Homework #1 Connect the CTs to the differential relays to properly account for the transformer phase shift a A C b c B A a B b C c R OP R R OP R R OP R 1 Homework #2 a A B c b C I230 230kV 75MVA IH TH 87 I46 46kV IL TL Given the bank information above and the information below, choose CT ratios and differential relay taps so that the relay slope is not exceeded by mismatch 230kV CT available ratios: 1200/5, 800/5, 600/5, 400/5, 300/5, 200/5, 100/5 26kV CT available ratios : 2000/5, 1200/5, 800/5, 600/5, 400/5, 300/5, 200/5, 100/5 Differential relay taps: 3.2, 3.5, 3.8, 4.2, 4.6, 5.0, 8.7 Differential relay slope: 25% 2