PDLPC416FR-KNX
LightMaster Dimmer Actuator
General Description
The PDLPC416FR-KNX is designed to provide cost effective control of multiple
lighting control protocols for electronic lamp drivers and actuators. Each of the four
control outputs support DALI broadcast, DALI Addressed, 1-10V and DSI protocols.
The control signals can be programmed to operate in tandem with the four
internal switched outputs, which will automatically isolate the power circuit when all
associated channels are at 0%. This feature is useful for energy savings applications,
as DALI ballasts draw a significant amount of power when the lamps are turned
off via a DALI command. The device is DIN rail mountable, designed to be installed
in a switchboard next to the circuit breakers supplying power to the controlled
lighting circuits. The PDLPC416FR-KNX contains an integral DALI bus power supply,
removing the need for an additional external device.
Technical Data
Control Circuit Supply
100-240V 50/60Hz Single Phase at 0.5A
Control Outputs
4 x Control Outputs, each selectable to;
• DALI broadcast: max 20 DALI loads/
ch and a total limit of 80 fittings max
per box
• DALI addressed: max 20 DALI loads/
ch and a total limit of 64 DALI fittings
max per box
• 1-10V: max 20 1-10V loads/ch (max
10mA sink/source) and a total limit of
80 1-10V ballast max per box
• DSI: max 20 DSI loads/ch and a total
limit of 80 DSI fittings max per box
Mains Outputs
4 x 16 Amp feed thru single/multiphase
switched circuits for mains supply max.
inrush current 500A
1 x maintained NC switched output,
rated 5A resistive
Control IO
1 x KNX TPI bus, 21-30Vdc,
max 10mA bus load
4 x voltage free single pole switched
inputs, SELV
DALI bus Power Supply
In built, rated 40mA per channel @ 15V
User Controls
Over-ride switch for each switched
channel
On/Off status indicator for each
switched output
KNX Programming push button & LED
Diagnostic Functions*
• DALI lamp failure reporting
• DALI Ballast failure reporting
• DALI emergency test reporting
• DALI ballast runtime tracking for
each ballast
• Device Online/Offline status
Supply Terminals
Line, Neutral, Earth
1 x 4mm2 max conductor size
KNX TPI Bus Terminals
Wago 243, 0.6-0.8mm single core
conductor diameter
Output Terminals
4 x Ballast power circuit Line In, Line out
1 x 4mm2 max conductor size
1 x maintained NC switched output,
Line In, Line Out, 1 x 4mm sq max
conductor size
4 x Ballast control circuit - D+, D1 x 2.5mm2 max conductor size
Input Terminals:
4 x voltage free single pole switched
inputs, SELV, DC1-DC4, 2 x 1mm sq.
max. conductor size per pole
Environment
-5º to 45ºC operating ambient
temperature
-25º to 70ºC storage temperature
0% to 90% RH non condensing
Compliance
CE, KNX
Enclosure
Polycarbonate DIN Rail enclosure
(12 units wide)
Dimensions
H 96mm x W 211mm x D 75mm
Weight
Packed weight 0.65kg
* Compatible application software is
required for analysing diagnostic data. The
availability of some diagnostics is dependent
on the ballast type.
PDLPC416FR-KNX
LightMaster Dimmer Actuator
Load Compatibility
DALI, DSI and 1-10V HF ballasts
DALI, DSI and 1-10V transformers
DALI, DSI and 1-10V LED drivers
DALI and DSI Relay Modules
Electrical Diagram
E
N
L
Supply:
100-240V
50/60Hz
1 Phase
Switch CH1 In
Switch CH1 Out
Switch CH2 In
Switch CH2 Out
µP
Switch CH3 In
Switch CH3 Out
DC1
Switch CH4 In
COM
DC2
Switch CH4 Out
DC3
EM Switch
COM
DC4
KNX
EM Switch
1-10V/DSI/DALI
Ballast Ch1 DA –
Ballast Ch1 DA +
1-10V/DSI/DALI
Ballast Ch2 DA –
Ballast Ch2 DA +
1-10V/DSI/DALI
Ballast Ch3 DA –
Ballast Ch3 DA +
1-10V/DSI/DALI
Ballast Ch4 DA –
Ballast Ch4 DA +
–
+
For further information contact:
www.philips.com/knx • knx.info@philips.com
PDLPC416FR-KNX Data Sheet Rev C May 2012
Specifications subject to change without notice.
© Not to be reproduced without permission.
Unit 6, 691 Gardeners Road Mascot 2020 Australia.
ABN 33 097 246 921