A B C D E F G H I J K L M N O P R Q T S U V W X Y Z AA AB AC AC AD AE AF AG AH AI FULHAM EMERGENCY LIGHTING APPLICATION NOTE 32 AJ The FULHAM Intelligent Ballast automatically goes to full light output, when it loses communication with the Controller. This provides expected light output from emergency fixtures either supplied with Normal/Emergency power or battery devices, ensuring egress design light levels during emergency conditions. Moreover, Intelligent Sensors and Control Switches will automatically disable, when Normal power supply is removed from the Controller. 28 To ensure consistent operation as described above, please follow the power supply indications in the provided diagram. Ensure identified emergency fixtures are supplied with Normal/Emergency or battery power and that the Controller is supplied by Normal power. 27 AM AM AN AO 33 32 ·FULHAM CONTROLLER (CT-MLC-A04-M) ·MANAGES 25,000 SQFT WITH UP TO 256 DEVICES 31 FULHAM DALI DEVICES 30 The FULHAM Building and Area Solutions provide simple compatibility for implementation of emergency lighting. The provided diagram indicates how Normal and Normal/Emergency power should integrate to the FULHAM solution to ensure consistent and expected FULHAM performance in an emergency lighting condition. 29 AL ·FULHAM SERVER HARDWARE ·FULHAM SERVER SOFTWARE 31 30 AK FULHAM SYSTEM INTELLIGENCE 33 ·INTELLIGENT BALLAST (CF-DA-UNV-xxx-Tx-x) ·SUPPORTS MOST T8/T5/T5HO LAMP TYPES & CONFIGURATION 29 ·CONTROL SWITCH (CU-A-SSC004-S-WD) ·SCENE CONTROLLER - SUPPORTS 4 INDEPENDENT SCENES & DIMMING CAPABILITIES 28 ·INTELLIGENT SENSOR (CS-AA-IOP-xx-C) ·SHORT/LONG RANGE PHOTO/OCCUPANCY SENSOR 27 FULHAM QUICK CONNECT SYSTEM SHARE OCC IN SHARE OCC OUT PHOTO SENSOR TO BALLAST OCC SENSOR TO BALLAST OCC SENSOR DALI&OCC IN 24 PROVIDE NORMAL POWER FEED AND BATTERY BACKUP FOR OR FOR BATTERY SUPPLIED EMERGENCY LIGHTING FIXTURES 23 INTELLIGENT BALLAST CONSULT BALLAST LABEL FOR APPROPRIATE 1/2/3-LAMP CONFIGURATION WIRING DIAGRAM 22 21 A ·DALI PATCH CABLES (CW-C5-4545-I-xxx) ·PLENUM RATED RJ45 CAT5E CABLE FOR QUICK CONNECT DALI CONNECTIONS - 8FT, 16FT, 25FT AND 100FT LENGTH VARIANTS B ·BALLAST DALI CABLE (CW-C5-1212-C-012) ·PLENUM RATED RJ12 CAT5E CABLE FOR QUICK CONNECT BOX TO INTELLIGENT BALLAST - 12FT LENGTH 24 23 ·CONTROL SWITCH CABLE (CW-C5-1245-I-016) ·PLENUM RATED RJ45/RJ12 CAT5E CONVERSION CABLE FOR QUICK CONNECT DALI CONNECTIONS - 16FT LENGTH C PROVIDE NORMAL/EMERGENCY POWER FEED FOR NORMAL LIGHTING FIXTURES 20 PROVIDE NORMAL POWER FEED (CONTROLLER PROVIDES POWER TO THE DALI DEVICES) D D 18 22 B 17 B 21 MULTI-PORT ·STANDARD MULTI-PORT NETWORK SWITCH NETWORK ·ADD ADDITIONAL SWITCHES WHEN PORTS ARE NO LONGER AVAILABLE TO SUPPORT ADDITIONAL CONTROLLERS SWITCH CONTROL SWITCH D 25 PHOTO SENSOR 3RD PARTY EQUIPMENT PROVIDE NORMAL/EMERGENCY POWER FEED OR FOR NORMAL/EMERGENCY LIGHTING FIXTURES 19 26 ·QUICK CONNECT BOX (CW-Qx) ·CLASS 2 COUPLER FOR GENERAL QUICK CONNECT SYSTEM CONNECTIONS SHARE OCC BALLAST DALI&OCC OUT PHOTO BALLAST 25 BLOCK 26 20 D ·LINE VOLTAGE WIRES FOR LINE, NEUTRAL AND GROUND 19 E ·STANDARD NETWORKING CAT-5-ETHERNET CABLE 18 C 17 B 15 E SHARE OCC IN SHARE OCC OUT PHOTO SENSOR TO BALLAST OCC SENSOR TO BALLAST A OCC SENSOR DALI&OCC IN UP TO 4 DALI LOOPS PER CONTROLLER. EACH DALI LOOP SUPPORTS UP TO 64 DALI DEVICES 13 SHARE OCC BALLAST DALI&OCC OUT PHOTO BALLAST BLOCK OCC SENSOR TO BALLAST PHOTO SENSOR DALI LOOP 1 CONTROLLER 16 A SHARE OCC IN SHARE OCC OUT PHOTO SENSOR TO BALLAST OCC SENSOR DALI&OCC IN A MULTI-PORT NETWORK SWITCH 14 OCC BALLAST DALI&OCC OUT PHOTO BALLAST SHARE QUICK CONNECT BOX BLOCK D 16 15 PHOTO SENSOR INTELLIGENT SENSOR 14 13 E 12 12 EXTEND TO NEXT DALI DEVICE(S) 11 11 10 10 9 9 CLOUD/ LOCAL SERVER 8 8 7 7 6 6 5 5 4 BJS All information provided is intended solely for general information purposes only and we cannot take responsibility for the results or consequences of any attempt to use or adapt any of the information, including, without limitation, any design configuration, equipment configuration, equipment requirements, component interoperability or other miscellaneous configuration specifications. The drawing is provided "as is", without warranty of any kind, either express or implied, including, but not limited to, any implied warranties of fitness for a particular purpose, or accuracy. 3 2 FULHAM A B C D E F G H I J K L M N O P Q R S T U V W X Y Z AA AB AC AC 3 1-323-779-2980 2 AREA EM The drawing only provides one possible configuration. The actual configuration may differ based on a number of factors including client spaces, use and conditions. 1 4 FULHAM EMERGENCY LIGHTING APPLICATION NOTE 2014-05-23 4 1 AD AE AF AG AH AI AJ AK AL AM AM AN AO