A Study on the Effect of Distributed Generation on Short-Circuit Current Insu Kim Ronald G. Harley Electrical Engineering Alabama A&M University Normal, AL, 35711, USA insu.kim@aamu.edu Electrical and Computer Engineering Georgia Institute of Technology, Atlanta, GA, USA Professor Emeritus at the University of KwaZulu-Natal in South Africa, rharley@ece.gatech.edu Abstract-In short-circuit studies, phase shifts in transformers and insisted that transformers connected in different ways have a significant impact on fault current [11]. Another recent study discussed the accuracy of transformer models presented from the Alternative Transients Program that shift phases in positive- and negative-sequence networks [12]. However, these studies have not analyzed distribution networks not only heavily or weakly meshed but also enhanced by DG resources with relatively high capacity (e.g., 30 and 50 percent). Thus, the objective of this study is (a) to present an accurate short­ circuit analysis algorithm able to calculate the magnitude and the phase angle of fault current in meshed or radial networks, including phase shifts through transformers, and (b) to analyze the effect of not only various capacities (e.g., 10, 30, and 50 percent) of DG resources but also various locations of faults on current that flows during the short circuit. (e.g., connected in wye-delta or vice versa) make difficult to calculate fault current flowing in sequence-component networks. Therefore, they are often ignored because the magnitude of fault current is much more of interest than phase angles from the protection point of view (e.g., overcurrent relays). As high­ capacity distributed deployed into generation direction and the phase distribution (DG) networks, angle resources they may are being change the of fault current and cause abnormal operations of directional or distance relays. Thus, the objective of this paper is to develop a short-circuit analysis algorithm able to (a) calculate changes in phase shifts caused by transformers in sequence networks with high-capacity DG sources and (b) analyze the effect of not only various capacities (e.g., 10, 30, and 50 percent) of DG resources but also various locations of faults on current that flows during a short circuit. To verify the developed algorithm, using MATLAB, case studies that generate a single line-to-ground fault on (a) the high- and low-voltage sides and (b) a weakly meshed network are presented. Index Terms-Distributed generation (DG), phase shift, sequence network, short circuit, and single line-to-ground fault. I. INTRODUCTION As high-capacity distributed generation (DG) resources such as small-scale synchronous generators, solar, and wind farms are being deployed into distribution networks, they may change current that flows during a short circuit or an electrical fault. Thus, many studies have presented various methods for short circuit studies, which can be classified by the following three methods: (1) solving sequence networks using symmetrical components [1-3], (2) iterative compensation methods using bus admittance matrices [4, 5], (3) iterative compensation methods using bus impedance matrices [6-9]. However, these study ignored phase shifts through transformers since the magnitude of fault current is much more of interest than phase angles from the protection point of view (e.g., overcurrent relays). To examine phase shifts of transformers, a study presented a mathematical model and graph theory (which is referred to as a V-equivalent) of the delta-wye transformer that shift phases [10]. Another study modeled the transformer and the load in short circuit analysis 978-1-5090-0687-8/16/$31.00 ©2016 IEEE This paper is organized as follows: Section 2 describes a problem statement, and Section 3 presents the short-circuit theory for analyzing phase shifts of transformers and meshed networks. Section 4 provides a flowchart of the implemented short-circuit analysis algorithm. Section 5 introduces case studies for calculating short-circuit current using the proposed algorithm. Section 6 summarizes major conclusions of this study. II. PROBLEM STATEMENT If a fault occurs on an external line of a distribution system with high-capacity DG resources, fault current flowing from DG resources will flow to the faulted line, which is a reverse direction when compared to the case without DG resources. Furthermore, since phase angle changes in fault current caused by DG resources may affect the protection coordination of directional or distance relays, they should not be ignored. Thus, this study is to develop a short-circuit analysis algorithm able to calculate a phase angle of fault current, including phase shifts through transformers. For this purpose, it applies a phase-shifting method to positive- and negative-sequence networks. In addition, this study changes the capacity of DG resources and fault locations in a case study in order to examine their effect on the magnitude of fault current. III. SHORT-CIRCUIT STUDY A. Current of a Single Line-to-Ground Fault In the circuit theory, a power system network with n nodes can be expressed by currents injected at nodes and voltages induced at nodes with regard to the reference: V=Zb,J, (l) where Zbus is referred to as the bus impedance matrix. The bus impedance matrix is useful to find the fault current. For example, if the phase a of line i is faulted to the ground, single line-to-ground (SLG) fault currents of zero, positive, and negative sequences are given by I o =I I =I 2 = VJ ' Zo(i, i)+ZI(i, i)+Z2(i, i)+3Zr (c) Zero sequence Fig. I. Equivalent sequence networks of a transformer connected in delta­ grounded wye. C. Meshed Topology (2) where 10, hand h = zero-, positive-, and negative-sequence currents of faulted bus or line i, respectively, V;= prefault voltage of Thevenin's equivalent voltage source in the positive-sequence network (typically lLO° PU), Zo(i, i) , ZI (i, i) , and Z2(i, i) = zero-, positive-, and negative­ sequence open-circuit driving-point impedances of faulted bus or line i in bus impedance matrices, respectively, Zr= fault impedance. The fault current If of line i is IJ =310 =311 =312, Fig. 2 presents a meshed topology consisting of four buses and branches, which can be used to increase the reliability of distribution systems by adding switches between the branches or lines. In the short-circuit study, if (a) each branch or line has an impedance of ideally 0 and (b) a fault occurs on one of the branches or buses, currents flowing through each branch cannot be calculated from the Ohm's equation (e.g., I2.I=VdZ2/, but the impedance of Z2/ is 0). Therefore, this study applies the Kirchhoffs Current Law (KCL) to the meshed topology. For example, if a fault occurs on bus 3 in Fig. 2, currents flowing through the branches is determined by the following KCL: [ 1j I I. 3 o 1 0 /2•1 12 1 0 0 1 12•4 IF - 13 o 0 -1 1 �3 � where Ii,j = the current that flows from buses ito j, 1 (3) B. Representation of Transformers in Sequence Networks In short-circuit studies, since the main concern of which is usually the magnitude of fault current, phase shifts through transformers are often ignored. In other words, transformers are replaced by simply zero-, positive-, and negative-sequence impedances. To examine such phase shifts of transformers, Fig. 1 illustrates a method that shifts phases between two buses in positive- and negative-sequence networks in the case of a transformer connected in delta-grounded wye. In the positive-sequence network of the transformer balanced in three phases, a phase of +30° will be shifted from buses ito j, shown in (a). The negative sequence shifts by -30°. -1 0 0 (4) Ii = the current incoming to or outgoing from bus i. Since It, h h h and IF can be determined by solving the sequence networks, the currents flowing through branches, (e.g., 12, 1 ) can be found by an inverse transformation of (4). Fig, 2, 4-bus meshed topology [13]. (a) Positive sequence IV. IMPLEMENTATlON OF THE SHORT-CIRCUIT ANALYSIS ALGORITHM Using MATLAB, this study implements an algorithm that (a) builds bus impedance matrices for positive-, negative-, and zero-sequence networks, (b) calculates SLG fault current, and (c) applies the proposed phase-shifting method to sequence networks. This study used the four rules presented in [1] in order to build the bus impedance matrix. Fig. 3 presents a (b) Negative sequence flowchart of the developed short-circuit algorithm, which will be verified in the following case studies. V. A. CASE STUDY A Distribution Network with DG In Fig. 4, this study presents a case study of the distribution system with a DG source in order to (a) verify the proposed algorithm that calculates phase shifts through transformers, (b) evaluate changes in fault current when a fault occurs on either high- or low-voltage sides, and (c) examine the effect of the capacity of DG and the location of faults on fault current. For this purpose, this study initially generates a SLG (single line-to-ground) fault on the high-voltage side of the distribution system, phase a of feeder 1, and on the low­ voltage side, feeder 2. A fault impedance, Zf, of 0 is assumed and a synchronous generator with a capacity of 10 MVA, which is 10 percent of a total generation capacity of 100 MVA, is used as an example of a DG source. In this case study, load current is ignored because it is often negligible when compared to large fault current. Then, this study builds bus impedance matrices according to the steps presented in Fig. 3, decomposes the distribution system into zero-, positive-, and negative-sequence networks, shown in Fig. 5, and applies phase shifts of transformers to positive- and negative­ sequence networks. Finally, it calculates fault current flowing from a faulted line to the ground. Fig. 5. Equivalent sequence network of the distribution system after a SLG fault occurs on feeder 1. TABLE I to TABLE IV show fault currents after a SLG fault. If a SLG fault occurs on the high-voltage side (feeder 1) of the distribution system with a lO-MW synchronous generator, a current of 1.4489L-47.04° PU in phase a flows to the ground. But if the same type fault occurs on the low­ voltage side of the distribution system, feeder 2, a current of 1.2128L-85.34° PU flows, which is lower than 1.4489L47.04° pu. That is, in the distribution system with DG sources, a SLG fault close to the substation seems to increase the magnitude of fault current. Next, the proposed algorithm calculates phase shifts, particularly 30°, in voltage and current of transformers balanced in delta-grounded wye or vice versa, in positive- and negative-sequence networks, which can be seen in the columns of hh VI, and V2 of each table. Note that * sign in the Bus column of TABLE II and TABLE IV indicates a current direction. For example, "Generator*-7 Bus S" indicates a line current outgoing from the generator, which does not contain phase shifts through the delta-wye transformer. Bus Generator BusS Feeder I (Fault) BusR Feeder 2 DG Fig. 3. A flowchart of the developed short-circuit analysis algorithm. Fig. 4. A distribution system with a synchronous generator at the end. Bus Generator* �BusS BusS* � Feeder I Feeder 1* � Fault BusR* � Feeder 2 Feeder 2* �BusR DG' � Feeder 2 TABLE T PHASE VOLTAGES AFTER A FAULT ON FEEDER I Volta e in PU Phase A Phase B Phase C V,(Zero) v 1 (Positive) V,(Negative) OLO° lLO° OLO° ILO° IL-120° IL120° L-21.26° L-149.41° L89.74° L-136.59° L27.76° L-135.0Io L-155.38° L96.78° L-152.02 L29.40° L-148.53° L-18.62° L-144.27° L83.81° L-137.52 L28.38° L-145.18° LI4.81° L-120.00° LI08.42° L-1.l5° L-1l5.18° 0.6343 OLO° 0.3683 0.7495 ILO° 1.0008 1.0895 0.9399 1.0000 IL-120.00° 0.9907 1.0535 0.9567 0.7109 ILI20.00° 0.1219 0.4208 0.1405 OLO° OLO° 0.8735 0.7103 0.7494 0.8072 ILO° 0.1317 0.2898 0.2518 0.1937 OLO° TABLE IT LINE CURRENTS AFTER A FAULT ON FEEDER I Current in PU 1,(Zero) Phase A Phase B Phase C I, (positive) h(Negative) 0.6709 0.6709 OLO° L-45.0Io LI34.99° L-45.39° LI37.82° LI37.82° OLO° OLO° 1.0235 1.4489 L-47.04° 0.4269 0.1388 0.1388 L-50.99° L-42.18° L-55.18° LI24.82° L-55.18° LI24.82° 0.1677 0.1677 0.1677 0.1677 OLO° 0.3873 0.3873 L-75.0Io L-15.0Io L-46.59° L-45.0Io L-45.0Io L-47.04° L-47.04° L-47.04° L-42.18° L-47.52° L-55.18° L-55.18° OLO° OLO° L-85.18° L-25.18° OLO° OLO° L-85.18° L-25.18° 0.1388 0.1388 0.2488 0.4830 0.2341 0.3873 0.4830 0.0968 0.0968 0.0968 0.3873 0.4830 0.0968 0.0968 0.0968 Fig, 6. Flows of fault currents after a single line-to-ground fault on feeder 1, Bus Generator TABLE TIT PHASE VOLTAGES AFTER A FAULT ON FEEDER2 Volta e in PU Phase A Phase B Phase C Vo(Zero) V,(Positive) V,(Negative) BusS Feeder I (Fault) BusR ILO° 0,8811 L-32,83° 0,7813 L-144,80° 0,7592 ILI20,00° 1,0000 L90,00° 1,0000 L-140.49° L90,00° L-52,23° L-134,18° L90,00° L-I13.44° LI12,04° 0,7038 OLO° DG ILO° Bus 0,9060 L-41.44° Feeder 2 Generator* �BusS BusS* � Feeder I Feeder 1* �BusR BusR* � Feeder 2 Feeder 2* � Fault DG* � Feeder 2 IL-120,00° 0,6186 0,9117 IL-120,00° 1.0000 0,9662 ILI20,00° OLO° OLO° OLO° OLO° 0,2426 L-175,34° OLO° ILO° 0,9275 OLO° 0,0737 L29,21° LI60,04° L30,67° LI46,52° L32.49° LI42,62° LO,91° L178,5JD 0,8382 0,7496 0,6210 ILO° 0,1621 0,2532 0,3793 OLO° TABLE TV LINE CURRENTS AFTER A FAULT ON FEEDER 2 Current in PU lo(Zero) Phase A Phase B Phase C l,(posilive) h(Negative) 0.4333 L-79,96° 0,3753 L-79,95° 0,3753 L-79,95° 0,3753 L-79,95° 1.2128 L-85,34° 0,7824 L-88,32° 0,2167 LI00,04° OLO° OLO° OLO° OLO° 0,2167 L-79,96° 0,2167 LI00,04° 0,3753 LI00,05° 0,3753 LI00,05° 0,3753 LI00,05° OLO° 0,2167 L-79,96° OLO° 0,2167 0,2167 L-79,96° L-79,96° L-49,95° L-109,95° L-49,95° L-109,95° L-49,95° L-109,95° L-85,34° L-85,34° L-85,34° L-85,34° L-91.49° L-91.49° OLO° OLO° OLO° 0.4043 0.4043 0,2167 0,2167 0,2167 0.4043 0,1896 0,2167 impedance compared to the substation in the case of SO percent DG, the magnitude of current caused by a fault occurred close to the DG source is greater than that caused by a fault close to the substation. For example, the substation has jO.34 PU of positive-sequence impedance and j0.49 PU (zero­ sequence) but SO percent DG has jO.4 PU (positive-sequence) and jO.12 PU (zero-sequence). If a fault occurs on feeder 2 in the case of SO percent DG, an equivalent impedance of the zero-sequence network is only jO. l2 Pu. Therefore, it shows the highest magnitude of fault current in all the cases. In addition, in the all cases, the higher capacity a DG source has, fault current with the higher magnitude flows. Note that in the case of without DG, the fault location of feeder 2 was moved to the secondary side of the grounded wye-delta transformer in Fig. 4, (to avoid that fault current does not flow in the case of a fault on feeder 2 of the test feeder without DG because the side of the DG source is open in the zero-sequence network). 0,2167 0,2167 0.4043 0,1896 Fig. 6 shows fault currents that flow in each phase of the distribution system after a single SLG fault occurs on feeder 1. A fault current of 6,708.28L-47.04° A, which is the summation of currents flowing from the substation, 4,738.S1L-4S.39° A, and the DG source, 1,976.42L-SO.99°, flows to the ground. Since this study assumes a DG source with a capacity of 10 MVA at 0.38 kV, a large fault current of 2S,486.11L-SS.18° A flows from the distributed generator. In the previous case study, this study fixed the capacity of a DG source to 10 percent of a total generation capacity of 100 MVA. To examine the effect of not only varying capacities of DG resources but also the location of faults on the magnitude of fault current, this study changes not only the capacity of DG resources in a range of 10 MW (10 percent) to SO MW (SO percent) but also fault locations. Fig. 7 shows the trends in the magnitude of fault currents. In the cases of without DG and 10 percent DG, if a SLG fault occurs close to the substation (e.g., Bus S), the magnitude of fault current is greater than that caused by a fault occurred far from the substation (e.g., Feeder 2). However, since the DG source has relatively low Fig, 7. Fault currents when capacities of a DG source and locations of a fault are varying. B. Meshed Network To verify the proposed algorithm that analyzes faults occurring on the meshed network, this study presents a case study of the IS-bus meshed distribution system in Fig. 8 and generates a SLG fault on bus 13 of the network. TABLE V shows the results of fault currents of each branch with an impedance of 0, calculated from equation (4). Note that h= h.13 + 115,13 + 113 . In this case study, load current is also ignored. ground, and three-phase faults. In addition, this study did not analyze sufficiently large distribution networks. However, the developed algorithm can be extended for such cases by taking into account of load current, implementing the other fault types, and modeling large distribution networks, all of which are still our future work. REFERENCES [1] [2] [3] Fig. 8. A meshed IS-bus distribution network. TABLE V LINE CURRENTS AFTER A SLG FAULT OCCURS ON Bus 13 Current in PU Bus Phase Phase Phase A lo(Zero) [,(Positive) h(Negative) B C OLO° OLO° 0.0078L-58.96° 0.0078L-58.96° 0.0026L-58.96° 0.0026L-58.96° ,7 19 0.0078L-58.96° OLO° OLO° 0.0078L-58.96° 0.0026L-58.96° 0.0026L-58.96° 19.15 0.0233L-58.96° OLO° OLO° 0.0233L-58.96° 0.0078L-58.96° 0.0078L-58.96° 1,.13 115.13 0.0233L-58.96° OLO° OLO° 0.0233L-58.96° 0.0078L-58.96° 0.0078L-58.96° 0.0155L-58.96° OLO° OLO° 0.0155L-58.96° 0.0052L-58.96° 0.0052L-58.96° 1/3 0.062IL-58.96° OLO° OLO° 0.0621L-58.96° 0.0207L-58.96° 0.0207L-58.96° IF VI. CONCLUSION The main objective of this study is to develop a short­ circuit analysis algorithm able to (a) calculate phase shifts of transformers in sequence networks and (b) analyze the behavior of fault current of distribution systems enhanced by DG resources. For this purpose, this study has applied a phase­ shifting method to positive- and negative-sequence networks and has presented case studies in which the capacity of DG resources and fault locations are changed. The results from the case studies show that in a distribution system with low­ capacity DG sources (e.g., less than or equal to 10 percent of total generation capacity), if a SLG fault occurs close to the substation, the magnitude of fault current can be greater than that caused by a fault occurred far from the substation. However, if the DG source has relatively low impedance when compared to the substation, in a distribution system with high­ capacity DG sources (e.g., 30 and 50 percent), the magnitude of current caused by a fault occurred close to the DG source can be greater than that caused by a fault occurred close to the substation. Finally, the proposed algorithm has calculated phase shifts, particularly 30°, in voltage and current of transformers balanced in delta-grounded wye or vice versa in positive- and negative-sequence networks, including a meshed network. Although this study presented a short-circuit analysis algorithm able to analyze a SLG fault on the distribution system with DG sources, it ignored load current (because it is negligibly lower than fault current) and did not implement the other fault types such as double line-to-line, double line-to- [4] [5] [6] A.R. Bergen and V. Vittal, Power Systems Analysis, NJ: Prentice Hall, pp. 311-317, 2000. V. Brandwajn and W.F. Tinney, "Generalized Method of Fault Analysis, " IEEE Transactions on Power Apparatus and Systems, vol. 104, pp. 1301-1306, 1985. C.F. Dalziel, "Analysis of short circuits for distribution systems, " Transactions on Electrical Engineering, vol. 61, pp. 757-763, 1942. G. Gross, and H.W. Hong, "A Two-Step Compensation Method for Solving Short Circuit Problems, " IEEE Transactions on Power Apparatus and Systems, vol. 101, pp. 1322-1331, 1982. T.R. Chen et aI., "Distribution system short circuit analysis-A rigid approach, " IEEE Transactions on Power Systems, vol. 7, pp. 444-450, 1992. W.H. Kersting and W.H. Phillips, "Distribution System Short Circuit Analysis, " Proceedings of the 25th Intersociety Conference, [7] [8] [9] [10] [11] [12] [13] Energy Conversion Engineering Reno, Nevada, USA, Aug. 12-17, 1990. J.H. Teng, "Fast short circuit analysis method for unbalanced distribution systems, " IEEE Power Engineering Society General Meeting, Toronto, Canada, July 13-17, 2003. J.H. Teng, "Systematic short-circuit-analysis method for unbalanced distribution systems, " lEE Proceedings Generation, Transmission and Distribution, vol. 152, pp. 549-555, 2005. J.H. Teng, "Unsymmetrical Short-Circuit Fault Analysis for Weakly Meshed Distribution Systems, " IEEE Transactions on Power Systems, vol 25, pp. 96-105, 2010. R.M. Roberge and R.G. Rhoda, "Short Circuit Study Incorporating Phase Shifting Components, " IEEE Transactions on Power Apparatus and Systems, vol. 91, pp. 1101-1107, 1972. A. Tan, W.H.E. Liu, and D. Shirmohammadi, "Transformer and load modeling in short circuit analysis for distribution systems, " IEEE Transactions on Power Systems, vol. 12, pp. 1315-1322, 1997. A. Wang, Q. Chen, and Z.P. Zhou, "Study of the phase shifting effects of transformer on fault analysis model of power system, " 2007 International Power Engineering Conference, Meritus Mandarin, Singapore, Dec 3-6, 2007. A. J. Wood, B. F. Wollenberg, G.B. Sheble, Power generation, operation, and control, New York: J. Wiley & Sons, pp.465, 2013.