Boston Gear® Ratiotrol® DC Motor Speed Control Installation and Operation Doc. No. 86986 VEL-RG Series 1/6 – 1 HP VEH-RG Series 1 – 5 HP Table of Contents Section I Introduction . . . . . . . . . . . . . . . . . . . . . . . . . 3 General Description . . . . . . . . . . . . . . . . . . 3 Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Operator Controls. . . . . . . . . . . . . . . . . . . . . 3 Model Types . . . . . . . . . . . . . . . . . . . . . . . . 3 Controller Identification . . . . . . . . . . . . . . . . 3 Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Operation Conditions . . . . . . . . . . . . . . . . . 4 Performance Characteristics . . . . . . . . . . . . 4 Standard Features . . . . . . . . . . . . . . . . . . . . 4 Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . 5 Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Principles Of Operation . . . . . . . . . . . . . . . . 5 Section II Installation . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Mounting Instructions . . . . . . . . . . . . . . . . . 6 Wiring Instructions . . . . . . . . . . . . . . . . . . . . 7 Initial Startup . . . . . . . . . . . . . . . . . . . . . . . . 8 Section III Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Power On/Off . . . . . . . . . . . . . . . . . . . . . . . 10 Run . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Speed Control . . . . . . . . . . . . . . . . . . . . . . 10 Reversing . . . . . . . . . . . . . . . . . . . . . . . . . 10 Jogging . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Inoperative Controller . . . . . . . . . . . . . . . . 11 Section IV Maintenance . . . . . . . . . . . . . . . . . . . . . . . 12 General . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Adjustment Instructions . . . . . . . . . . . . . . . 12 Troubleshooting . . . . . . . . . . . . . . . . . . . . . 14 Section V Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Section VI Option Combinations . . . . . . . . . . . . . . . . . 18 Section VII List of Illustrations Figure No. 1 Four-Quadrant Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Figure No.2 Enclosure Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 6 Figure No.3 Chassis Dimensions . . . . . . . . . . . . . . . . . . . . . . . . 6 Figure No.4 Dimensions Operator Control Station . . . . . . . . . . . . . . 7 Figure No.5 Connection Diagram Run/Stop . . . . . . . . . . . . . . . . . 19 Figure No.6 Connection Diagram Run/Stop/Jog Selection with Jog Speed Pot . . . . . . . . . . . . . . . . . 20 Figure No. 7 Connection Diagram Run/Stop/Forward, Reverse Selection . . 21 Figure No. 8 Schematic, Control Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Figure No. 9 Schematic, Power Board 1/6 - 2 HP . . . . . . . . . . . . . . . . . . . . . . . . 23 Figure No. 10 Schematic Power Board 3 & 5 HP . . . . . . . . . . . . . . . . . . . . . . . . . 24 Figure No. 11 Internal View, Standard Controller . . . . . . . . . . . . . . . . . 25 Figure No. 12 Internal View 1/6 - 2 HP Chassis . . . . . . . . . . . . . . . . . 26 Figure No. 13 Internal View, 3 & 5 HP Chassis . . . . . . . . . . . . . . . . . . 27 List of Tables Table No. 1 Operator Control Stations . . . . . . . . . . . . . 3 Table No. 2 Typical Application Data . . . . . . . . . . . . . . 4 Table No. 3 Speed Regulation Characteristics . . . . . . . 4 Table No. 4 Dynamic Braking Characteristics. . . . . . . 10 Table No. 5 Troubleshooting . . . . . . . . . . . . . . . . . . . . 14 Table No. 6 Parts List, Controllers . . . . . . . . . . . . . . . 17 Table No. 7 Option Combinations . . . . . . . . . . . . . . . . 18 Illustrations . . . . . . . . . . . . . . . . . . . . . . . . 19 2 Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control Section I General Information Introduction Model Types This equipment manual contains installation, operation, and maintenance instructions for VEL/HRG Single-phase Adjustable Speed Regenerative DC Motor Controllers. A parts list and illustrations are also included. Regenerative controllers are supplied in one of two basic model types, as follows: General Description Regenerative Controllers are high performance units which statically rectify single-phase AC line power to regulated DC for adjustable speed four quadrant armature control of DC motors. Applications include those requiring controllable bidirectional torque for overhauling loads, contactorless reversing or precise position control. These controllers comply with applicable standards established by the National Electrical Code and NEMA for industrial motor and control equipment Motors VEL/H RG controls 1/6 through 3 HP have been factory-adjusted to run with permanent magnet motors supplied by Boston Gear. The VEHRG500CM, 5 HP control has been adjusted to operate with 18500A-B or 18500ATF-B motors Operator’s Control The operator controls may be customer supplied or supplied by Boston Gear as a companion to the controller. Boston Gear’s standard operator control stations contain industrial rated components in a NEMA Type 1 TENV enclosure, as listed in Table 1. Table 1. Operator Control Stations Catalog Number 66953RS PushButtons Run-Stop Emerg. Stop Toggle Switch ----- 66954RS Run-Stop Emerg. Stop Run-Jog 66955RS Run-Stop Emerg. Stop Fwd-Rev 1.Standard-Packaged functional controller supplied in a rugged die-cast aluminum NEMA Type 12 enclosure in ratings from 1/6 through 2 HP. 2.-CM-Basic chassis-mount controller, supplied in ratings from 1/6 through 5 HP, for those who want to build their own drive system by the addition of special logic or auxiliary control devices. This model is a complete self-contained functional controller which includes a power conversion and regulator module, AC line and DC loop protection, and a motor contactor. Various pre-engineered options are available. Controller Identification Each controller contains a data label. This label identifies the controller, user connection terminals and maximum wire size, controller ratings, operation notes, and applicable options. Ratings 1. Horsepower Range . . . . . . .1/6 – 5 HP 2. Power Source . . . . . . 115 VAC, 1-phase, 50 or 60 Hz. 3. 115VAC Unit Output Voltages (1/6-1HP) Armature . . . . . . . . . . . . . . . .0-90 VDC Field . . . . . . . . . . . . . . . . . . . .100 VDC 4. 230VAC Unit Output Voltages (1-5HP) Armature . . . . . . . . . . . . . . .0-180 VDC Field . . . . . . . . . . . . . . . . . . . .200 VDC 5. Service Factor . . . . . . . . . . . . . . . . .1.0 6. Duty . . . . . . . . . . . . . . . . . . .Continuous 7. Overload Capacity (Armature Circuit) . . .150% for 1 minute 8. Reference Power Supply . . . . .±10 VDC Potentiometer (2) Motor Speed 100-0-100 Motor Speed 100-0-100 Jog Speed 30-0-30 Motor Speed 0-100 Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 3 Section I General Information Table 2 Typical Application Data Component Line 1-Phase Ac Input (Full Load) DC Output (Full Load) 115V Unit Amps 230V Unit Rated Horsepower 1/2 3/4 1 1 1/2 1/6 1/4 1/3 3.9 6.0 8.7 12.4 15.8 5.0 --- 2 3 5 --- --- --- --- --- --- --- --- 8.8 12.6 17.0 22.0 35.0 .48 .58 .71 1.0 1.4 2.0 Motor Armature 90V 2.0 2.8 3.5 5.4 8.1 10.5 --- Amps Motor Field Amps (max) --2.0 --- --2.0 --- --- --2.0 2.0 --- --- --2.0 --- 5.5 2.0 2.0 8.2 --2.0 11.6 15.1 24.0 ------2.0 2.0 2.0 0.5 0.75 1.0 1.5 2.2 3.0 4.5 6.0 KVA 180V 100V 200V Full-Load Torque (lb. ft.) with 1750 RPM Base Speed Motors Std. Ch. (1/6-2HP) Controller Weights Ch. (3-5HP) 3.0 4.0 5.0 8.0 --- --- --- 9.0 15.0 11.5 lbs (5.2 kg) 12.5 lbs (5.7 kg) 17.0 lbs (7.7 kg) Operating Conditions Performance Characteristics 1. Line Voltage Variation — ±10% of rated 2. Line Frequency Variation — ±2 Hertz of rated 3. Ambient Temperature* Standard Model Controller . . . . . . . . . . . . . .0 to 40ºC (32 to 104ºF) Chassis Model Controller* . . . . . . . . . . . . . .0 to 55°C (32 to 131°F) 4. Altitude (standard) . . . . .1000 meters (3300 feet) maximum 1. Speed Range (controlled) – 0 to motor base speed 2. Efficiency (maximum speed) a. Controller SCR regulator - 99% b. Complete drive (controller with motor, typical) - 85% 3. Displacement Power Factor (at rated speed with rated load)- 87% 4. Acceleration (standard) – By current limit 5. Speed Regulation (see Table 3) – Regulation percentages are of motor base speed under steady-state conditions. 6. Ripple Frequency - 120 Hz w/60 Hz line - 100 Hz w/50 Hz line * Temperature within the enclosure in which the Chassis is mounted. Table 3 Speed Regulation Characteristics Variable Regulation Method Standard Voltage Feedback with IR Compensation Optional Speed (Tach) Feedback Speed Range Load Change 95% Line Voltage ±10% Field Heating (1) Cold/Normal Temperature ±1.5% ±1.5% ±7.0% ±0.5% 30:1 ±0.2% ±0.2% ±0.2% ±0.2% 100:1 ±10ºC (1)Does Not Apply to Permanent Magnet Motors. Standard Features 1. Power Conversion --– Dual full-wave converter consisting of two back-to-back bridges of four silicon controlled rectifiers (SCR’s) each. Power bridges are integrated, encapsulated components. 4 2. Static Reversing--Solid-state reversal of motor armature. 3. Static Braking--Smooth regenerative braking under the following conditions: Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control Section I General Information Standard Features a. Overhauling load-whenever the driven load attempts to exceed the speed reference signal b. Speed reference change (signal reduction or change in polarity). c. Stop function-motor brakes to minimum speed before motor contactor opens. 4. Feedback-Counter EMF voltage with adjustable IR compensation. 5. AC Line Protection-AC line fuse(s) provide instantaneous protection from peak loads and fault currents. 6. DC Loop Protection-Current limit fuse provides protection from inverting faults. 7. Voltage Transient Protection-Metal oxide suppressor (varistor) across the AC line, and RC networks across the power bridges, minimize effects of high voltage spikes from the AC power source. 8. Isolated Regulator-Internal DC circuits are isolated from the AC power circuitry for operator and equipment safety and simplified application. The control reference input common may be grounded or connected without additional isolation to other drive controllers or grounded output process controllers or grounded output process controllers. Isolation eliminates line voltage to ground potentials on the MOTOR SPEED potentiometer 9. Control Transformer-24-volt secondary isolates operator controls and magnetic control logic from the AC power source for operator protection. 10. Motor Contactor-Provides positive disconnection of motor armature from the controller output, and undervoltage protection. Contactor is sequenced with the regulator so that the controller is turned off before the contactor makes or breaks, thereby providing contact longevity. Adjustments The following potentiometers are located on the standard control circuit boards in the controller: 1. Current Limit (common forward and reverse circuits)--50 to 150% of full-load torque 2. Gain (motor stability, factory set)--Adjustable 3. 4. 5. 6. for individual motor characteristics IR (load) Compensation – 0 to 100% of rated load Maximum Speed (common forward and reverse circuits) 60 to 100% of motor base speed Phase Shift (factory set)--Adjustable for individual motor characteristics Error (factory set)--Line frequency calibration Options Standardized pre-engineered optional equipment can be supplied with controllers at additional costs. See Section VI for option listing. Principles of Operation VEL/H RG Regenerative Controllers, also known as four quadrant controllers, not only control motor speed and direction of rotation, but also the direction or motor torque. See Figure 1. Figure 1. Four-Quadrant Operation QUADRANT II QUADRANT I MOTOR ROTATION TORQUE QUADRANT III QUADRANT IV NOTE: Arrows Same Direction Motoring (Pulling) Arrows Opposite Direction Braking (Holding) Under braking conditions, controllers convert the mechanical energy of the motor and connected load into electrical energy, which is returned (regenerated) to the AC power source. With reference to Figure 1, page 5, when the drive (controller and motor) is operating in Quadrants I and III, motor rotation and torque are in the same direction, and the drive functions as a conventional nonregenerative unit. In Quadrants II IV, motor torque opposes the direction of motor rotation, which results in controlled braking. The drive can switch rapidly from motoring to braking modes while simultaneously controlling the direction of motor rotation. Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 5 Section II Installation 3. Shock-mount the controller if it is subjected to external vibrations. Shock and excessive vibrations are detrimental to controller performance and life. Vibration can cause general deterioration of connections, and component damage. 4. Standard operator control stations can be wall-mounted using the two holes in the back of the enclosure. See Figure 4. 5. If the motor is to be foot-mounted, bolt the motor to a firm, flat foundation. If the foundation is not flat, use shims to prevent strain when tightening the bolts. If the motor is to be connected directly to a machine, be sure of correct alignment. Pulleys and couplings must slip freely onto the motor shaft. Mounting Instructions 1. Surface mount the controller in a dry location with the mounting holes (or tabs) provided. The standard enclosure should not be used where a watertight, weatherproof, or explosion proof enclosure is required. See Figure 2 or 3 for mounting dimensions. Caution Never Mount The Controller Immediately Beside Or Above HeatGenerating Equipment, Or Directly Below Water And Steam Pipes. 2. Allow for free air circulation around the controller-four inches minimum clearance on all sides, for maximum cooling efficiency. If the controller is user-mounted in an enclosure, allow for adequate ventilation. Air passages into the bottom, with exit openings near the top, form an adequate configuration. If a small enclosure is used, a ventilation fan may be required. Max. Control Proj. 1.33 .65 (34) (17) Control Panel 9.34 (237) 6.00 (152) Never hammer the pulleys, couplings, or motor shaft, nor overtighten drive belts or timing chains. Bearing damage could result. 1.35 (34) 12.00 (305) 1.75 (44) Caution D Mounting Slots Width .25 (6) W M2 M3 M4 D 8.59 (218) 1.20 (30) Conduit Entrance ¾-14 N.P.T. (4) Places 10.55 (268) 6.0156 (153) 9.06 (230) 16.81 (427) .25 (6) Figure 2. Enclosure Dimensions Model HP VEL/H RG16-200CM VEH RG300/500CM Dimensions (Inches) W H 1/6-2 9 7/8 13 3-5 12 3/4 13 M1 D 12 1/4 6 9/16 12 M4 M3 Holes 5 3/8 2 7/16 3/16 1/2 7/16 9/32 6 1/4 11 3/8 Figure 3. Chassis Dimensions 6 M2 Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control Section II Installation Wiring Instructions 1. Refer to the nameplate in the controller and be sure the input voltage and frequency to the controller complies with its rating. 2. The controller is protected from normal line transients and surges. However, to prevent problems from high-energy transients and large surges, observe the following: a. Place the controller on a feeder line separate from that supplying large inductive loads. b. If the input to the controller comes directly from a transformer, always switch power ON and OFF between the transformer secondary and the controller. Caution Never make or break power in the transformer primary. Transients could be generated which could damage the controller. c. If the controller must be fed from an AC feeder which also feeds highly inductive loads, supply additional suppression to limit transients or surges to 150% of peak line voltage. 2.06 (52) 3.00 (76) 1.12 (28) Dia. One End 1.50 (38) .88 (22) Max. Control Proj. 3.00 (76) .19 (5) Dia. (2) Holes Caution 1. Oversize or solid wire, as well as large screwdrivers for electrical connections, can break terminal board barriers. 2. All wiring must comply with the national and local electrical codes 4.Use the 3/4-14 NPT tapped conduit holes in the enclosure of standard controllers to facilitate wiring. 5. All external wiring for low voltage signal sources; e.g., potentiometers, tachometer generators, transducers, should be run in separate conduit from all other wiring. Use twisted shielded cable. Maintain the separation of power and signal wiring within an enclosure by two inches minimum. Caution Pickup from unwanted signals can cause erratic operation and / or controller damage. 6. Since the DC circuits are isolated from the AC input power, the reference input common can be grounded, or connected without additional isolation to other drive controllers or grounded output process controllers. 7. Interconnection wiring is required between the controller, AC input power, operator controls, and applicable optional equipment. 7.50 (191) 1.62 (41) 3. The wire size of the input power and motor wiring can be determined from Table 2 and the controller data label. Stranded wire is recommended for all external wiring. 9.00 (229) .69 (18) AC Power Connections Caution .75 (19) Figure 4. Operator Control Station Dimensions Caution Never Use The Power Factor Correction Capacitors On The Input Line To The Controller. These Capacitors May Damage The SolidState Components Be sure metal chips from drilled conduit holes in a n enclosure do not enter the controller. Metal chips can cause short circuits and/or grounds which can damage the controller. Connect the AC input power wires to controller Terminals L1 and L2. See Figure 11, 12 or 13, as applicable. If one of the power wires is a neutral wire (grounded potential), connect it to Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 7 Section II Installation Terminal L2 and connect the hot wire (H) to Terminal L1. Connect the controller enclosure to an earth ground according to applicable electrical codes. A Ground Connection Screw (GND) is provided for this purpose in enclosed controllers. (See Figure 11) operating conditions. Therefore, startup adjustments should not be needed. However, the following startup procedure should be performed for proper operation, system compatibility, and safety. Motor Connections 1. Be sure all interconnection wiring is correct, and all wiring terminations are tightened securely. Wiring errors and accidental grounds can cause controller and/or motor damage. 2. Check the factory sealed potentiometers on the control board and be sure they are at their factory settings. See Figure 11, 12 or 13 for potentiometer locations. If any potentiometer has been moved, return it to its factory setting. NOTE: The MAX SPD (R52) and GAIN NO. 1 (R6) potentiometers are not sealed. 3. Turn the MOTOR SPEED potentiometer to zero on its dial. 4. If used, place the RUN/JOG switch in RUN position. 5. Couple the motor to the machine (load). 6. Turn on the AC power. 7. Depress the RUN button, and slowly turn the MOTOR SPEED potentiometer until the motor rotates. If motor rotation is opposite to that desired, stop the motor with the STOP button, turn off the AC input power, and interchange the motor armature leads at the motor connection box 8.Turn the MOTOR SPEED potentiometer to 100 on its dial. The motor should run at top speed. Top speed is rated (base) speed. If top speed cannot be reached, check motor armature voltage. If armature voltage is below rated, proceed as follows: Controller Minimum Rating Line Voltage 115 VAC 103 VAC 230 VAC 207 VAC a. Check for insufficient line voltage on controller Terminals L1 and L2. Minimum requirements are as follows: b. If the motor has a shunt field, check the voltage on Terminals F+ and F-. If rated line voltage is 115 VAC, the shunt Field Check the motor data plate and be sure the HP, voltage, and current ratings are compatible with ratings listed on the controller data label. Connect the motor field and armature terminals (or leads) to controller Terminals F+, F-, A+ and A-, respectively.* (See Figures 11, 12, or 13) Caution Do not ground the motor wiring. Grounded wiring can cause controller damage. NOTE* Terminals F+ and F- are not used with permanent-magnet motors Connect the motor thermal switch, if used, in series with Terminal 1 (Terminal Board TB1) on the controller power board. Operator Control Station Connections Connect the operator control station as shown in Figure 5, 6 or 7 (as applicable) Each standard operator control station contains two stop push-buttons-STOP and EMER STOP. A Stop function provides controlled regenerative braking, and an Emergency Stop function drops out the motor contactor immediately, applies dynamic braking and prevents a restart until the motor stops. If dynamic braking is impractical (due to load inertia) or is not desired, disconnect DB resistor(s). If one of the stop functions is not used, be sure to series connect the two stop buttons so that each button will stop the motor. The MOTOR SPEED potentiometer must be 10,000 ohms with a 1/2 watt minimum rating. Initial Startup Before energizing the controller for the first time, be familiar with any installed options. See the option selection table in Section VI. The controller has been factory tested and adjusted with a motor under simulated 8 Startup Procedure Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control Section II Installation voltage should be 100 VDC, ±10 VDC. If rated line voltage is 230 VAC, the shunt filed voltage should be 200 VDC, ±20 VDC c. Depress a RUN button, and turn the MOTOR SPEED potentiometer to 100 on its dial. d. Turn the MAX SPD potentiometer (R52) Caution Do not exceed rated armature voltage. Excessive armature voltage may cause the controller fuses to blow when motor speed is decreased rapidly from top speed or when a Stop function is initiated. until rated armature voltage is recorded. See Figure 11, 12 or 13 for the location of R52. e. If desired, maximum speed can be decreased to 60% of motor base speed. f. If the adjustment of Potentiometer R52 does not increase top speed, see Indication #7 in the troubleshooting table (Table 5). Also see Step 2 of this Startup Procedure. 9. If the MOTOR SPEED potentiometer has a “zero-center” for bidirectional operation, turn it fully counterclockwise to 100. The motor should run in the reverse direction at rated speed Forward and reverse maximum speeds should be identical. 10. If motor speed is unstable, proceed as follows: a.Run the motor at half speed and slowly turn the GAIN NO. 1 potentiometer (R6) clockwise until motor speed stabilizes. See Figure 11, 12 or 13 for the location of R6. If instability increases, turn potentiometer R6 counterclockwise until motor speed stabilizes. b.If the adjustment of potentiometer R6 does not stabilize motor speed, adjust R6 for minimum instability, then turn the IR COMP potentiometer (R63) counterclockwise until motor speed stabilizes. See Figure 11, 12 or 13 for the location of R63. If motor speed does not stabilize, see Indication #9 in the troubleshooting table (Table 5). Also see “Adjustment Instructions” in Section IV. 11. If the rate or acceleration of braking response is too slow, if top speed cannot be reached after performing Step 8, or if there is a probability of armature current being limited, proceed as follows: a.Turn off the AC power and connect a zero center DC ammeter in series with the motor armature. Suggested ammeters are as follows: HP Ammeter Rating Scale 1/6-2 30-0-30 3-5 50-0-50 b.Apply AC power, set the MOTOR SPEED potentiometer at 50%, and depress the RUN button. During acceleration, the ammeter should read 150% or rated armature current. Depress the STOP button, and the ammeter should again record 150% armature current. c. If 150% of rated armature current is not recorded, refer to Stop 9 of “Adjustment Instruction” in Section IV. 12. Turn the MOTOR SPEED potentiometer to 0 and depress the STOP button. 13. Close and latch the enclosure door. Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 9 Section III Operation Stop General Depress the STOP button or the EMER STOP button to stop the motor. VEL/H-RG Controllers provide the following operation functions: Run, Stop, Emergency Stop, Speed Control, and Reversing. The actual operator controls and location of same will vary according to the model controller and the options selected. When the STOP button is depressed, the controller provides controlled regenerative braking When the EMER STOP button is depressed, power is removed immediately from the motor armature, and the motor dynamically brakes to a stop. An Antiplug Relay (APR) prevents the motor from being restarted until it stops. Relay APR picks up immediately after the motor starts and drops out immediately before the motor stops. APR contacts, connected in the run/stop logic, prevent an operation function until a safe minimum speed is attained. Power ON/OFF Controllers are energized when AC power is applied to the controller. Normally, this occurs when the user supplied input line disconnect switch or circuit breaker is turn on. Run NOTE: If the dynamic braking is disconnected, depressing the EMER STOP button will cause the motor to stop at a rate proportional to the deceleration (coast) rate of the driven load. To start the motor, depress the RUN button, and the motor will accelerate to the setting of the MOTOR SPEED potentiometer. Speed Control Dynamic braking provides exponential rate braking of the motor armature, which occurs when the circuit opens between the controller and the motor armature, and a Resistor (DB) connects across the armature. Motor speed is directly proportional to the setting of the MOTOR SPEED potentiometer. This potentiometer may be adjusted while the motor runs or may be preset at any position before the motor is started. When an Emergency Stop (dynamic braking) function is initiated, the motor functions as a DC generator and feeds the kinetic energy of its armature and connected load through Resistor DB where it is dissipated as heat. This opposes motor rotation, thereby stopping the motor. Reverse When a zero-center MOTOR SPEED potentiometer is used, turning it one direction rotates the motor in a particular rotating direction at a speed directly proportional to the potentiometer setting. Turning the potentiometer in the opposite direction, rotates the motor in the opposite direction at a speed directly proportional to the potentiometer setting. When the potentiometer is in center position, motor speed is zero. Resistor DB is rated to provide initial braking torque as shown in Table 4. Caution High inertia loads and / or armature voltage higher than rated may extend braking time beyond the wattage rating of the resistor. Table 4. Dynamic Braking Characteristics Component Braking Torque % Stops Per Minute 10 Unit 115V Rated Horsepower 1/6 1/4 1/3 1/2 3/4 1 1 1/2 2 3 5 300 215 170 110 75 60 --- --- --- --- 230V --- --- --- --- --- 220 115V 9 6 5 5 4 4 --- --- --- --- 230V --- --- --- --- --- 4 3 3 4 4 Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 145 105 170 100 Section III Operation Jog Controller are capable of jogging, but Option 9 must be selected for the function. If jogging is installed, place the RUN/JOG toggle switch in JOG position and jog the motor with the RUN button. Jog is momentary, causing motor rotation only while the RUN button is depressed. Release the RUN button to stop the motor. Jog speed is controlled by a separate JOG SPEED potentiometer, adjustable from 0 to 30% of motor base speed. Inoperable Motor If the motor stops and/or won’t start, check the controller for a blown fuse. See Figure 11, 12 or 13 for fuse locations. The fuses provide instantaneous protection for the solid-state components from fault currents and peak loads. Therefore, if a fuse blows replace it with an exact replacement. Caution Do not substitute fuses. Substitute fuses can cause controller and/or motor damage. If the replacement fuse blows, turn off the AC power and refer to the troubleshooting table in Section IV of this manual. Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 11 Section IV Maintenance Maintenance WARNING 1. CONTROLLERS CONTAIN HIGH VOLTAGE WHICH CAN CAUSE ELECTRIC SHOCK RESULTING IN PERSONAL INJURY OR LOSS OF LIFE. 2. NEVER CLEAN, REPAIR OR ADJUST THE CONTROLLER WITH THE AC POWER ON. General Controllers require very little maintenance, other than occasional visual inspection and, if necessary, external cleaning. They must be kept dry and reasonably free from dust, dirt, and debris. No parts require periodic replacement. Maintain the motor according to maintenance instructions supplied by the motor manufacturer. Visual Inspections 1. Be sure all wires are fastened securely. 2. Check components for damage due to overheating or breakage. All damaged and/or faulty components must be replaced satisfactory operation. Adjustment Instructions Controllers are factory adjusted with a motor under simulated operating conditions. Therefore, except for initial startup adjustments (see Section II), readjustments should not normally be needed. However, if circuit boards are replaced, or to make the controller compatible with another type motor, the following adjustments can be made. All adjustments must be made in strict conformance to the following instructions. Refer to Figure 11, 12 or 13 when performing the adjustment instructions. Equipment Required 1.Ungrounded oscilloscope or an oscilloscope isolated from the AC supply. 2.A zero center DC ammeter (1/6-2 HP 30-030 scale; 3-5 HP, 50-0-50 scale). 3.Digital voltmeter or a multimeter with minimum input impedances of 20,000 ohms/volt DC and 5,000 ohms/volt AC. 4.Tachometer (useful, but not required). 12 Power on Adjustments 1.Turn on the AC power. 2.Connect the oscilloscope probe to Pin #1 of Integrated Circuit U9 (or Test Point TP5, if provided), located on the control board. Be careful not to short circuit the pins on U9. 3. Adjust the POS ERROR (FWD RAMP) potentiometer (R81) until the negative peaks of the waveform on the oscilloscope are at zero volts, as shown below. +10V 0 Positive Peaks Negative Peaks NOTE: If negative peaks are less than zero volts, unstable operation and/or fuse blowing will occur. 4.Connect the oscilloscope probe to Pin #7 of U9 (or Test Point TP6, if provided). 5.Adjust the NEG ERROR (REV RAMP) potentiometer (R89) for the results described in Step 3. 6.Uncouple the motor from the load (machine). 7.Set the MOTOR SPEED potentiometer at zero. 8.Depress the RUN button and slowly turn the MOTOR SPEED potentiometer to 50% in either direction. Check for stable motor speed. If motor speed is unstable, see Indication #9 in the troubleshooting table (Table 5). 9.With the MOTOR SPEED potentiometer set at 50%, alternately depress the STOP and RUN buttons while observing the ammeter. During acceleration and braking, armature current should reach 150% of rated. If necessary, adjust the CUR LIMIT potentiometer (R16) to attain 150% rated armature current immediately after a RUN or STOP button is depressed. NOTE: If the controller contains bidirectional linear acceleration or “soft” acceleration/deceleration, the rate of acceleration must be set at minimum to attain the correct results when performing Step 9. 10. Turn the MOTOR SPEED potentiometer toward zero until the motor is running approximately 50 RPM. Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control Section IV Maintenance 11. Connect the oscilloscope probe to Test Point TP2 on the control board. 12. Turn the CUR STBLY potentiometer (R28) clockwise until the waveform frequency is 60 Hertz. Then turn Potentiometer R28 counterclockwise until the waveform frequency is 120 Hertz. 13. Stop the motor and recouple it to the load (machine). 14. Depress the RUN button and run the motor at half speed in the rotating direction so that Terminal 2 on the input board is positive, with respect to Terminal 4. This is normally the forward rotating direction. 15. Connect the oscilloscope probe to Test Point TP1 on the control board. 16. a. Slowly turn the GAIN NO. 2 Potentiometer (R11) clockwise until the peaks of the waveform become unequal in voltage (height) as shown below. 16ms Unequal Peaks b. Slowly turn GAIN NO. 2 Potentiometer (R11) counterclockwise until the waveform peaks are equal, as shown below. 16 ms Equal Peaks 17. With the motor running at half speed, turn the GAIN NO. 1 Potentiometer (R6) counterclockwise until the waveform becomes unstable. Then turn potentiometer R6 clockwise until the waveform stabilizes. 18. Connect the oscilloscope probe to Test Point TP3 on the control board. 19. Slowly turn the IR COMP potentiometer (R63) counterclockwise until the oscilloscope displays minimum AC ripple. If motor speed is unstable, turn potentiometer R63 counterclockwise until motor speed stabilizes. 20. Adjust the 0 SHIFT Potentiometer (R47) for minimum AC ripple at Test Point TP3. If motor is unstable, turn IR COMP Potentiometer R63 counterclockwise until motor speed stabilizes. 21. Set maximum speed as described in Steps 8d through 8g under “Initial Startup” in Section II. 22. Stop the motor, turn off the AC power and disconnect all test equipment. Troubleshooting Most electrical failures are caused by incorrect connections, overload, or the accumulation of dirt, dust or moisture. Dirt and dust deposits limit the transfer of heat from the solid-state components. Moisture, usually caused by either “wash-down” or condensation, can cause insulation failures and short circuits. Be sure the controller is clean and dry before doing troubleshooting. WARNING BE SURE THE AC POWER IS TURNED OFF BEFORE WORKING ON THE CONTROLLER. If repeated fuse blowing and/or power bridge failures occur, turn off the AC power and protect the Power Bridge (BR1) by connecting a 4 ohm, 300 watt resistor in series with the Current Transformer (CT1) primary, as follows: HP Rating 1/6-2 3-5 Installation Instructions Remove the wire from Tab E1 on the power board, and connect the resistor between the wire and Tab E1. Remove the wire from Terminal 10 at Terminal Board TB-2 on the power board and connect the resistor between the wire and Terminal 10. Then, check the AC input power for transients (high level spikes) or rapid power fluctuations. Remove the resistor after the cause of failure has been corrected. If a circuit board fails, check all inputs to the board for proper values before replacing the board. Install a resistor, as described above, before applying power to a new circuit board. If the controller operates correctly, turn off the AC power and remove the resistor. Use standard troubleshooting procedures; e.g., continuity checks, to detect faults in relay and switching logic and operator controls. Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 13 Section IV Maintenance Maintenance Table 5. Troubleshooting Indication 1. AC Line Fuse (F1, F3) blows when power is applied to controller 2. AC Line Fuse (F1, F3) blows when motor starts to turn 3. AC Line Fuse (F1, F3) blows while motor is running Possible Cause Wiring faulty or incorrect Circuit, component, or wiring grounded Power Bridge (BR1, BR2) shorted Power board failure Control board failure Shunt field shorted or grounded Power Bridge (BR1, BR2) shorted Motor shorted or grounded Control board failure causing SCR’s to turn on fully Low line voltage Overload Loose or corroded connection. Wiring faulty, incorrect or grounded Top speed set too high 4. Armature Fuse (F2) blown Motor shorted or grounded SCR breaking down (intermittently shorting) in Power Bridge (BR1, BR2) Control board failure causing SCR false firing or misfiring Overload 5. Fuses not blown, but motor won’t run Wiring faulty, incorrect, or grounded between the controller and motor. Armature shorted or grounded AC line open 6. Motor rotates when speed reference is zero Operator controls or relay logic inoperable MOTOR SPEED potentiometer failure Motor Failure Control, input or power board failure High line voltage Power Bridge (BR1, BR2) shorted Control or input board failure 14 Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control Corrective Action Check all external wiring terminating in the controller. Remove unwanted ground. Replace shorted power bridge Replace power board. Replace control board. Repair or replace motor. Replace shorted power bridge. Repair or replace motor. Replace control board Check for rated line voltage, ±10%, controller AC line terminals. Check shunt field current. Insufficient shunt field current causes excessive armature current. If field current is OK, check for mechanical overload. I If the unloaded motor shaft does not rotate freely, replace motor bearings. Also check for shorted armature. Check fuse terminals and all terminals, connections and wiring between the line, controller and motor. See Steps 8d through 8g under “Initial Startup” in Section II. Repair or replace motor. Replace faulty power bridge. Replace control board. Check shunt field current. Insufficient shunt field current causes excessive armature current. If field current is O OK, check for mechanical overload. If the unloaded motor shaft does not rotate freely, replace motor bearings. Check wiring and connections Repair or replace motor. Be sure external disconnect switch or circuit breaker is turned on and ra rated AC power is applied to controller. Repair accordingly. Replace potentiometer. Repair or replace motor. Replace faulty board. Check for rated line voltage, ±10%, on controller AC line terminals. Replace shorted power bridge. Replace faulty board. Section IV Maintenance Maintenance Table 5. Troubleshooting Indication 7. Motor does not attain top speed Possible Cause Low line voltage Overload 8. Motor runs at fast speed only 9. Unstable speed MOTOR SPEED potentiometer failure MAX SPEED potentiometer (R52) misadjusted Control or input board failure Power Bridge (BR1, BR2) failure Power Bridge (BR1, BR2) failure Control board failure Feedback circuit open AC line voltage oscillating Oscillating load connected to the motor Motor failure SCR’s misfiring or false firing 10. High, unstable speed, low torque 11. Top speed only 1/2 (approximately) of motor base speed and motor noisy (possible half-waving) 12. Motor surges when starting 13. Line and armature current excessive 14. Shunt field current insufficient Armature and field connections interchanged Power Bridge (BR1, BR2) failure Power Bridge (BR1, BR2) breaking down Faulty control board Power Bridge (BR1, BR2) breaking down (shorting intermittently) Faulty control board Overload Open shunt field winding or wiring to the shunt field Field bridge failure 15. Shunt field current excessive Field bridge failure Shunt field windings shorted Corrective Action Check for rated line voltage, ±10%, on controller AC line terminals. Check shunt filed current. Insufficient shunt field current causes excessive armature current. If filed current is OK, check for mechanical overload. If Unloaded motor shaft does not rotate freely, replace motor bearings. Also check for shorted armature. Replace potentiometer. See Steps 8d through 8g under “Initial Startup” in Section II. Replace faulty board. Replace faulty power bridge. Replace faulty power bridge. Replace faulty board. Check for open Resistor (R5-R8) and feedback board. Observe line voltage with voltmeter or oscilloscope. If oscillations occur, contact electrical or local utility company. Correct condition accordingly. Check motor brushes and replace if needed. Repair or replace motor. Replace Power Bridge (BR1, BR2) and/or control board. Check controller-to-motor wiring. Replace faulty power bridge. Replace faulty power bridge Replace control board. Replace faulty power bridge. Replace control board. Check shunt field current. Insufficient shunt field current causes excessive armature current. If field current is OK, check for mechanical overload. If unloaded motor shaft does not rotate freely, replace motor bearings. Also check for shorted armature. Check motor shunt field and associated circuitry for loose connection or broken wire. Replace field bridge (Diodes D1, D2, D3, D4) or power board. Replace field bridge (Diodes D1, D2, D3, D4) or power board. Check shunt field current and/or measure shunt field resistance and compare with motor data plate. Repair or replace motor. Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 15 Section IV Parts List Maintenance Table 5. Troubleshooting Indication 16. Motor thermal switch open (if so equipped) Possible Cause Ventilation insufficient Motor armature drawing excessive current Motor overheating from friction Shorted motor windings faulty bearings 16 Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control Corrective Action Free the motor intake and exhaust screens from dirt, dust and debris. Check shunt field current. Insufficient shunt field current causes excessive armature current. If field current is OK, check for a mechanical overload. Check for misalignment. Realign motor. Repair motor. Section V Options Parts List Table 6. Parts List Boston Part Number Drawing Designation APR BR1, BR2 --------F1 F2 F3 ------------RV1 DB Description Relay, Antiplug Power Bridge Control Board Latch Fuse, Line Fuse, Armature Fuse, Line Feedback Board Input Board Power Board Varistor Resistor, Dyn. Brake 115 VAC 230 VAC 1/6-1 HP 1-2 HP 3-5 HP 60263 66940 66936 63817 66946 66946 66952 66945 66943 66937* 60878 66920 60263 66940 66936 63817 66946 66946 66947 66945 66943 66937* 60878 66920 60263 66942 66936 63817 66949 66949 66951 66945 66943 66938* 60878 66924 NOTE: *Specify horsepower when ordering. Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 17 Section VI Option Combinations Illustrations Table 7. Option Combinations All VEL/H RG Controllers are supplied, as standard, with Dynamic Braking. Other options are listed below. Only one option from Group “C” can be utilized in a single control. Group No. A 18 Description Remarks 4 -- Dynamic Braking Unidirectional Operation -21 Direction by Selector Switch 10-Turn Speed Pot Standard Standard, by reconnection of of remote station to input board Specify Remote Station Item No. 66955 Specify Kit No. 66929, for installation in remote station-unidirectional only B 9 Jog by Selector Switch, Adjustable Specify Remote Station Item No. 66954 C 17 17S 22 25 Adj. Bidirectional Linear Accel. “Soft” Accel/Decel DC Tach. Follower DC Signal (ma) Follower Specify Specify Specify Specify D 24 DC Tach. Feedback Specify Item No. 66932 Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control Item Item Item Item No. No. No. No. 66925 66926 66930 66935 Run Emer. Stop Stop Motor 100 Speed 0 10K, 1/2W 100 GND Station 4 3 2 1 7 6 5 8 12 11 10 9 Notes: 1 6 5 4 2 3 TB1 1 2 3 4 5 6 Controller Power Board 1. Add wires 1 thru 9 from operator control station to TB1 and TB3 in the controller. 2. Wires 7, 8 and 9 must be 3-conductor twisted and shielded cable-such as Alpha No. 2258/3. 3. Connect shield of wires 7, 8 and 9 to controller or enclosure ground. 4. For unidirectional operation move wire 7 to TB3-3 and remove the 100-0-100 label on the run speed dial. Beneath this label is the 0-100 legend. 1 2 3 4 5 TB3 9 8 7 Part #66953 Figure 5. Connection Diagram, Run/Stop, Remote Control Station, 7 8 9 TB1 13 Input Board Section VII Illustrations Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 19 20 Jog Run Emer. Stop Stop Motor 100 Speed 0 10K, 1/2W 100 Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control GND Station 4 3 2 1 7 6 5 8 12 11 10 9 Notes: 1 6 5 4 2 3 1 2 3 4 5 6 TB1 Controller Power Board 1. Add wires 1 thru 9 from operator control station to TB1 and TB3 in the controller. 2. Wires 7, 8 and 9 must be 3-conductor twisted and shielded cable-such as Alpha No. 2258/3. 3. Connect shield of wires 7, 8 and 9 to controller or enclosure ground. 4. For unidirectional operation move wire 7 to TB3-3-4 and remove the 100-0-100 label on the run and jog dials. Beneath this label is the 0-100 legend. 9 1 8 2 7 3 4 5 TB3 Figure 6. Connection Diagram, Run/Stop/Jog Selection with . Remote Control Station, Part #66954 7 8 9 TB1 13 Input Board Section VII Illustrations EMER STOP STOP RUN FWD REV 11 8 10 6 3 2 5 0 100 2 1 4 3 6 9 7 11 Remote Station 66955 5 4 3 2 1 TB1 9 8 7 6 10 10 13 9 12 11 11 NOTES: 9 1 8 2 7 3 10 4 5 TB3 1 6 5 4 2 3 TB1 1 2 3 4 5 6 Controller Power Board 1. Add Wires 1 thru 10 from operator control station to TB1 and TB3 in the controller. 2. Wires 7, 8 and 9 must be 4-conductor twisted and shielded cable-such as Alpha No. 2258/4. 3. Connect shield of wires 7, 8 and 9 to controller or enclosure ground. Input Board Figure 7. Connection Diagram, Run/Stop/Forward-Reverse Selection, Remote Control Station Part # 66955 1 4 Motor Speed Section VII Illustrations Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 21 22 4 R5 47 27k R3 R1 47 +24v +12v 8 6 -12v Sum 7 10 R1 1k Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control J5 Power XFMR Off Regen. To Stop 20 VAC Sync XFMR P5 To Power BD Current XFMR Arm Feedback 21 22 20 19 +12v 16 17 82.5k 1% R4 1k R3 D2 D1 14 15 13 5 9 12 11 10 6 1 4 D8 R134 D30 IN5393 (2 PL) D31 C9 .47 100k C36 + 50/ 50v D34 D35 R150 100 R71 R70 22k R69 22k R52 10k 68k Q22 R151 220 Q24 10k 1% G R19 100k R53 10k 10 R153 Q25 Q23 4.7 R152 Q27 MJE234 D39 D38 D36 D37 Q26 + 47k R145 47k .01 C12 C41 .1 Q20 .01 +12v C13 C42 .1 14 Q21 13 U22 3146 C43 .1 R147 +12v 22k +12v 27k R78 R79 27k 2.2m +12v 27k R80 C14 .01 .01 C15 3 2 1611 76 10 74C 12 1 221 4 9 8 1514 R65 2.2k 14 3 -12v 100k 1% R86 R87 100k R84 10 R88 C17 .1 +6v +12v TP5 C18 3.3k R85 4.7 C19 6.8/35v TP6 C22 .1 C20 .1 R92 9 8 +12v U2F -12v 2.2k +12v Ramp Reset Ramp Reset 10 13 R94 U11D C21 10 .1 R93 Alt Cycling Alt Cycling Alt Cycling R83 2 - .047 9 22k 1 + 14 11 74C 10 3 324 + U9B 8 339 - U11C 914 U2E Alt Cycling C16 Ramp Reset Ramp Reset Direction Direction Phase Control +12v +12v Rev 1 Fwd 1 Phase Control +12v 4011 4 5 U3B U3A 13 4011 11 12 .047 6 5 324 + 4 R91 14 1 4011 2 7 U14A 9 - 100k 1% 8 324 + U9C 11 -12v W1 U4B 6 14 1 4011 2 7 U18A W2 4023 Neg. Error U14C R89 100 R90 6 4 4 - 100k 150k 5 4011 339 5+ U14D U10D 4011 U14B 4011 13 11 12 4011 U8C 9 10 8 4011 U8D 3 4 3 5 11 10 4023 U4A 12 R81 100 R82 4 +12v 6 100k 50k 4011 339 U8B +6v 7 + U9C U6D 4011 3 27 1 W4 +12v 8 14 4011 10 7 9 U3D W3 Pos. Error 6 - U7D U2B 1 5 +324 7 74C 914 R66 22k 12 11 4011 13 6 4 4011 5 U6B 9 Q7 R36 10 4011 8 R35 100k U6C C5 .1 10 +12v 14 U2A 74C 914 4 +12v 7 +12v R95 1k 8 64 1 2 3 R155 D14 1k R154 5 7 C27 .01 C24 .01 8 U17 7 455 6 4 1 5 2 3 R97 TP7 1 7 4023 9 8 +12v D22 R124 3 8 10k U21 12 2 455 7 R125 13 10 2.2k 9 4012 64 1 5 1 C31 C32 U19B 1 .01 .01 3 R157 Inhibit 2 4001 U16D 1k Start Up R116 +12v 10 R114 D18 +12v 3 8 10k U20 2 2 455 7 R115 1 4 2.2k 5 4012 64 1 5 3 C28 7 U19A 5 .01 R156 4 C29 Inhibit 6 4001 U16C 1k .01 Start Up 10k R106 22k C26 13 .01 Inhibit 12 4001 11 Start Up U16B 11 13 9 10 4012 12 U15B R105 10k 3 14 R96 4 1 2.2k 5 4012 2 U15A +12v C23 .01 9 Inhibit 8 4001 10 U16A Start Up +12v U5D +12v 8 10 9 4011 U5D +12v 10 D10 W5 1 14 3 2 4011 U3C 1 3 2 4011 13 5 11 4 12 4011 6 4011 U5C U5B Figure 8. Schematic Control RG, Figure 8. Schematic ControlBoard Baord VEL/H VEL/H RG, Part #66936 Part #66936 -12v C39 4/50v C44 .1 R77 27k R64 100k +12v R56 -12v 10 C8 .1 100k R22 47k R33 R34 220k +12v Q6 R27 100k 3 2 1611 7 6 10 74C 12 4 1 221 14 9 8 15 +12v Q19 U22 R146 3146 10k +6v R143 47k R144 47k +6v C38 4/50v R142 100k R141 100k R140 10k Q3 R21 22k R24 R55 2 49.9k1% - U7C 324 1 + 3 R26 100k 47k R23 R20 220k R75 10k 13 74C 12 +12v 914 U2C R76 +12v 10k 5 74C 6 914 U2D +24v R139 47k 220k .01 + 339 - U11B R74 R73 C11 R72 C10 5 + 220k .01 2 4 339 - U11A U22 R137 Q18 5 C34 10k 4 6.8/ 35v R138 3146 3 4.7k R136 10k +24v 10k 1% U22 Q171 2 3146 + R135 3 C33 10k 68/ 35v -24v D33 C35 250/ 50v R149 22k D32 +24v IN5393 (2 PL) D29 D28 R61 R50 R25 22k 3 D 200k1% - U78 TP3 R54 324 + 14 100k1% R51 100 Q2 Q4 +24v 2 324 + U1C 3 1 R18 250k 100k 22k 100k G +12v R30 2.2M C40 C4 R28 Cur 05k Stabl .001 .22 100 R31 - TP2 10 U1C + 5 324 7 8 + 9 -324 U1B 4 R32 D Cur Lmt R15 100 R16 R17 0 D5 D4 R58 100k 1% IR 49.9k 1% R60 13 - 14 TP4 100 R630 Comp R59 49.9k 1%12324 + 100k +12v 100k R62 D40 1% 3 49.9k 14 + 12v 1% 339 8 10 +6v U10A 12 13 339 11 U10B + +6v IN5393 (2 PL) D27 D26 To Input Board J6-2 6.49 k% R68 1k 1% R67 D9 D7 8 IN5593 2 PL R57 100 7 D6 3 R42 Max Spd Q5 Q1 G 100k 3 D R6 Gain #1 0 C1 0 100 R11 6AW #2 2M .022 100 10k C2 R12 150 pf 100k 13 R13 R8 324 12 + 100k 2.2k D3 R9 -12v R14 C5 10 .1 47k R43 Shift R41 1% R47 2 1M 1% 73.2k 9 - U7A R46 25k R48 324 8 + 100 82.5k1% 3.7k 4 R45 10 C7 R49 1M 1% +12v 1.0 330k R44 10 73.2k C6 1% .1 Max Spd Pot Arm Current -12v +24v Fdbk Sum J5-6 18 15 12 13 2 820, 1/2W 9 D1 10v R4 Spd Ref R2 11 100k C1 73.2k 1% .01 1% R6 3 R5 -24v 56k 820, 1/2W D2 4 10v Spd. Error 5 Cur. Input R2 Feedback Board Comm Fwd +10 1 Spd Input 2 Rev -10 3 External Input Board J6 1 Reset C25 .1 R99 1k .47 R126 10k Q13 R111 47 Q11 R102 47 Q9 R130 47 R129 100 D23 Q15 R119 R121 10K 47 D19 R120 100 R109 10k D15 R110 100 R100 10k D11 R101 100 1k R128 10k R127 R107 10k 1k R118 C30 .1 R107 10k 1k R108 R98 10k Q8 R39 220k +24v R148 100 2w C37 100k R38 2.2k R37 +24v R103 J1 220 R131 220 Q16 220 R132 D25 IN4933 220 T4 D24 IN4933 Q14 D21 IN4933 R123 3 R122 220 4J3 T3 D20 IN4933 1 Q12 220 D17 IN4933 R113 3 R112 J2 220 4 T2 D16 IN4933 1 Q10 D13 IN4933 R104 3 T1 D12 220 4 IN4933 1 G2 + G3 AC1 G1 + G4 AC2 AC1 G2 + G3 AC2 G1 + G4 P4 To BR2 (Rev) P3 To BR2 (Rev) P2 To BR1 (Fwd) P1 To BR1 (Fwd) Notes: (Unless Otherwise Specified) 1. All Resistor Values Are in Ohms 2. All Capacitor Values are in Microfarads 3. All REsistors Are ¼ W 5% 4. All Capacitors Are 100v 10% 5. All Pots Are ½ W 10% 6. All Diodes Are IN4148 7. All RET's Are 2N5462 8. All NPN's Are 2N5462 9. All PNP's Are MP56517 10. Last Ref Designations used-R157, C40, D40, U22 11. Ref. Designations not used-R40, R133, R7 12. Jumpers-W1 thru W5 may be removed to isolate IC's (U3, U5, U8 & U14) From +12v Power Supply Section VII Illustrations To Speed Circuit L2 115V 230V Supply L1 11 T1 Emerg. Stop 5 60S6 4PL 6 E9 3 4 Com. Off BR2 1 10 + G2 .1uf 50V AC2 E15 D15 IN5393 K1 P5 G1 .1uf 50V G3 .1uf 50V AC1 10 R11 C6 + 50uf 50V M D13 R10 IN5393 D14 IN5393 K2 6 Regen To Stop E14 E16 3 K1 2 4 P5 Run Jog Run K1 K2 20V T2 7 E3 E4 G4 .1uf 50V - Main Contactor Emerg. Stop Relay Pilot Relay BR1 .1 uf 50V G3 G1 AC1 .1uf 50V - + E3 E4 R1 22 C4 .1uf 500V R4 22 P5 1% 1/3HP 1/4HP 1/6HP 115V 1HP 3/4HP 1/2HP 230V 2HP 1 1/2HP 1HP E7 M1 M1 D7 3.4 2.9 2.0 3 3 4 AMPS No. Turns 9.4 1 7.6 1 1/2 5.2 2 M1 A1 Remove 56K Res. For 180V Arm. A2 56K 2W D6 IN5397 4 PL D8 Arm. 90V/180V 2HP Max. R9 68K 2W APR D5 D8 Opt. 15 1039 50W E8 Current Transformer Turn Data TB1 TB2 R8 1M 1/4W 1% M1 R7 2M 1/2W 1% 3 1/2W E11 2 E12 NOTES: 1. Terminal Identification - E6 R3 22 .1uf C3 50V .1uf G4 500V AC2 G2 .1uf 50V E5 Figure 9. Schematic, Power Board, 1/6-2 HP Part #66937 Stop 4 115V E10 NC 6 E13 8 5 8 7 P5 2.2K R12 E1 CT1 E2 P1 P5 115V 2 C5 10uf + 50V D11 APR K2 K2 APR D9 D10 D12 24V AC E17 AC D3 D4 F- 20V E18 COM 20V E19 IN5393 4 PL Blk/Wht 115V 115V Blk D1 D2 Motor Thermal Switch Blk/Red Wht Jumper For 115V (Typ) 25A F3 Jumper For 115V RV1 25A F1 F+ 100V/200V Shunt Field Remove Jumpers For F2 180V Arm 25A (Typ) C2 R5 .1uf 1M 500V 1% R2 R6 22 2M Section VII Illustrations Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 23 24 Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 1 60A F3 3 1 APR K2 CT1 K2 K1 K2 4 RUN RUN D11 P5 D12 E18 9 E19 12 E17 11 E16 10 E15 6 E14 1 C5 10 + 6 STOP D9 24V D10 20V 20V 8 20V E9 8 E10 7 E13 4 JOG SEE CHART 10 11 60S6 R12 4 PL 2.2K T1 APR BLK/WHT 115V BLK/RED WHT 115V BLK 1 115V 4 2 D3 D4 F- 2 1 T2 5 115V2 20V D1 D2 Emerg 5 Stop 6 RV1 70A Motor Thermal Switch L2 L1 F1 F+ 200V SHUNT FIELD 3 2 2 D14 K1 D13 + C7 0.1 G3 C10 0.1 G1 + G2 C11 0.1 G4 2 1 R3 22 1W 9 C3 0.1 500V C1 0.1 500V R1 22 1W 8 R5 IM 1% R7 2M 1/2W 1% R4 22 1W C4 0.1 500V C2 0.1 500V R2 22 1W 4 P5 2 E11 E12 3 M1 5 M1 R8 IM 1% R7 2M 1/2W 1% M1 M1 9 OPT. 1039 8 DB 15 50W 2 PL 70A F2 Unless Otherwise Specified-All Resistor Values In Ohms All Capacitor Values In Microfarads All Diodes IN5393 All Resistor 1/4w 5% All Capacitors 50v 10% TB1 TB2 Indicates Components Not Mounted On Printed Wiring Board BR1 - G3 AC2 C13 C12 0.1 0.1 AC1 Emerg Stop Relay Main Contactor Pilot Relay 4 2 1 3 Figure 10. Schematic Power Board, 3 & 5 HP Part #66938 11 K2 2.2K R10 K1 C9 0.1 G1 AC1 M1 1/2W R11 1.5K 10 BR2 C8 0.1 G2 AC2 C6 0.1 G4 - HP 3 5 7 D7 D5 6 D8 D6 A2 AMPS 14.5 24 3 R9 68K 2W IN5397 4 PL APR 4 A1 TURNS 2 1 ARM 180V MAX Section VII Illustrations 230V Neg Error Pot J5 R81 Control BD Wire Harness TP7 J1 Line Connection Terminals + Resistor DB (Option 1039) D.B Res. (Option) Line Fuse Line Fuse E13 E14 T1 Ground Connection Screw Gnd + Figure 11. Internal View, Standard Controller, 1/8-2 HP Pos Error Pot 1 U9 R89 L1 TP4 R63 + J2 J3 TB2 APR Power Board + IR Comp Pot R28 L2 TP5 TP6 TP2 7 R16 J4 A2 F+ F- TP3 R47 A1 Max Spd Pot R52 6 Shift Pot R6 5 R11 J6 4 TP1 TB1 Motor Connection Terminals 3 Input Bd TB3 Data Label 2 Feedback BD Gain No. 1 Pot Gain No. 2 Pot BR2 BR1 T2 + Arm Fuse 1 Cur Limit Pot Cur Stbly Pot P2 25A Power Bridge Power Bridge Latch Section VII Illustrations + Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 25 1 2 3 4 5 D6 D5 R9 D4 6 D2 A1 A2 F+ F- D3 L2 Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control L1 R2 R8 E12 R5 C4 C3 BR1 - 2 E6 4 5 BR2 BR1 Blk C1 C2 BR2 E8 D8 E7 D8 A 115V 115V B 230V Blk Red Blk Wht T2 Wht E9 E10 CT R3 R4 3 7 6 Resistor DB (Option 1039) Arm Fdbk E11 CT R1 R7 (Option) E2 BR1 AC2 R6 D.B. Res. D1 Line Fuse M1 BR2 AC2 1 8 BR1 + BR2 - AC Line Voltage 115 115 115 115 115 115 230 230 230 230 230 AC Line DC ARM AMPS AMPS 3.9 2.0 5.0 2.8 6.0 3.5 8.7 5.4 12.4 5.4 15.8 10.5 4.2 2.6 5.9 3.8 8.8 5.5 12.8 8.2 17.0 11.6 Unit is Calibrated For Horsepower Checked 180 VDC 200 VDC 90 VDC 100 VDC Line Voltage 115V 230V Power Bridges *Option Wiring Information Maximum Input 100 VDC at 50 VA Indicates Options Installed In Unit 10340D "S" Curve Accel 1036 Linear Accel/Decel 1039 Dynamic Braking 1049A Process Control Follower *1055A DC Tach Follower *1061D DC Tach Feedback Armature Voltage (Max) Field Voltage (2 Amps Max) Replacement Fuses F1 & F2 - Shawmut A25X25 F3 - BUS NON25 Motor Thermal Button Or Other Motor Overcurrent Protection Must Be Provided. Drive HP 1/6 1/4 1/3 1/2 3/4 1 1/2 3/4 1 1-1/2 2 MODEL 2200 Instruction Manual Data Label Hinge Hinge TP4 TP3 J5 U9 R89 1 7 Max Spd Pot Control Bd R81 TP5 TP6 TP2 R28 R11 TP1 R6 Neg Error Pot TP7 J6 TB3 J1 J2 J3 J4 Gain No. 1 Pot Gain No. 2 Pot Feedback Bd. Input Bd. R16 IR Comp Pot R63 R52 R47 o Shift Pot Cur Limit Pot Figure 12. Internal View, 1/6-2 HP Chassis, Controller CT1 E5 F2 25A D C E19 E18 E17 Listed Industrial Control Equipment + Ground Connection Screw D8 D7 BR2 AC1 E4 BR1 AC2 F1 25A K2 D9 D11 D13 Line Fuse R10 F3 25A D14 APR T1 UL ® E15 E16 E13 E14 C6 RV1 K1 C5 R11 Line Connection Terminals Motor Connection Terminals TB2 TB1 Power Bd D10 D12 D15 Arm Fuse 26 Power Board .188 Dia. Mounting Hole Ref. 4 - PL. Pos Error Pot Cur Stbly Pot Wire Harness Section VII Illustrations TB1 K1 1 3 4 5 6 1 7 APR K2 2 3 8 F1 9 4 F+ 5 RV1 7 T2 F- 1 4 Blk Whit Blk 6 8 CT1 F3 Line Fuse 10 Arm Fdbk 11 TB2 F2 M1 Motor Connection Terminals Power Bridge Line Connection Terminals BR2 D.B. Res L1 A2 A1 L2 D.B. Res Ground Connection Screw Resistors DB (Option 1039) Hinge Hinge TP3 J5 U9 TP2 Figure 13. Internal, 3 & 5 HP Chassis, Controller R11 TP1 R6 Neg Error Pot TP7 J6 TB3 J1 J2 J3 J4 Gain No. 1 Pot Gain No. 2 Pot Input Board Max Spt Pot R28 1 R89 R81 TP5 7 TP6 R16 Feedback Board IR Comp Pot R63 R52 R47 O Shaft Pot Cur Limit Pot Figure 13. Internal, 3 & 5 HP Chassis, Controller Main Contactor 9 Line Fuse Armature Fuse Model VEL/H RG Pos Error Pot Instruction Manual Book 0439 Cur Stbly Pot Data Label Wire Harness Illustrations Power Board 2 BR1 Power Bridge .188 Dia. Mounting Hole Ref. 4-PL. Section VII Illustrations Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control 27 Warranty Warranty Boston Gear warrants that products manufactured or sold by it shall be free from defects in material and workmanship. Any products which shall within two (2) years of delivery, be proved to the Company’s satisfaction to have been defective at the time of delivery in these respects will be replaced or repaired by the Company at its option. Freight is the responsibility of the customer. The Company’s liability under this limited warranty is limited to such replacement or repair and it shall not be held liable in any form of action for direct or consequential damages to property or person. The foregoing limited warranty is expressly made in lieu of all other warranties whatsoever, express, implied and statutory and including without limitation the implied warranties of merchantability and fitness. No employee, agent, distributor, or other person is authorized to give additional warranties on behalf of Boston Gear, nor to assume for Boston Gear any other liability in connection with any of its products, except an officer of Boston Gear by a signed writing. Boston Gear, Inc. 14 Hayward Street • Quincy, MA 02171 617-328-3300 • Fax: 617-479-6238 www.bostongear.com 28 Doc. No. 86986 • Boston Gear® Ratiotrol® DC Motor Speed Control Printed In The USA