Technical data sheet SKM230-T-B12

advertisement
Technical data sheet
SKM230-T-B12
Control module for maximum two
damper actuators CM24K-.. in
technical building installations
• Air damper size up to approx. 0.4 m²
• Nominal voltage AC 230 V
• Control Open-close
• Power off reserve function
Technical data
Electrical data
Nominal voltage
Nominal voltage frequency
Nominal voltage range
Power consumption in operation
Power consumption in rest position
Power consumption Rest position Note
Power consumption for wire sizing
Storage energy
Connection primary
Connection secondary
Actuator - module connection
Safety
Weight
AC 230 V
50/60 Hz
AC 198...264 V
16 W
1.5 W
0 W when power off / position closed
24 VA
66 Ws
Terminal for 2 x 1.5 mm² Cu wire or
2 x 1.0 mm² Cu strands (cable Ø 4...10 mm)
Terminal for 3 x 1.5 mm² Cu wire or
3 x 1.0 mm² Cu strands (cable Ø 4...10 mm)
Cu wire: min 0.5 mm², max 1.5 mm²
Cu strand: min. 0.5 mm², max. 1.0 mm²
Length max. 200 m
Protection class IEC/EN
Degree of protection IEC/EN
EMC
Low voltage directive
Certification IEC/EN
Mode of operation
Rated impulse voltage supply / control
Control pollution degree
Ambient temperature
Non-operating temperature
Ambient humidity
Maintenance
II Protective insulated
IP40
CE according to 2004/108/EC
CE according to 2006/95/EC
IEC/EN 60730-1
Type 1
4 kV
2
-30...50°C
-40...80°C
95% r.h., non-condensing
Maintenance-free
Weight approx.
0.43 kg
Safety notes
!
www.belimo.eu
• The device must not be used outside the specified field of application, especially not
in aircraft or in any other airborne means of transport.
• Caution: Power supply voltage!
• Only authorised specialists may carry out installation. All applicable legal or
institutional installation regulations must be complied during installation.
• The device may only be opened at the manufacturer’s site. It does not contain any
parts that can be replaced or repaired by the user.
• The device contains electrical and electronic components and must not be disposed
of as household refuse. All locally valid regulations and requirements must be
observed.
SKM230-T-B12 • en-gb • 2015-09-22 • subject to changes
1
Control module for maximum two damper actuators
CM24K-.. in technical building installations
SKM230-T-B12
Product features
The Power off reserve function characterises the behaviour of the controlled module
and/or the connected damper actuators in the event of an electricity interruption or
a power shutdown. It is guaranteed in such cases that the actuators will move into
Closed position, no matter which position they happen to be presently located at, at all
times and without manipulation. The storage energy loaded in the module during the
Opening function ensures this.
Mode of operation
The module SKM230-T-B12 can only be used with the appropriate air damper
actuators CM24K.. and works within the application with one or two actuators. The
compact design of the module makes it possible to install in hollow ceiling spaces or
raised floors - if needed up to 200 m away from the application.
Application
Electrical installation
• Caution: Power supply voltage!
• The module can also be operated with only one damper actuator.
Notes
!
Wiring diagrams
CM24K..
CM24K..
+
–
+
–
~
T
2
1
2
1
2L
1N
3
OUT 1
3
OUT 2
AC 198 ... 264 V
50/60 Hz
IN
Dimensions [mm]
Dimensional drawings
168
30
20 ... 25
100
140
2
SKM230-T-B12 • en-gb • 2015-09-22 • subject to changes
www.belimo.eu