part Three of the 1985 NBC was also amended to provide protection for the disabled in the event of an emergency. The new requirements affected only Part Three buildings. Generally speaking, that meant buildings used for assembly, and institutional occupancies, as well as buildings larger than 600 sq m in building area or three storeys in building height used for residential, business, retail, and medium- or low-hazard industrial occupancies. While apartment buildings were required to provide accessible entrances, corridors, etc., individual residential suites were exempted from many of the requirements, except where a province or territory specified that certain units must be accessible. Houses, including detached, semi-detached, duplexes, triplexes, town houses, row houses and boarding houses, were – and still are – specifically exempted. There were no equivalent accessibility requirements in Part Nine for buildings up to 600 sq m in area and three storeys in height. 3. Provincial/Territorial building codes began in the 1980s Provinces and territories (and some municipalities) have jurisdiction over building regulation in Canada. However, for a long time, provinces and territories allowed municipalities to create their own building requirements. The country’s National Building Code (NBC)3 was intended as a model for the appropriate jurisdictions to use when they were introducing or upgrading their building requirements. Even with a national model code, leaving regulation to municipalities resulted in a chaotic situation. So, the first provinces introduced their own province-wide building code acts and regulations in the 1980s. Today, most provinces and territories have done so. Some adopt the NBC without amendment, while others make changes and/or additions. All provinces and territories have signed on to the principle of harmonization to the greatest extent possible. In addition to enacting provisions for barrier-free access, many provinces have specified that a certain percentage of multi-family units must be accessible. (See below for more details.) 2 Now renumbered as section 3.8. Preparation of the NBC is overseen by an independent body, Canadian Commission on Building and Fire Codes, with advice from the Provincial/Territorial Policy Advisory Committee on Codes, and staffed by the National Research Council. 3 2 Codes are only one part of the answer It is also important to note that building code requirements are only one element of a series of tools being used to address accessibility for the disabled. Others include: Legislation: anti-discrimination clauses in Canada’s national Charter of Rights and Freedoms which took effect in 1982 (disability was added to the Charter late in the drafting process) anti-discrimination clauses in provincial/territorial human rights legislation the Accessibility for Ontarians with Disabilities Act (2005) and its associated current and proposed standards International Convention: Canada’s signing of the United Nations Convention on the Rights of Persons with Disabilities (March 2007) and recent ratification of same (March 2010).4 Government’s own building programs: construction and renovation programs by federal, provincial and municipal governments and agencies to make their buildings, public spaces and services accessible Incentives and government funding program conditions: subsidies and incentives from federal, provincial or municipal governments for accessible buildings and/or units Canada Mortgage and Housing Corporation (CMHC) mortgage insurance for multiunit housing, which requires a percentage of units to be accessible 4 Article 9 of that convention deals with accessibility, stating: 1. To enable persons with disabilities to live independently and participate fully in all aspects of life, States Parties shall take appropriate measures to ensure to persons with disabilities access, on an equal basis with others, to the physical environment, to transportation, to information and communications, including information and communications technologies and systems, and to other facilities and services open or provided to the public, both in urban and in rural areas. These measures, which shall include the identification and elimination of obstacles and barriers to accessibility, shall apply to, inter alia: a) Buildings, roads, transportation and other indoor and outdoor facilities, including schools, housing, medical facilities and workplaces; b) Information, communications and other services, including electronic services and emergency services. 2. States Parties shall also take appropriate measures: a) To develop, promulgate and monitor the implementation of minimum standards and guidelines for the accessibility of facilities and services open or provided to the public; b) To ensure that private entities that offer facilities and services which are open or provided to the public take into account all aspects of accessibility for persons with disabilities; ... (plus 6 more subsections not specifically related to buildings) 3 Research and information: research into products, design, etc. by the National Research Council and others participation in development of voluntary standards such as the Canadian Standards Association’s B651-04 Accessible Design for the Built Environment Demonstration projects: development and demonstration of various housing options such as Flex-Housing by CMHC and others Private market initiatives and experience: experience from builders’ and developers’ projects mostly designed for specific individuals or niche markets and housing sectors such as seniors’ buildings and retirement communities Approval powers: requirement of specific design features by municipalities through rezoning process/development agreements This list is not exhaustive. These other tools have their own scope and goals, and their own strengths and weaknesses. Full discussion of them is beyond the scope of this paper. Provincial status in brief British Columbia British Columbia’s code was amended in 2009 to set out requirements which local governments must use if they decide to pass a bylaw requiring adaptable apartment units. A number have done so, usually by specifying a percentage of units, whether government funded or not. The province has no plans at this time for further accessibility-related changes to the code. Alberta Currently Alberta uses NBC accessibility requirements, but expands 3.8.1.1(3) to require a specified number (generally equivalent to 10 and 20%) of units in new government-funded residential projects to be ‘adaptable’. Specific requirements for adaptable units are contained in a STANDATA. Alberta Municipal Affairs staff have received requests from the public for increased accessibility, such as visitability, to be included in proposals for Alberta-specific code changes for the Alberta Building Code, 2012. The Building Technical Council has reviewed the recommendations and the province is expected to release its document on proposed Albertaspecific code changes for public comment late this year or in 2012. Saskatchewan The Saskatchewan building code requires 5% of units in new rental buildings to be barrier-free. Requirements cover accessible washrooms, space in bedrooms and kitchens, finishes in kitchens, and barrier-free balconies. No changes are expected at this time. 4 Manitoba Manitoba published changes to its building code, including new requirements for accessibility/universal design for Part Three multi-unit residential buildings, in March 2011. Most come into effect as of January 1, 2012. The province is also working on Made-in-Manitoba Accessibility Legislation, similar to that introduced in Ontario. That is expected to produce wideranging standards and regulations for removing various types of barriers experienced by seniors and people with disabilities. Ontario The current Code requires 10% of units in new multi-unit buildings to have an internal barrierfree path of travel, which triggers other requirements for doors sizes and washrooms. Under the Accessibility for Ontarians with Disabilities Act, 2005 (AODA), the Ministry of Community and Social Services has been coordinating efforts to produce wide ranging plans and standards to achieve an “accessible Ontario” by 2025. In 2010, an Advisory group proposed standards under AODA for the built environment, including many on- and off-site elements affecting multi-unit residential. Ministries of Community and Social Services (disabilities directorate) and Municipal Affairs and Housing (building code) are doing further analysis of the proposals, and research to make sure that any future requirements they may adopt are clear, consistent, enforceable and build on current accessibility requirements. Requirements for small housing may be considered later. Quebec Proposals for adaptability in multi-unit buildings are expected to be submitted to the Advisory Council of the Regie du batiment du Quebec in August 2011 for approval to proceed. If granted, proposed code changes are expected to be released for public comment in late 2011 or 2012. New Brunswick Officials with the Department of Public Safety have engaged stakeholder groups through an advisory committee. The mandate of this committee is to make recommendations for enhancing the barrier-free requirements in Section 3.8 of the National Building Code. Nova Scotia Nova Scotia has fairly extensive requirements for 5% accessible units in all multi-family buildings. The expectation is that they will be discussing visitability for all housing types within two years. Prince Edward Island There is no province-wide building code in PEI. Three municipalities have adopted the NBC: Summerside and Stratford have added a requirement that one in every 12 units in new apartment buildings be barrier free as defined in Section 3.8 of the NBC; Charlottetown has similar proposals before Council. Newfoundland A Buildings Accessibility Act requires at least one accessible unit in all apartment-type buildings and barrier-free access to all floors in those with more than 15 units. Regulations are similar to the NBC but in a somewhat different format and with changes. They were last amended in 2006 and staff do not expect significant imminent changes. 5 Requirements in the National Building Code, 2010 At this point, the NBC requirements in Section 3.8 represent the base for requirements across the country. Recognized Goal Accessibility is one of the four Objectives which were defined for the NBC when it moved to an objective-based format in 20055. Today, the NBC sets out what that means in two sub-objectives, as follows: An objective of this Code is to limit the probability that, as a result of the design or construction of the building, a person with a physical or sensory limitation will be unacceptably impeded from: accessing the building or circulating within it (OA1 Barrier-Free Path of Travel using the building’s facilities (OA2 Barrier-Free Facilities) 2.1.1.2 Application of Objectives 5) Objective OA, Accessibility (and its sub-objectives), does not apply to a) detached houses, semi-detached houses, houses with a secondary suite, duplexes, triplexes, townhouses, row houses and boarding houses, b) buildings of Group F, Division 1 major occupancy*, and c) buildings that are not intended to be occupied on a daily or full-time basis, including automatic telephone exchanges, pumphouses and substations. As noted in the box above, there is a clear exemption from the accessibility objective for single family housing and small multiples. * (high hazard industrial) Requirements in Part Nine Part Nine of the NBC applies to smaller buildings (up to 600 m2 in building area or three storeys in building height6) used for residential, business and personal services, mercantile or mediumand low-hazard industrial occupancies. The main requirements for accessibility in Part Nine buildings are found in Section 9.5.2 Barrier-Free Design. This section contains only three subsections: 5 The others are Safety, Health, and Fire and Structural Protection of Buildings 6 Buildings divided by a firewall may be considered separate buildings in determining the 600 m2 area. Residential buildings divided by a 1 hr. fire separation extending through all storeys and service spaces may also be considered separate buildings, as long as each separated portion is no more than three storeys. Part A, 1.3.3.4 6 9.5.2(1) says every building except those exempted by 3.8.1.1 (which includes the exemption for single family housing and small multiples as described in the box above) or amended by 9.5.2(3) shall be designed in accordance with Section 3.8. 9.5.2(2) says that every floor area above or below the first storey which is required to have a barrier-free path of travel and is not sprinklered throughout must provide the fire protection found in 3.3.1.7. This includes one of a firefighter elevator, fire-separated zones, balconies providing temporary refuge for persons with disabilities (for residential occupancies), an exterior exit at ground level or a ramp leading to ground level. 9.5.2(3) provides a specific exemption, saying small apartment buildings that don’t have elevators only need to provide a barrier-free path of travel on the entrance storey, and even that is not required if there is more than 600 mm difference in floor elevation between the entrance level and every dwelling unit. Another important requirement is found in 9.5.5.3, which says that where one or more washrooms (containing a bathtub, shower or water closet) is served by a hallway at least 860 mm wide7, the doorway to at least one must be wide enough to accommodate a 760 mm door and provide access to each of those fixtures. This is outside the barrier-free section, and appears to apply to all housing. Requirements in Part Three – Section 3.8 Design Assumption For Section 3.8 Barrier-Free Design, where most of the requirements for accessibility are found, Appendix A adds a statement about the level of physical/mobility disability addressed. “Design Assumption: This Section contains minimum provisions to accommodate a person using a typical manual wheelchair or other manual mobility assistance devices such as walking aids, including canes, crutches, braces and artificial limbs.” Occupancies affected by Section 3.8 Except as exempted from the overall Accessibility Objective (see 3.8.1.1., below) or amended by Part 9.5.2 (as described above), some or all of the requirements in Section 3.8 apply to all buildings used for assembly, care, treatment, and detention occupancies, and larger residential, business and personal services, mercantile or medium- and low-hazard industrial occupancies. Section 3.8 Exemption for houses (and other): As with the overriding Objective, Section 3.8 includes this exemption for single family housing and small multiples: 7 Narrower hallways (minimum 710 mm) are permitted for hallways only serving bedrooms and bathrooms, but there must be a second exit at the end of the hall or from each bedroom. In that case, washroom doors are only required to be 610 mm wide. 7 3.8.1.1 The requirements of this Section apply to all buildings except a) detached houses, semi-detached houses, houses with a secondary suite8, duplexes, triplexes, townhouses, row houses and boarding houses ... Requirement for Washroom Doors Since the 1985 edition, sentence 3.8.3.3(2) of the NBC has required the door to at least one washroom within a suite of residential occupancy to which Part Three applies to be wide enough to provide access for a manual wheelchair. This is defined as a clear width of 800 mm when the doors are in the open position. It is roughly parallel to the requirement in Part Nine, above, although as it is within section 3.8 on Barrier-Free Design, the exemption in 3.8.1.1. (above) means it doesn’t apply to larger detached houses, etc. Requirement for Barrier-Free Path of Travel Most of the specific requirements for accessibility are triggered by being part of, or within an area requiring, a barrier-free path of travel. It can be helpful to think of this as at least one route through all floor areas normally accessible to the public, allowing persons with physical and sensory disabilities to access the building, circulate within it or use its facilities. This affects entrances, lobbies, service areas, work places, elevators, corridors, public washrooms, access to parking, etc. 3.8.2.1 Exemptions from wheelchair accessibility The NBC contains a number of exemptions where a barrier-free path of travel for people in wheelchairs is not required.9 These exemptions include spaces which are not normally public, such as service rooms, elevator machine rooms, janitor’s rooms, service spaces, crawl spaces, attic or roof spaces, high hazard industrial occupancies, and: a) Exemptions affecting floors and floor levels A barrier-free path of travel for people in wheelchairs is not required (for a number of spaces, including): 3.8.2.1(2)g to floor levels not served by a passenger elevator, a platform-equipped passenger-elevating device, an escalator, or an inclined moving walk 3.8.2.1(2)l within those parts of a floor area that are not at the same level as the entry level, provided amenities and uses provided on any raised or sunken level are accessible on the entry level by means of a barrier-free path of travel b) General exemption for all residential units not designated accessible 8 The exemption for secondary suites was added in the 2010 Code, as part of a package of code changes to allow these uses. 9 Requirements intended to help those with non-wheelchair disabilities, affecting vision, hearing, etc, would still apply. 8 A barrier-free path of travel for people in wheelchairs also is not required: 3.8.2.1(2)k within a suite of residential occupancy that has not been designated by an authority having jurisdiction10 to be accessible for use by persons with physical disabilities (emphasis added) The effect of these is that multi-family projects with elevators must meet requirements for an accessible path from the sidewalk to at least one main accessible entrance, through the vestibule and lobby, including ramps, doors, public washrooms, etc., to all other floors served by an elevator including those with recreation facilities, laundry, accessible parking, etc., and along corridors to the residential units. The units themselves are not required to meet accessibility requirements in 3.8 unless they have been designated. Multi-family projects without elevators only need to provide access into and through the entrance floor. If they come within the scope of Part Nine, they do not have to make the entrance floor accessible if all dwelling unit entrances are at least 600 mm above or below the entrance level. Again, the units themselves are not required to meet accessibility requirements in 3.8 unless they have been designated. Requirements and exemptions affecting accessing the building and travelling to the units Element Entrances Barrier-free path of travel 10 Requirements Not less than 50% of the pedestrian entrances must be barrier free and lead from the outdoors at sidewalk level or by a ramp from a sidewalk Doors must comply with requirements in 3.8.3.3 Generally, must be not less than 920 mm wide, except that the minimum clear width permitted for open doorways is “not less than 800 mm” Exterior walks must be not less than 1 100 mm wide have a slip resistant, continuous and even surface have a level area next to an entrance doorway conforming to 3.8.4(1)(c) NBC reference 3.8.1.2 3.8.3.3 3.8.1.3.(1) exception in 3.8.3.3 3.8.2.3 a province/territory or a municipality which has been given jurisdiction 9 Element Requirements NBC reference If a barrier-free path of travel is more than 30 m long, it must contain passing areas 1 500 mm wide by 1 500 mm long at intervals no more than 30 m Walking surfaces must: not have any openings that a ball more than 13 mm in diameter could go through only have elongated openings that are approximately perpendicular to the direction of travel be stable, firm and slip resistant be bevelled at a maximum slope of 1 in 2 at changes in level not more than 13 mm and have sloped floors or ramps at changes in level more than 13 mm A barrier-free path of travel may include ramps, elevators or similar If an escalator or inclined moving walk provides access from the entrance level to another floor, there must also be an interior barrier-free access (ramp, elevator, passenger lift), with appropriate signage 10 Element Fire protection Ramps in barrier-free path of travel – Requirements every storey above or below the first storey that is not sprinklered throughout and has a barrier-free path of travel must have one of the following: a) a firefighter elevator b) fire separations dividing the floor area into at least two zones so that persons with disabilities can be accommodated in each one, and can travel to the other safely c) (residential) have balconies conforming to Sentence (5), except on the storey containing the required barrier-free entrance d) have an exterior exit at ground level, or e) have a ramp leading to ground level NBC reference 3.3.1.7.(1) Sentence 5 calls for balconies to have direct barrier-free access, space 1.5 m minimum in depth, and a minimum of 1.5 m2 for each non-ambulatory occupant Floors or walks in a barrier-free path of travel having a slope steeper than 1 in 20 shall be designed as ramps clear width of not less than 870 mm slope of not more than 1 in 12 level area of not less than 1 500 mm by 1 500 mm at the top and bottom and at intermediate levels of a ramp leading to a door, so that on the latch side the level area extends not less than a) 600 mm beyond the edge of the door opening if the door swings towards the approach side b) 300 mm if the door swings away from the approach side level area not less than 1 200 mm long and at least the same width as the ramp, at intervals not more than 9 m along its length, and where there is an abrupt change of direction 3.3.1.7.(5) 11 3.8.4.(3) 3.8.4.(1)(a) 3.8.4.(1)(b) 3.8.4.(1)(c) 3.8.4.(1)(d) Element Requirements Parking Public washrooms Doorways and Doors located in a barrier-free path of travel (active leaf only) handrails and guards meeting 3.4.6.5 and 3.4.6.6 barrier-free path of travel from exterior parking (if provided) to barrier-free entrance, and/or (if served by an elevator) from at least one level of indoor parking to all parts of the building required to be accessible (also specific requirements for exterior passenger loading zone) Only applies to residential projects if there is a public washroom (e.g., in pool or gym areas) minimum clear width in the open position is 800 mm threshold no more than 13 mm higher than the finished floor, and bevelled (except at the entrance to a dwelling unit) door closer works with force of a) 38 N for exterior door b) 22 N for interior door and has a closing period of not less than 3 seconds unless equipped with a power door operator, there must be a clear space on the latch side the same height as the doorway and extending a) 600 mm beyond the edge of the door opening if the door swings towards the approach side b) 300 mm if the door swings away from the approach side a vestibule located in a barrier free path of travel shall ... provide a distance between doors in series of not less than 1 200 mm plus the width of any door that swings into the space of travel 12 NBC reference 3.8.4.(1)(e) 3.8.2.2 See 3.7.2 and 3.8.2.3 3.8.2.2.(1) 3.8.3.3.(4) 3.8.3.(7) 3.8.3.(9) 3.8.3.(10) 3.8.3.3.(11) Element Elevators, etc. Controls in a barrier-free path of travel Requirements level floor area on each side of a door in a barrier-free path of travel that is as wide as the door plus the clearance on the latch side in 3.8.3.3.(10) dimension perpendicular to the door of not less than the barrier-free path or travel (but need not be more than 1 500 mm) A passenger elevating device in 3.8.2.1 shall conform to CAN/CSA-B355, “Lifts for Persons with Physical Disabilities” 3.8.1.5 applies, except that controls for an elevator must be accessible to a person in a wheelchair – i.e., 400 – 1200 mm above the floor NBC reference 3.8.3.3.(13) 3.8.3.5 3.8.1.5 Requirements and exemptions affecting designated units themselves Even where residential units are designated as accessible, the NBC provides some exemptions from other requirements. For example: 3.8.2.1.(2)(j) (A barrier-free path of travel for people in wheelchairs is not required ...) within floor levels of a suite of residential occupancy that are not at the same level as the entry level to the suite 3.8.2.3.(2) A washroom need not (meet the barrier-free requirements in 3.8.3.8 to 3.8.3.12) provided: a) it is located within a suite of residential occupancy ... (If such a bathroom contains a bathtub, however, it will have to meet the space requirements for universal bathrooms in 3.8.3.12) The following chart lists some of the key requirements for residential suites which have been designated to be accessible for persons with disabilities. 13 Element Doors to dwelling units (located in a barrier-free path of travel) Barrier-free path of travel: Ramps in barrier-free path of travel Washrooms Requirements minimum clear width in the open position of 800 mm NBC reference 3.8.2.2.(1) threshold no more than 13 mm higher than the finished floor, and bevelled unless equipped with a power door operator, there must be a clear space on the latch side the same height as the doorway and extending c) 600 mm beyond the edge of the door opening if the door swings towards the approach side d) 300 mm if the door swings away from the approach side vestibule located in a barrier free path of travel shall ... provide a distance between doors in series of not less than 1 200 mm plus the width of any door that swings into the space of travel rectangular level floor area on each side of a door in a barrier-free path of travel that is as wide as the door plus the clearance on the latch side in 3.8.3.3(10) dimension perpendicular to the door of not less than the barrier-free path or travel (but need not be more than 1 500 mm) Generally, must be not less than 920 mm wide, except that the minimum clear width permitted for open doorways is “not less than 800 mm” A barrier-free path of travel may include ramps, elevators or similar See requirements in 3.8.4 3.8.3.3.(4) Not required to meet 3.8.3.8 to 3.8.3.12 if within a suite of residential occupancy 3.8.2.3.(2) See 3.7.2 14 3.8.3.3.(10) 3.8.3.3.(11) 3.8.3.3.(13) 3.8.1.3.(1) exception in 3.8.3.3 Element Accessible shower, lavatory and water closet Bathtubs Universal Toilet Rooms Grab bars Requirements Doorways in a path of travel to at least one bathroom within a suite of residential occupancy shall have a clear width of at least 800 mm when the doors are open Including requirements for dimensions, clearances, grab bars. (Would apply to “accessible apartment suites” unless alternate standards are specified) Where a bathtub is provided in a suite of residential occupancy required to be barrier-free, it shall be located in a room meeting 3.8.3.12.(1) space requirements (see sections of Universal Toilet Rooms, below) and conform to 3.7.2.9 and be equipped with a hand-held shower head conforming to 3.8.3.13.(1)(h) must ... c) have one lavatory conforming to Article 3.8.3.11., d) have one water closet conforming to the requirements of Article 3.8.3.9. that has a clearance to the walls of i) not less than 285 mm and not more than 305 mm on one side, and ii) not less than 875 mm on the other side, e) have grab bars conforming to Clause 3.8.3.8.(1)(d), f) have no internal dimension between the walls that is less than 1 700 mm, ... h) be designed to permit a wheelchair to back in alongside the water closet in the space referred to in Subclause (d)(ii), and i) be designed to permit a wheelchair to turn in an open space not less than 1 500 mm in diameter Grab bars that are installed shall resist a load not less than 1.3 kN applied vertically or horizontally 15 NBC reference 3.8.3.3.(2) 3.8.3.13 3.8.3.17.(1) 3.8.3.12.(1) 3.7.2.8 Element Counters Elevators, etc. Controls in a barrier-free path of travel Requirements only regulated for counters where the public is served, work areas, etc. A passenger elevating device in 3.8.2.1 shall conform to CAN/CSA-B355, “Lifts for Persons with Physical Disabilities” controls for operation of building services or safety devices must be mounted 400 – 1200 mm above the floor (except elevator controls must meet 3.5.2.1.(3) ) 16 NBC reference 3.8.3.14 3.8.3.5 3.8.1.5 Comparison with Provincial Requirements for Residential Suites: NOTE: The lists here are not exhaustive, and other requirements may apply, especially to common areas. BRITISH COLUMBIA In Brief: British Columbia’s code was amended in 2009 to set out requirements which local governments must use if they decide to pass a bylaw requiring adaptable apartment units. A number have done so, usually by specifying a percentage of units, whether government funded or not. The province has no plans at this time for further accessibility-related changes to the code. Current Code Requirements BC adopts the NBC with province-specific amendments. For accessibility, the government has added a new consolidated subsection 3.8.5 to its code, dealing with Adaptable Dwelling Units, effective December 31, 2009. It applies to single storey units in new multiunit residential buildings. The requirements are not mandatory for all of these units. However, local governments can add a requirement for adaptable housing to their bylaws, with a reference to this section. Because municipalities in BC (except Vancouver) may not require standards in excess of the building code without provincial approval, this section establishes a ceiling for mandatory requirements for adaptable dwellings. On the other hand, municipalities can negotiate conditions on projects requiring subdivision, rezoning, or similar planning approvals. Subsection 3.8.5 of the BCBC requires: Element Building Access: Corridors and passageways Requirement Corridors and passageways providing access to adaptable dwelling unit entrances and common facilities must be not less than 1 200 mm in width and provide a clear areas of 1 500 mm x 1 500 mm adjacent to the elevator entrance and at intervals not exceeding 10 m where it is more than 10 m from the elevator to the end of the corridor 17 Matches NBC? 3.8.1.3.(1) barrier-free path of travel, only requires 920 mm in width matches 3.8.1.3.(4) for clear area, but NBC allows 30 m intervals in a BFPT Element Doorways Adaptable dwelling unit doorways (within unit) Clear space Adaptable dwelling unit bathrooms Grab bar support Adaptable dwelling unit kitchens Outlets, switches and controls Requirement Doorways in the accessible path of travel throughout the building (but not within the suite) must have a clear opening width not less than 850 mm doorways providing access to common living areas and at least one bathroom and one bedroom shall have a clear opening width of not less than 800 mm Floor space on both sides of the bathroom and bedroom doors above shall conform to 3.3.1.13.(10)(b) The accessible bathroom shall be designed to be adaptable for use by persons in wheelchairs by providing: not less than 1 800 mm from the front edge of the toilet to the facing wall not less than 510 mm from the front face of the bathtub or shower to the centre line of the toilet a clear floor area in front of the lavatory not less than 760 mm wide by 1 220 mm deep, centred on the lavatory Walls adjacent to the toilet and bathtub or shower shall accommodate the future installation of conforming grab bars, able to resist a vertical or horizontal load of not less than 1.3 kN Shall be designed so that the range and sink are adjacent or can have continuous counter between them Outlets (electrical, telephone, cable and data) intended for use by the occupants shall be located between 455 and 1 200 mm above the floor Switches and controls intended for occupant use shall be located between 900 mm and 1 200 mm above the floor 18 Matches NBC? NBC 3.8.3.3 equivalent is 800 mm matches 3.8.3.3.(1) size requirements for doorways in a BFPT, which would apply to designated accessible units This is a different approach than found in the NBC No requirement for future grab bars, but 3.7.2.8 has the same requirement for load resistance where they are installed No equivalent requirement Separate requirements for outlets and controls The new subsection 3.8.5 was prompted by municipal action and interest, and allows those local governments that wish to require adaptable apartment units to do so on a consistent basis, without imposing the requirements in other areas where they aren’t wanted. Several municipalities have introduced requirements, and others have proposals under consideration. North Vancouver has had Adaptable Housing Guidelines in place since 1998, for example. In 2003, it expanded that to three levels of adaptability. The basic level is essentially what was added to the BCBC. Pitt Meadows is one of the newest municipalities to join the fray. It adopted a new adaptable housing policy and bylaw amendment in February, 2011. The regulations require all apartments in new multi-unit rental and condominium buildings with a common corridor and an elevator to be constructed as adaptable units. For those projects that do not require a rezoning, the bylaw would call up the Adaptable Dwelling Unit section of the BCBC. For those which require rezoning approval, the municipality would require some additional features as part of the approval, plus registering a restrictive covenant on title to ensure the adaptability of the units. Additional features for the rezoning process include: indicating on plan how a dwelling can be retrofitted for barrier free access to front door, parking space and onsite amenities providing adaptable parking spaces – a minimum of two adaptable space for buildings with 0-25 required space; 10 for those with 151-200, and 20 for those with 401-450 – and these spaces must be 3.7 m wide, although adjacent adaptable spaces may share a 1.2 m access space (amended in May 2011); plus manoeuvering space for doorway if there is a stepless entrance in the garage – the space may overlap stall design maximum 13 mm thresholds for access doors throughout the unit at least one window in the common area with a sill height not more than 750 mm above floor level at least one full accessible bathroom and full accessible bedroom, located on the same level Future Directions: A spokesperson for BC says that there are no current plans for additional requirements for accessibility or visitability. Aging in place initiatives are cross-jurisdictional. So far, they are mostly involved with increased densification around urban cores, and transit. 19 ALBERTA In Brief: Currently Alberta uses NBC accessibility requirements, but expands 3.8.1.1(3) to require a specified number (generally equivalent to 10 and 20%) of units in new government-funded residential projects to be ‘adaptable’. Specific requirements for adaptable units are contained in a STANDATA. Alberta Municipal Affairs staff have received requests from the public for increased accessibility, such as visitability, to be included in proposals for Alberta-specific code changes for the Alberta Building Code, 2012. The Building Technical Council has reviewed the recommendations and the province is expected to release its document on proposed Alberta-specific code changes for public comment late this year or in 2012. Current Code Requirements Alberta adopts the NBC, but also introduces Alberta-specific code changes. In Section 3.8, the Alberta government sets out requirements for the number of adaptable units required in new government-funded projects. If a residential project is funded in whole or in part by the Government of Alberta, adaptable dwelling units which could be made to meet barrier-free design principles must be provided. (Requirement is: 2 or more units in a 10-25-unit project, 5 or more in a 26-50 unit project, 10 or more in 51-100, 15 or more in 101-200, and 20 or more in a 200+-unit-project. This is not limited to specific housing types.) Interpretation details are given in a STANDATA11 (see below). The Province also added an Appendix note to 3.8.1.1 (3), which calls for flexibility: “Providing adaptable dwelling units which could be made to meet barrier-free design principles needs further clarification. In designing dwelling units, it is difficult to anticipate the specific needs of individuals, If a dwelling unit is inhabited by an ablebodied person as well as a person confined to a wheelchair, the height at which the kitchen counters are to be installed becomes an issue. Flexibility must allow the height of different work stations to be raised or lowered. Adaptable means that the dwelling unit can be adjusted to suit all occupants’ needs. For this to happen, each occupant’s limitations must be understood. As a general rule, the pathway from the street to the entrance of the dwelling unit must be well marked and free of curbs or steps. A person in a wheelchair must be able to turn into and turn around in any room. Work stations for persons in 11 STANDATA are prepared by Alberta’s Safety Services and the Safety Codes Council. This one is a Building Code Interpretation, which applies across the province. 20 wheelchairs must be capable of being lowered to the person’s height with allowance for their feet beneath. For persons who are blind or deaf, a common electric circuit must interconnect all rooms and be able to be connected to the fire alarm, intrusion alarm, intercom or phone system.” The requirement for adaptable housing is further defined in the Building Code Interpretation STANDATA 06-BCI-01012. It identifies required features as: Element Turning space Doorways Thresholds Accessible shower Accessible lavatory 12 Requirement Open space not less than 1 500 mm in diameter for turning in entryways, kitchens, washrooms and (if applicable) laundry areas Minimum 800 mm clear width when in the open position for every doorway into rooms within the dwelling unit Matches NBC? No matching provisions As doorways in designated path of travel, this would be called up for designated accessible units. No more than 13 mm in height and bevelled, for doorways above ditto At least one washroom in the adaptable dwelling unit must have a Matches 3.8.3.13(1)(a) to (d) and (g), which would be called up for designated barrier-free shower: accessible units, but omits requirements for not less than 1 500 mm wide and 900 mm deep clear space in front not less than 900 mm deep and the same width as a seat, grab bars, hand-held shower head and recessed soap holders the shower slip resistant floor surface bevelled 13 mm threshold (temp mix/control) valve operable with closed fist matches 3.8.3.4 (a) to (d) but does not call distance between centreline and side wall is not less than 460 mm up requirements for soap and towel rim height not more than 865 mm above floor clearance beneath is not less than 760 mm wide, 735 mm high at the dispensers front edge, 685 mm high 205 mm back from the front edge, and 230 mm high from 280 mm to 430 mm back from the front edge available online at http://www.municipalaffairs.gov.ab.ca/documents/ss/STANDATA/building/bci/06BCI010.pdf 21 Element Accessible water closet (toilet) Requirement Matches NBC? seat not less than 400 mm and not more than 460 mm above the floor matches 3.8.3.9.(1) (a) to (d), plus 3.8.3.12(1)(c) easily accessible or automatic flushing controls have a seat lid or other back support not have a spring-actuated seat have clearance to the walls of not less than 285 mm and not more than 305 mm on one side and not less than 875 mm on the other Room for The accessible washroom must be designed to permit a wheelchair to wheelchair back in alongside the water closet in the minimum 875 mm space required above Accessible Must have at least one section not less than 760 mm long centred over a matches 3.8.3.14(1), but the NBC only kitchen knee space as defined below applies this to counters at which the public counter - size is served ditto - height Top surface no more than 865 mm above the finished floor level clarification of 3.8.3.14(2), but the NBC only applies this to counters at which the public is served ditto – knee Not less than 760 mm wide, 685 mm high and 485 mm deep 3.8.3.14(3) for barrier-free counters as space above, intended to be used as a work space ditto – Must be provided with a means of adjusting their height so that the no such requirement intended for counter surface is not less than 710 mm above the finished floor level, installation of and not more than the height of the adjacent counter a kitchen sink or range Kitchen sink The sink referred to above shall be provided with a clearance of not less no such requirement for sinks in kitchens than 760 mm wide, 735 mm high at the front edge, 685 mm high at 205 (but it matches the requirement in mm back from the front edge, and 230 mm high from 280 mm to 430 3.8.3.11(1)(c)(iv) for bathroom sinks) mm back from the front edge 22 In addition to the above elements which are seen as mandatory to comply with Alberta’s 3.8.1.1(3), the STANDATA identifies the following as items to be taken into consideration: Lighting equipped to provide an average 50 lx at floor or tread level in all living spaces of the dwelling unit Door frames and base boards contrasting in colour and texture from the surface to which they are applied Windowsills located not more than 865 mm above the floor level, with easy-to-use opening devices Controls for building services or safety devices (electrical switches, outlets, thermostats and intercom switches) accessible to a person in a wheelchair, operable with one hand and mounted between 400 mm and 1 200 mm above the floor Sink and lavatory faucets that operate automatically or have lever-type handles that do not close under spring action Bathrooms designed to allow installation of appropriate grab bars Of note: in May 2011, the Alberta Legislature debated and agreed to a private member’s motion put before it by government MLA Cal Dallas. Rather than calling for new code requirements, that motion stated: “Be it resolved that the Legislative Assembly urge the Government to utilize incentives to encourage visitability standards in all newly constructed single-family homes, including one zerostep entrance, wider doorways (minimum 32 inch clear door opening), and a main floor half bathroom.” Future Directions Several groups, municipalities, etc. submitted accessibility-related requests for Alberta-specific changes to the building code for the 2012 code cycle. An Alberta spokesperson reports that the Province’s Barrier-Free Council has been concentrating on stadium seating, hotel suites/rooms and measures to increase accessibility for all new residential units, with or without government funding. Visitability (zero-step entrance, larger foyer, and at least one basically accessible bathroom on the main floor) has been one of the Council’s main interests. A number of the public code change requests called for inclusion of the Adaptable Dwelling Unit STANDATA into Division B of the code. Additional requests include higher design standards for parking, and such things as requiring structural support for grab bars, and for ceiling lifts in the bathrooms and bedrooms of adaptable units, clear turning space in front of closets, minimum 850 mm clear opening width for doorways in a barrier-free path of travel (including to bathrooms within adaptable suites), areas of refuge in sprinklered (as well as unsprinklered) floor areas, extra manoeuvring space at corners in smaller public corridors, etc. 23 Proposals have been put before the Building Technical Council, and a number will be included in the public review, probably later this year. That includes requirements in the Adaptable Dwelling Unit STANDATA, applied to multi-unit buildings. Some other recommendations will be referred to the CCBFC for discussion as potential changes to the NBC. Final decisions on Alberta’s 2012 code contents are expected next year. The provincial Design Guide also will be updated after the Code has been published, to reflect any changes in the regulations or new considerations on accessibility. As in other areas of the country, several municipalities are also taking steps on accessibility. Edmonton, for example, is considering zoning bylaw amendments which could allow smaller unit sizes and lower parking requirements for seniors’ congregate housing, or a separate land use class for seniors’ projects. Criteria may include universal design/accessibility, smaller/convertible dwelling units, accessory convenience stores and/or health services and provision of indoor community amenity space including a common dining area. Other initiatives are outlined in Edmonton’s “Making Our Houses Lifelong Homes: Accessible Housing for Seniors” report. That document reports on an October 2009 Mayor’s Roundtable on accessible housing/universal design for seniors. Recommendations included a mix of incentives for builders and consumers and legislation or zoning practices mandating features for new home construction. SASKATCHEWAN In Brief: The Saskatchewan building code requires 5% of units in new rental buildings to be barrier-free. Requirements cover accessible washrooms, space in bedrooms and kitchens, finishes in kitchens, and barrier-free balconies. No changes are expected at this time. Current Code Requirements: Saskatchewan adopts the NBC with some amendments13. Since 1998, they have amended the code to say at least one unit or 5% of the units, whichever is higher, in new rental apartment buildings must be barrier-free. Condominium apartment buildings are specifically exempted from this requirement. Key requirements for these units include: 13 available online at http://www.qp.gov.sk.ca/documents/English/Regulations/Regulations/U1-2R5.pdf 24 Element Accessible washrooms Kitchens Sleeping areas Balconies Requirement minimum 1 500 x 1 500 mm clear floor space toilet and sink meeting requirements in 3.8.3 lever faucet handles grab bars accessible shower minimum 1 500 mm clear space/turning circle lever faucet handles insulated/protected pipes 1 200 mm or less above floor no sharp edges or rough corners designed so that the range and sink are adjacent or can have continuous counter between them minimum 1 500 mm clear turning circle on one side of the bed barrier-free, meeting size requirements in 3.3.1.7.(5) Matches NBC? equivalent to 3.8.3.8.(1)(a) or 3.8.3.17.(1)(i) same 3.8.3.8.(1)(d) 3.8.3.13 no equivalent requirement No equivalent requirement for bedrooms 3.3.1.7.(5) Future Directions: A representative of building standards staff was not aware of any proposals at this time to increase requirements or extend them to Part Nine residential, either in this form or as adaptability, visitability, etc. 25 MANITOBA In Brief: Manitoba published changes to its building code, including new requirements for accessibility/universal design for Part Three buildings, in March 2011. Most come into effect as of January 1, 2012. The province is also working on Made-in-Manitoba Accessibility Legislation, similar to that introduced in Ontario. That is expected to produce wide-ranging standards and regulations for removing various types of barriers experienced by seniors and people with disabilities. Made-in-Manitoba Accessibility Legislation In November, 2010, Manitoba released a “Discussion Paper for Made in Manitoba Accessibility Legislation”. The main goal is to prevent and remove barriers to accessibility for seniors and people with disabilities, rather than relying on individuals pursuing the complaints process of human rights legislation to create change. The province points to legislation introduced in the United States, Australia and Ontario. “While these laws take different forms,” its discussion paper says, they contain common elements, including “clear, specific and achievable goals”, “accessibility standards for both the public and the private sectors”, and “regular review of the progress made”. Current Code Requirements: At the moment, Manitoba is using the NBC 2005 requirements for accessibility14. However, the government published its Manitobaregulation adopting the 2010 NBC and Manitoba-specific changes on March 31, 2011. That document has included a number of recommendations from the Barrier-Free subcommittee which has been examining code requirements in Section 3.8 and some other areas that affect accessibility. New requirements move towards more “universal design”, and the scope of several articles has been widened. The new requirements will take effect as of January 1, 2012. Key elements include: 14 regulation adopting the NBC 2005 with amendments is available online at http://web2.gov.mb.ca/laws/regs/pdf/b093-127.06.pdf 26 Element Scope Accessible entrances Requirement Barrier-free path of travel Doors 3.8.1.1 (1) keeps the exemption for small housing pedestrian entrances in buildings covered under 3.8.1.1 (1) are required to be barrier-free and lead to the outdoors at sidewalk level or by a ramp to the sidewalk where this isn’t practical for alterations to an existing building, at least one pedestrian entrance must be barrier-free required from all barrier-free entrances required as above “throughout the building and to all of the building exits” removes the NBC exemption for “floor levels not served by a passenger elevator (and similar elevating devices)”, but adds one for “interior paths of travel that are not a means of egress” adds an exemption so that unsprinklered floor areas which conform to 3.3.1.7 (1) (a) through (c) (i.e., floor areas which provide a firefighter elevator, are fire separated into at least two zones, or (residential only) provide “area of refuge” balconies) do not have to provide a barrier-free path of travel to all exits minimum width of 1 100 mm requirements for detectable warning surfaces where elevation changes more than 225 mm (full width; colour, texture, resiliency and sound; etc.) clear width of every public pedestrian doorway shall be not less than 850 mm in the open position same width required for the door to at least one full bathroom in a suite of residential occupancy (except small housing) power door operator required on a door at every entrance to a residential occupancy (except individual dwelling units) vestibule must provide a distance between doors in series of 1 500 mm plus the width of any door that swings into the space 27 Matches NBC? yes 3.8.1.2 requires 50% of entrances different approach 3.8.1.3 requires 920 mm no equivalent - applies to doorways in a barrier-free path of travel, and specifies 800 mm - applies to doors in a path of travel to that bathroom, and specifies 800 mm - no equivalent requirement 1 200 mm Element Ramps Requirement Exterior walkways Universal toilet rooms Other maximum slope of ramp used for pedestrian traffic is 1:12 in all occupancies 3.8.3.4 (1) applies to ‘ramps’ clear width of not less than 900 mm between handrails or inside of guard level areas 1 500 mm x 1 500 mm at intervals not more than 9 m level areas 1 800 mm long x 1 500 mm at changes in direction greater than 90o colour and texture contrast to mark leading edge of landing and beginning and end of ramp (also for stair nosings, treads and risers) not less than 1 200 mm in clear width not less than 1 500 mm if immediately adjacent to and at the same level as moving vehicles if a storey of a building is not serviced by an elevator or inclined moving walk, it shall be equipped with a universal toilet room or barrier-free washroom minimum 1 700 x 1 700 mm turning space more specific requirements for signage, prohibition on curved stairs in an exit, larger dimensions for exterior passenger loading zones, and uses the term “mobility device” rather than “wheelchair” in most instances installation of assistive listening systems in large classrooms or theatres installation of visual signals as part of fire-alarm systems 28 Matches NBC? - various – most 1:10 - 3.8.3.4 (1) applies to ramps in a barrierfree path of travel - 870 mm - 1 200 mm long x width of ramp - same as above - colour or texture - 1 000 mm - no equivalent requirement new 1 500 x 1 500 mm Guidelines on Visitability for government-funded projects In addition, approximately 20% of units built in Manitoba under the Affordable Housing Initiative (AHI) contain visitable design features. As outlined in provincial guidelines, these include a minimum of: one level, no-step entrance - minimum 36 inches (914 mm) wide - on an accessible route wider doorways - minimum of 32 inches (813 mm) clear passage throughout a wheelchair accessible bathroom on the main floor (can include the space under the sink in calculating the normal 1 500 turning radius) The guideline also says that other desirable features would include: Reinforced bathroom walls (for the installation of grab bars, if desired) Levered door handles and single-lever kitchen and bathroom faucets Raised electrical outlets - 18 inches (45.7 centimetres) from the door Lowered climate controls Lowered light switches - 48 inches (121.9 centimetres) from the door A Manitoba Housing representative says that visitability is required as a condition of funding for these Affordable Housing Initiative projects. For infill projects, they don’t require the normal 1 500 mm turning radius in the bathroom, but the visitor must be able to wheel in and wheel out. Future Directions: As above, changes affecting multi-unit buildings were released in April. Staff expects the Subcommittee will start discussing recommendations for Part Nine buildings, including the small housing types currently exempted by the building code, within the next couple of years. 29 ONTARIO In Brief: The current Code requires 10% of units in new multi-unit buildings to have an internal barrier-free path of travel, which triggers other requirements for doors sizes and washrooms. Under the Accessibility for Ontarians with Disabilities Act, 2005 (AODA), the Ministry of Community and Social Services has been coordinating efforts to produce wide ranging plans and standards to achieve an “accessible Ontario” by 2025. In 2010, an Advisory group proposed standards under AODA for the built environment, including many on- and off-site elements affecting multi-unit residential. The Ministries of Community and Social Services (disabilities directorate) and Municipal Affairs and Housing (building code) are doing further analysis of the proposals, and research to make sure that any future requirements they may adopt are clear, consistent, enforceable and build on current accessibility requirements. Requirements for small housing may be considered later. Current Code Requirements: Ontario’s Building Code15 specifies that at least 10 per cent of the units in all new apartment buildings must have a barrier-free path of travel from the suite entrance door to at least one bedroom at the same level, and at least one bathroom with not less than 4.5 m2 in area. Several requirements differ from those in the NBC. Element General Requirement barrier-free path of travel from sidewalk to (but not into) all suites, with a minimum width of 1 100 mm barrier-free path of travel into 10% of suites, and along path to (but not into) one bedroom and one bathroom in each of those suites doorways in a barrier-free path of travel with a clear width of not less than 850 mm in the open position an accessible balcony if required in accordance with 3.3.1.7.(1) to (3) of Ontario’s code 15 available online at http://www.search.e-laws.gov.on.ca/en/isysquery/4c518dc0-84d9-4ab8-bfbbeb7fdba655ed/2/doc/?search=browseStatutes&context=#hit1 30 Matches NBC? Width for interior corridors is minimum 920 mm silent 800 mm different approach Element Bathrooms within the 10% of suites required to meet accessibility Controls (for vision impaired) Ramp dimensions Grab bar ‘readiness’ Requirement 2 minimum 4.5 m floor area in designated suites minimum door width of 760 mm where the corridor is at least 1 060 mm wide minimum door width of 810 mm where the corridor is less than 1 060 mm wide Matches NBC? different approach to space requirement extra requirements may apply in common areas for location of vision No equivalent requirements panels in barrier-free-path of travel and marking for glass doorways minimum width between handrails: 900 mm (NBC is 870) level area at top and bottom of ramps: 1 600 x 1 600 (NBC is 1 500) level area at intervals not more than 9 m and where there are abrupt changes in direction: 1 670 mm all dwelling unit washroom walls framed with wood or sheet steel framing must provide reinforcement for future installation of grab bars 3.8.3.4 No equivalent requirement Accessibility for Ontarians with Disabilities Act (AODA) Passed in 2005, AODA sets a goal of reaching an “accessible Ontario” by 2025. It requires accessibility plans and standards to be created in five key areas: accessible customer relations, accessible transportation, accessible information and communications, employee accessibility, and accessible built environment. As proposed standards for each area were produced by the relevant Standard Development Committee they were submitted to the Minister of Community and Social Services (MCSS) for decision on further action. The customer service regulation has been in force since January 2008, and an integrated regulation addressing transportation, information and communications and employment is expected to be enacted in 2011. 31 Final broad-ranging proposals from the Accessible Built Environment Standards Development Committee, issued in 2010, are still under review. They include recommendations for a large number of things not dealt with in the Building Code, as well as building requirements for many types of occupancies. This discussion only deals with the recommendations for residential buildings. The report specifically excludes retrofit projects and the small housing types currently exempted from accessibility requirements in the Code. For multi-unit buildings, it proposes requirements for common access and circulation, interior accessible routes, exterior spaces, plumbing elements and facilities and building performance and maintenance. Some of the proposals are consistent with current code requirements, some are beyond its scope (e.g., those related to maintenance), and there are a number of increases. In particular, Section 13 of the report called for all individual dwelling units in multi-unit buildings to be “visitable”, and all units larger than 46.5 m2, and 50% of smaller units, to be “adaptable”. A Committee Comment in that Section says that it “represents a broad-based framework that requires more detailed work to develop the concepts of visitability and adaptability”. As proposed in the report, “visitability” would include having a zero step entry and at least one living space and a washroom on the visitable level. Corridors on that level were proposed be at least 920 mm wide and have no level changes requiring steps. Except for those serving a closet or pantry, doors would need a clear opening of 900 mm. Washrooms were proposed to have a clear floor area at least 920 mm wide by 1 200 mm long. A two-piece washroom would be acceptable. Alarms should have an auditory and a visual mode, and an electrical rough-in for a power door would be required beside the main entry door. The definition of “Adaptability” would include that, where possible, the unit should be designed so that rooms can be enlarged through removal of non-structural interior walls. For washrooms, this should allow later expansion to accommodate a mobility device and zero-threshold roll-in shower. The report also called for washrooms to provide blocking for future installation of grab bars (already required in the Code in Ontario). An adaptable unit should also “consider the provision of a level ceiling to allow for the future installation of a patient lift track”. Future Directions: The proposed Accessible Built Environment Standard is under review by staff at the Building and Development Branch of the Ministry of Municipal Affairs and Housing (MMAH), which is responsible for development of Ontario’s Building Code, and at the Accessibility Directorate of Ontario in the MCSS. While information posted by MMAH in the fall of 2010 with the first round of 32 proposed Building Code amendments suggested accessibility would be dealt with in the 2011 round, when those proposals were released in February accessibility was identified as an area for further study instead. MMAH and MCSS have said that the government wants to make sure that any requirements that become law are clear, consistent, enforceable and build on current accessibility requirements. As such, they are working together to complete a thorough analysis of the proposed Accessible Built Environment standard. In addition, the committee that developed the final proposed standard recommended that government conduct further research in some key areas. Once research and analysis of the standard is complete, the government will make decisions on what will become law and when, and those requirements proposed for integration into the Ontario Building Code will be included in the code consultation process. Requirements for small housing may be considered later. QUEBEC In brief: Proposals for adaptability in multi-unit buildings are expected to be submitted to the Advisory Council of the Regie du batiment du Quebec in August 2011 for approval to proceed. If granted, proposed code changes are expected to be released for public comment in late 2011 or 2012. Current Code Requirements: Quebec uses the NBC with minor changes. It has adopted a version of Section 3.816 which requires 10% of suites in hotels and motels to meet accessibility requirements. Future Directions: An Accessibility Group has been working on proposals for new requirements which would affect multi-unit residential buildings. The Regie du batiment du Quebec initially set a target for staff to submit proposed code changes for accessibility to its Advisory Council in March 2011, but that has been put off until August. Preparation has been delayed by work involved with energy efficiency 16 available online at http://www2.publicationsduquebec.gouv.qc.ca/dynamicSearch/telecharge.php?type=3&file=/B_1_1/B1_1R0_01_01_A.HTM, see sentences (59) to (77). 33 regulations. If that group gives approval to proceed, the proposed changes would be published for public comment in late 2011 or 2012. The approach may require 100% of units on floors served by an elevator to be adaptable in residential buildings required to provide barrier-free entrances and path of travel. Where there is no elevator (but a barrier-free path of travel is required), 100% of the units on the ground floor may be required to be ‘adaptable’. Specific requirements would probably include zero-step entrance, a bit wider doorways and corridors, ability to renovate a bathroom to accommodate a wheelchair, space in kitchens and bedrooms, window height, some elements of wardrobes, and balconies, but not full accessibility. The NBC exemption for small housing (single detached to boarding houses) would remain. Proposals for requiring accessibility/visitability in small housing types currently exempt from accessibility requirements are not anticipated in the near future. NEW BRUNSWICK In Brief: Officials with the Department of Public Safety have engaged stakeholder groups through an advisory committee. The mandate of this committee is to make recommendations for enhancing the barrier-free requirements in Section 3.8 of the National Building Code. Current Code Requirements: New Brunswick, which regulates building in unincorporated areas of the province through planning commissions, adopted the 2005 NBC in 2009. Municipalities, which regulate building through bylaws passed under the Community Planning Act, also adopt the NBC but can add to it. Requirements for accessibility in larger municipalities appear to follow the 2005 NBC without amendment.17 17 Communications from building officials in Fredericton and the City of Saint John. 34 Future Directions: The New Brunswick Building Code Act received Royal Assent in 2009 and is scheduled to be proclaimed by 2012 adopting the 2010 NBC by reference (work is well under way on the supporting regulations). Municipalities will still be able to pass by-laws with technical requirements that go beyond those in the referenced NBC. Any provincial proposals for enhancing the barrier-free requirements in section 3.8 of the NBC would proceed as a proposed regulation, with the normal public comment period. NOVA SCOTIA In Brief: Nova Scotia has fairly extensive requirements for 5% accessible units in all multi-family buildings. The expectation is that they will be discussing visitability for all housing types within two years. Current Code Requirements: The Nova Scotia building code is based on the NBC with some modifications and additions to suit the province. Most requirements for accessibility are essentially the same as those in the NBC. The biggest change is that Nova Scotia has added a new sentence 3.8.1.1.(6) requiring all multiple family buildings to provide one barrier free unit in every 20 units. This applies across the board, whether the units are publicly funded or not. The exemption for houses, semi-detached, duplexes, triplexes, townhouses, row houses, boarding houses and rooming houses is retained. Specific requirements for Suites of Residential Occupancy Required to be Barrier-Free are found in the added subsection 3.8.3.18. (Details are in the chart below.) The province has also added requirements for designated barrier-free parking stalls. 35 Houses, including semi-detached, duplexes, triplexes, townhouses, row houses, boarding houses, and rooming houses, are exempt from all accessible provisions so these would not apply. The building code also sets out two Alternate Compliance Methods for application of accessibility requirements to renovation/alteration of existing buildings: a barrier-free washroom need not be provided in an existing building with a building area of less than 120 m2 where an existing building has a building area of less than 120 m2 and the slope from the entrance level floor to the street or public way is greater than 1 in 10 and no alternate access for a street or public way is possible, the owner may use a stair with a maximum rise of 150 mm and minimum run of 280 mm and tactile landings with contrasting colour nosings and an unobstructed width of 1 m Section 3.8 requirements in Nova Scotia18 apply when there are more than three residential suites. For those buildings, one in 20 residential suites must conform to the following: Element General 18 Requirement Matches NBC? Where a suite of residential occupancy is required to provide barrier-free yes access, it shall be served by: entrances in accordance with 3.8.1.2 barrier-free path of travel to, into, and throughout each required suite in accordance with 3.8.1.3 an accessible balcony if required in accordance with NBC 3.3.1.7.(c) barrier-free controls (as outlined below) available online at 36 Element Washrooms Requirement Kitchens 2 minimum 3.7 m floor area, with no dimension less than 1 700 mm (when the door swings out) and 4.0 m2 floor area, with no dimension less than 1 800 mm (when the door swings in) toilet and sink meeting requirements in 3.8.3. lever faucet handles grab bars where a shower is provided, it must meet 3.8.3.13 (1)(a) to (i) where a tub is provided, it must meet 3.8.3.13 (3)(a) to (d) a ground-fault-interrupter (GFI) razor outlet located not more than 1 200 mm above the floor level minimum 1 200 mm clearance between counters and all opposing base cabinets, counter tops, appliances or walls, except in a U shaped kitchen the minimum distance shall be 1 500 mm minimum clear floor space of 750 mm x 1 200 mm at each major appliance 37 Matches NBC? different approach to space requirement rest match, except NBC has no requirement for a GFI razor outlet no equivalent requirements for kitchens Element Kitchens (contd) Requirement a minimum of one work surface: o 750 mm wide x 600 mm deep and 810 mm to 860 mm above the floor o at least one electrical receptacle at the front or side of the work surface o a clear floor area 750 mm wide x 1 200 mm (which may extend 480 mm under the work surface) o knee space at least 750 mm wide, 480 mm deep and 680 mm high base cabinets shall have a minimum toe space 150 mm deep and 230 mm high sinks shall: o be mounted with the rim between 810 to 860 mm above the floor o have a knee space at least 750 mm wide, 250 mm deep and a toe space 750 mm wide and 250 mm deep and 230 mm high o have the same size of clear floor area as for counters o have faucets with lever handles o insulated hot water and drain pipes where they abut required clear space upper cabinets shall have a minimum of one shelf not more than 1 200 mm above the floor storage cabinets’ doors and drawers shall o have a handle that is easily graspable o be mounted at the top of base cabinets and the bottom of upper cabinets 38 Matches NBC? no equivalent requirements for kitchens Element Controls Sleeping areas Requirement controls for the operation of building services or safety devices, including all electrical switches, thermostats, intercom switches, and kitchen controls shall be: accessible to a person in a wheelchair operable with one hand mounted not more than 1 200 mm above the floor electrical receptacles shall be located between 400 and 550 mm above the floor, except for bathroom GFI razor outlet per 3.8.3.18.(3)(f) and kitchen counter outlet per 3.8.3.18.(4)(c)(v) minimum floor area of 12.25 m2 one horizontal dimension not less than 3.35 m at least one closet with o minimum clear opening of 900 mm o clothes hanger rods located at a height of 1 200 mm o at least one shelf at a height of 1 370 mm Matches NBC? 3.8.1.5 No equivalent requirement for bedrooms Future Directions: Building Code staff say they expect to be discussing visitability for all residential units, including the small housing forms currently exempt from the accessibility objective, within two years. Any proposals will proceed through normal processes, including public comment periods. 39 PRINCE EDWARD ISLAND In Brief: There is no province-wide building code in PEI. Three municipalities have adopted the NBC: Summerside and Stratford have added a requirement that one in every 12 units in new apartment buildings be barrier free as defined in Section 3.8 of the NBC; Charlottetown has similar proposals before Council. Current Code Requirements: Requirements differ across the province. Outside of Charlottetown, Summerside and (very recently) Stratford, Prince Edward Island uses the United States-based National Fire Protection Association’s NFPA 101 - Life Safety Code, which concentrates on number of exits, means of egress, fire alarms and fire protection of building elements. By regulation, the province also requires new construction in those geographic areas to meet the Barrier-Free Design section of the 1990 NBC, and to produce a Quality Control Plan showing how compliance will be achieved. Enforcement for projects in affected municipal areas is carried out by the municipal building official; the province provides those services in rural areas. Charlottetown and Summerside adopt the NBC. Summerside has just updated to the 2010 NBC effective May 16, 2011, and amended it to also require one unit in every 12 units in new apartment construction to be barrier-free. Charlottetown did the same in June (one unit in 12 for smaller buildings; one in 18 for those 36 units and up). The requirements for these barrier-free units include minimum dimensions and facilities for sleeping areas, bathrooms and kitchens. The City of Stratford has also this spring adopted a bylaw to adopt the NBC 2010 rather than NFPA 101 and introduce the same requirement for one in every 12 apartment units to be barrier-free. Future Directions: The Province has recently appointed a person to oversee a project to adopt the NBC province-wide. 40 NEWFOUNDLAND In Brief: A Buildings Accessibility Act requires at least one accessible unit in all apartment-type buildings and barrier-free access to all floors in those with more than 15 units. Regulations are similar to the NBC but in a somewhat different format and with some changes. They were last amended in 2006 and staff do not expect significant imminent changes. Current Code Requirements: Newfoundland and Labrador does not regulate accessibility through a building code, but through a separate Buildings Accessibility Act passed in 1996 and its regulations19, which apply across the province. Under that regime, all apartment buildings with more than 15 units constructed or renovated/altered since December 1981 must make “all floors to which the public and occupants have lawful access” accessible to persons with disabilities from an accessible entrance, and provide at least one accessible residential unit. If the cost of the reconstruction is less than 50% of the replacement cost of the building, it will be exempt from these accessibility requirements as an “existing building”. Also, smaller apartment buildings with 5 to 14 units must provide at least one residential unit in which all rooms are on the same level or which are connected by a ramp, but access throughout the remaining suites is not required. Where buildings are divided into separate sections by firewalls, each portion is considered a separate building. Some of the key elements include: Element Barrier-free path of travel Requirement 19 Matches NBC? at least one accessible entrance opening at sidewalk level of to a ramp leading to a sidewalk public corridors: minimum width of 1 100 x 1 100 mm available online at http://assembly.nl.ca/Legislation/sr/Regulations/rc961140.htm 41 Element Barrier-free path of travel (cont’d) Barrier-free path of travel Doors into and within dwelling unit Other Requirement Matches NBC? turning area of 1 500 x 1 500 mm at end of any corridor exceeding 3 000 mm in length interior corridors: minimum width of 920 mm, no openings that will pass a sphere more than 13 mm in diameter, may include ramps areas of refuge or an accessible balcony in accordance with NBC 3.3.1.7.(c) ramp width: minimum of 870 mm between handrails level area at top and bottom: 1 500 mm x 1 500 mm and at intermediate levels; extending 600 mm beyond the latch side of the door (except 300 mm beyond if door opens away from the ramp) turning areas of 1 200 x the same width as the ramp at intervals of not more than 9 m entrance door: minimum clear width when open of 800 mm door to at least one bathroom in the accessible unit: minimum 760 mm Similar requirements to NBC in many areas Same smaller Future Directions: The regulations were amended in 2006, and provincial staff do not anticipate any changes to these standards at the moment. Some proposals may arise from municipalities. 42