VAV700 Multi-functional air volume flow controller with integrated web server Product description ● Performance features Product description High-speed adaptive control system for variable control of room supply air and room exhaust air volume flows, particularly suitable for clean rooms and laboratories. The integrated dual port switch allows a simple and effective Ethernet-networking of volume flow controllers (supply air/ exhaust air) and fume hood controllers FC700 within the laboratory and the complete building. The parameterisation and the data access occur with a standard web browser. Native BACnet®/IP with trendlog and intrinsic reporting are optional implemented. Modbus® is supported as further field bus systems. Extended requirements afford a radiator respectively a cooler as well as pressure maintenance of the room. Besides these performance features the multi-functional volume flow controller VAV700 balances all network-connected consumer loads and calculates the necessary room supply air respectively room exhaust air needed for the maintenance of the parameterised room air exchange (e. g. eightfold). A high-speed control algorithm compares the setpoint with the actual value measured by a differential pressure transmitter and controls the air volume quickly, precisely and steadily, independent of pressure fluctuations in the duct system. The system data and setpoint values (volume flow, temperature, pressure, humidity, etc.) are freely programmable and will be saved voltage fail-safe in the FLASH. Up to three freely configurable static differential pressure sensors allow the detection and regulation of the room pressure of two independent rooms besides the volume flow regulation. Up to four free slots allow a flexible and cost-effective adjustment of the controlling respectively measuring task to the customer specific requirements. Operation and activation mode (setpoint setting) analogue, digital, BACnet®, Modbus® The multi-functional volume flow controller VAV700 is available in seven activation versions with the setpoint setting as the main distinctive feature. The following operation and activation modes are supported (depending on the version): Type Activation mode Operation mode variable constant VAV700 (VAV) (CAV) TCP/IP, Ethernet -IP Yes Yes Analogue 0(2) - 10 V Digital (1-3-level) -AD -AD Yes No No Yes BACnet, TCP/IP, Ethernet -BIP Yes Yes BACnet, MS/TP, RS485 -BM Yes Yes Modbus® IP -MIP Yes Yes -M Yes Yes Modbus , RS485 ® Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com Performance features Modular variable volume flow control system System data stored voltage fail-safe Integrated web server Simple Ethernet-networking with dual port switch Modular expandable by pluggable boards Parameterisation and fetch of all system values via standard web browser Up to three position independent static differential pressure sensors -100 to 300 Pa, freely configurable for exhaust air, supply air, room pressure Volume flow range 1:15 Patented maintenance-free measuring device with two ring chambers and self-cleaning effect Fast, predictive and adaptive control algorithm Fast, stable and precise control via direct activation of hysteresis-free actuator Suitable for supply air and exhaust air volume flow control in laboratories and clean rooms (consider a sufficiently large room leakage) Adjustment of the volume flow ≤ 2 sec Closed loop control Analogue setpoint input 0(2) - 10 V DC/1 mA Analogue actual value outpur 0(2) - 10 V DC/10 mA Two freely programmable relays with potential free reverse contact Two (expandable) digital inputs for forced control VMIN, VMED, VMAX and damper = SHUT (CAV-mode). Additional temperature loop control for heating and/or cooling Integrated room balancing in network operation Internal plausibility monitoring of the sensor system Various extension moduls for digital in/out, analogue in/ out and field bus Control mode after power failure is freely programmable Integrated native BACnet® (IP or MS/TP) with trendlog and intrinsinic reporting Supply voltage 24 V AC provided by customer or 230 V AC optional via internal transformer Round and rectangular version made of steel and PPs 1 VAV700 Multi-functional air volume flow controller with integrated web server Order code: volume flow controller with integrated web server [a] VAV700 - BIP a b -T c -2 d [c] Type VAV700 Variable Air Volume Controller [b] Connection to BMS/field bus module IP Internal networking TCP/IP, Ethernet AD BIP Analogue/digital (expandable module EM10) Native BACnet® BM Native BACnet®, MS/TP, RS485 MIP Modbus®, IP M 0 24 V AC/30 VA extern T Internes Netzteil 230 VAC/24 VAC/30 VA [d] 1 2 Modbus®, RTU, RS485 Supply voltage 5 Sensor equipment with static differential pressure sensors All sensors are freely configurable as exhaust air, supply air, room pressure, duct pressure 1. Sensor -100...+300 Pa 1. Sensor -100...+300 Pa 2. Sensor -100...+300 Pa 1. Sensor -100...+300 Pa 3. Sensor -50...+50 Pa 5 Important: Specify air volume VMIN, VMAX respectively VCONST and mode of analogue activation 0 - 10 V DC or 2 - 10 V DC. Order additionally measuring device with damper and actuator (page 4). Order additionally optional expandable modules (page 3). Ordering example: volume flow controller VAV700 High-speed multi-functional variable balancing volume flow controller via BACnet® IP, 2 relays, with internal power supply 230 V AC, with 2 static differential pressure sensors (-100 - 300 Pa). Make: SCHNEIDER 2 Type: VAV700-BIP-T-2 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Order code: Extension modules Extension modules Remarks/Scope of delivery 2 analogue inputs, 2 analogue outputs, 2 digital inputs, 2 relay outputs Suitable for conventional connection to the building management system (BMS) 4 analogue inputs, 4 analogue outputs General applications, actuator and valve activation (in preparation) 6 relay outputs General applications, actuator and valve activation (in preparation) EM10 EM10 -- EM20 -- EM30 --- EM40 4 Triac outputs For valve activation, heating/cooling EM50 12 digital inputs, opto coupler General applications, e.g. switchable air (2-step CAV) -- EMNA Charging circuit with discharge circuit for battery backup 12 V DC With battery backup 12 V DC/1,2 Ah in its own housing (in preparation) Important: Maximal 4 extension modules are pluggable (4 free slots in the FC700). Please order separately according to the desired functionality. Ordering example: Extension module 1 x EM10 for conventional connection to the building management system with 2 analogue inputs, 2 analogue outputs, 2 digital inputs, 2 relay outputs. Make: SCHNEIDER Type: EM10 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 3 VAV700 Multi-functional air volume flow controller with integrated web server Order code: measuring device with damper and actuator, round version DD-250-S-K-G-0-RR-1 DD - 250 -S -K -G -0 - RR -1 a b c d e f g h [a] Measuring device MD Maintenance-free measuring device VAV700-BIP-T-2 [d] K Damper blade seal (0 = without) with (stainless steel = standard), see [c] VD Venturi nozzle DD Measuring nozzle [e] Rubber lip seal (0 = without) KD Measuring cross with orifice ring G with (only steel and stainless steel), see [c] SD Measuring cross without orifice ring [f] Cladding (0 = without) [b] Nominal diameter DN [mm] D with cladding 100 bis 400 100, 110, 160, 200, 225, 250, 280 [g] 315, 355, 400 Pipe connections Inflow Outflow Remarks MM socket socket only PPs(el), PVC FF flange flange PPs-el (electrically conductive) MF socket flange PPs(el), PVC, steel, stainless steel only PPs(el), PVC Polyvinyl chloride (PVC) FM flange socket only PPs(el), PVC S Galvanised steel RR pipe pipe V2 Stainless steel 1.4301 (V2A) PPs(el), PVC, steel, stainless steel V4 Stainless steel 1.4571 (V4A) [c] P Pel PVC Material Polypropylene (PPs), fire retardent [h] Order preferred Fast running actuator type 1 for VAV700 controller (better positioning). Order Fast running actuator type 8 (8 Nm) for nominal pipe diameter ≥ 280 mm. Fast running actuator 1 Fast Direct Drive SCHNEIDER 12 V, 3 Nm, 3 sec for 90° 8 Analogue actuator 24 V, 8 Nm, 4 sec for 90° Important: Volume flows and dimensions see page 28 to 31. Order Volume flow controller VAV700 and measuring device (MD, VD, DD, KD or SD) with damper always separately. Depending on the selected measuring device pay attention on sufficient inflow and outflow (> 2 x D). Ordering example: damper with measuring device and actuator, round version, galvanised steel Measuring nozzle with damper, DN 250, galvanised steel with damper blade seal, with rubber lip seal, without cladding, pipe/pipe, fast running actuator 3 s for 90 ° (fast direct drive SCHNEIDER). Make: SCHNEIDER Type: DD-250-S-K-G-0-RR-1 Material Polypropylene (PPs) PPs-el (electrically conductive) Polyvinyl chloride (PVC) Galvanised steel Stainless steel 1.4301 (V2A) Stainless steel 1.4571 (V4A) 4 P Pel PV S V2 V4 Versions measuring device MD, VD MD, VD MD, VD DD, KD, SD DD, KD, SD DD, KD, SD Available nominal diameter 110, 160, 200, 225, 250, 280 315, 355, 400 110, 160, 200, 225, 250, 280 315, 355, 400 110, 160, 200, 225, 250, 280 315, 355, 400 100, 125, 160, 200, 225, 250, 280 315, 355, 400 100, 125, 160, 200, 225, 250, 280 315, 355, 400 100, 125, 160, 200, 225, 250, 280 315, 355, 400 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Order code: measuring device with damper and actuator, rectangular version DD-600-400-S-0-0-1 DD - 600 -400 -S -0 -0 -1 a b c d e f g [a] Measuring device MD Maintenance-free measuring device DD Measuring nozzle VAV700-BIP-T-2 [d] P Material Polypropylene (PPs), fire retardent KD Measuring cross with orifice ring Pel PPs-el (electrically conductive) SD Measuring cross without orifice ring PVC Polyvinyl chloride (PVC) S Galvanised steel [b] Nominal width B [mm] V2 Stainless steel 1.4301 (V2A) 200, 300, 400 V4 Stainless steel 1.4571 (V4A) [e] Damper blade seal (0 = without) 200 bis 1000 [c] 100 bis 400 500, 600, 700 800, 900, 1000 K with (steel, stainless steel = standard), see [c] 100, 160, 200, 250, 300, 400 [f] Cladding (0 = without) Designs: D with cladding Nominal height H [mm] PPs, airtight shutting consider special nominal height (195, 360, 525, 690) [g] 1 Order preferred Fast running actuator type 1 for VAV700 controller (better positioning). Order Fast running actuator type 8 (8 Nm) for nominal width ≥ 250 mm and nominal height ≥ 250 mm. 8 Fast running actuator Fast Direct Drive SCHNEIDER 12 V, 3 Nm, 3 sec for 90° Analogue actuator 24 V, 8 Nm, 4 sec for 90° Stetiger Antrieb 24 V, 8 Nm, 3-5sec für 90° Use always with airtight design (with damper blade seal) Important: Volume flows and dimensions see page 32 to 34. Order Volume flow controller VAV700 and measuring device (MD, VD, DD, KD or SD) with damper always separately. Depending on the selected measuring device pay attention on sufficient inflow and outflow (> 2 x D). Ordering example: damper with measuring device and actuator, rectangular version, galvanised steel Measuring nozzle with damper, width = 600 mm, height = 400 mm, galvanised steel, without damper blade seal, without rubber lip seal, without cladding, flange/flange, fast running actuator 3 s for 90 ° (fast direct drive SCHNEIDER). Make: SCHNEIDER Type: DD-600-400-S-0-0-1 Material Versions measuring device Polypropylene (PPs) P PPs-el (electrically conductive) Pel Polyvinyl chloride (PVC) PV Galvanised steel S Stainless steel 1.4301 (V2A) V Stainless steel 1.4571 (V4A) V MD MD MD DD, KD, SD DD, KD, SD DD, KD, SD Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com Nominal widths B [mm] 200 - 1000 200 - 1000 200 - 1000 200 - 1000 200 - 1000 200 - 1000 Nominal heights Airtight version H [mm] special nominal heights H [mm] 100...400 195, 360, 525, 690 100...400 195, 360, 525, 690 100...400 195, 360, 525, 690 100...400 100...400 100...400 100...400 100...400 100...400 5 VAV700 Multi-functional air volume flow controller with integrated web server General functional description Web browser operation Block diagram Picture 1 shows the block diagram and the piping of the static differential pressure sensor with a maintenance-free measuring system. All plugs of the sensors and actuators are pre-assembled and directly pluggable on the outside of the FC700-housing. That means an immense reduction of the assembly time and a simplification of the commissioning. The high speed hysteresis-free actuator is operated in the proven direct drive mode and guarantees high control accuracy, highest durability and lifetime. The pre-assembled CAT6/CAT7-cable for the Ethernetnetworking will be plugged in the dual port switch and the system is ready for commissioning. . Measuring system - + Actuator M Feedback Potentiometer The internal web sites of the integrated web server can be visualised via a standard web browser. Adjustments and parameter can be simply changed. By using a standard web browser project-dependent files are no longer necessary to access the central building control system worldwide and at any time. The internal visualisation software VIS7000 reduces significantly the system costs (data points) on the building management system level and can assume the building management functions if necessary. Native BACnet®-IP The building management system is provided with a multitude of data and therefore allows an optimsed requirement planning and process control. Native BACnet® (IP or MS/TP) guarantees a fast, simple and direct connection to the building management system without additional gateways. Our own BACnet® stack developed by SCHNEIDER guarantees maximum flexibility. We support the read-out and storage of trendlog data as well as intrinsic reporting. Backup accumulator VAVcontroller VAV700 230 VAC Power line Day/Night operation Digital In-/Outputs Analogue In-/Output 0...10 VDC BACnet / LON-Network Ethernet/IP Simple wiring and fast commissioning A simple and fast wiring and commissioning are the main parameters to reduce significantly the installation and assembly costs. The dual port switch integrated on the CPU-board allows an easy daisy chain wiring with preassembled cables. Laptop Picture 1: block diagram volume flow controller VAV700 Networking The networking offers maximum flexibility and safety. The connection to the building management system offers the complete ventilation control and monitoring of all laboratories. A flexible network-adjustment is simply realised by modular extension cards. Besides the already integrated native BACnet® (IP or MS/TP) and Modbus® (IP or MS/TP) LON® is also available. The field bus boards can be retrofitted simply and at any time for all SCHNEIDER LabSystem products. Internet technology with integrated web server The FC700 possesses an integrated web server for a simple data exchange and to improve the system security and it communicates via the Internet protocol TCP/IP. The operation and parameterisation is carried out by a laptop with a standard web browser. For this reason a simple circuit-entering into multivendor capable building management systems is guaranteed and the system is therefore prepared for all future applications. 6 Picture 2: Daisy chain wiring Room supply air Controller Controller Controller Controller Room exhaust air VAV700 FC700 FC700 FC700 FC700 VAV700 The wiring can be executed radially as well. Therefore the connection of the bus cable is omitted. All standard cables, e. g. sensor cable, actuator cable, etc. are pre-assembled and externally pluggable. The commissioning, configuration, diagnosis and visualisation of all system data (e. g. control time, damper position and setpoint settings) occur centrally through the network by a control unit via PC with standard web browser or decentrally via infrared interface of the graphic indication and operation panel. Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server General functional description Building management system Extension modules The building management system (BMS) balances the air requirement of the complete building and can additionally run a plausibility check on all room controllers. Day/nightswitch, visualisation of status and fault detections as well as actual values can be simply integrated. Remote maintenance and fault remote diagnosis as well as an air consumption recording relating to the laboratory respectively to the fume hood with an individual accounting can be realised as well. Up to four free extension slots are available on the motherboard of the VAV700-controller. The controller can be easily and cost-effectively extended to further functions. Up to three position independent sensors For VAV700 up to three position independent static sensors (-100-300 Pa) are available and can be freely configured. Because of the high sensibility and resolution a volume flow range of 1:15 can be adjusted smoothly. The function classifications exhaust air, supply air and room pressure to the static differential pressure sensors are freely configurable. Therefore the controller can be simply and flexibly adjusted to all kind of applications. All data and measuring values are available at any time by the connected network. Customer specifically developed extension modules for special measuring, control and regulation functions on demand. The following extension modules are available: Extension module Function EM10 2 analogue inputs, 2 analogue outputs, 2 digital inputs, 2 relay outputs EM20 4 analogue inputs, 4 analogue outputs (in preparation) EM30 6 relay outputs (in preparation) EM40 4 Triac outputs for fan regulation, heating/cooling EM50 12 digital inputs, opto coupler EMNA Charging circuit with discharge circuit for battery backup 12 V DC (in preparation) EMSC Automatic sash closing module Picture 3: Sensor board with three static differential pressure sensors Picture 4: Four free slots Slot 6 (right) is always equipped with the sensor board and slot 5 with the CPU board. The slots 1 to 4 (left to right) can be freely equipped with the above listed extension modules. Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 7 VAV700 Multi-functional air volume flow controller with integrated web server General functional description Heating and cooling of the laboratory Visualisation The heating and cooling of laboratories via appropriate heating and cooling registers can also be executed by FC700. The appropriate analogue and Triac outputs to regulate the heating and cooling valves will be made availabe by the extension modules EM10 to EM40. The power supply of the valves is provided by FC700 and the independent closed loop which is already implemented by default. All relevant data is available for the building management system (BMD) via the network and can be used for facility management functions. A better planning and utilisation of the ressources as well as a reduction of energy and operational costs are the significant characteristics. All measured room values e. g. temperatures, humidity, pressure are available as actual value via network. Picture 5: Valve activation The visualisation software module VIS7000 is the reasonable extension of PRO7000 and allows the simple creation of room graphics and a free alignment of single devices (e. g. fume hood, volume flow controller, etc.) in the room. This is a cost-efficient integral system solution with functions of the building management system. Measuring system - + Actuator M The touchscreen controller PAD7000 developed by SCHNEIDER is especially adjusted to the requirements of the laboratory ventilation system and adopts the functionalities of the building management system. Special templates are freely disposable. Trendlog and intrinsic reporting are implemented as well. Networking via BACnet® (IP or MS/TP) and LON® is supported. Feedback Potentiometer Backup accumulator VAV controller VAV700 Laboratory occupation plans, night setback and individual accounting of the air consumption data, energy-efficient operation as well as the safety improvement via remote maintenance and remote diagnosis of the fume hood controller and the volume flow controller for room supply air and room exhaust air are the outstanding advantages of the network technology with an integrated building management system (BMS). 230 VAC Power line Day/Night operation Digital In-/Outputs Analogue In/Output 0...10 VDC BACnet / LON-Netzwork Ethernet/IP EM20 M Dehumidify M Humidify M Cooling 4 Analogue inputs 4 Analogue outputs M Heating - Picture 6: Touchscreen Controller PAD7000 Laptop + Project planning The project planning and parameterisation software PRO7000 is compatible to Windows and is used for a simple and fast commissioning. Parameterisation of devices can be executed from a central point for the entire room respectively the entire building. All data of the connected devices with integrated web server by SCHNEIDER can be indicated via standard web browser and entries can be done password protected. 8 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Functional description Volume flow measurement with a position independent static differential pressure transmitter Using a suitable measuring device (maintenance-free measuring system (MD), Venturi measuring tube (VD), measuring tube (DD) or measuring cross (KD) the differential pressure is determined by a position independent differential pressure transmitter. The measurement is very accurate and stable over the entire measuring range of -100 - 300 pa , making it possible to regulate a volume flow range of upt to 1:15. Unlike the thermo-anemometric measuring principle (dynamic sensor), air does not flow through the static differential pressure transmitter, making it particularly suitable for measuring in dusty and contaminated (corrosive) media (its suitability should be checked in individual cases). The suitability of the thermo-anemometric measuring principle for such media is very limited, as the sensor becomes dirty or is affected by corrosive air and thus measurement may be very imprecise or inaccurate. Parameterisation of the volume flow controller The volume flow controller can be parameterised via laptop (with software PC2500) or web browser in the network as follows: Function Significance Remarks VMIN minimum volume flow ≥ shield factor B * 1,5 (rule of thumb) VMAX maximum volume flow ≤ shield factor B * 16 (ule of thumb) Shield factor measuring device constant 10 - 2000 Type default controller configuration analogue (VAV) Offset steady +/- value for constant load +9990 m3/h to - 9990 m3/h digital (CAV) Volume flow setting VMIN, VMAX The volume flow adjustment and parameterisation is done via laptop (with software PC2500) or via the web browser in the network. The demanded volume flow is entered as a numeric value. Thereby means: Function Volume flow Reference signal w VMIN minimum 0(2) < w ≤ 10 V DC VMAX maximum w = 10 V DC The allocation of the analogue demand signal w to the volume flow Vmin and Vmax illustrates the VAV-curve (variable operation mode). Demand signal w (setpoint setting via analogue input A-In) With the demand signal w (setpoint selection), the volume flow can be constantly switched between VMIN and VMAX, at which the following is always true: 0 m3/h = 0(2) V DC, VMAX = 10 V DC The regulated volume flow actual value (A-Out) is available as 0(2) - 10 V DC output voltage (with extension board EM10) or via network. Various master/slave operating modes can be implemented with this signal. Shield factor (C-value) The shield factor is the design and geometry dependent constant of the used measuring device. The volume flow is calculated according to the following formula: . . V = c. p Typ default (setpoint value = analogue or digital) The controller configuration specifies the operating mode (analogue or digital). In network operation mode (variable volume flow controller = VAV) the volume flow is regulated linearly via network depending on the setpoint setting. In analogue operating mode (variable volume flow controller = VAV) the volume flow is regulated linearly based on the analogue demand signal w (setpoint value via analogue input A-In). In digital operating mode (constant volume flow controller = CAV) the volume flow is regulated in stages based on the digital inputs In1 and In2. Up to four different volume flows (VMIN, VMED and VMAX and VEMERGENCY) can be regulated. An analogue demand signal is not required. In both operating modes (VAV and CAV) pressure fluctations in the duct system are recognised and automatically regulated. Offset for integrating of constant loads With the offset value a fixed value is programmed (+9990 to - 9990 m3/h) that is added to the volume flow setpoint (+ offset = increases the volume flow setpoint, - offset decreases the volume flow setpoint). This makes it possible to integrate constant loads. A constant difference between supply and exhaust air is therefore possible in master/slave mode. This function is particularly important in airtight rooms (e.g. clean rooms). V = air volume c = geometrical constant (shield factor) p = differential pressure = air density Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 9 VAV700 Multi-functional air volume flow controller with integrated web server Function description ● Analogue operational mode Notes on controller dimensioning (dimensions and volume flow) Determination of the volume flow for laboratory applications under consideration of the flow velocity v Due to measurement accuracy it must be ensured that at the minimum volume flow VMIN the flow velocity in the volume flow controller does not fall below 2 m/s. Volume flow Flow velocity v VMIN v ≥ 1,5 m/s VMAX v ≤ 7,0 m/s Due to noise development, in laboratory applications it must be ensured that at the maximum volume flow VMAX the flow velocity in the volume flow controller does not exceed 7,5 m/s. The flow velocity of the volume flow VMin has to be 1,5 m/s at least (lower control range) and must not exceed 7,0 m/s (Vmax) due to noise protection reasons. The volume flows VMIN, VMED, VMAX are freely programmable within the range 50 - 25.000 m3/h, but care must be taken to ensure suitable volume flow controller dimensions with regard to the volume flow range while at the same time taking the flow velocity into account. Analogue operation mode Variable volume flow controller (VAV) Diagram 1: Variable volume flow regulation (VAV) The volume flow can be constantly controlled between VMIN und VMAX with the demand signal w, at which the following is always true: Leading signal w (A-In1) [V] 0m3/h = 0(2) V DC 0(2) < VMIN ≤ 10 V DC VMAX = 10 V DC Always note: 1. Minimum control value VMIN = shield factor B * 1.5 2. Values < VMIN are not regulated 3. With reference signal w < 0.3 V, the damper will be SHUT VMAX 10 9 9 8 8 7 7 6 6 5 5 VMIN 4 4 3 3 2 2 1 1 0 0 0 200 400 600 800 Variable operation In the example diagram 1 the volume flows VMIN = 300 m3/h and VMAX = 750 m3/h are programmed. The volume flow actual value signal (A-Out2) correlates with the regulated volume flow.The advanced setpoint at analogue output A1Out is available and the value to be achieved by the actual value. An advanced setpoint is very effective for interconnecting modules with their own operating time requiring a stable signal (e.g. control of frequency inverters, etc.). [V] 10 VMIN VMAX Air flow volume actual value (A-Out1) In variable volume flow operating mode the desired volume flow is predefined by a demand signal w (setpoint setting). The value range of the demand signal is 0(2)...10V DC. 1000 [m3/h] Air flow volume Table 1: Forced control during digital operational mode (CAV-mode) Digital inputs Function In1 In2 Analogue setpoint setting via A-In The volume flow does not fall below VMIN, even when the demand signal w lies below the corresponding VMAX signal (in the example diagram 1: w = 4V). 0 0 VMAX 0 0 VMIN 1 0 Forced control via digital inputs VEMERGENCY, damper SHUT/OPEN ON/OFF 0 1 VEMERGENCY, damper SHUT/OPEN ON/OFF 1 1 Through appropriate wiring of the digital inputs In2, In3 and In4 the functions described in table 1 can be executed directly. The wiring of the digital inputs is as follows: 0 = contact open (no current) 1 = contact closed (under current) 10 Contact open = 0, contact closed = 1. The variable operation mode (analogue setpoint setting via A-in) is only possible, if the digital inputs are In1 = 0 and In2 = 0, which means that they are not under current (contact open). All functions are freely configurable under consideration of the digital inputs. Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Digital operating mode (CAV) ● Master-slave-sequence control Digital operating mode Constant volume flow controller (CAV) Diagram 2: Constant volume flow control (CAV) In1 In2 0 0 [V] VMAX VMAX 10 9 8 7 The available operating stages are shown in diagram 2 and table 2. 1 level, 2 level, 3 level or 4 level operation can be easily implemented by direct control of the digital inputs. 6 5 VMIN VMIN 1 4 0 3 The volume flows are programmed to the values VMIN = 875 m3/h, VMED = 1750 m3/h and VMAX = 2150 m3/h. VMED must always lie between VMIN and VMAX. The volume flow actual value signal (A2-Out) correlates with the regulated volume flow. 2 1 SHUT SHUT VEMERGENCY 0 1 1 1 0 0 500 Damper SHUT The following is valid for the volume flow actual value: Air flow volume actual value (A-Out) Function In constant volume flow operating mode (digital operating mode) the desired volume flow is controlled based on the digital inputs. 1000 1500 2500 [m3/h] 2000 VMIN VMAX Air flow volume Table 2: Forced control during digital operational mode (CAV-mode) 0m3/h SHUT = = 0(2) V DC 0(2) < VMIN ≤ 10 V DC VMAX = 10 V DC Digital inputs Function This master-slave sequence control is always used if the room pressure must be maintained at an equal percentage ratio of supply and exhaust air. Sufficient replacement flow of the difference between the supply and exhaust air must be ensured in this operating mode. The master controller is programmed with the volume flow values VMIN and VMAX and the demand signal w is added on directly. The volume flow actual value of the master controller provides the demand signal for the slave controller, which can be programmed with other VMIN and VMAX volume flow values depending on the application. In2 0 0 VMAX 0 0 VMIN 1 0 VEMERGENCY, damper SHUT/OPEN ON/OFF 0 1 VEMERGENCY, damper SHUT/OPEN ON/OFF 1 1 Contact open = 0, contact closed = 1. Picture 7: Block diagram: Master-slave-sequence control in VAV-mode Building Management System If the master controller is mounted in the supply air and the slave controller in the exhaust air and positive (+) room pressure is required, the slave controller must be programmed with the lower percentage volume flow values VMIN and VMAX in relation to the master controller. If negative (-) room pressure is required, the slave controller must be programmed with the lower percentage volume flow values VMIN and VMAX in relation to the master controller. T Supply air VAV Exhaust air VAV dp M dp M VAV700-AD Master Network Master-slave-sequence control with equal percentage ratio in VAV operation In1 Analogue setpoint setting via A-In Leading signal w VAV700-AD Slave Air flow volume actual value DDC Substation Air volume actual value Sample settings for master-slave controllers: Slave (+) Master Slave(-) VMIN 240 300 360 VMAX 600 750 900 The master slave sequence control applies for both equal percentage ratio and constant difference between supply and exhaust air. The demand signal w (A-In) is added on to the master controller and the volume flow actual value A1Out (with extension module EM10) provides the demand signal for the slave controller. This ensures that the slave controller always follows the master controller. For safety reasons, master/slave sequence control must always be given preference over parallel control. Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 11 VAV700 Multi-functional air volume flow controller with integrated web server Master-Slave sequence control Master-slave sequence control with constant difference in VAV operating mode (analogue operating mode) 10 9 9 8 8 7 7 6 6 5 5 VMIN 4 3 2 2 1 1 0 0 If negative (-) room pressure is required, the slave controller must be programmed with a positive offset. Sample settings for master-slave controllers: 0 200 400 600 VMIN 1000 [m3/h] 800 VMAX VMIN Air flow volume Master VMAX Air flow volume Slave(-) VMIN VMAX Air flow volume Slave(+) Diagram 4: Sequence control (master-slave) with constant difference [V] [V] VMAX 10 10 constant difference Supply-/Exhaust 9 Leading signal w (A-In) In addition, the offset is also programmed in the slave controller. If the master controller is mounted in the supply air and the slave controller in the exhaust air and positive (+) room pressure is required, the slave controller must be programmed with a negative offset. 4 3 This form of master/slave sequence control is used when room pressure with a constant difference between supply and exhaust air is required. This operating mode is selected for airtight rooms (e.g. clean rooms). The master controller is programmed with the volume flow values VMIN and VMAX and the demand signal w (A8-in) is added on directly. The volume flow actual value (A2-out) of the master controller provides the demand signal for the slave controller, which is programmed with the same volume flow values VMIN and VMAX, depending on the application. [V] VMAX 10 Air flow volume actual value (A-Out) [V] 8 9 8 7 7 6 6 5 5 VMIN 4 4 3 3 Slave (+) Master Slave(-) 2 2 VMIN 300 300 300 1 1 VMAX 750 750 750 0 0 Offset -150 0 +150 In this example, the volume flow values VMIN and VMAX of the slave (+) controller and the slave (-) controller were programmed with the volume flow values of the master controller. For negative room pressure the offset of the slave (-) controller must be programmed with +150 m3/h. The constant difference between supply and exhaust air is maintained over the entire volume flow range of VMIN to VMAX. Master-slave sequence control in CAV operating mode (digital mode) In CAV operating mode the digital inputs of the master controller are wired to control the different operating stages (see table 3). The volume flow actual value A1-Out (with extension board EM10) of the master controller provides the demand signal for the slave controller. 12 0 200 400 600 VMIN VMAX VMIN VMIN 800 Air flow volume actual value (A-Out) The equal percentage ratio between supply and exhaust air is maintained throughout the entire volume flow range of VMIN to VMAX. Diagram 3: Sequence control (master-slave) in equal percentage ratio Leading signal w (A-In) In the sample settings, the volume flow values VMIN und VMAX of the slave (+) controller were programmed to -20% (negative room pressure) in relation to the volume flow values of the master controller. For negative room pressure the volume flow values VMIN and VMAX of the slave (-) controller must be programmed to +20 % in relation to the volume flow values of the master controller. 1000 [m3/h] Air flow volume Master VMAX Air flow volume Slave(-) VMAX Air flow volume Slave(+) DDC/BMS control If the master controller is controlled via a DDC/BMS (demand signal w or digital control) the volume flow actual value of the slave controller can be added on as feedback and therefore used to monitor the functioning of both volume flow controllers (master and slave). Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Multi functional applications in analogue or network operating mode • Heating and/or cooling Volume flow controller network operating modes The variable volume flow controller VAV700 is especially developed for the networked operation and possesses different operating modes which can be configured via the network. The following controller types are implemented : Variable volume flow controller 2-level constant volume flow controller Balancing volume flow controller Room volume flow differential controller Multi-functional applications in the network operating mode (BACnet, Modbus®) Besides the on the previous pages described classical volume flow controller operating modes e. g. variable volume flow controller, 3-level constant volume flow controller, balancing volume flow controller and room volume flow differential controller the following additional multi-functional applications are implemented on the VAV700: Actual value collection of room pressures Own temperature control loop for heating and/or cooling Own pressure cascade control loop Via the available extension modules any customer specific applications can be cost-effectively implemented. Actual value collection of room pressures The volume flow controller VAV700 has up to two free static differential pressure transmitter -100 - 300 Pa which can be freely configured e. g. for a pressure cascade control loop or for measuring of room pressures. Additionally, any analog values 0 (2) ... 10 VDC can be connected to the analog inputs of the expansion modules (eg EM10) and are available as BACnet objects on the network. The PICS-list (Protocol Inplementation Conformance Statements) for BACnet® applications can be requested or downloaded from our web site www.schneider-elektronik.com Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 13 VAV700 Multi-functional air volume flow controller with integrated web server Extension modules The motherboard of the FC700 controller possesses up to four free extension slots for special functions. The controller can be arbitrarily extended to further functions besides the sash closing function (extension module EMSC). controlling and regulation functions can be easily and costeffectively developed. The following extension modules are available: Custom made extension modules for special measuring, Extension modules Functionality Description EM10 In- and outputs Suitable for general applications: 2 analogue inputs Measuring of temperature, humidity, pressure 2 analogue outputs Building management system connection, volume flow controller regulation, valve regulation 2 digital inputs Building management system connection, regulation 2 relay outputs Building management system connection, valve regulation (2-point), status report EM20 In- and outputs Suitable for general applications: (in preparation) 4 analogue inputs Measuring of temperature, humidity, pressure Analogue room balancing 4 analogue outputs Building management system connection, volume flow controller regulation, valve regulation EM30 Outputs Suitable for general applications: (in preparation) 6 relay outputs Building management system connection, valve regulation (2-point), status report EM40 Outputs Suitable for valve regulation: 4 Triac outputs Direct regulation of heating and cooling valves (2-point) Inputs Suitable for switchable extraction and alarm: 12 digital inputs, opto coupler 2 steps constant air volume, alarm, status report EMNA Special module Suitable for external battery backup: (in preparation) Charging circuit with discharge circuit for battery backup 12 V DC This module is required for an optional external battery backup 12 V DC. EM50 14 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Room plan 1 (standard) ● fume hood controller FC700 with TCP/IP-networking via Ethernet The room plan 1 shows the networking by default with the Internet protocol TCP/IP via Ethernet. Due to the high data transfer rate it is possible to network any number of subscribers. The response time of the linked subscribers (e. g. room supply volume flow controller) is sufficiently secured even during heavy data traffic. Commissioning via Internet protocol TCP/IP Wiring The commissioning can occur decentrally for all linked subscribers via a standard web browser or directly via infrared interface at the fume hood with a laptop and the installed software PC2500. For a simple data transfer and to improve the system security VAV700-IP has an integrated web server and communicates via the Internet protocol TCP/IP by default. The operation, parameterisation and commissioning occur via laptop with standard web browser. The integrated dual port switches of VAV700 and FC700 allow a simple and fast daisy chain wiring with pre-assembled CAT6/CAT7 patch cables and therefore reduce the assembly and installation costs significantly. Therefore the connecting of the bus cable is omitted and all standard cables like sensor cable, actuator cable, etc. are pre-assembled and pluggable on the outside. The internal websites of the integrated web server can be visualised worldwide with a standard web browser. Therefore a simple remote maintenance can be realised. The internal visualisation software VIS7000 reduces significantly the system costs (data points) on the building management system level and can assume the building management functions if necessary. Balancing The volume flow controller VAV700-IP balances the required room supply air and room exhaust air independently according to the laboratory exhaust air and controls the calculated value self-sufficiently. If the added exhaust air of the fume hoods is not sufficient for the maintenance of a defined room air exchange rate (e. g. room air exchange rate = quadruple or octuple) the room exhaust air volume flow controller raises the volume flow as long as the requested room air exchange rate is reached. Extension modules Any function extensions can be simply and modulary realised by the subsequently pluggable extension modules. Besides the sash closing function (extension module EMSC) miscellaneous input and output modules (analogue and digital) for measuring value collection (temperature, humidity) respectively for controlling heating and cooling valves as well as field bus modules (LON®) are available. The controller can be arbitrarily extended to further functions besides the sash closing function (extension module EMSC). The room supply air volume flow controller follows the total room exhaust air, reduced by a fixed value or a percentaged reduction. Therefore the required low pressure in the laboratory according to DIN 1946, part 7 is guaranteed for all operating conditions. The supply of the volume flow controller with 24 V AC has to be provided by the customer. The optional room management controller RMC700 can be connected directly to the network via LON® or Modbus® and regulates e. g. day/night operation per room. Status and operation information (temperature, humidity, pressure) can be indicated additionally on the graphic display. All extension modules are embedded in the networking and provide the data and measuring values via the Internet protocol TCP/IP. Optional: Room management controller RMC700 Notes: RMC700 FC700-IP Isttemperatur: 21 °C 75 % rF Tagbetrieb FC FC FC RMC700 VAV700-IP 24 VDC Tag FUME HOOD #1 FUME HOOD #2 FUME HOOD #3 Nacht Notfall I/O Ein/ Aus ETHERNET TCP/IP Cable type: IY(St)Y 1x2x0,8 Room supply airflow control dp M VAV700-IP 24 VAC = Fume hood controller, fully variable, with Internet Protokoll TCP/IP = Room management controller Day/Night operation (optional), Status display = High speed variable airflow controller VAV, with Internet Protokoll TCP/IP = 24 VAC external voltage for VAV700-IP and RMC700 Modbus RS485 Attention! Room exhaust airflow control Ethernet-Network cable must be wired with CAT6 cable. Do not exceed the maximum cable length. dp M VAV700-IP 24 VAC Cable type: CAT 6 24 VAC ETHERNET TCP/IP Building Management System ETHERNET TCP/IP To more Laboratories Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 15 VAV700 Multi-functional air volume flow controller with integrated web server Room scheme 2 ● Volume flow controller VAV700/FC700 with BACnet-IP networking and room visualisation The room plan 2 shows a networking with native BACnet®IP protocol. The BACnet®-IP protocol is increasingly established as de facto standard for the building automation. Due to the high data transfer rate it is possible to network any number of subscribers. The response time of the linked subscribers (e. g. room supply volume flow controller) is sufficiently secured even during heavy data traffic. Wiring The project planning and parameterisation software PRO7000 is compatible to Windows® and is used for a simple and fast commissioning. Parameterisation of devices can be executed from a central point for the entire room respectively the entire building. All data of the connected devices with integrated web server by SCHNEIDER can be indicated via standard web browser and entries can be done password protected. The visualisation software module VIS7000 is the reasonable extension of PRO7000 and allows the simple creation of room graphics and a free alignment of single devices (e. g. fume hood, volume flow controller, etc.) in the room. This is a cost-efficient integral system solution with functions of the building management system. Refer to description of room plan 1. Balancing Refer to description of room plan 1. Native BACnet®-IP A BACnet® stack implemented in the 700 product series allows the direct communication with the business management system RMS700 by SCHNEIDER. Gateways are not required anymore and due to the direct implementation of the BACnet® stack to the CPU board the term „native BACnet®“ has been created. BACnet® is a multivendor capable interface for management systems and allows the simple implementation and visualisation of functions. The touchscreen controller PAD7000 developed by SCHNEIDER is especially adjusted to the requirements of the laboratory ventilation system and adopts the functionalities of the building management system. Special templates are freely available. Trendlog and intrinsic reporting are implemented as well. Bild 8: Touchscreen Controller PAD7000 Extension modules Refer to description of room plan 1. List of objects and object types The PICS list (Protocol Implementation Conformance Statements) for BACnet® applications can be required or downloaded from our website: www.schneider-elektronik.com. Room visualisation Optional Room Management and Information System RMS700-BIP FC FC Notes: FC700-BIP FC RMS700-BIP 24 VDC FUME HOOD #1 Room supply airflow control FUME HOOD #2 BACnet-IP 24 VAC FUME HOOD #3 Room exhaust airflow control Attention! Ethernet-Network cable must be wired with CAT6 cable. Do not exceed the maximum cable length. dp M dp M VAV700-BIP VAV700-BIP = Fume hood controller, fully variable, with BACnet-IP protocol = Room Management and Information system, Touchscreen graphik display with BACnet-IP protocol = High speed variable airflow controller VAV, with BACnet-IP protocol = 24 VAC external power supply for VAV700-BIP VAV700-BIP 24 VAC Cable type: CAT 6 24 VAC BACnet-IP Building Management System BACnet-IP To more Laboratories 16 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Extended applications Room controller functions With this technology sustainable and energy-efficient office and functional buildings can be realised which can be certified according to LEED or DGNB. Each fume hood controller FC700 can be upgraded with 4 boards at most with the universal extension modules EM, so that complete room controller functions can be realised. A permanently enhanced variety of modular boards is available for the individual process application. With the extension modules EM10 to EM50 the following functions can be realised: All relevant data are available via TCP/IP, BACnet®/IP over Internet or for a central building management system. Decentral closed loops adopt the independent room controlling functions without intervention of the building management system which mainly dynamically visualises the processes and rooms. Room temperature controlling with setpoint setting Room humidity controlling with setpoint setting The room pressure maintenance of laboratory and clean rooms as well as the energetic capacity accounting is easily realised. Activation of heating and cooling valves for static radiators respectively cooling ceiling or fan coils (with EM30, 6 relay outputs for fan activation, step 1 to 3). The visualisation software module VIS7000 allows the simple creation of dynamic room graphics and a clear exposition on the PC. This is a cost-efficient integral system solution with functions of the building management system. Activation of the demand-based room illumination Activation of the curtains (automatic shading) Alarm detection (e. g. gas alarm, water alarm) PAD7000 adopts the management system. Extinguish functions FC FC Fume hood #1 Fume hood #2 functionalities Fume hood #n dp M EM20 M Dehumidify M Humidify Cable type: CAT 6 Lab alarm (e.g. gas) dp M VAV700-IP 4 Analog inputs 4 Analog outputs 24 VAC p building Exhaust VAV Lab alarm (e.g. water) VAV700-IP a FC ETHERNET TCP/IP Supply VAV of M Cooling M Heating + 24 VAC EM30 6 Relay outputs + Set Act. % rH Room humidity Set Act. ࢡ Room temperature ETHERNET TCP/IP M Room light Louver ETHERNET TCP/IP To more labrooms Building Management System Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 17 VAV700 Multi-functional air volume flow controller with integrated web server Room scheme 3 ● Volume flow controller VAV700 with analogue input and laboratory controller LCO500 system (BMS). The room plan 2 shows the connection of the volume flow controller VAV700-AD (analogue input) with up to 9 fume hoods (Ain 1 to Ain 9) with the laboratory controller LCO500. The laboratory controller regulates up to eight freely configurable volume flow controllers for room supply air/room exhaust air (Aout1 to Aout8). The internal switching power supply (optional) provides a maximum of 8 volume flow controllers with supply voltage 24 V DC which simplifies the planning and the implementation is more cost-effective. The laboratory controller LCO500 fulfills the functionality of a DDC-substation respectively a router. The following data are available as network variables in the business management system: readout of the exhaust air actual values of the fume hoods Ain1 to Ain10 readout of the summed-up room balances (room supply air/room exhaust air) setpoints for 8 analogue outputs readout of the 8 digital outputs setting of the 8 relay outputs The analogue inputs Ain1 to Ain10 will be summed-up and can be combined to miscellaneous groups on the analogue outputs Aout1 to Aout8. Thereby any configurations are possible. Therefore it is possible to regulate independently e. g. several laboratories (max. 8) with one room supply air volume flow controller each and 10 fume hoods at most. Like it is shown in room plan 2 an additionally room exhaust air can be configured besides the room supply air. Each room exhaust air volume flow controller requires an analogue input (recirculation actual value room exhaust air). Therefore special functions like day/night switchover of the fume hood controller, regulation and monitoring of the room control unit, temperature regulation as well as controlling of the heating and cooling valves are simply realisable. Extended functions like remote maintenance are realisable as well. By day/night switchover, retrieval and comparison of the individual exhaust air actual values each fume hood can be checked regarding this function. Networking with building management system The optional room management controller RMC700 can be connected directly via LON® or Modbus® to the network and regulates e. g. day/night operation per room. Status and operation information (temperature, humidity, pressure) can be additionally indicated on the graphic display. A cost-effective and simple connection to the multivendor capable building management system (BMS) can be realised via the network by an optional field bus module (LON®, BACnet® or Modbus®). Via the BACnet® bus board a native BACnet® can be realised which means that no gateways are necessary to possibly implement protocols and data. Therefore a full compatibility as well as a simple and fast commissioning is guaranteed. The laboratory controller LCO500 combines the analogue technology with the advantages of the bus technology and offers a cost-effective, flexible and secure regulation and visualisation per room via the building management system. For detailed description please refer to data sheet LCO500. With the extension of the digital fault warning inputs (optional) all fault warnings of the connected fume hoods will be gathered and sent via network to the building management FC FC FC Option: Room Management Controller RMC700 Notes: RMC700 FUME HOOD #1 FUME HOOD #2 FC Isttemperatur: 21 °C 75 % rF FUME HOOD #3 bis #8 FUME HOOD #9 24 VDC Tag Cable type: IY(St)Y 4x2x0,8 Ein/ Aus Ain1 Ain2 Ain3 … Ain9 Ain10 Din1 Din2 Din3 … Din9 T/N T/N T/N ... T/N Aout1 Laboratory Controller Aout2 LCO500 24 VDC 24 VDC dp M VAV700-AD Cable type: IY(St)Y 4x2x0,8 Option: Power supply 24V DC/75 W Power line 230 VAC +-10% I/O Optional Fieldbus module: LON, BACnet or Modbus NETWORK (LON or Modbus) Room supply air VAV Nacht Notfall = Fume hood controller, fully variable, analogue output 0(2)...10 VDC = Laboratory controller, 10 analogue inputs = Room management controller (option) Day-/Night operation, status display VAV700-AD = Fast variable multi-functional air volume flow controller, with analogue input 0...10 VDC Ain1 … Ain10 = 10 analogue inputs 0...10 VDC Din1 … Din10 = 10 digital inputs T/N = Day/Night operation fume hoods (room control) wired as parallel day/night control via aditional connector board Aout1 … Aout8 = 8 analogue outputs 0...10 VDC 24 VDC = 24 VDC supply voltage for air volume controller VAV700-AD LCO500 RMC700 Tagbetrieb Room exhaust air VAV dp M Attention! Observe cable specifications of the connected network. Don´t exceed max. cable lenght. VAV700-AD Cable type: IY(St)Y 4x2x0,8 Building Management System NETWORK (LON, BACnet or Modbus) 18 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Connection diagrams Connection diagram VAV operating mode Connection diagram VAV operating mode 10...20 VA N Leading signal w 0(2)...10V DC from Laboratory controller LCO500, DDC/GLT GND L VAV700-AD N L VAV operation (analogue) Air flow volume actual value GND Master 0(2)...10V DC The volume flow actual value signal of the slave-VAV can be connected as a feedback signal to the laboratory controller LCO500, the DDC or BMS, whereby the functionality of the complete master-slave-sequence control can be checked. A forced control is possible as well (please refer to table 1 on page 9). The allocation digital input/function is freely programmable. 24V AC Supply Connection via safety transformer max. 10 VA The analogue lead signal is connected by the transmitter (e.g. temperature sensor, setpoint device) respectively by the laboratory controller LCO500, the DDC or BMS. The volume flow actual value signal of the master-VAV generates the lead signal of the slave-VAV. VAV700-AD Slave VAV operation (analogue) GND to LCO500, DDC/GLT 0(2)...10V DC Air flow volume actual value Connection diagram CAV operating mode Connection diagram CAV operating mode L CAV operation (digital) Air flow volume actual value GND N 0(2)...10V DC VAV700-AD Master VAV700-AD Slave The volume flow controller VAV700 is designed as a network controller by default. The system is completely independent by direct connection with the fume hood controller FC700. The internal communication runs via Modbus® IP or via BACnet®-IP respectively LON® on demand. All relevant data and parameters are exchanged on a sufficient rate and the balancing of room supply air respectively the required room exhaust air to maintain the necessary room air exchange rate is automatically calculated and adjusted via the connected volume flow controllers VAV700. VAV operation (analogue) GND 0(2)...10V DC Air flow volume actual value to LCO500, DDC/GLT Connection diagram network operating mode N Slave L VAV700-IP VAV operation (Network) TCP/IP-Ethernet VAV700-IP Master All relevant data like actual values and parameterised setpoints are available for the BMS connected to the network. L Dual-PortSwitch N from Laboratory controller LCO500, DDC/GLT TCP/IP-Ethernet 24V AC Suppply 10...20 VA Connection via safety transformer max. 10 VA The integrated Ethernet-dual port switch allows a fast and cost-effective daisy-chain-wiring with pre-assembled cables. The commissioning and parameterisation of all connected devices (FC700, VAV700, etc) are carried out from an arbitrary central point. In2 L Dual-PortSwitch Connection diagram network operating mode Operating modes CAV In1 N The master is adjusted during CAV operating mode and the slave during VAV operating mode. The slave follows the actual value of the master. The feedback of the volume flow actual value signal to the laboratory controller LCO500 or DDC/BMS is possible as well. 10...20 VA 24V AC supply Connection via safety transformer max. 10 VA The different CAV operating steps are apparent in table 2 on page 10. The volume flow Vmax is adjusted if both digital inputs (In1 and In2) are not under current, which means that the contacts are open. The current feed of In1 adjusts Vmin and of In2 adjusts VEmergency. The allocation digital input /function is freely programmable. VAV operation (Network) TCP/IP-Ethernet Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com to LCO500, DDC/GLT 19 VAV700 Multi-functional air volume flow controller with integrated web server Network cable specifications ● BACnet® ● Modbus® BACnet®-cable specifications (MS/TP, RS485) In a BACnet®-network (MS/TP, RS485) is only daisy-chainwiring allowed (no free topology, like LON®) MS/TP (master slave/token-passing) The master slave/token passing-protocol has been developed by ASHRAE and is only available for BACnet®. The connection to the field bus occurs via the cost-effective interface EIA RS 485. MS/TP can be operated in a pure master slave-mode, with token delivery between equal nodes (peer to peer token passing methods) or in a combination of both methods. EIA RS 485 standard The EIA RS 485 standard defines a bidirectional bus system with up to 32 participants. Given that several transmitters work on a common wire, it has to be guaranteed by a protocol that maximum one data transmitter is active at any time (e. g. MS/TP). All other transmitters have to be in a high-resistance condition during this time. The ISO-standard 8482 standardises the cable topology with a maximum length of 500 m. The participants have to be connected to this daisy-chained bus cable ( line topology) via a branch line with a maximum length of 5 m. A cable termination with termination resistors (2 x 120 Ohm) on both ends is basically necessary, to avoid reflections. If no data transfer takes place (data transmitter inactive) a defined resting level should be adjusted on the bus system. This can be achieved by connecting wire B over 1 k Ohm to ground (pull down) and wire A over 1 k Ohm to + 5 V DC. During installation each wire of the twisted pair (A and B) has to be necessarily applied alone. The correct polarity of the twisted pair has to be necessarily regarded because a false polarity causes the inversion of the data signals. Especially in case of difficulties in connection with the installation of new end devices each failure detection should begin with checking the bus polarity. Generally recommended is the laying of daisy-chained shielded wires and to ground the shielding one-sided (GND). 20 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Network cable specifications ● BACnet® ● Modbus® Network extension in bus and daisy chain-structure The bus cable is laid in one string. The nodes are connected via short branch line (maximum 5 m). EIA RS 485 in Bus- / Line topology (daisy chain) For a safe transmission in networks with bus/daisy chain topology the following issues have to be regarded: 1 2 3 Field module Field module Field module A B A B A B +5V 1k The bus wire has to be connected to bus terminator at both ends (R1 = R2 = 120 Ω) The second terminator is necessary in either case max. 5 m 120 120 A The maximum cable length of the branch lines must not exceed 5 m B Maximum 32 participants can be connected to a bus / daisy chain- structure max. 5 m Wires drilled. Cable shielded. 1k The maximum cable length is 500 m A B Field module GND max. 500 m Picture 10 shows the bus/daisy chain topology of EIA RS 485 standards with the maximum cable length. Maximum distance between busterminator: Maximum length of stub line: Use always drilled shielded cable. Only bus-/ line topology allowed. Table 3 specifies different cables suitable for EIA RS 485 standard. Picture 10: pology Table 3: Specifications of different cable types max. 32 Field modules 500 m 5m EIA RS 485 in bus/daisy chain to- EIA RS 485 in bus/daisy chain topology Cable types Manufacturer Conductor diameter [mm] AWG Conductor cross section [mm²] Li2YCYPiMF Lapp 0,80 20,4 0,503 78,4 500 miscellaneous 0,80 20,4 0,503 73 300 78,7 500 52,8 400 31,2 500 JY(St)Y 2 x 2 x 0,8 shielded 9843 paired FPLTC222-005 EIB-YSTY Belden 24 Northwire Diverse 22 1,0 0,80 Rloop Ω/ max. conductor length km of bus cable [m] All cables have to be shielded and the shield has to be grounded (GND). Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 21 VAV700 Multi-functional air volume flow controller with integrated web server Network cable specifications ● BACnet® ● Modbus® Ethernet-cable specification Ethernet-cable Cat-6A is suitable for structured wiring of all connected devices in the field bus technology for an increased bandwidth requirement of 10 Gigabit-Ethernet (10GBASE-T). Cat-6A is suitable for transmission frequencies up to 500 MHz and distances up to 100 m as well as downward compatible to existing network protocols. Cat-6A is defined by the international standards committee ISO/IEC (International Organization for Standardization/International Electrotechnical Commission). Modbus®-cable specification (RS485) Modbus® is an application log for the information exchange between field modules with integrated Modbus® controllers. The Modbus® protocol is settled on the application layer of the OSI reference model and supports the master slave mode between intelligent devices. . The Modbus® protocol defines the information type on which the Modbus® controllers communicate. It describes how a Modbus® controller approaches another controller via request, how this controller answers and how failures are detected and documented. The Modbus® protocol functions on request answer-base and offers different services which are specified by function codes. The Modbus® protocol determines during the communication how each controller gets to know the device address and recognises the information which belong to it. Besides it defines the releasing actions and which information the Modbus® controller can gather from the information flow. If an answer is requested then it will be configured in the controller and is sent by the Modbus® protocol to the appropriate station. The Modbus® can be cost-efficiently realised via EIA RS 485 and is therefore excellently suitable for the laboratory internal networking. The wiring described for the EIA RS 485 standard (please refer to BACnet®) has to be absolutely complied with. SCHNEIDER products in networked systems Due to the retrofit field bus modules for LON®, BACnet® and Modbus® by SCHNEIDER the complete system is very flexible, individual and cost-efficiently adaptable to different networks. We offer the complete system from one source without compatibility problems. For detailed cable specifications please refer to SCHNEIDER LabSystem handbook, chapter 10.0. 22 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Mounting instructions Mounting instructions Volume flow controller, round version Distance after bend molded part Mounting instructions Volume flow controller, rectangular version Distance after bend molded part min. 1xD min. 1xDiag. Distance after miscellaneous molded parts (e. g. T-piece, swivel fitting, reducer, etc.) Distance after miscellaneous molded parts (e. g. T-piece, swivel fitting, reducer, etc.) min. 2xD min. 2xDiag. Distance after fire damper Distance after fire damper min. 2xD min. 2xDiag. Distance after silencer Distance after silencer min. 2xD D = diameter Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com min. 2xDiag. W x H = width x height S = slant 23 VAV700 Multi-functional air volume flow controller with integrated web server Dimensions ● Volume flow ranges, round version ● galvanised steel, stainless steel 1.4301 Volume flow controller with damper and integrated measuring nozzle, round version Material: galvanised steel, stainless steel 1.4301 (V2A) Meas. system: DD (measuring nozzle), standard galvanised steel high controller precision and response sensitivity static differential pressure transmitter -100 - 300 Pa insensitive even under inappropriate inflow measuring nozzle with integrated ring meas. chamber fast and stable volume flow control (< 2 s) damper with rubber lip seal For the laboratory supply air (volume flow controller made of steel) the measuring nozzle DD (standard version) or optional the measuring cross with additional shield KD is delivered. DD-250-S-0-0-0-MM-1 Given that the volume flow control range VMin, VMax and VNom is different for each measuring system the volume flow values for each nominal size of the specific measuring device is listed below. Nominal size Volume flow V , V , V at a flow velocity v measuring nozzle DD (standard) MIN MAX VAV700-X-X-X Installation length NENN NS [mm] v ≈ 1 m/s V [m3/h] v = 6 m/s V [m3/h] v ≈ 10m/s V [m3/h] W [mm] L1 [mm] L [mm] 100 28 160 277 378 40 298 MIN MAX NOM 125 45 253 450 378 40 298 160 76 418 762 388 40 308 200 123 658 1230 408 40 328 225 156 836 1559 433 40 353 250 208 1035 2078 443 60 363 280 236 1302 2356 513 60 393 315 294 1651 2944 543 60 423 355 381 2102 3811 613 60 493 400 469 2674 4694 673 60 553 250 300 Actuator NMQ-12 100 100 Actuator NMQ-12 Damper Damper Co n VA troll V5 er 00 7 Controller VAV500 Air direction 10 0 + Pressure nibbles L1 L1 Measuring nozzle NW Built-in length = L Overall length = B Planning instruction for volume flow determination: Consider volume flow in relation to flow velocity v V = volume flow at a flow velocity v = 1 bis 2 m/s V = volume flow at a flow velocity v = 6 m/s (recommended) V = volume flow at a flow velocity v = 10 bis 12 m/s MIN MAX NOM Due to the flow noise of the volume flow VMAX the flow velocity v should not overrun 6 m/s during the laboratory operation (exhaust and supply air). In case of exceeding this value the required noise level of < 52 dB(A) according to DIN1946, part 7 can only be reached with complex sound absorption. The maximal adjustable volume flow VMAX should always be about 40 % below VNOM. 24 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Dimensions ● Volume flow ranges, round version ● galvanised steel, stainless steel 1.4301 Material: galvanised steel, stainless steel 1.4301 (V2A) Volume flow controller with damper and integrated measuring cross respectively maintenance-free measuring device (only available in stainless steel), round version Meas. KD (measuring cross with additional shield) system: SD (measuring cross without additional shield) MD (maintenance-free measuring system), only available in stainless steel high controller precision and response sensitivity static differential pressure transmitter -100 - 300 Pa consider sufficient inflow distance (≥ 2*D) measuring nozzle with shield fast and stable volume flow control (< 2 s) damper with rubber lip seal KD-250-S-0-0-0-MM-1 For the laboratory supply air (volume flow controller in steel design) the measuring cross with additional shield KD or optional the measuring nozzle DD (standard version) is delivered. The measuring device MD (patented by SCHNEIDER) is only available in plastic or steel. VAV700-X-X-X Given that the volume flow control range VMin, VMax and VNom is different for each measuring system the volume flow values for each nominal size of the specific measuring device is listed below. Nominal size Volume flow control range V , V , V of the measuring devices KD, MD at a flow velocity v MIN Measuring cross with additional shield KD (standard) MAX Measuring cross without additional shield SD Maintenance-free measuring device MD (only in stainl. steel 1.4301) v ≈ v= v≈ 1 m/s 6 m/s 10 m/s VMIN VMAX VNENN [m3/h] [m3/h] [m3/h] NS [mm] v ≈ 1 m/s V [m3/h] v= 6 m/s V [m3/h] v≈ 10 m/s V [m3/h] v ≈ 1 m/s V [m3/h] v= 6 m/s V [m3/h] v≈ 10 m/s V [m3/h] 100 19 160 191 36 160 364 28 205 125 33 253 329 68 253 675 36 265 MIN MAX NOM MIN MAX Installation length NOM NOM W [mm] L1 [mm] L [mm] 277 340 28 284 364 360 28 304 160 54 418 537 123 418 1230 59 434 589 410 28 354 200 95 658 953 189 658 1888 100 679 1005 450 28 394 225 128 836 1282 250 836 2500 130 850 1300 475 28 419 250 161 1035 1611 308 1035 3083 163 1060 1628 500 28 444 208 1330 2078 550 28 494 280 229 1302 2286 393 1302 3932 315 296 1651 2962 485 1651 4850 267 1683 2667 600 28 544 2138 3447 650 28 594 2714 4347 700 28 644 355 390 2102 3897 675 2102 6755 345 400 553 2674 5525 824 2674 8141 435 300 250 Actuator NMQ-12 100 100 Actuator NMQ-12 Damper Damper Co n VA troll V5 er 00 12 Controller VAV500 Air direction 10 0 + Pressure nibbles L1 Measuring cross L1 NW Built-in length = L Overall length = B Recommended volume flow V at a flow velocity v = 6m/s. Consider planning instruction for volume flow control range V , V MAX MIN Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com MAX und V NOM on page 28. 25 VAV700 Multi-functional air volume flow controller with integrated web server Dimensions ● Volume flow ranges, round version ● PPs, PPs-el, PVC Volume flow controller with damper and integrated maintenance-free measuring system, round design Material: PPs, PPs-el, PVC Meas. system: MD (maintenance-free measuring device), standard in PPs, PPs-el, PVC high controller precision and response sensitivity measuring device with integrated ring meas. chamber insensitive even under inappropriate inflow maintenance-free and self cleaning static differential pressure transmitter -100 - 300 Pa option: tight closing damper according to DIN The measuring device MD (patented by SCHNEIDER) offers the best quality/price ratio for the laboratory exhaust air (volume flow controller in PPs design) and is delivered by default. MD-250-P-0-0-0-MM-1 Given that the volume flow control range VMin, VMax and VNom is different for each measuring system the volume flow values for each nominal size of the specific measuring device is listed below. Volume flow V , V , V at a flow velocity v Measuring device MD (standard) VAV700-X-X-X Nominal size InnerØ NS [mm] D [mm] v ≈ 1 m/s V [m3/h] v = 6 m/s V [m3/h] v ≈ 10m/s V [m3/h] W [mm] L1 [mm] L [mm] Ext. Ø D1[mm] MIN MIN MAX MAX NOM NOM Installation length Flange dimensions K d [mm] [mm] No. 110 111 28 205 277 300 40 220 170 150 7 4 125 126 36 265 364 300 40 220 185 165 7 8 160 161 59 434 589 340 40 260 230 200 7 8 200 201 100 679 1005 350 50 250 270 240 7 8 250 251 163 1060 1628 400 50 300 320 290 7 12 315 316 267 1683 2667 490 50 390 395 350 9 12 400 401 435 2714 4347 580 50 480 480 445 9 16 Make: MD-XXX-P-MM-1 (socket/socket) Make: MD-XXX-P-FF-1 (flange/flange) Ring chamber 1 with measuring drills d=3,0mm Ring chamber 1 with measuring drills d=3,0mm Air direction Air direction L1 Built-in length = L L1 Overall length = B Overall length = built in length = B Ring chamber 2 both sides with measuring drills d=3,0mm Ring chamber 2 both sides with measuring drills d=3,0mm Damper 90° shifted arranged to the measuring tube Damper 90° shifted arranged to the measuring tube Recommended volume flow V at a flow velocity v = 6m/s. Consider planning instruction for volume flow control range V , V MAX MIN 26 MAX und V NOM on page 28. Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Dimensions ● Volume flow ranges, round version ● PPs, PPs-el, PVC Volume flow controller with damper and integrated maintenance-free Venturi measuring nozzle, round version Material: PPs, PPs-el, PVC Meas. system: VD (Venturi meas. nozzle), against extra charge high controller precision and response sensitivity Venturi nozzle with integrated ring meas. chamber insensitive even under inappropriate inflow maintenance-free and self cleaning static differential pressure transmitter -100 - 300 Pa option: tight closing damper according to DIN SCHNEIDER offers besides the patented measuring-device MD the Venturi measuring nozzle VD (against extra charge) for the laboratory exhaust air (volume flow controller in PPs design). VD-250-P-0-0-0-MM-1 Given that the volume flow control range VMin, VMax and VNom is different for each measuring system the volume flow values for each nominal size of the specific measuring device is listed below. Volume flow V , V , V at a flow velocity v Measuring device VD VAV700-X-X-X Nominal size InnerØ NS [mm] D [mm] v ≈ 1 m/s VMIN [m3/h] v = 6 m/s VMAX [m3/h] v ≈ 10m/s VNENN [m3/h] W [mm] L1 [mm] L [mm] Ext.Ø D1[mm] 110 111 33 205 329 300 40 220 170 125 126 45 265 450 300 40 220 160 161 69 434 693 340 40 260 MIN MAX NOM Installation length Flange dimensions K d [mm] [mm] No. 150 7 4 185 165 7 8 230 200 7 8 200 201 106 679 1057 350 50 250 270 240 7 8 250 251 159 1060 1593 400 50 300 320 290 7 12 315 316 279 1683 2789 490 50 390 395 350 9 12 400 401 449 2714 4486 580 50 480 480 445 9 16 Ring chamber 1 with measuring drills d = 3,0mm Ring chamber 2 with measuring drills d = 3,0mm D Air direction L1 Built-in length = L Ring chamber 2 with measuring drills d = 3,0mm Air direction D Ring chamber 1 with measuring drills d = 3,0mm Make: VD-XXX-P-FF-1 (flange/flange) D1 Make: VD-XXX-P-MM-1 (socket/socket) L1 Overall length = B K d Overall length = built in length = B Recommended volume flow V at a flow velocity v = 6m/s. Consider planning instruction for volume flow control range V , V MAX MIN Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com MAX und V NOM on page 28. 27 VAV700 Multi-functional air volume flow controller with integrated web server Dimensions ● Volume flow ranges, rectangular design ● PPs, PPs-el, PVC ● not airteight closing Volume flow controller with damper and inte- Material: PPs, PPs-el, PVC grated measuring device, rectangular version, Meas. MD (maintenance-free measuring device), standard not airteight closing system: in PPs, PPs-el, PVC high controller precision and response sensitivity static differential pressure transmitter -100 - 300 Pa consider sufficient inflow distance (≥ 2*D) measuring nozzle with integrated ring meas. chamber fast and stable volume flow control (< 2 s) maintenance-free and self cleaning The measuring device MD (patented by SCHNEIDER) offers the best quality/price ratio for the laboratory exhaust air (volume flow controller in PPs, PPs-el and PVC design) and is delivered by default. VAV700-X-X-X DD-400-300-P-0-0-1 400 500 600 700 800 900 1000 250 300 350 400 216 648 1296 324 972 1944 432 1296 2592 540 1620 3240 648 1944 3888 756 2268 4536 - 288 864 1728 432 1296 2592 576 1728 3456 720 2160 4320 864 2592 5184 1008 3024 6048 1152 3456 6912 - 360 1080 2160 540 1620 3240 720 2160 4320 900 2700 5400 1080 3240 6480 1260 3780 7560 1440 4320 8640 1620 4860 9720 1800 5400 10800 432 1296 2592 648 1944 3888 864 2592 5184 1080 3240 6480 1296 3888 7776 1512 4536 9072 1728 5184 10368 1944 5832 11664 2160 6480 12960 504 1512 3024 756 2268 4536 1008 3024 6048 1260 3780 7560 1512 4536 9072 1764 5292 10584 2016 6048 12096 2268 6804 13608 2520 7560 15120 576 1728 3456 864 2592 5184 1152 3456 6912 1440 4320 8640 1728 5184 10368 2016 6048 12096 2304 6912 13824 2592 7776 15552 2880 8640 17280 [m3/h] VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM Damper + Air direction + 400 Damper ca. 60 ca. 100 B MAX 28 - Controller Pressure nibble Intermediate sizes on demand. Recommended volume flow V at a flow velocity v = 6m/s. Consider planning instruction for volume flow control range V , V MIN Actuator Measuring device H 300 200 35 200 150 Range Actuator W [mm] Volume flow controller VMIN (at v = 2 m/sec), VMAX (at v = 6 m/s), VNOM (at v = 12 m/sec) Height H [mm] Controller Width MAX und V NOM 35 on page 28. Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Dimensions ● Volume flow ranges, rectangular version ● PPs, PPs-el, PVC ● airteight closing Volume flow controller with damper and inte- Material: PPs, PPs-el, PVC grated measuring device, rectangular version, Meas. MD (maintenance-free measuring device), standard airteight closing according to DIN 1946, part 4 system: in PPs, PPs-el, PVC high controller precision and response sensitivity static differential pressure transmitter -100 - 300 Pa consider sufficient inflow distance (≥ 2*D) measuring nozzle with integrated ring meas. chamber fast and stable volume flow control (< 2 s) maintenance-free and self cleaning The measuring device MD (patented by SCHNEIDER) offers the best quality/price ratio for the laboratory exhaust air (volume flow controller in PPs, PPs-el and PVC design) and is delivered by default. The airteight closing model is only available in the following special dimensions. VAV700-X-X-X DD-400-360-P-K-0-1 500 600 700 800 900 1000 1420 4260 8519 1909 5728 11457 2399 7197 14394 2889 8666 17332 3378 10135 20269 3868 11604 23207 4357 13072 26145 4847 14541 29082 1764 5293 10586 2373 7118 14237 2981 8943 17887 3590 10796 21537 4198 12594 25188 4806 14419 28838 5415 16244 32489 6023 18069 36139 [m3/h] VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM Damper + - Air direction Controller Pressure nibble + 400 Damper ca. 60 ca. 100 B Intermediate sizes on demand. Recommended volume flow V at a flow velocity v = 6m/s. Consider planning instruction for volume flow control range V , V MAX MIN Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com Actuator Measuring device H 400 705 2114 4227 1075 3226 6452 1446 4338 8677 1817 5451 10902 2188 6563 13126 2559 7676 15351 2929 8788 17576 3300 9900 19801 3671 11013 22026 35 300 479 1436 2873 731 2192 4385 983 2948 5897 1235 3704 7409 1487 4460 8921 1739 5216 10433 1991 5972 11945 - Actuator 200 253 759 1518 386 1159 2318 519 1558 3117 653 1958 3916 786 2358 4715 - Range Controller Width Volume flow controller VMIN (at v = 2 m/ sec), VMAX (at v = 6 m/s), VNOM (at v = 12 m/sec) Height H [mm] W 195 360 525 690 855 [mm] MAX und V NOM 35 on page 28. 29 VAV700 Multi-functional air volume flow controller with integrated web server Dimensions ● Volume flow ranges, rectangular version ● galvanised steel, stainless steel 1.4301 Volume flow controller with damper and integrated measuring device, rectangular version Material: galvanised steel, stainless steel 1.4301 (V2A) Meas. system: MD (maintenance-free measuring device), standard, stainless steel DD (measuring nozzle), standard, galvanised steel KD (measuring cross with additional shield) SD (measuring cross without additional shield) high controller precision and response sensitivity static differential pressure transmitter -100 - 300 Pa consider sufficient inflow distance (≥ 2*D) maintenance-free measuring device MD, stainless steel 1.4301 fast and stable volume flow control (< 2 s) measuring nozzle DD, galvanised steel and stainless steel 1.4301 For the laboratory supply air (volume flow controller in steel design) the measuring nozzle DD (standard version) or optional the measuring cross with additional shield KD is delivered. VAV700-X-X-X The measuring device MD (patented by SCHNEIDER) offers the best quality/price ratio for the laboratory exhaust air (volume flow controller in PPs, PPs-el and PVC design) and is delivered by default. Width Volume flow controller VMIN (at v = 2 m/sec), VMAX (at v = 6 m/s), VNOM (at v = 12 m/sec Höhe H [mm] B 100 150 200 250 300 350 400 [mm] 600 700 800 900 1000 432 1296 2592 648 1944 3888 864 2592 5184 1080 3240 6480 1296 3888 7776 1512 4536 9072 1728 5184 10368 1944 5832 11664 2160 6480 12960 504 1512 3024 756 2268 4536 1008 3024 6048 1260 3780 7560 1512 4536 9072 1764 5292 10584 2016 6048 12096 2268 6804 13608 2520 7560 15120 [m3/h] 576 1728 3456 864 2592 5184 1152 3456 6912 1440 4320 8640 1728 5184 10368 2016 6048 12096 2304 6912 13824 2592 7776 15552 2880 8640 17280 VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM VMIN VMAX VNOM Intermediate sizes on demand. Recommended volume flow V at a flow velocity v = 6m/s. Consider planning instruction for volume flow control range V , V MAX MIN 30 MAX Damper Controller Pressure nibble Air direction + Actuator Measuring cross 400 Damper H 500 360 1080 2160 540 1620 3240 720 2160 4320 900 2700 5400 1080 3240 6480 1260 3780 7560 1440 4320 8640 1620 4860 9720 1800 5400 10800 35 400 288 864 1728 432 1296 2592 576 1728 3456 720 2160 4320 864 2592 5184 1008 3024 6048 1152 3456 6912 - Controller VAV500 300 216 648 1296 324 972 1944 432 1296 2592 540 1620 3240 648 1944 3888 756 2268 4536 - Actuator NMQ-12 200 144 432 864 216 648 1296 288 864 1728 360 1080 2160 432 1296 2592 504 1512 3024 - DD-600-400-S-0-0-1 Range 105 und V NOM B 35 on page 28. Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Sound values ● PPs-volume flow controller with maintenance-free measuring device, round design Table 4: flow noise 4000 Hz 53 64 67 71 73 50 59 65 69 74 53 64 67 71 73 47 60 62 67 69 48 62 64 66 70 54 61 65 67 70 53 62 66 72 72 54 61 65 67 70 47 61 63 68 70 49 62 64 68 70 53 58 61 64 66 52 60 64 67 70 53 58 61 64 66 49 57 59 64 66 49 59 61 67 69 53 57 61 64 68 56 60 63 66 68 53 57 61 64 68 51 55 57 61 63 50 57 59 64 66 51 55 58 60 62 57 59 63 67 69 51 55 58 60 62 54 55 57 58 60 53 54 56 59 61 50 53 54 56 59 58 59 63 68 69 50 53 54 56 59 52 51 53 55 57 50 52 54 56 58 56 49 50 53 55 57 60 63 66 65 56 49 50 53 55 50 47 49 51 53 48 48 50 51 53 Definitions: in Hz: fm LW in dB/octave: in dB(A): LWA L in dB(A): ∆pg in Pa: V in m3/h: v in m/s: 42 43 45 48 51 59 62 64 61 61 42 43 45 48 51 50 48 50 50 52 48 47 49 50 52 60 60 63 66 69 65 67 70 73 75 60 60 63 66 69 57 59 61 64 66 57 60 62 66 68 52 52 55 58 61 57 59 62 65 67 52 52 55 58 61 49 51 53 58 58 49 52 54 58 60 56 67 72 75 76 55 61 68 70 75 56 67 72 75 76 52 65 67 72 74 53 67 69 73 75 58 67 72 73 76 57 64 70 74 77 58 67 72 73 76 52 66 68 73 75 54 67 69 73 75 55 64 69 71 72 54 64 70 72 74 55 64 69 71 72 54 62 64 69 71 54 64 66 72 74 60 63 67 69 72 59 66 70 73 74 60 63 67 69 72 56 60 62 66 68 55 62 64 69 71 59 60 63 65 67 63 66 69 72 74 59 60 63 65 67 59 60 62 63 65 58 59 61 64 66 57 58 60 62 64 67 67 69 71 73 57 58 60 62 64 57 56 58 60 62 55 57 59 61 63 58 60 59 59 61 67 66 67 69 71 58 60 59 59 61 55 52 54 56 58 53 53 55 56 58 L in dB(A) 2000 Hz 42 44 48 53 56 46 55 55 56 58 42 44 48 53 56 37 42 44 47 49 38 44 46 53 55 8000 Hz 1000 Hz 50 52 56 61 64 54 63 63 64 66 50 52 56 61 64 45 50 52 55 57 46 52 54 61 63 LWA in dB(A) 500 Hz 22 27 35 45 51 39 42 45 46 50 22 27 35 45 51 32 29 31 33 35 32 30 32 35 37 4000 Hz 250 Hz 33 35 41 49 54 49 56 52 52 55 33 35 41 49 54 33 31 33 38 40 34 34 36 42 44 2000 Hz 125 Hz 46 42 46 51 55 46 60 58 58 60 46 42 46 51 55 35 38 40 43 45 36 40 42 46 48 1000 Hz 63 HZ 45 47 50 55 59 47 53 58 59 62 45 47 50 55 59 38 43 45 47 49 38 46 48 53 55 500 Hz L in dB(A) 46 51 56 59 58 47 51 55 57 59 46 51 56 59 58 43 49 51 55 57 44 52 54 62 64 250 Hz LWA in dB(A) 44 48 53 57 62 47 53 56 60 62 44 48 53 57 62 45 50 52 56 58 47 53 55 61 63 125 Hz 8000 Hz 47 51 58 60 66 50 57 61 64 65 47 51 58 60 66 47 55 57 57 59 48 54 56 58 60 63 HZ 4000 Hz 50 55 62 62 67 47 56 59 61 63 50 55 62 62 67 42 52 54 59 61 41 53 55 60 62 L in dB(A) 2000 Hz 148 290 434 579 724 226 452 679 905 1131 353 707 1060 1414 1767 561 1122 1683 2244 2806 905 1810 2714 3619 4524 8000 Hz 1000 Hz 2 4 6 8 10 2 4 6 8 10 2 4 6 8 10 2 4 6 8 10 2 4 6 8 10 LWA in dB(A) 500 Hz 400 fm in Hz 250 Hz 315 fm in Hz 125 Hz 250 fm in Hz 63 HZ 200 ∆pg = 500 Pa LW in dB/octave V in m3/h 160 ∆pg = 250 Pa LW in dB/octave v in m/s Nom. size in mm ∆pg = 100 Pa LW in dB/octave 54 58 57 56 58 66 66 70 69 70 54 58 57 56 58 55 53 55 55 57 53 52 54 55 57 65 67 69 71 73 73 73 76 78 80 65 67 69 71 73 62 64 66 69 71 62 65 67 71 73 57 59 61 63 65 65 65 68 70 72 57 59 61 63 65 54 56 58 61 63 54 57 59 63 65 mid-band frequency of the octave band sound power level determined in the echo chamber overall noise level, A-rated noise level, A-rated, room attenuation of 8 dB/octave considered total pressure difference (measured in front of and behind the volume flow controller) volume flow flow velocity Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 31 VAV700 Multi-functional air volume flow controller with integrated web server Sound values ● PPs-volume flow controller with maintenance-free measuring device, round design Table 5: Case-radiated noise 250 315 400 33 42 48 54 54 37 53 47 47 54 33 25 37 44 48 50 31 39 46 47 52 25 26 36 42 47 49 28 37 42 46 49 26 31 34 38 41 44 32 42 44 45 47 31 42 42 44 46 47 34 39 41 44 44 42 47 45 46 47 48 37 38 40 43 44 47 41 39 40 41 43 32 34 35 41 41 41 L in dB(A) 34 33 35 37 40 26 29 32 35 38 34 8000 Hz 42 41 43 45 48 34 37 40 43 46 42 LWA in dB(A) 20 22 23 26 26 22 29 29 26 30 20 4000 Hz 31 30 33 35 36 27 29 31 32 34 31 2000 Hz 38 38 38 40 42 28 30 35 38 40 38 1000 Hz 36 36 37 40 43 26 30 33 38 40 36 500 Hz 25 29 33 38 42 27 30 34 39 41 25 250 Hz 24 32 38 42 45 27 33 38 41 45 24 125 Hz 26 36 41 43 46 30 37 43 44 49 26 63 HZ 33 43 47 49 52 28 38 44 45 52 33 LWA in dB(A) 23 24 27 33 39 18 23 25 29 33 23 33 32 33 34 35 33 34 34 37 38 33 50 49 49 51 53 41 45 47 50 51 50 42 41 41 43 45 33 37 39 42 43 42 4 707 38 32 27 23 27 27 20 7 32 24 43 36 32 29 36 38 30 22 41 33 42 37 36 34 42 45 39 32 49 41 6 8 10 2 4 6 8 10 2 4 6 8 10 1060 1414 1767 561 1122 1683 2244 2806 905 1810 2714 3619 4524 41 46 51 34 44 46 51 53 33 45 47 52 54 34 41 45 34 42 44 44 46 36 42 44 46 48 32 40 46 31 36 38 42 44 33 39 41 47 49 29 39 46 29 35 37 41 43 33 39 41 47 49 30 35 41 25 30 32 34 36 25 33 35 40 42 29 31 37 24 27 29 32 34 26 30 32 36 38 22 22 28 24 22 24 29 31 26 26 28 34 36 9 10 18 24 21 23 25 27 24 22 24 27 29 35 41 47 33 38 40 43 45 34 40 42 49 51 27 33 39 25 30 32 35 37 26 32 34 41 43 47 49 52 39 52 54 59 61 40 54 56 60 62 41 43 46 34 48 50 55 57 37 50 52 56 58 38 42 45 35 43 45 50 52 35 45 47 53 55 33 38 42 37 41 43 47 49 35 45 47 53 55 37 40 43 41 42 44 45 47 40 41 43 46 48 38 40 42 41 40 42 44 46 40 42 44 46 48 33 35 36 41 38 40 42 44 40 40 42 43 45 23 26 26 42 40 42 42 44 40 39 41 42 44 43 45 48 45 47 49 52 54 45 48 50 54 56 35 37 40 37 39 41 44 46 37 40 42 46 48 48 54 54 44 57 59 64 66 45 59 61 65 67 44 48 50 39 53 55 60 62 42 55 57 61 63 42 47 49 40 48 50 55 57 40 50 52 58 60 38 41 44 42 46 48 52 54 40 50 52 58 60 44 46 47 46 47 49 50 52 45 46 48 51 53 46 47 48 46 45 47 49 51 45 47 49 51 53 40 41 43 46 43 45 47 49 45 45 47 48 50 33 34 35 47 45 47 47 49 45 44 46 47 49 49 51 53 50 52 54 57 59 50 53 55 59 61 41 43 45 42 44 46 49 51 42 45 47 51 53 Definitions: in Hz: fm LW in dB/octave: in dB(A): LWA L in dB(A): ∆pg in Pa: V in m3/h: v in m/s: 32 31 32 35 41 47 26 31 33 37 41 31 L in dB(A) 9 7 9 10 18 6 6 12 14 19 9 8000 Hz 15 20 22 22 28 20 20 20 22 26 15 4000 Hz 28 27 29 31 37 20 27 28 30 33 28 2000 Hz 26 27 30 35 41 20 23 28 33 38 26 1000 Hz 20 23 29 39 46 19 23 28 33 37 20 500 Hz 21 27 32 40 46 20 27 32 35 39 21 250 Hz 8000 Hz 28 32 34 41 45 22 33 37 39 43 28 125 Hz 4000 Hz 30 38 41 46 51 24 31 38 39 43 30 63 HZ 2000 Hz 148 290 434 579 724 226 452 679 905 1131 353 LWA in dB(A) 1000 Hz 2 4 6 8 10 2 4 6 8 10 2 L in dB(A) 500 Hz fm in Hz 250 Hz fm in Hz 125 Hz fm in Hz 63 HZ 200 ∆pg = 500 Pa LW in dB/octave V in m3/h 160 ∆pg = 250 Pa LW in dB/octave v in m/s Nom. size in mm ∆pg = 100 Pa LW in dB/octave mid-band frequency of the octave band sound power level determined in the echo chamber overall noise level, A-rated noise level, A-rated, room attenuation of 8 dB/octave considered total pressure difference (measured in front of and behind the volume flow controller) volume flow flow velocity Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Sound values ● Steel volume flow controller with measuring nozzle, round design Tabelle 6: Flow noise 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz LWA in dB(A) L in dB(A) 63 HZ 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 33 41 45 51 40 48 52 58 43 51 55 61 49 57 61 67 51 59 63 69 53 61 65 71 54 62 66 72 55 63 67 73 56 64 68 74 57 65 69 75 40 54 55 56 42 56 57 58 44 58 59 60 46 60 61 62 47 61 62 63 48 62 63 64 49 63 64 65 50 64 65 66 51 65 66 67 52 66 67 68 37 49 51 55 39 51 53 57 43 53 55 59 43 55 57 61 44 56 58 62 45 57 59 63 46 58 60 64 47 59 61 65 48 60 62 66 49 61 63 67 35 45 45 51 37 47 47 53 39 49 49 55 41 51 51 57 42 52 52 58 43 53 53 59 44 54 54 60 45 55 55 61 46 56 56 62 47 57 57 63 34 40 40 45 36 42 42 47 38 44 44 49 40 46 46 51 41 47 47 52 42 48 48 53 43 49 49 54 44 50 50 55 45 51 51 56 46 52 52 57 33 36 37 40 35 38 39 42 37 40 41 44 39 42 43 46 40 43 44 47 41 44 45 48 42 45 46 49 43 46 47 50 44 47 48 51 45 48 49 52 32 35 25 37 34 37 37 39 36 39 39 41 38 41 41 43 39 42 42 44 40 43 43 45 41 44 44 46 42 45 45 47 43 46 46 48 44 47 47 49 33 34 35 35 36 37 38 38 37 38 39 39 38 39 40 40 38 38 39 40 39 40 41 41 38 41 41 42 39 41 42 42 41 41 42 43 42 43 44 44 39 45 49 52 41 47 51 54 43 49 53 56 45 51 55 58 46 52 56 59 47 53 57 60 48 54 58 61 49 55 59 62 50 56 60 63 51 57 61 64 31 37 41 44 33 39 43 46 35 41 45 48 37 43 47 50 38 44 48 51 39 45 49 52 40 46 50 53 41 47 51 54 42 48 52 55 43 49 53 56 37 43 48 58 45 51 56 66 48 54 59 69 54 60 65 75 55 61 66 76 57 63 68 78 58 64 69 79 57 63 68 78 61 67 72 82 64 70 75 85 43 57 63 67 45 59 65 69 47 61 67 71 49 63 69 73 50 64 70 74 51 65 71 75 52 66 72 76 47 61 67 71 54 68 74 78 55 69 75 79 43 54 59 63 45 56 61 65 47 58 63 67 49 60 65 69 50 61 66 70 51 62 67 71 52 63 68 72 42 53 64 62 54 65 70 74 55 66 71 75 41 50 57 58 43 52 59 60 45 54 61 62 47 56 63 64 48 57 64 65 49 58 65 66 50 59 66 67 44 53 61 60 52 61 68 69 53 62 69 70 39 46 51 53 41 48 53 5 43 50 55 57 45 52 57 59 46 53 58 60 47 54 59 61 48 55 60 62 45 52 58 58 50 57 62 64 51 58 63 65 38 44 48 49 40 46 50 51 42 48 52 53 44 50 54 55 45 51 55 56 46 52 56 57 47 53 57 58 47 53 56 57 49 55 59 60 50 56 60 61 37 43 46 47 39 45 48 49 41 47 50 51 43 49 52 53 44 50 53 54 45 51 54 55 46 52 55 56 40 46 54 56 48 54 57 58 49 55 58 59 31 36 39 42 39 44 47 46 37 42 45 48 44 49 52 55 44 49 52 55 45 50 53 56 46 51 54 57 45 50 53 56 48 53 56 59 49 54 57 60 46 53 56 59 48 55 58 61 50 57 60 63 52 59 62 65 53 60 63 66 54 61 64 67 55 62 65 68 56 63 66 69 57 64 67 70 58 65 68 71 38 45 48 51 40 47 50 53 42 49 52 55 44 51 54 57 45 52 55 58 46 53 56 59 47 54 57 60 48 55 58 61 49 56 59 62 50 57 60 63 41 45 53 56 49 53 61 64 55 59 67 70 60 64 72 75 61 65 73 76 63 67 75 78 64 68 76 79 66 70 78 81 67 71 79 82 59 73 81 84 48 61 69 71 50 63 71 73 52 65 73 75 54 67 75 77 55 68 76 78 56 69 77 79 57 70 78 80 58 71 79 81 59 72 80 82 60 73 81 83 47 58 66 67 49 60 68 69 51 62 70 71 53 64 72 73 54 65 73 74 55 66 74 75 56 67 75 76 57 68 76 77 58 69 77 78 59 70 78 79 46 56 61 63 48 58 63 65 50 60 65 67 52 62 67 69 53 63 68 70 54 64 69 71 55 65 70 72 56 66 71 73 57 67 72 74 58 68 73 75 45 53 57 59 47 55 59 61 49 57 61 63 51 59 63 65 52 60 64 66 53 61 65 67 54 62 66 68 55 63 67 69 56 64 68 70 57 65 69 71 44 52 54 56 46 54 56 58 48 56 58 60 50 58 60 62 51 59 61 63 52 60 62 64 53 61 63 65 54 62 64 66 55 63 65 67 56 64 66 68 41 47 51 54 43 49 53 56 45 51 55 58 47 53 57 60 48 54 58 61 49 55 59 62 50 56 60 63 51 57 61 64 52 58 62 65 53 59 63 66 Definitions: in Hz: fm LW in dB/octave: in dB(A): LWA L in dB(A): ∆pg in Pa: V in m3/h: v in m/s: L in dB(A) 63 HZ 85 170 257 344 130 263 396 530 216 434 652 871 337 680 1024 1370 422 850 1279 1709 529 1065 1604 2144 666 1339 2014 2690 843 1692 2543 3394 1073 2160 3252 4347 1364 2736 4111 5488 8000 Hz L in dB(A) 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 LWA in dB(A) LWA in dB(A) 400 8000 Hz 355 4000 Hz 315 2000 Hz 280 1000 Hz 250 500 Hz 225 fm in Hz 250 Hz 200 fm in Hz 125 Hz 160 fm in Hz 63 HZ 125 ∆pg = 500 Pa LW in dB/octave V in m3/h 100 ∆pg = 250 Pa LW in dB/ocave v in m/s Nom. size in mm ∆pg = 125 Pa LW in dB/ocave 41 46 50 52 42 47 51 53 46 51 55 57 47 52 56 59 48 53 57 59 49 54 58 60 50 55 59 61 51 56 60 62 52 57 61 63 53 58 62 64 52 58 62 65 54 60 64 67 56 62 66 69 58 64 68 71 59 65 69 72 60 66 70 73 61 67 71 74 62 68 72 75 63 69 73 76 64 70 74 77 44 50 54 57 46 52 56 59 48 54 58 61 50 56 60 63 51 57 61 64 52 58 62 65 53 59 63 66 54 60 64 67 55 61 65 68 56 62 66 69 mid-band frequency of the octave band sound power level determined in the echo chamber overall noise level, A-rated noise level, A-rated, room attenuation of 8 dB/octave considered total pressure difference (measured in front of and behind the volume flow controller) volume flow flow velocity Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 33 VAV700 Multi-functional air volume flow controller with integrated web server Sound values ● Steel volume flow controller with measuring nozzle, round version Table 7: Case-radiated noise 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 8000 Hz LWA in dB(A) L in dB(A) 63 HZ 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz 15 23 27 33 22 30 34 40 25 33 37 43 36 45 48 54 41 50 53 60 45 54 57 63 46 55 58 64 47 55 59 65 48 56 60 66 47 55 59 65 22 36 37 38 24 38 39 40 26 40 41 42 33 47 48 49 37 51 52 53 40 54 55 56 41 55 56 57 42 56 57 58 43 57 58 59 42 56 57 58 21 33 35 39 23 35 37 41 27 39 41 45 30 42 44 48 31 43 45 49 30 42 44 48 33 45 47 51 32 44 46 50 35 47 49 53 37 49 51 55 22 32 32 38 20 30 30 36 21 31 31 37 24 34 34 40 27 37 37 43 27 37 37 43 31 41 41 47 29 39 39 45 31 41 41 47 33 43 43 49 18 24 24 29 20 26 26 31 23 29 29 34 25 31 31 36 30 36 36 41 28 34 34 39 33 39 39 44 30 36 36 41 35 41 41 46 36 42 42 47 20 23 24 27 22 25 26 29 24 27 28 31 28 31 32 35 30 33 34 37 30 33 34 37 32 35 36 39 33 36 37 40 38 41 42 45 33 36 37 40 21 24 24 26 25 28 28 30 27 30 30 32 30 33 33 35 31 34 34 36 32 35 35 37 32 35 35 37 34 37 37 39 36 39 39 41 37 40 40 42 22 23 23 24 27 28 29 29 28 29 30 32 30 31 32 32 30 30 31 32 31 32 33 33 29 32 32 33 31 33 34 34 34 34 35 36 35 36 37 37 24 31 34 37 26 33 36 39 28 35 38 41 32 38 42 45 35 41 45 48 35 41 45 48 37 43 47 50 37 43 47 50 40 46 50 53 40 46 50 53 16 23 26 29 18 25 28 31 20 27 30 33 24 30 34 37 27 33 37 40 27 33 37 40 29 35 39 42 29 35 39 42 32 38 42 45 32 38 42 45 19 25 30 40 27 33 37 48 30 36 41 51 41 47 52 62 45 51 56 66 49 55 60 70 50 56 61 71 42 48 53 63 53 59 64 74 54 60 65 75 25 39 45 49 27 41 47 51 29 43 49 53 36 50 56 60 40 54 60 64 43 57 63 67 44 58 64 68 32 46 52 56 46 60 66 70 45 59 65 69 27 38 43 47 29 40 45 49 33 44 49 53 36 47 52 56 37 48 53 57 36 47 52 56 39 50 55 59 27 38 49 47 41 52 57 61 43 54 59 63 28 37 44 45 26 35 42 43 27 36 43 44 30 39 46 47 33 42 49 50 33 42 49 50 37 46 53 54 28 37 45 44 37 46 53 54 39 48 55 56 23 30 35 37 25 32 37 39 28 35 40 42 30 37 42 44 35 42 47 49 33 40 45 47 38 45 50 52 31 38 44 44 40 47 52 54 41 48 53 55 25 31 35 36 27 33 37 38 29 35 39 40 33 39 43 44 35 41 45 46 35 41 45 46 37 43 47 48 37 43 46 47 43 49 53 54 38 44 48 49 26 32 35 36 30 36 39 40 32 38 41 42 35 41 44 45 36 42 45 46 37 43 46 47 37 43 46 47 32 38 46 48 41 47 50 51 42 48 51 52 20 25 28 31 30 35 38 38 30 33 36 39 36 41 44 47 36 41 44 47 37 42 45 48 37 42 45 48 37 42 45 48 41 46 49 50 42 47 50 53 31 38 42 44 33 40 44 46 35 42 46 48 39 46 49 52 42 49 52 55 42 49 52 55 44 51 54 57 44 51 54 57 47 54 57 60 47 54 57 60 23 30 34 36 25 32 36 38 27 34 38 40 31 38 41 44 34 41 44 47 34 41 44 47 36 43 46 49 36 43 46 49 39 46 49 52 39 46 49 52 23 27 35 38 31 35 43 46 37 41 49 52 47 51 59 62 51 55 65 66 55 59 67 70 56 60 68 71 58 62 70 73 59 63 71 74 59 63 71 74 30 43 51 53 32 45 53 55 34 47 55 57 41 54 62 64 45 58 66 68 48 61 69 71 49 62 70 72 50 63 71 73 51 64 72 74 50 63 71 73 31 42 50 51 33 44 52 53 37 48 56 57 40 51 59 60 41 52 60 61 40 51 59 60 43 54 62 63 42 53 61 62 45 56 64 65 47 58 66 67 33 43 48 50 31 41 46 48 32 42 47 49 35 45 50 52 38 48 53 55 38 48 53 55 42 52 57 59 40 50 55 57 42 52 57 59 44 54 59 61 29 37 41 43 31 39 43 45 34 42 46 48 36 44 48 50 41 49 53 55 39 47 51 53 44 52 56 58 41 49 53 55 46 54 58 60 47 55 59 61 31 39 41 43 33 41 43 45 35 43 45 47 39 47 49 51 41 49 51 53 41 49 51 53 43 51 53 55 44 52 54 56 49 57 59 61 44 52 54 56 30 36 40 43 34 40 44 47 36 42 46 49 39 45 49 52 40 46 50 53 41 47 51 54 41 47 51 54 43 49 53 56 45 51 55 58 46 52 56 59 Definitions: in Hz: fm LW in dB/octave: in dB(A): LWA L in dB(A): ∆pg in Pa: V in m3/h: v in m/s: 34 L in dB(A) 63 HZ 85 170 257 344 130 263 396 530 216 434 652 871 337 680 1024 1370 422 850 1279 1709 529 1065 1604 2144 666 1339 2014 2690 843 1692 2543 3394 1073 2160 3252 4347 1364 2736 4111 5488 8000 Hz L in dB(A) 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 3 6 9 12 LWA in dB(A) LWA in dB(A) 400 8000 Hz 355 4000 Hz 315 2000 Hz 280 1000 Hz 250 500 Hz 225 fm in Hz 250 Hz 200 fm in Hz 125 Hz 160 fm in Hz 63 HZ 125 ∆pg = 500 Pa LW in dB/octave V in m3/h 100 ∆pg = 250 Pa LW in dB/octave v in m/s Nom. size in mm ∆pg = 125 Pa LW in dB/octave 30 35 39 41 33 38 42 44 37 42 46 48 39 44 48 51 40 45 49 51 41 46 50 52 41 46 50 52 43 48 52 54 45 50 54 56 46 51 55 57 37 43 47 50 39 45 49 52 41 47 51 54 45 51 55 58 48 54 58 61 48 54 58 61 50 56 60 63 50 56 60 63 53 59 63 66 53 59 63 66 29 35 39 42 31 37 41 44 33 39 43 46 37 43 47 50 40 46 50 53 40 46 50 53 42 48 42 55 42 48 52 55 45 51 55 58 45 51 55 58 mid-band frequency of the octave band sound power level determined in the echo chamber overall noise level, A-rated noise level, A-rated, room attenuation of 8 dB/octave considered total pressure difference (measured in front of and behind the volume flow controller) volume flow flow velocity Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Sound values ● PPs-volume flow controller with measuring cross, rectangular version Table 8: Airflow surface Width B [mm] 200 300 400 500 600 700 800 900 1000 100 160 Height H [mm] 200 250 300 400 0,020 0,032 0,040 0,050 0,060 0,080 0,030 0,048 0,060 0,075 0,090 0,120 0,040 0,064 0,080 0,100 0,120 0,160 0,050 0,080 0,100 0,125 0,150 0,200 0,060 0,096 0,120 0,150 0,180 0,240 0,070 0,112 0,140 0,175 0,210 0,280 0,080 0,128 0,160 0,200 0,240 0,320 0,090 0,144 0,180 0,225 0,270 0,360 0,100 0,160 0,200 0,250 0,300 0,400 Table 9: Flow noise ∆pg = 1000 Pa 4000 Hz LWA in dB(A) L in dB(A) 71 76 80 82 2000 Hz 73 77 80 84 1000 Hz 73 78 81 84 500 Hz 74 79 80 85 250 Hz 74 78 79 85 125 Hz 64 68 74 77 L in dB(A) 72 76 82 85 4000 Hz 2000 Hz 63 67 73 76 LWA in dB(A) 1000 Hz 65 69 75 78 500 Hz 67 71 76 79 250 Hz 67 72 78 80 125 Hz 68 73 78 81 L in dB(A) 68 73 79 81 4000 Hz 3 6 9 12 LWA in dB(A) 2000 Hz fm in Hz 1000 Hz fm in Hz 500 Hz fm in Hz 250 Hz LW in dB/octave 125 Hz 1 ∆pg = 500 Pa LW in dB/octave v in m/s Area A in m2 ∆pg = 250 Pa LW in dB/octave 69 74 78 81 78 82 86 89 70 74 78 81 81 84 86 87 82 85 88 89 81 84 87 89 81 84 86 90 80 84 86 89 77 82 85 88 86 90 92 95 78 82 84 87 Table 10: Case-radiated noise ∆pg = 1000 Pa 4000 Hz LWA in dB(A) L in dB(A) 58 62 65 66 2000 Hz 63 66 67 70 1000 Hz 68 73 75 78 500 Hz 74 80 79 83 250 Hz 82 85 85 90 125 Hz 57 61 65 66 L in dB(A) 65 69 73 74 4000 Hz 2000 Hz 50 50 54 57 LWA in dB(A) 1000 Hz 51 54 58 60 500 Hz 56 58 61 63 250 Hz 62 66 70 71 125 Hz 68 72 75 77 L in dB(A) 75 80 85 86 4000 Hz 3 6 9 12 LWA in dB(A) 2000 Hz fm in Hz 1000 Hz fm in Hz 500 Hz fm in Hz 250 Hz LW in dB/octave 125 Hz 1 ∆pg = 500 Pa LW in dB/octave v in m/s Area A in m2 ∆pg = 250 Pa LW in dB/octave 53 57 61 64 72 76 77 80 64 68 69 72 90 95 95 94 82 85 87 87 77 79 82 84 72 75 75 78 67 70 71 73 60 66 69 71 80 83 85 86 72 75 77 78 Table 11: Correction factor for flow noise and case-radiated noise A [m²] 0,04 0,06 0,08 0,10 0,12 0,16 0,2 0,25 0,3 0,4 0,5 0,6 0,8 1 CF [-] - 14 - 12 - 11 - 10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 Definitions: in Hz: fm LW in dB/Oktave: in dB(A): LWA L in dB(A): in Pa: ∆pg V in m3/h: v in m/s: A in m2: CF mid-band frequency of the octave band sound power level determined in the echo chamber overall noise level, A-rated noise level, A-rated, room attenuation of 8 dB/octave considered total pressure difference (measured in front of and behind the volume flow controller) volume flow flow velocity airflow surface (W x H) correction factor Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 35 VAV700 Multi-functional air volume flow controller with integrated web server Sound values ● Steel volume flow controller with measuring cross, rectangular version Table 12: Airflow surface Width B [mm] 200 300 400 500 600 700 800 900 1000 100 160 Height H [mm] 200 250 300 400 0,020 0,032 0,040 0,050 0,060 0,080 0,030 0,048 0,060 0,075 0,090 0,120 0,040 0,064 0,080 0,100 0,120 0,160 0,050 0,080 0,100 0,125 0,150 0,200 0,060 0,096 0,120 0,150 0,180 0,240 0,070 0,112 0,140 0,175 0,210 0,280 0,080 0,128 0,160 0,200 0,240 0,320 0,090 0,144 0,180 0,225 0,270 0,360 0,100 0,160 0,200 0,250 0,300 0,400 Table 13: Flow noise ∆pg = 1000 Pa 74 79 80 85 73 78 81 84 73 77 80 84 71 76 80 82 L in dB(A) 74 78 79 85 LWA in dB(A) 64 68 74 77 4000 Hz 2000 Hz 72 76 82 85 2000 Hz 1000 Hz 63 67 73 76 1000 Hz 500 Hz 65 69 75 78 500 Hz 250 Hz 67 71 76 79 250 Hz 125 Hz 67 72 78 80 125 Hz L in dB(A) 68 73 78 81 L in dB(A) LWA in dB(A) 68 73 79 81 4000 Hz 4000 Hz 3 6 9 12 LWA in dB(A) 2000 Hz fm in Hz 1000 Hz fm in Hz 500 Hz fm in Hz 250 Hz LW in dB/octave 125 Hz 1 ∆pg = 500 Pa LW in dB/octave v in m/s Area A in m2 ∆pg = 250 Pa LW in dB/octave 69 74 78 81 78 82 86 89 70 74 78 81 81 84 86 87 82 85 88 89 81 84 87 89 81 84 86 90 80 84 86 89 77 82 85 88 86 90 92 95 78 82 84 87 Table 14: Case-radiated noise ∆pg = 1000 Pa 74 80 79 83 68 73 75 78 63 66 67 70 58 62 65 66 L in dB(A) 82 85 85 90 LWA in dB(A) 57 61 65 66 4000 Hz 2000 Hz 65 69 73 74 2000 Hz 1000 Hz 50 50 54 57 1000 Hz 500 Hz 51 54 58 60 500 Hz 250 Hz 56 58 61 63 250 Hz 125 Hz 62 66 70 71 125 Hz L in dB(A) 68 72 75 77 L in dB(A) LWA in dB(A) 75 80 85 86 4000 Hz 4000 Hz 3 6 9 12 LWA in dB(A) 2000 Hz fm in Hz 1000 Hz fm in Hz 500 Hz fm in Hz 250 Hz LW in dB/octave 125 Hz 1 ∆pg = 500 Pa LW in dB/octave v in m/s Area A in m2 ∆pg = 250 Pa LW in dB/octave 53 57 61 64 72 76 77 80 64 68 69 72 90 95 95 94 82 85 87 87 77 79 82 84 72 75 75 78 67 70 71 73 60 66 69 71 80 83 85 86 72 75 77 78 Table 15: Correction factor for flow noise and case-radiated noise A [m²] 0,04 0,06 0,08 0,10 0,12 0,16 0,2 0,25 0,3 0,4 0,5 0,6 0,8 1 CF [-] - 14 - 12 - 11 - 10 -9 -8 -7 -6 -5 -4 -3 -2 -1 0 Definitions: fm in Hz: in dB/Oktave: LW LWA in dB(A): L in dB(A): in Pa: ∆pg V in m3/h: v in m/s: A in m2: CF 36 mid-band frequency of the octave band sound power level determined in the echo chamber overall noise level, A-rated noise level, A-rated, room attenuation of 8 dB/octave considered total pressure difference (measured in front of and behind the volume flow controller) volume flow flow velocity airflow surface (W x H) correction factor Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Connection diagram Air hosing of static differential pressure sensors - Housing, right side 1, 2, 3 Max. 3 static differential pressure sensors Optional, up to 3 position-independent static differential pressure sensors with measuring ranges (-100 to +300 Pa), (-50 to +50 Pa) and / or (-100 to +1000 Pa) for various measuring tasks. The functionality for the static differential pressure sensor, like exhaust air / supply air, auxilary air, room pressure and / or duct pressure is freely configurable. Lay out air hose kink-free in a loop against ingress of condensation 1 2 3 i Check assignment of function to the air connections! View: housing, right side Air connection (Example) Function Description 1 Exhaust air static differential pressure sensor -100 bis +300 Pa (connect plus and Minus hose) 2 Auxilary air static differential pressure sensor -100 bis +300 Pa 3 Room pressure static differential pressure sensor -50 bis +50 Pa x Duct pressure static differential pressure sensor -100 bis +1000 Pa Overview wiring and sensor hosing Measuring system Lay out air hose kink-free in a loop against ingress of condensation + - Actuator i M Feedback Potentiometer VAVcontroller VAV700 X8 X9 X1 X7 X4 X6 X41 230 VAC Power line X3 Analogue Input Temperature sensor, passive Digital In-/Output BACnet/IP Optional Functional display FA-2.0 485 m³/h Tag OK LOW ECO Laptop Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 37 VAV700 Multi-functional air volume flow controller with integrated web server Connection overview Power Input / Output - Plugs - Housing, left side X41 Power Input 230 VAC The power supply is done via the plug at the left caseside. Optional prewired cabling can be done with WAGO connectors / sockets or with IEC connectors. This simplifies installation and prevents errors. ! Attention! Always disconnect the mains input X41 power input light when working on the device. - Ensure that the controller is power-free Power Supply X41 L L1 230 VAC Only after controller is power-free installation work must be carried out. N N View: housing, left side Plug / Socket X41 38 Function Description Power supply Optional: WAGO socket for Power supply 230 VAC Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Motherboard - Top view Front FA-2.0 High speed actuator linear 0...10 VDC X23 X22 X21 FA-1.0 SW3 JP8 JP7 JP6 Power Supply X20 JP4 CAN-Bus JP5 SW1 JP3 SW2 JP2 JP1 X2 X3 FA-2.0 not applicable for VAV700 Analog Input X4 PT100/ PT1000 X5 not applicable for VAV700 X6 High speed actuator NMQ-12 Direct Drive X1 JP9 X7 Digital I/O 2 x Opto-In 2 x Relay-Out Outside connections housing, back side Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 39 VAV700 Multi-functional air volume flow controller with integrated web server Connection description - Motherboard - Top view Plug / Socket Jumper X20 CAN-Bus plug for extension purposes SW3 X21 Terminator 120 Ohm for CAN-Bus Second FA-2.0, Functional display, 6-pole socket RJ45 JP7, JP8 Plug in jumper JP7 and JP8 if you use one FA-2.0. In case of two FA-2.0 jumper JP7 and JP8 are not plugged = open. X22 Second FA-1.0, Functional display, 8-pole socket RJ45 X23 Actuator, linear, 0...10 VDC JP6 Signal swap X23, Pin 4 and 6 Signal GND/Power GND NETZ Internal connection to power supply board CPU CPU-Board with Ethernet-connection X8 and X9 (external connection at the back side). CPU-Bord must always be plugged here. EMDP DP-Board with 1, 2 or 3 free configurable differential sensors assembled. Extension module EMDP must always be plugged here. EM1 Extension module e. g. EM10, EM50, EMSC etc. optional plug-in EM2 Extension module e. g. EM10, EM50, EMSC etc. optional plug-in EM3 Extension module e. g. EM10, EM50, EMSC etc. optional plug-in EM4 Extension module e. g. EM10, EM50, EMSC etc. optional plug-in Plug / Socket Jumper FA-2.0, Functional display, 6-pole socket RJ45 X2 Not applicable for VAV700 X3 Analogue Input JP9 Universal Analogue Input (special equipment) PT100/PT1000, passive Temperature sensor JP1, JP2, JP3 ! External connections - Housing, back side X1 X4 40 Internal connections - Motherboard PT100/PT1000-Adaption X5 Not applicable for VAV700 X6 NMQ-12, High speed Actuator Direct Drive X7 Digital I/O, 2 x Opto In, 2 x Relay Out SW1, SW2 Optocoupler Input via external voltage or dry contact JP4, JP5 RC-element (time delay) In use of 24 VAC JP4 and/or JP5 plugged. In use of 24 VDC JP4 and/or JP5 not plugged. For terminal connections please refer to the VAV700 Wiring and connection diagram! Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Connection diagram External connections - Housing, back side Grounding Cover X9 X8 Grounding cable cover X1 X2 X3 X4 X5 X6 X7 X Function Description X Function X1 FA-2.0 Functional display 2. Generation, FAZ0700 with graphic display, 6-pole plug X5 AFS100 X6 Actuator X7 X2 FA-1.0 Not applicable for VAV700 X3 A-In Analog Input X4 PT100 or PT1000 Temperature sensor input PT100 or PT1000 X1 Description Not applicable for VAV700 X8 High speed damper actuator NMQ-12, Direct-Drive-Mode Digital IN/OUT 2 x Optocoupler Input, 2 x Relay Output 2 x changeover 24 VAC/3 A ETHERNET Channel-IN-Dual-Port-Switch X9 ETHERNET Channel-OUT-Dual-Port-Switch Functional display 2. Generation (FA-2.0) The functional display has to be mounted visible for the operator (e.g. in the room). FA-2.0 Plug-in only the new functional display (FA-2.0 in X1 with 6-pin plug). A second plug for the respective functional display generation (FA-2.0 = X21) is located on the inside on the motherboard. i Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com ATTENTION on functional displays from the second generation! In use of one functional display FA-2.0 jumpers JP7 and JP8 must be plugged-in. In case of two functional displays FA-2.0 jumpers JP7 and JP8 must be unplugged (=open). These jumpers are located on the inside on the motherboard near the connector X21. 41 VAV700 Multi-functional air volume flow controller with integrated web server Connection overview Motherboard - Case open Front with internal connections Left side for Power Supply, Light and Auxilary air Right side for differential presssure sensor connection Back side with external connections EMDP with 1, 2 or 3 static differential pressure sensors Plug / Socket CPU EMDP 42 CPU-Borad with Ethernet-sockets X8, X9 EM1 till EM4 for Extension modules, e. g. EM10, EM50, EMSC etc. Minimum configuration required for FC700, VAV700, DPC700 CPU-Board with Ethernet-connection X8 and X9 (external connection at the back side). CPU-Bord must always be plugged here. DP-Board with 1, 2 or 3 free configurable differential sensors assembled. Extension module EMDP must always be plugged here. EM1 Extension module e. g. EM10, EM50 etc. optional plug-in EM2 Extension module e. g. EM10, EM50 etc. optional plug-in EM3 Extension module e. g. EM10, EM50 etc. optional plug-in EM4 Extension module e. g. EM10, EM50 etc. optional plug-in Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com VAV700 Multi-functional air volume flow controller with integrated web server Technical data General Nominal voltage Max. charging rate Max. power input Recovery time Operational temperature Humidity External supply Power input Housing Protection class Material Colour Dimensions (LxWxH) Weight Appliances terminals Relay outputs Number Operating principle Max. switching voltage Max. steady current 230 V AC/50/60 Hz/+-15 % 200 mA 35 V A 600 ms 0 OC to +55 OC max. 80 % relative, noncondensing 24 V AC/50/60 Hz/+-10 % 20 V A IP 20 steel plate white, RAL 9002 (290 x 208 x 100) mm approx. 2,8 kg screw-type terminal 1,5 mm2 1 light relay make contact 24 V AC 3A Digital inputs (galvanically isolated) Number 2 optocoupler Max. input voltage 24 V DC +-15 % Max. input circuit 10 mA (per input) Maintenance-free measuring system MD with damper Material polypropylene (PPs) Measuring system integrated measuring system with two ring chambers Optional instead of MD: Venturi measuring device VD with damper Material PPs, PPs-el, PVC Measuring system integrated Venturi measuring nozzle Optional instead of MD, VD: Measuring nozzle DD with damper Material galvanised steel, stainless steel 1.4301 (V2A) Measuring system integrated measuring nozzle Optional instead of MD, VD, DD: Measuring cross KD with damper Material galvanised steel, stainless steel1.4301 (V2A) Measuring system integrated measuring cross Actuator Full load Regulating time Activation Resolution Feedback delay angle Analogue input 1 input 3 Nm 3 s for 90 ° direct with integrated flow monitoring < 0,5 ° < 0,5 ° via potentiometer 0(2) - 10 V DC, 1 mA Differential pressure transmitter Number 3 Measuring principle static Pressure range -100 - 300 Pascal 8 - 800 Pascal optional Response time < 10 ms Sensor burst pressure 500 mbar ETHERNET specification Amount 1 dual port switch Velocity 100 MBit Cable CAT 6 BACnet® specification Interface Ethernet, TCP/IP optional RS 485, MS/TP Modbus® specification (optional) Interface Ethernet, TCP/IP optional RS 485, MS/TP Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com 43 VAV700 Multi-functional air volume flow controller with integrated web server Dimensions ● Scale drawings Housing VAV700: top view 325 315 10 300 180 200 20 Housing VAV700: side view Changes reserved • All rights reserved © SCHNEIDER + - + - 200 + - 95 Static differential pressure sensor (max. 3) + Connection = positive pressure - Connection = negative pressure Tender specification VAV700 For the complete tender specification please visit our website www.schneider-elektronik.com SCHNEIDER Elektronik GmbH Phone: +49 (0) 6171 / 88 479 - 0 Industriestraße 4 Fax: +49 (0) 6171 / 88 479 - 99 61449 Steinbach • Germany e-mail: info@schneider-elektronik.de 44 Technical documentation VAV700 • Date: 01/2015 • www.schneider-elektronik.com