15 - technical information

advertisement
15 - TECHNICAL INFORMATION
488
Motor full load currents
489
DOL Starting
Fuse links
Circuit Breakers
490
491
Assisted Starting
Fuse links
GE Circuit Breakers
GE Contactors
492
493
494
Auto Transformer Starting
GE Contactors
495
Fire Pump Starting
Fuse Links
Circuit Breakers
496
497
Type 2 Coordination
DOL Class 10
DOL Class 20
Star Delta
498
500
501
Transformers & Capacitors
General Information
Capacitor Protection Circuit Breakers
Capacitor Protection Fuse Links
Fuse Links TRx
502
504
505
503
Back Up Protection
MCCB & Switch
Fuses & MCB’s
Circuit Breakers
506
506
507
Discrimination & Selectivity
Fuses & Fuses
Circuit Breakers
509
510
Enhanced Discrimination & Selectivity
Circuit Breakers
516
Fuse Link Temperature De-rating
522
Protection of Cables with Fuse Links
523
GE Contactors for Lighting Circuits
524
Relay Equivalent Selection Chart
526
TECHNICAL
Motor Protection - general information
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
487
MOTOR PROTECTION
General
In a circuit that provides power to a motor a number of protective & Control devices are normally present. The combination of these devices must be coordinated to
ensure the efficiency & optimal protection of the motor. Here, the protection of such circuits strongly depends on the operational requirements, as the application for
which the motor is used, the required starting frequency, required service level & applicable safety standards.
Category
Load type
AC1
AC2
Non Inductive motor
Slip ring motor
AC3
Squirrel-cage motor
AC4
Squirrel-cage motor
(Cos phi = 0.45 <= 100A)
(Cos phi = 0.35 > 100A)
Trip Class
10A
10
20
30
1.2 x In
t < 2 hours
t < 2 hours
t < 2 hours
t < 2 hours
Ir setting
(min)
Energization
Starting
Switching off while running
Regenerative breaking
Inching
Energization
Switching off while running
Starting
Switching off while running
Regenerative breaking
Pluging
Inching
Required
tripping time at
1.5 x In
7.2 x In
t < 2 min.
2 <= t <= 10sec.
t < 4 min.
4 <= t <= 10sec.
t < 8 min.
6 <= t <= 10sec.
t < 12 min.
8 <= t <= 10sec.
COORDINATION TYPE 2 TEST SEQUENCE
Co ordination
The standards require tests to define the co ordination between the protective & switching devices within the motor circuit.
Depending on the state of the components after the test two coordination.
Classes, 1 & 2 have been defined.
The unique properties of the Record Plus breakers allow GE to offer solutions to meet the highest standard. Type 2 co ordination.
Motor current
Test with
ie (AC3)
current “r”
Ie <= 16A
1kA
16 < Ie <= 63A
3 kA
63 < Ie <= 125A
5 kA
125 < Ie <= 315A
10 kA
315 < Ie <= 630A
18 kA
After this test the original characteristics of the contactor
and thermal relay MUST remain unchanged.
After this test the short-circuit protection must trip within
10 ms at a fault current >= 15 x In
Type 2 - Short-circuit test with current “Iq”
<= 50kA
This value which is generally 15kA is used to check the coordination of
the device used in the motor starter circuit. For each combination with
Record Plus™ breakers this value is mentioned in the following tables.
After test with this current the following conditions must be met.
No or minor welding of the contactors after testing; contact separation is
simple and easy.
The switchgear and controlgear are fully operational after test.
IPD INDUSTRIAL PRODUCTS
488
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
MOTOR PROTECTION
MOTOR RATED OUTPUTS AND FULL LOAD CURRENTS
Motor Rating
kW
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
185
200
220
250
300
HP
1/8
1/6
1/4
1/3
0.5
0.75
1
1.5
2
3
5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
175
200
220
250
270
300
350
400
Full Load Current (A)
At 415V
At 440V
At 1000V
0.4
0.38
0.5
0.47
0.6
0.56
0.8
0.75
1.1
1
0.46
1.5
1.4
0.63
1.8
1.7
0.76
2.6
2.4
1.1
3.4
3.2
1.5
4.8
4.5
2
7.6
7.2
2.7
11
10.3
4.6
14
13.2
5.9
21
19.8
8.8
28
26.4
11.8
34
32
14.3
40
38
17
55
52
23
66
62
28
80
75
33
100
94
42
135
127
57
160
150
67
200
188
84
230
216
97
260
245
108
280
264
116
320
301
134
350
329
147
380
357
160
430
404
181
510
479
214
TECHNICAL
Notes:
1. Full load current values are nominal for standard squirrel-cage induction motors of rated
speed 1500 rpm (4 pole).
Possible deviation of FLC values ±10% depending on type and manufacturer.
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
489
MOTOR PROTECTION
FUSE SELECTION FOR DIRECT-ON-LINE MOTOR STARTING
Motor FLC (A)
From
0
0.8
1.5
2.1
3.1
6.2
9.1
11.1
14.5
15.5
18.1
22.1
28.1
45.1
58
80.1
99.1
128.1
180.1
216.1
270.1
328.1
385.1
430.1
500.1
560.1
620.1
645.1
To
0.7
1.4
2
3
6.1
9
11
14.4
15.4
18
22
28
45
58
80
99
128
180
216
270
328
385
430
500
560
620
645
680
Recommended GEC,
GE or IPD Fuse-Link Rating (A)
Type T ‘gG’
Type T ‘gM’
DIN Type ‘gL’ - ‘gG’
2
4
4
4
6
6
10
10
16
16
20
20
25
20M25†
25
32
20M32†
32
35
32M35
35
40
32M40
40
50
32M50
50
63
32M63
63
80
63M80
80
100
63M100
100
125
100M125
125
160
100M160
160
200
200
250
200M250
250
315
200M315*
315
355
315M355
355
400
400
450
400M450
500
500
500
560
630
630
630
670
630M670
800
710
800
750
1000
† Type NIT for 415V or less.
* Type TF, if motor FLC does not exceed 200A and voltage is 500V or less.
Notes:
1. Assumed starting conditions:
Motor Rating
Run-Up
Up to 1kW
5 x FLC for 5 secs.
1.1 to 7.5kW
6 x FLC for 10 secs.
7.6 x 75kW
7 x FLC for 10 secs.
Greater than 75kW
6 x FLC for 15 secs.
Operating cycle of 2 starts in rapid succession and up to 8 starts per hour.
2. Suitable adjustments to the recommended rating may be necessary for:
(a) Starting conditions in excess of the assumed starting conditions.
(b) High enclosure (fluid environment) temperatures, refer to fuse de-rating information
indicated on page 522.
IPD INDUSTRIAL PRODUCTS
490
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
MOTOR PROTECTION
GE CIRCUIT BREAKER GUIDE FOR DIRECT-ON-LINE MOTOR STARTING 415V APPLICATIONS
Motor Rating
kW
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
185
200
220
250
300
315
335
375
400
FLC
(A)
1.1
1.5
1.8
2.6
3.4
4.8
7.6
11
14
21
28
34
40
55
66
80
100
135
160
200
230
250
270
320
350
380
430
510
550
590
660
700
MCB
Series G
(Curve C)
2
4
6
10
10
16
20
25
32
50
FD
63
16
20
32
40
50
63
FD
160
Circuit Breaker Types and Ratings (A)
MCCB Type
FE
FE
FG
FG
FK
160
250
400
630
800
64
80
100
125
160
20
32
40
50
63
80
100
125
160
100
125
160
200
250
100
125
160
200
250
300
400
250
300
400
450
500
550
630
400
450
500
550
630
700
800
FK
1250
400
450
500
550
630
700
800
900
1050
1200
1250
FK
1600
640
700
800
900
1050
1200
1250
1400
1500
Notes:
1. FLC values are nominal for standard squirrel-cage induction motors of rated speed 1500 rpm (4 poles). Possible deviation of FLC
values ± 10% depending on type and manufacturer.
2. Circuit breaker ratings are based on carrying 100% FLC continuous and 600% FLC for 10 seconds. Operating cycle 2 starts in
rapid succession and up to 8 starts per hour.
TECHNICAL
3. Suitable adjustments to the indicated ratings may be necessary for:
a) Starting conditions in excess of the above conditions.
b) High enclosure (fluid environment) temperatures.
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
491
MOTOR PROTECTION
FUSE SELECTION FOR ASSISTED MOTOR STARTING
(Star-Delta, Autotransformer, Resistor or Reactor)
Motor FLC (A)
From
0
1.5
2.2
3.2
5.6
10.1
14.1
18.1
22.1
28.1
32.1
40.1
51.1
80.1
100.1
125.1
160.1
200.1
250.1
315.1
355.1
400.1
450.1
500.1
560.1
630.1
670.1
710.1
To
1.4
2.1
3.1
5.5
10
14
18
22
28
32
40
51
80
100
125
160
200
250
315
355
400
450
500
560
630
670
710
750
Recommended GEC,
GE or IPD Fuse-Link Rating (A)
Type T ‘gG’
Type T ‘gM’
DIN Type ‘gL’ - ‘gG’
2
4
4
4
6
6
10
10
16
16
20
20
25
20M25
25
32
32
35
32M35
35
40
32M40
40
50
50
63
63
80
80
100
100
125
125
160
160
200
200
250
250
315
315
355
355
400
400
450
500
500
500
560
630
630
630
670
800
710
800
750
800
Notes:
1. Assumed starting conditions:
Motor Rating
Run-Up
Up to 1kW
2.5 x FLC for 20 secs.
1.1 to 7.5kW
3.5 x FLC for 20 secs.
Greater than 75kW
3.5 x FLC for 15 secs.
Operating cycle of 2 starts in rapid succession and up to 8 starts per hour.
2. Suitable adjustments to the recommended ratings may be necessary for:
(a) Starting conditions in excess of the assumed starting conditions.
(b) High enclosure (fluid environment) temperatures more than 35°C. Some fuses need
to be derated as indicated on page 522.
IPD INDUSTRIAL PRODUCTS
492
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
MOTOR PROTECTION
GE CIRCUIT BREAKER GUIDE FOR ASSISTED MOTOR STARTING
(STAR-DELTA, 415V APPLICATIONS)
Motor Rating
kW
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
185
200
220
250
300
315
335
375
400
FLC
(A)
1.1
1.5
1.8
2.6
3.4
4.8
7.6
11
14
21
28
34
40
55
66
80
100
135
160
200
230
250
270
320
350
380
430
510
550
590
660
700
MCB
Series G
(Curve C)
2
4
4
6
6
10
16
20
25
40
50
FD
63
16
20
32
40
50
63
Circuit Breaker Types and Ratings (A)
MCCB Type
FD
FE
FE
FG
FG
160
160
250
400
630
64
80
90
100
125
160
20
32
40
50
63
80
90
100
125
160
100
125
160
200
250
100
125
160
200
250
280
300
320
380
400
250
280
300
320
380
400
450
550
630
FK
800
320
380
400
450
550
650
700
750
800
FK
1250
400
450
550
650
700
750
850
950
Notes:
1. FLC values are nominal for standard squirrel-cage induction motors of rated speed 1500 rpm (4 poles). Possible
deviation of FLC values ± 10% depending on type and manufacturer.
2. Circuit breaker ratings are based on carrying 100% FLC continuous and 600% FLC for 10 seconds. Operating cycle 2
starts in rapid succession and up to 8 starts per hour.
TECHNICAL
3. Suitable adjustments to the indicated ratings may be necessary for:
a) Starting conditions in excess of the above conditions.
b) High enclosure (fluid environment) temperatures.
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
493
MOTOR PROTECTION
GE CONTACTOR GUIDE FOR STAR-DELTA MOTOR STARTING
415V APPLICATIONS
Motor Rating
kW
FLC (A)
0.37
1.1
0.55
1.5
0.75
1.8
1.1
2.6
1.5
3.4
2.2
4.8
3.7
7.6
5.5
11
5.5
11
7.5
14
7.5
14
11
21
15
28
18.5
34
18.5
34
22
40
22
40
30
55
30
55
37
66
37
66
45
80
55
100
75
135
90
160
110
200
132
230
150
250
160
270
185
320
200
350
220
380
250
430
300
510
315
550
335
590
375
660
400
700
Contactor Types
Line and Delta
Star
MCO
MCO
MCO
MCO
MCO
MCO
MCO
MCO
MCO
MCO
MCO
MCO
MCO
MCO
MC1
MCO
CL00
CL00
MC1
MCO
CL00
CL00
CL02
CL00
CL02
CL01
CL25
CL01
CL03
CL01
CL25
CL02
CL03
CL02
CL04
CL25
CL04
CL03
CL45
CL25
CL45
CL03
CL06
CL04
CL07
CL45
CL08
CL06
CL09
CL07
CK75C
CL08
CK75C
CL08
CK75C
CL09
CK08C
CL09
CK08C
CK75C
CK85B
CK75C
CK09B
CK75C
CK09B
CK75C
CK95B
CK08C
CK10C
CK08C
CK10C
CK85B
CK10C
CK09B
CK10C
CK09B
TOL Relay Types
MT03D
MT03E
MT03F
MT03G
MT03H
MT03J
MT03K
MT03M
RT1L
MT03N
RT1M
RT1P
RT1S
RT1T
RT1T
RT1U
RT1U
RT1V
RT1V
RT1W
RT1W
RT2G
RT2H
RT2J
RT2L
RT3D
RT3E
RT3F
RT3F
RT3F
RT4P
RT4P
RT4P
RT4R
RT5C
RT5C
RT5D
RT5D
Notes:
1. FLC values are nominal for standard squirrel-cage indication motors of rated speed
1500 rpm (4 poles).
Possible deviation of FLC values ± 10% depending on type and manufacture.
2. Contactor types based on the following conditions:
a) Starting duration not more than 20 seconds.
b) Starting frequency of 2 starts in rapid succession and up to 8 starts per hour.
3. TOL relays selected for direct connection to the line contactor, in the delta branch of the
motor starter circuit.
4. Suitable adjustments to the indicated types may be necessary for:
a) Starting conditions in excess of the above conditions.
b) High enclosure (fluid environment) temperatures.
IPD INDUSTRIAL PRODUCTS
494
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
MOTOR PROTECTION
GE CONTACTOR GUIDE FOR AUTOTRANSFORMER MOTOR
STARTING 415V APPLICATIONS
Motor Rating
kW
FLC (A)
0.37
1.1
0.55
1.5
0.75
1.8
1.1
2.6
1.5
3.4
2.2
4.8
3.7
7.6
3.7
7.6
5.5
11
5.5
11
7.5
14
11
21
15
28
18.5
34
22
40
30
55
30
55
37
66
45
80
55
100
75
135
90
160
110
200
132
230
150
250
160
270
185
320
200
350
220
380
250
430
300
510
315
550
335
590
375
660
400
700
Line
MCO
MCO
MCO
MCO
MCO
MCO
MC1
CL00
MC2
CL01
CL02
CL25
CL04
CL45
CL45
CL07
CL07
CL08
CL08
CL10
CK75C
CK08C
CK85B
CK09B
CK09B
CK95B
CK10C
CK10C
CK10C
CK11C
CK11C
CK11C
CK12B
CK12B
CK12B
Contactor Types
Transformer
MCO
MCO
MCO
MCO
MCO
MCO
MCO
CL00
MC1
CL00
CL00
CL01
CL02
CL25
CL04
CL45
CL45
CL06
CL07
CL07
CL09
CL10
CK75C
CK75C
CK08C
CK08C
CK85B
CK09B
CK09B
CK95B
CK10C
CK10C
CK10C
CK11C
CK11C
Star
MCO
MCO
MCO
MCO
MCO
MCO
MC0
CL00
MC0
CL00
CL00
CL01
CL02
CL02
CL25
CL25
CL03
CL04
CL45
CL06
CL07
CL08
CL09
CL10
CK75C
CK75C
CK75C
CK08C
CK08C
CK85B
CK09B
CK09B
CK95B
CK95B
CK10C
TOL Relay Types
MT03F
MT03G
MT03H
MT03J
MT03K
MT03L
MT03M
RT1N
MT03P
RT1N
RT1P
RT1T
RT1V
RT1W
RT1W
RT2G
RT2G
RT2J
RT2J
RT2M
RT3E
RT3F
RT4P
RT4P
RT4P
RT4P
RT5C
RT5C
RT5C
RT5D
RT5E
RT5E
RT5E
RT5E
RT5E
Notes:
1. FLC values are nominal for standard squirrel-cage indication motors of rated speed
1500 rpm (4 poles). Possible deviation of FLC values ± 10% depending on type and
manufacture.
2. Contactor types based on the following conditions:
a) Starting duration not more than 20 seconds.
b) Starting frequency of 2 starts in rapid succession and up to 8 starts per hour.
c) Auto-transformer tap at 80%.
TECHNICAL
3. Suitable adjustments to the indicated types may be necessary for:
a) Starting conditions different to the above conditions.
b) High enclosure (fluid environment) temperatures.
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
495
MOTOR PROTECTION
FUSE SELECTION FOR FIRE PUMP MOTOR STARTING
Motor FLC (A)
kW
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
185
200
220
250
300
FLC (A)
1.1
1.5
1.8
2.6
3.4
4.8
7.6
11
14
21
28
34
40
55
66
80
100
135
160
200
230
250
270
320
350
380
430
510
Recommended GEC,
GE or IPD Fuse-Link Rating (A)
Type T ‘gG’
Type T ‘gM’
DINType ‘gL’ - ‘gG’
4
4
6
4
6
6
10
6
16
10
16
16
20
20
32
20M32
25
35
20M35
32
50
32M50
40
63
32M63
50
80
63M80
63
80
63M80
80
100
63M100
100
125
100M125
125
160
100M160
160
160
160
200M250
200
250
250
200M250
250
315
315
355
315M355
315
355
315M355
355
400
400
450
400M450
500
450
400M450
500
500
630
560
630
630
800
Notes:
1. FLC values are nominal for standard squirrel-cage induction motors of rated speed 1500 rpm
(4 pole).
Possible deviation of FLC values ±10% depending on type and manufacturer.
2. Recommend fuse ratings are based on carrying 125% FLC continuously and operating in not less
than 20 seconds at 600% FLC, in accordance with Clause 7.2.9.2 of AS/NZS 3000:2007.
3. Suitable adjustments to the recommended ratings may be necessary for high enclosure (fluid
environment) temperatures, refer to de-rating information indicated on page 522.
IPD INDUSTRIAL PRODUCTS
496
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
MOTOR PROTECTION
GE CIRCUIT BREAKER GUIDE FOR FIRE PUMP MOTOR STARTING 415V APPLICATIONS
Motor Rating
kW
0.37
0.55
0.75
1.1
1.5
2.2
3.7
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
150
160
185
200
220
250
300
315
335
375
400
FLC
(A)
1.1
1.5
1.8
2.6
3.4
4.8
7.6
11
14
21
28
34
40
55
66
80
100
135
160
200
230
250
270
320
350
380
430
510
550
590
660
700
MCB
Series G
(Curve C)
4
6
6
10
16
16
25
40
50
63
FD
63
FD
160
Circuit Breaker Types and Ratings (A)
MCCB Type
FE
FE
FG
FG
FK
160
250
400
630
800
64
80
100
125
140
20
32
40
50
63
80
100
125
140
16
20
32
40
50
100
125
140
180
220
100
125
140
180
220
300
400
220
300
400
450
500
550
580
320
400
450
500
550
580
700
750
800
FK
1250
400
450
500
550
580
700
750
800
1000
1250
FK
1600
700
750
800
1000
1250
1300
1400
1500
1600
Notes:
1. FLC values are nominal for standard squirrel-cage induction motors of rated speed 1500 rpm (4 poles). Possible deviation of FLC
values ± 10% depending on type and manufacturer.
2. Circuit breaker ratings are based on carrying 125% FLC continuously and opening in not less than 20 seconds at 600% FLC, in
accordance with clause 7.2.9.2 of AS/NZS 3000:2007.
TECHNICAL
3. Suitable adjustments to the indicated ratings may be necessary for high enclosure (fluid environment) temperatures.
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
497
MOTOR PROTECTION
TYPE 2 COORDINATION
CLASS 10 PROTECTION @ 415V AC
For type 2 Coordination @ other voltage, please refer to product catalogues of your local representative.
Upstream Record Plus Breakers selection
N
H
L
Type
IIcc values in kA Ue= 400/415V AC
50kA
80kA
130kA
FD63/160
FE160/250
50kA
80kA
130kA
FG 400/630
50kA
80kA
130kA
FK 800/1250
50kA
80kA
100kA
SELECTION OF ASSOCIATED COMPONENTS (1)
Motor
P(kW)
0.75
1.1
1.5
2.2
3
4
5.5
7.5
10
11
15
18.5
22
25
30
37
45
55
75
90
110
132
160
200
220
250
300
315
335
In
2
2.6
3.6
5
7
8.3
11.5
16.1
21
22
30
37
43
49
58
72
86
104
144
179
207
247
300
360
400
462
560
582
619
Breaker details
Type
Ie
FD63 /FE160
3 (2)
FD63 /FE160
3 (2)
FD63 /FE160
7
FD63 /FE160
7
FD63 /FE160
7
FD63/FE160
12.5
FD63/FE160
12.5
FD63/FE160
20
FD63 /FE160
30
FD63 /FE160
30
FD63 /FE160
30
FD63/FE160
50
FD63/FE160
50
FD63/FE160
50
FD/FE160
80
FD/FE160
80
FD/FE160
100
FE160
125
FE160
160
FE250
250
FE250
250
FE250
250
FG400
350
FG630
500
FG630
500
FG630
500
FK800
800
FK800
800
FK800
800
Im
35
35
70
80
86
125
150
200
300
300
390
478
561
635
800
934
1121
1346
1869
2500
2691
3214
3900
4680
5200
6004
6720
6985
6810
Contactor
Type + O.R.
CL25+RT1J
CL25+RT1K
CL03+RT1K
CL03+RT12L
CL03+RT1M
CL06+RT2AN
CL06+RT2AN
CL06+RT2B
CL06-RT2C
CL06-RT2C
CL06-RT2D
CL06+RT2E
CL06+RT2G
CL06+RT2G
CL09+RT2H
CL09+RT2J
CK75C+RT2L
CK85B+RT3E
CK85B+RT3F
CK95B+RT4N
CK10B+RT4P
CK10B+RT4R
CK10B+RT5C
CK12B+RT5C
CK12B+RT5D
CK12B+RT5D
CK13B+RT5E
CK13B+RT5C
CK13B+RT5C
Notes:
(1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic setting of the breaker.
(2) The 3 AMP device is designed to operate AA current level up to 3.5 Amps.
IPD INDUSTRIAL PRODUCTS
498
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
MOTOR PROTECTION
TYPE 2 COORDINATION
CLASS 10 AND PROTECTION
(WITH SMR2 OTHER CLASSES POSSIBLE)
Upstream Record Plus Breakers selection
N
H
L
Type
IIcc values in kA Ue= 400/415V AC
50kA
80kA
130kA
FE160/250
FG400/630
50kA
80kA
130kA
SELECTION OF ASSOCIATED COMPONENTS (1)
Motor
P(kW)
5.5
7.5
10
11
15
18.5
22
25
30
37
45
55
75
90
110
132
160
200
220
250
In
11.5
16.1
21
22
30
37
43
49
58
72
86
104
144
179
207
247
300
360
400
462
Type
FE160
FE160
FE160
FE160
FE160
FE160
FE160
FE160
FE160
FE160
FE160
FE160
FE160
FE250
FE250
FE250
FG400
FG630
FG630
FG630
Breaker details
Ie
25
25
25
25
63
63
63
63
63
125
125
125
160
250
250
250
350
500
500
500
Im
150
200
300
300
390
478
561
635
800
934
1121
1346
1869
2500
2691
2967
3900
4680
5200
6004
Contactor
Type + O.R.
CL08
CL08
CL08
CL08
CL09
CL09
CL09
CL09
CL09
CK85B
CK85B
CK85B
CK85B
CK95B
CK95B
CK95B
CK10C
CK12B
CK12B
CK12B
TECHNICAL
Notes:
(1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic setting of the breaker.
(2) The 3 AMP device is designed to operate AA current level up to 3.5 Amps.
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
499
MOTOR PROTECTION
TYPE 2 COORDINATION
CLASS 20(3) PROTECTION
Upstream Record Plus Breakers selection
N
H
L
Type
IIcc values in kA Ue= 400/415V AC
50kA
80kA
130kA
FD63/160
FE160/250
50kA
80kA
130kA
FG 400/630
50kA
80kA
130kA
FK 800/1250
50kA
80kA
100kA
SELECTION OF ASSOCIATED COMPONENTS (1)
Motor
P(kW)
In
0.75
2
1.1
2.6
1.5
3.6
2.2
5
3
6.6
4
8.3
5.5
11.5
7.5
16.1
10
21
11
22
15
30
18.5
37
22
43
49
25
30
58
37
72
45
86
55
104
75
144
90
179
110
207
132
247
160
300
200
360
220
400
250
462
300
560
315
582
335
619
Breaker details
Type
Ie
FD63/FE160
3 (2)
FD63/FE160
3 (2)
FD63/FE160
7
FD63/FE160
7
FD63/FE160
7
FD63/FE160
12.5
FD63/FE160
12.5
FD63/FE160
20
FD63/FE160
30
FD63/FE160
30
FD63/FE160
30
FD63/FE160
50
FD63/FE160
50
FD63/FE160
50
FD/FE160
80
FD/FE160
80
FD/FE160
100
FE160
125
FE160
160
FE250
250
FE250
250
FE250
250
FG400
350
FG630
500
FG630
500
FG630
500
FK800
800
FK800
800
FK800
800
Im
35
35
70
80
86
125
150
200
300
300
390
478
561
635
800
934
1121
1346
1869
2500
2691
3214
3900
4680
5200
6004
6720
6985
6810
Contactor
Type + O.R.
CL25+RT12J
CL25+RT12K
CL03+RT12K
CL03+RT12L
CL03+RT12M
CL06+RT2AN
CL06+RT2AN
CL06+RT2B
CL06-RT2C
CL06-RT2C
CL06-RT22D
CL06+RT22E
CL06+RT22G
CL06+RT22G
CL09+RT22H
CL09+RT22J
CK75C+RT22L
CK85B+RT32E
CK85B+RT32F
CK95B+RT32F
CK10B+RT5LB
CK10B+RT5LB
CK10B+RT5LB
CK12B+RT52LC
CK12B+RT52LD
CK12B+RT52LD
CK13B+RT5LE
CK13B+RT5LE
CK13B+RT5LE
Notes:
(1) The contactor has a breaking capacity that is sufficient to operate the specified motor up to the specified magnetic setting of the breaker.
(2) The 3 AMP device is designed to operate AA current level up to 3.5 Amps.
IPD INDUSTRIAL PRODUCTS
500
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
MOTOR PROTECTION
TYPE 2 COORDINATION
START DELTA STARTERS
Upstream Record Plus Breakers selection
N
H
L
Type
IIcc values in kA Ue= 400/415V AC
50kA
80kA
130kA
FD63/160
FE160/250
50kA
80kA
130kA
FG400/630
50kA
80kA
130kA
FK800/1250
50kA
80kA
130kA
Breaker details
Type
Ie
FD63/FE160
7
FD63/FE160
7
FD63/FE160
12.5
FD63/FE160
12.5
FD63/FE160
20
FD63/FE160
30
FD63/FE160
30
FD63/FE160
30
FD63/FE160
50
FD63/FE160
50
FD63/FE160
50
FD/FE160
80
FD/FE160
80
FD160
100
FE160
100
FE160
125
FE160
160
FE250
250
FE250
250
FE250
250
FG400
350
FG630
500
FG630
500
FG630
500
FK800
800
FK800
800
FK800
800
Im
80
86
125
150
200
300
300
390
478
561
635
800
934
1121
1121
1346
1869
2500
2691
3214
3900
4680
5200
6004
6720
6985
6810
Contactor
Type + O.R.
CL03+RT12L
CL03+RT1M
CL06+RT2AN
CL06+RT2AN
CL06+RT2B
CL06-RT2C
CL06-RT2C
CL06-RT2D
CL06+RT2E
CL06+RT2G
CL06+RT2G
CL09+RT2H
CL09+RT2J
CL09+RT2L
CK75C+RT2L
CK85B+RT3E
CK85B+RT3F
CK95B+RT4N
CK10B+RT4P
CK10B+RT4R
CK10B+RT5C
CK12B+RT5C
CK12B+RT5D
CK12B+RT5D
CK13B+RT5E
CK13B+RT5C
CK13B+RT5C
Delta
Cont.
CL03
CL03
CL04
CL04
CL45
CL45
CL45
CL45
CL06
CL06
CL06
CL09
CL09
CL09
CL10
CK75C
CK08C
CK85B
CK95B
CK95B
CK95B
CK10C
CK10C
CK10C
CK12C
CK12C
CK12C
Star
Cont.
CL03
CL03
CL04
CL04
CL45
CL45
CL45
CL45
CL06
CL06
CL06
CL09
CL09
CL09
CL10
CL10
CL10
CK75C
CK75C
CK75C
CK85B
CK10C
CK10C
CK10C
CK12C
CK12C
CK12C
TECHNICAL
Motor
P(kW)
In
2.2
5.0
3
6.6
4
8.3
5.5
11.5
7.5
16.1
10
21
11
22
15
30
18.5
37
22
43
25
49
30
58
37
72
45
86
45
86
55
104
75
144
90
179
110
207
132
247
160
300
200
360
220
400
250
462
300
560
315
582
335
619
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
501
TRANSFORMER RATINGS
GUIDE TO LOW VOLTAGE FAULT LEVEL
kVA
15
25
50
100
150
200
300
315
400
500
600
750
750
800
1000
1200
1350
1500
2000
2500
mVA
kVA/1000
0.015
0.025
0.050
0.100
0.150
0.200
0.300
0.315
0.400
0.500
0.600
0.750
0.750
0.800
1.000
1.200
1.350
1.500
2.000
2.500
Current (I)
@ 11kV
0.79
1.31
2.62
5.25
7.87
10.5
15.75
16.53
20.99
26.24
26.24
39.36
39.36
41.99
52.49
62.98
70.86
78.73
104.97
131.22
Current (I)
@ 433V
20
33.33
66.67
133.34
200.01
266.67
400.01
420.01
533.35
666.69
666.69
1000.03
1000.03
1066.70
1333.37
1600.05
1800.05
2000.06
2666.74
3333.43
Typical
%Z
4.75
4.5
4.5
4.75
4.75
4.75
4.75
5
4.75
4.75
4.75
4.75
6.25
4.75
4.75
5
5.25
5.5
5.5
6
Z1 @ 433V
in Ohms
0.5937
0.3375
0.1687
0.0891
0.0594
0.0445
0.0297
0.0298
0.0223
0.0178
0.0148
0.0119
0.0156
0.0111
0.0089
0.0078
0.0073
0.0069
0.0052
0.0045
PSC @ 433V
in kA
0.421
0.741
1.482
2.807
4.211
5.614
8.421
8.400
11.228
14.035
16.843
21.053
16.000
22.457
28.071
32.001
34.287
36.365
48.486
55.557
Note:
The attached calculations are based on zero source impendance and are intended as a guide only.
Example: Fault level for 400kA Sub:
Ohms = KV Line Voltage2 x %Z
MVA
KA = KV Line Voltage
IPD INDUSTRIAL PRODUCTS
502
Product Catalogue 2013
= (433)2
0.4x106 100
= 433
= 11.228 KA
Phone: 1300 556 601
www.ipdgroup.com.au
TRANSFORMER PROTECTION
FUSE SELECTION FOR 3-PHASE TRANSFORMER
PRIMARIES AT 415VAC
Transformer
Rating
kVA
0.5
1
2
3
4
5
6
7
8
10
12
15
20
25
30
40
50
75
100
125
150
200
250
300
400
500
630
750
Primary FLC (A)
0.8
1.5
3.1
4.6
6.1
7.7
9.2
10.7
12.2
15
18
23
31
38
46
61
77
115
153
191
230
306
383
459
612
765
964
1148
Recommended GEC,
English Electric
GE or IPD Fuse-Link
Rating (A)
Type T ‘gG’
DIN Type ‘gL’-’gG’
4
4
6
4
10
6
16
10
16
10
16
16
20
16
20
16
20
16
25
20
32
25
35
32
40
40
50
50
63
63
80
80
80
80
125
125
160
160
200
200
250
250
315
315
400
400
500
500
630
630
800
800
1250
1000
1250
-
TECHNICAL
Notes:
1. FLC values are typical only. Possible deviation of FLC values ±5%
depending on manufacturer.
2. Recommended fuse ratings allow for transformer magnetising inrush current
of 12 times FLC for 0.1 seconds.
3. Suitable adjustments to the recommended ratings may be necessary for
high enclosure (fluid environment) temperatures, refer to de-rating information
indicated on page 522.
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
503
TRANSFORMERS & CAPACITOR PROTECTION
Transformer
value
< 50 kvA
>= 50 kvA
1ph
kVA
2.5
4
5
6.3
8
10
12.5
16
20
25
31.5
40
50
63
80
100
125
160
Maximum crest
inrush values
1st Period
2nd Period
5 ms.
25 ms.
25 x In
12 x In
15 x In
8 x In
Transformer ratings
240V
3ph 400/415V
In
kVA
In
10
6.3
9
11
8
12
17
10
14
12.5
18
27
16
23
34
20
28
42
25
35
53
31.5
44
40
56
68
50
70
84
63
89
105
80
113
133
100
141
169
125
176
211
160
225
266
200
287
338
250
352
422
315
444
528
400
563
675
500
704
630
887
800
1126
1000
1408
3rd Period
45 ms.
5 x In
3.5 x In
Type
FD160N, FD160H or L
FD160N, FD160H or L
FD160N, FD160H or L
FD160N, FD160H or L
FD160N, FD160H or L
FD160N, FD160H or L
FD160N, FD160H or L
FD160N, FD160H or L
FD160N, FD160H or L
FD160N, FD160H or L
FD160N, FD160H or L
FE160N, H or L
FE160N, H or L
FE160N, H or L
FE250N, H or L
FE250N, H or L
FG400N, H or L
FG400N, H or L
FG630N, H or L
FG630N, H or L
FK800N or H
FK1250N or H
FK1250N or H
FK1600N or H
Record Plus breaker
Trip unit
type & rating*
LTMD-25
LTMD-25
LTMD-32
LTMD-32
LTMD-40
LTMD-50
LTMD-63
LTMD-80
LTMD-100
LTMD-125
LTMD-125
SMR1-125
SMR1-125
SMR1-160
SMR1-250
SMR1-250
SMR1-350
SMR1-350
SMR1-500
SMR1-630
SMR1-800
SMR1-1000
SMR1-1250
SMR1-1600
Ist
250
250
320
320
400
500
630
800
1000
1250
1250
PROTECTION OF CAPACITOR BANKS
Un = 400/415V
(phase to phase voltage)
Capacitor rating
Record Plus
(kVAr)
breaker
10
FD160N, FD160H or L
15
FD160N, FD160H or L
20
FD160N, FD160H or L
25
FD160N, FD160H or L
30
FD160N, FD160H or L
35
FD160N, FD160H or L
40
FD160N, FD160H or L
45
FD160N, FD160H or L
50
FD160N, FD160H or L
60
FD160N, FD160H or L
70
FD160N or FE160N, H or L
80
FE250N, H or L
90
FE250N, H or L
100
FE250N, H or L
120
FE250N, H or L
140
FG400N, H or L
160
FG400N, H or L
180
FG400N, H or L
200
FG630N, H or L
250
FG630N, H or L
300
FG630N, H or L
350
FK800N, H or H
IPD INDUSTRIAL PRODUCTS
504
Product Catalogue 2013
Phone: 1300 556 601
Ir setting
(min)
21 A
31 A
41 A
52 A
62 A
72 A
83 A
93 A
103 A
124 A
144 A
165 A
186 A
206 A
248 A
289 A
330 A
372 A
413 A
516 A
619 A
722 A
www.ipdgroup.com.au
CAPACITOR PROTECTION
FUSE SELECTION FOR 3-PHASE CAPACITOR BANKS AT 415VAC
Capacitor Bank
Rating
kVAr
5
7.5
10
15
20
25
30
35
40
50
60
75
90
100
110
120
135
150
160
180
190
200
225
240
275
300
360
400
FLC (A)
6.9
10.4
13.9
20.9
27.8
34.8
41.7
48.7
55.6
69.6
83.5
104
125
139
153
167
188
209
223
250
264
278
313
334
383
417
501
557
Recommended GEC,
GE or IPD Fuse-Link
Rating (A)
Type T ‘gG’
DIN Type ‘gL’-’gG’
16
16
16
16
25
25
32
32
50
50
63
63
63
63
80
80
100
100
125
125
125
125
160
160
200
200
250
250
250
250
250
250
315
315
315
315
355
355
400
400
400
400
450
500
500
500
500
500
630
630
630
630
750
800
1000
1000
Notes:
1. Recommended fuse ratings allow for a capacitor manufacturing tolerance of +10% on the kVAr
values and the possibility of up to 30% constant overload of a capacitor bank due to harmonic
currents.
TECHNICAL
2. Suitable adjustments to the recommended ratings may be necessary for high enclosure (fluid
environment) temperatures, refer to de-rating information indicated on page 522.
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
505
BACKUP PROTECTION
MCCB AND SWITCH DISCONECTOR BACKUP PROTECTION
Record Plus™ circuit breakers excel in their characteristics as current and energy limiting devices. This allows one to use lighter and more economical downstream
busbar systems and switchgear.
A frequently used combination is that of a Record Plus™ breaker, used as a protection and switching device in the mains switchboard, and a Dilos load break switch,
as an incomer, in a downstream, secondary switchboard. In this application the Dilos needs to be able to withstand the current and energy values on a short-circuit
event, this taking the limiting effects of the upstream breaker into account.
The table indicates the maximum prospective short-circuit that the combination of an upstream Record Plus™ and a downstream Dilos or Record Plus™ in its switch
disconnect variant (type Y) can withstand.
Protection of Switch Disconectors (Dilos or Record PlusTM) Valid for 400/415V AC
Upstream
Record Plus™
circuit breaker
FD160S
FD160S
FD160N
FD160N
FD160H
FD160N
FD160L
FD160L
FE160N
FE160N
FE160H
FE160H
FE160L
FE160L
FE250N
FE250H
FE250L
FG400N
FG400H
FG400L
FG630N
FG630H
FG630L
FK800N
FK800H
FK1250N
FK1250H
FK1600N
FK1600H
Breaking
capacity,
Icu = Ics
(kA eff.)
30
30
50
50
80
80
150
150
50
50
80
80
150
150
50
80
150
50
80
150
50
80
150
50
80
50
80
50
80
Downstream
Dilos switch
1 & 1H
2
1 & 1H
2
1 & 1H
2
1 & 1H
2
1 & 1H
2
1 & 1H
2
1 & 1H
2
3
3
3
4
4
4
4
4
4
6
6
6
6
7
7
Maximum
allowable
short-circuit
(kA eff.)
18
18
25
25
30
30
36
36
25
25
30
30
36
36
50
80
150
50
80
150
50
80
150
50
80
50
80
50
80
Downstream
Record Plus™
switch
FD63Y
FD160Y
FD63Y
FD160Y
FD63Y
FD160Y
FD63Y
FD160Y
FE63Y
FE160Y
FE63Y
FE160Y
FE63Y
FE160Y
FE250Y
FE250Y
FE250Y
FG400Y
FG400Y
FG400Y
FG630Y
FG630Y
FG630Y
FK800Y
FK800Y
FK1250Y
FK1250Y
FK1600Y
FK1600Y
Maximum
allowable
short-circuit
(kA eff.)
30
30
50
50
80
80
150
150
50
50
80
80
150
150
50
80
150
50
80
150
50
80
150
50
80
50
80
50
80
FAULT-CURRENT LIMITER FUSES SELECTION FOR
MINIATURE CIRCUIT BREAKERS AT 415VAC 50kA
PROSPECTIVE
Miniature
Minimum
Maximum Fuse Rating (A)
Circuit
Fuse
For
For
Breaker
Rating
GE Series
Ge Series
Rating (A)
(A)
G60
G100
4
20
200
250
6
25
200
250
10
40
200
250
16
50
200
250
20
63
200
250
25
80
200
250
32
100
200
250
40
125
200
250
50
160
200
250
63
160
200
250
Note: Fuses are type ‘T’, ‘gG’ or DIN type ‘gL’ - ‘gG’
IPD INDUSTRIAL PRODUCTS
506
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
BACKUP PROTECTION
Record Plus Moulded Case Circuit Breakers (at 400/415V AC; table B2 ed. 2c)
Icu
in kA
FE250V
36
FE250N
50
FE250H
80
FE250L
150
FG400N
50
Icu of the combination in kA
10
15
25
20
15
22
25
--25
25
30
36
30
30
30
36
42
36
36
36
42
50
42
42
42
50
65
50
50
30
36
42
36
36
36
42
50
42
42
42
50
65
50
50
22
25
--25
30
30
36
36
30
36
36
42
42
36
36
36
42
42
36
16
22
----
100
50
25
100
50
100
25
100
50
----------
----------
--42
---42
---
-80
50
-80
-50
-80
150
150
65
150
150
150
65
150
150
--42
---42
---
-80
50
-80
-50
-80
150
150
65
150
150
150
65
150
150
----------
--42
---42
---
-80
50
-80
-50
-80
150
150
65
150
150
150
65
150
150
----------
18
25
36
50
80
50
80
50
80
50
80
50
80
50
80
50
80
22
-----------------
25
30
----------------
30
36
42
---------------
36
42
50
80
--------------
42
50
65
150
150
-------------
30
36
42
---------------
36
42
50
80
-80
------------
42
50
65
150
150
150
150
-----------
22
-----------------
30
36
42
---------------
36
42
50
80
-80
-80
----------
42
50
65
150
150
150
150
150
150
---------
30
36
42
---------------
FG400H
80
FG400L
150
FG630N
50
FG630H
80
FG630L
150
Icu
in kA
Downstream
Redline
G60 & GT10
G100
GT25
<=25A
GT25; 32 & 40A
GT25; 50 & 63A
Surion
GPS1B/MS
<=10A
GPS1B/MS
12.5A
GPS1B/MS
>=16A
GPS1B/MH <=12.5A
GPS1B/MH
>12.5A
GPS2B/MS
10A
GPS2B/MS
>10A
GPS2B/MH
10A
GPS2B/MH
>10A
TM
Record Plus
FD63/160C
FD63/160E
FD63/160S
FD63/160N
FD63/160H
FE160N
FE160H
FE250N
FE250H
FG400N
FG400H
FG630N
FG630H
FK800N
FK800H
FK1250N
FK1250H
Upstream Record PlusTM type
FD63/160L FE160N FE160H FE160L
150
50
80
150
Upstream Record PlusTM type
FK800N FK800H FK800L FK1250N FK1250H FK1250L FK1600N FK1600H
50
80
100
50
80
100
50
80
Icu of the combination in kA
10
15
25
20
15
16
22
----
16
22
----
12
16
----
12
16
----
12
16
----
------
------
------
------
------
------
------
------
100
50
25
100
50
100
25
100
50
----------
----------
----------
----------
----------
----------
----------
----------
----------
----------
----------
----------
----------
18
25
36
50
80
50
80
50
80
50
80
50
80
50
80
50
80
36
42
50
80
-80
-80
-80
--------
42
50
65
150
150
150
150
150
150
150
150
-------
30
36
42
---------------
36
42
50
80
-80
-80
-80
-80
------
42
50
65
150
150
150
150
150
150
150
150
150
150
-----
------------------
---80
-80
-80
-80
-80
-80
-80
--
---100
100
100
100
100
100
100
100
100
100
100
100
100
100
------------------
---80
-80
-80
-80
-80
-80
-80
--
---100
100
100
100
100
100
100
100
100
100
100
100
100
100
------------------
---80
-80
-80
-80
-80
-80
-80
--
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
TECHNICAL
Downstream
Redline
G60 & GT10
G100
GT25
<=25A
GT25; 32 & 40A
GT25; 50 & 63A
Surion
GPS1B/MS
<=10A
GPS1B/MS
12.5A
GPS1B/MS
>=16A
GPS1B/MH <=12.5A
GPS1B/MH
>12.5A
GPS2B/MS
10A
GPS2B/MS
>10A
GPS2B/MH
10A
GPS2B/MH
>10A
TM
Record Plus
FD63/160C
FD63/160E
FD63/160S
FD63/160N
FD63/160H
FE160N
FE160H
FE250N
FE250H
FG400N
FG400H
FG630N
FG630H
FK800N
FK800H
FK1250N
FK1250H
FD63/160E FD63/160S FD63/160N FD63/160H
25
36
50
80
15
www.ipdgroup.com.au
Product Catalogue 2013
507
NOTES
IPD INDUSTRIAL PRODUCTS
508
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
DISCRIMINATION & SELECTIVITY
Supply
Source
Up-Stream
Fuse
Down-Stream
Fuse
Fault Point
DISCRIMINATION BETWEEN FUSES AT 415VAC
Type T ‘gG’
2
4
6
10
16
20
25
32
32
35
40
50
63
63
80
100
125
160
200
250
315
355
400
400
450
500
560
630
670
710
750
800
Down-Stream
Fuse Rating (A)
Type T ‘gM’
DIN Type ‘gL’-’gG’
4
6
10
16
20
20M25
25
20M32
32
32M35
35
32M40
40
32M50
50
32M63
63
63M80
80
63M100
100
100M125
125
100M160
160
100M200
200
200M250
250
200M315
315
315M355
400
400M450
500
630
630M670
800
Minimum Up-Stream
Fuse Rating (A)
Type T ‘gG’
DIN Type ‘gL’-’gG’
4
4
6
6
10
10
16
16
25
25
32
32
40
40
40
40
50
50
50
50
63
63
80
80
125
125
125
100
160
125
160
160
200
200
250
250
315
315
400
400
500
500
560
630
630
800
630
630
670
800
750
800
800
1000
1000
1000
1250
1250
1250
1250
-
Notes:
1. Fuses must be GE or IPD brands of fuse-links only. Not applicable for other manufacturers’ fuses.
2. The selected fuse ratings achieve discrimination for overload conditions and short-circuit currents up
to 80kA.
3. This discrimination ensures that the down-stream fuse operates and the up-stream fuse remains
unaffected.
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
TECHNICAL
4. Where the up-stream fuse supplies more than one down-stream fuse, the minimum up-stream fuse
rating should be increased to allow for load biasing effects.
15
www.ipdgroup.com.au
Product Catalogue 2013
509
DISCRIMINATION & SELECTIVITY
SELECTIVITY DISCRIMINATION TABLES
Selectivity Discrimination tables: Where discrimination is partial the selectivity limits in kA Is are listed. Where ‘T’ is found in the tables, this indicates total discrimination
up to the highest breaking capacity of the devices.
These discrimination/selectivity limits are only valid if the ratio between the current settimes, ranks or time settings of upstream & downstream breakers are equal or
higher than the factor indicated below.
L
TM
L
TM
TM
1.6
20
TM
LTM
LTMD
Mag. Break™
SMR1 & SMR1e
SMR1s, g and SMR2
MPRO 17, 20, 30 & 40
Terminology
Thermal Magnetic Trip Unit
Ir = Overload setting
Selective Thermal Magnetic Trip Unit
Ir = Overload setting
Magnetic Only Trip Unit
Im = Magnetic setting
Selective Electronic Trip Unit
Ir = Setting on LT device
Enhanced Electronic trip Unit
Mpact Electronic Trip Unit
Ir = Setting on LT device
LTD class, time setting at 7.2 x Ir
Im = Magnetic setting
Im = Magnetic setting
Ist = Setting on ST device
Ist = Setting on ST device
STD Delay setting on ST device
A2S Cropped short time delay setting
Inst. = Setting on I ( Instantaneous ) device
IPD INDUSTRIAL PRODUCTS
510
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
DISCRIMINATION & SELECTIVITY
SELECTIVE TABLES
(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D1 ED. 2C)
FDC & FDE 63/160 LTM
Upstream
FDS 63/160 LTMD
In in A
In
Downstream
40
50
63
50
63
80
In in A
100 125/ 160
40
50
T
3.5kA
T
63
80
100 125/160
6kA
6kA
T
T
8kA
T
T
3.5kA
T
T
T
T
T
T
T
T
T
-
T
10kA
T
T
T
-
T
T
T
-
T
1.6kA 3.5kA
T
T
T
T
T
T
T
T
T
10kA
T
T
T
-
T
T
T
T
T
1.6kA 3.5kA
0.8kA 1.2kA 6kA
6kA
1.2kA 3kA
6kA
T
8kA
3kA
4kA
6kA
-
-
3.5kA
T
T
T
-
-
3.5kA
T
T
6kA
-
-
-
3.5kA
T
T
-
-
-
3.5kA
T
T
-
-
-
-
8kA
T
-
-
-
-
8kA
T
T
25
-
32
-
-
40
-
-
-
50
-
-
-
63
-
-
-
1.2kA 1.5kA
-
1.5kA
2kA
6kA
10kA
T
10kA
10kA
T
T
T
T
10kA
10kA
T
T
T
6kA
8kA
T
3.5kA 10kA
T
T
T
T
3.5kA 10kA
T
T
T
T
0.8kA 1.2kA 6kA
6kA
T
1.6kA 3.5kA
T
T
T
T
1.6kA 3.5kA
T
T
T
T
T
25
-
32
-
-
40
-
-
-
50
-
-
-
63
-
-
-
1.2kA 3kA
6kA
8kA
-
-
10kA 10kA
T
T
-
-
10kA 10kA
T
3kA
4kA
6kA
-
-
3.5kA 10kA
T
T
-
-
3.5kA 10kA
T
6kA
-
-
T
-
-
16 0.6kA 2.5kA 6kA
20 0.6kA 2.5kA 3kA
Record Plus
40
Selectivity limit in kA*
16 0.6kA 2.5kA 6kA
20 0.6kA 2.5kA 3kA
HTI C curve
100 125/160
(A)
16 0.6kA 2.5kA 6kA
20 0.6kA 2.5kA 3kA
Redline
80
FDN, H & L 63/160 LTMD
In in A
1.2kA 1.5kA
-
3.5kA 10kA
-
1.5kA
2kA
-
-
-
-
8kA
T
-
-
-
-
8kA
10kA
T
10kA
10kA
T
T
T
T
10kA
10kA
T
T
T
T
6kA
8kA
T
3.5kA 10kA
T
T
T
T
3.5kA 10kA
T
T
T
T
1.6kA 3.5kA 15kA
T
T
1.6kA 3.5kA 15kA
T
T
-
-
10kA 10kA
3.5kA 10kA 15kA
6kA
T
6kA
8kA
-
-
10kA 10kA
3kA
4kA
6kA
-
-
3.5kA 10kA 15kA
T
-
-
6kA
-
-
-
3.5kA 10kA
T
-
-
-
2kA
-
-
-
8kA
T
-
-
-
-
-
40
-
-
-
50
-
-
-
63
-
-
-
T
-
1.2kA 3kA
-
32
T
6kA
0.8kA 1.2kA 6kA
25
T
3.5kA 10kA
1.2kA 1.5kA
-
1.5kA
T
-
T
T
T
T
T
T
3.5kA 10kA
T
8kA
T
-
80
-
-
-
-
-
1.9kA
-
-
-
-
-
2.5kA
-
-
-
-
-
2.5kA
100
-
-
-
-
-
1.9kA
-
-
-
-
-
2.5kA
-
-
-
-
-
2.5kA
T
T
3.5kA 15kA 15kA
T
T
10kA
T
T
-
10kA T
T
3.5kA 15kA 15kA
T
T
T
T
T
T
-
-
6kA
T
T
T
GPS1BS &
GPS1MS
20 0.6kA 2.5kA 6kA
25
-
6kA
10kA
T
1kA 1.2kA 6kA
6kA
T
GPS2BS &
GPS2MS
32
-
-
40
-
-
-
50
-
-
-
-
1.2kA 3kA
6kA
10kA
-
-
6kA
3kA
4kA
6kA
-
-
-
6kA
T
T
-
-
-
6kA
T
6kA
-
-
-
3.5kA
T
T
-
-
-
3.5kA
T
63
-
-
-
-
T
1.6kA
2kA
-
-
-
-
8kA
T
-
-
-
-
8kA
T
20
T
T
T
T
25
-
T
32
-
1.2kA 1.6kA
2.5kA 15kA 15kA
-
10kA 10kA
6kA
6kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
-
3.5kA
T
T
T
T
-
3.5kA
T
T
T
T
T
T
T
-
-
T
T
T
T
6kA
6kA
8kA
T
-
-
T
40
-
-
-
6kA
8kA
T
-
-
T
T
T
T
-
-
T
T
T
T
50
-
-
-
-
6kA
T
-
-
-
3.5kA
T
T
-
-
-
3.5kA
T
T
63
-
-
-
-
-
T
-
-
-
-
-
-
25 0.4kA 0.5kA 0.6kA 0.8kA 1kA
0.5kA 0.6kA 0.8kA 1kA
32
1.3kA
8kA
T
0.6kA 0.8kA 0.9kA 1.2kA 1.5kA 3.5kA
0.8kA 0.9kA 1.2kA 1.5kA 3.5kA
8kA
T
0.6kA 0.8kA 0.9kA 1.2kA 1.5kA 3.5kA
1.3kA
-
40
-
-
-
0.8kA 1kA
1.3kA
-
-
-
1.2kA 1.5kA 3.5kA
-
-
-
1.2kA 1.5kA 3.5kA
50
-
-
-
0.8kA 1kA
1.3kA
-
-
-
1.2kA 1.5kA 3.5kA
-
-
-
1.2kA 1.5kA 3.5kA
63
-
-
-
-
1kA
1.3kA
-
-
-
-
80
-
-
-
-
-
1.3kA
-
-
-
-
1.5kA 3.5kA
-
3.5kA
-
0.8kA 0.9kA 1.2kA 1.5kA 3.5kA
-
-
-
-
-
-
-
-
1.5kA 3.5kA
-
3.5kA
Remark; For MCB’s with D type Curve assume a C curve type with a one step higher rating.
E.G. Selectivity FD160 80Amp LTM with downstream C Curve 40A MCB = 3kA, for D curve 40A, take the value mentioned for 50A C curve, here 1.2kA
TECHNICAL
*Where T is mentioned Selectivity is full up until the Icu of the downstream device
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
511
DISCRIMINATION & SELECTIVITY
SELECTIVE TABLES
(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D2 ED. 2C)
Upstream
FE160N, H & L LTM
FE160N, H & L LTMD
FE160N, H & L SMR1
160A
FE250V LTM
160A
200A
FE250N, H & L LTMD
250A
125A
160A
200A
FE250N, H & L SMR1
63A
80A
100A
125A
160A
100A
125A
160A
63A
125A
250A
125A
160A
250A
6kA
6kA
8kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
25A
1.2kA
6kA
6kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
DME100
32A
1.2kA
3kA
6kA
8kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
B/C curve
40A
--
3kA
4kA
6kA
6kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
50A
--
--
1.5kA
6kA
6kA
T
T
T
--
T
T
T
T
T
T
T
T
T
T
T
T
Downstream
Selectivity limit in kA*
In (A)
Redline
<= 20A
63A
Redline
<= 20A
--
--
1.5kA
2kA
2kA
T
T
T
--
T
T
T
T
T
T
T
T
T
T
T
T
6kA
6kA
8kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
G60 & DM100
25A
1.2kA
6kA
6kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
B/C curve
32A
1.2kA
3kA
6kA
8kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
40A
--
3kA
4kA
6kA
6kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
50A
--
1.2kA
1.5kA
6kA
6kA
T
T
T
--
T
T
T
T
T
T
T
T
T
T
T
T
63A
--
--
1.5kA
2kA
2kA
T
T
T
--
T
T
T
T
T
T
T
T
T
T
T
T
6kA
6kA
8kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
G100 & GT25
Redline
25A
1.2kA
6kA
6kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
B/C curve
32A
1.2kA
3kA
6kA
8kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
40A
--
3kA
4kA
6kA
6kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Redline
HTI
C curve
Surion
<= 20A
50A
--
--
1.5kA
6kA
6kA
T
T
T
--
T
T
T
T
T
T
T
T
T
T
T
T
63A
--
--
1.5kA
2kA
2kA
T
T
T
--
T
T
T
T
T
T
T
T
T
T
T
T
80A
--
--
1.5kA
2kA
2kA
--
T
T
--
T
T
1.9kA
2.5kA
3kA
T
T
T
T
T
T
T
100A
--
--
--
--
2kA
--
--
T
--
--
T
1.9kA
2.5kA
3kA
--
T
T
T
--
T
T
125A
<= 20A
--
--
--
--
--
--
--
--
--
--
--
--
--
3kA
--
T
T
T
--
T
T
6kA
6kA
10kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GPS1BS &
25A
1.2kA
6kA
6kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GPS1MS
32A
1.2kA
3kA
6kA
10kA
10kA
T
T
T
T
T
T
10kA
T
T
T
T
T
T
T
T
T
GPS2BS &
40A
--
--
4kA
6kA
6kA
T
T
T
T
T
T
6kA
10kA
T
T
T
T
T
T
T
T
GPS2MS
Surion
50A
--
--
1.6kA
6kA
6kA
T
T
T
--
T
T
6kA
6kA
10kA
T
T
T
T
T
T
T
63A
--
--
--
2kA
2kA
--
T
T
--
T
T
2kA
6kA
6kA
T
T
T
T
T
T
T
<= 20A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
25A
15kA
15kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GPS1MH
32A
6kA
6kA
8kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GPS2BH &
40A
--
6kA
8kA
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GPS1BH &
GPS2MH
Record Plus
FD63/160E
LTM/MO/GTM
50A
--
--
6kA
T
T
T
T
T
--
T
T
T
T
T
T
T
T
T
T
T
T
63A
--
--
--
T
T
--
T
T
--
T
T
T
T
T
T
T
T
T
T
T
T
<= 40A
--
0.8kA
1kA
1.2kA
1.6kA
T
T
T
T
T
T
1.6kA
2kA
2.5kA
T
T
T
T
T
T
T
50A
--
--
1kA
1.2kA
1.6kA
T
T
T
--
T
T
1.6kA
2kA
2.5kA
T
T
T
T
T
T
T
63A
--
--
--
1.2kA
1.6kA
T
T
T
--
T
T
1.6kA
2kA
2.5kA
T
T
T
T
T
T
T
80A
--
--
--
1.2kA
1.6kA
--
T
T
--
--
T
1.6kA
2kA
2.5kA
T
T
T
T
T
T
T
100A
--
--
--
--
1.6kA
--
--
T
--
--
T
1.6kA
2kA
2.5kA
--
T
T
T
--
T
T
125A
--
--
--
--
--
--
--
--
--
--
--
--
2kA
2.5kA
--
--
T
T
--
--
T
160A
Record Plus
<= 40A
--
--
--
--
--
--
--
--
--
--
--
--
--
2.5kA
--
--
--
T
--
--
T
0.6kA
0.8kA
1kA
1.2kA
1.6kA
30kA
30kA
30kA
36kA
36kA
36kA
1.6kA
2kA
2.5kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
FD63/160S, N
50A
--
0.8kA
1kA
1.2kA
1.6kA
30kA
30kA
30kA
--
36kA
36kA
1.6kA
2kA
2.5kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
H&L
63A
--
--
1kA
1.2kA
1.6kA
30kA
30kA
30kA
--
36kA
36kA
1.6kA
2kA
2.5kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
LTMD
Record Plus
FE160 N, H & L
LTM/MO/GTM
80A
--
--
--
1.2kA
1.6kA
--
30kA
30kA
--
36kA
36kA
1.6kA
2kA
2.5kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
100A
--
--
--
--
1.6kA
--
--
30kA
--
--
36kA
1.6kA
2kA
2.5kA
--
42kA
42kA
42kA
--
50kA
50kA
125A
--
--
--
--
--
--
--
--
--
--
--
--
2kA
2.5kA
--
--
42kA
42kA
--
--
50kA
160A
--
--
--
--
--
--
--
--
--
--
--
--
--
2.5kA
--
--
--
42kA
--
--
50kA
<= 40A
50A
0.6kA
0.8kA
1kA
1.2kA
1.6kA
30kA
30kA
30kA
36kA
36kA
36kA
1.6kA
2kA
2.5kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
--
0.8kA
1kA
1.2kA
1.6kA
30kA
30kA
30kA
--
36kA
36kA
1.6kA
2kA
2.5kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
63A
--
--
1kA
1.2kA
1.6kA
30kA
30kA
30kA
--
36kA
36kA
1.6kA
2kA
2.5kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
80A
--
--
--
1.2kA
1.6kA
--
30kA
30kA
--
36kA
36kA
1.6kA
2kA
2.5kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
100A
--
--
--
--
1.6kA
--
--
30kA
--
--
36kA
1.6kA
2kA
2.5kA
--
42kA
42kA
42kA
--
50kA
50kA
125A
--
--
--
--
--
--
--
--
--
--
--
--
2kA
2.5kA
--
--
42kA
42kA
--
--
50kA
160A
--
--
--
--
--
--
--
--
--
--
--
--
--
2.5kA
--
--
--
42kA
--
--
50kA
*Where T is mentioned Selectivity is full up until the Icu of the downstream device.
IPD INDUSTRIAL PRODUCTS
512
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
DISCRIMINATION & SELECTIVITY
SELECTIVE TABLES
(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D3 ED. 2C)
Upstream
FE160N, H & L SMR1
FE250N, H & L LTMD
FE250N, H & L SMR1
125A
160A
FG400N, H & L SMR1 & 2
250A
250A
350A
400A
FG630N, H & L SMR1 & 2
63A
125A
160A
125A
160A
200A
250A
400A
500A
630A
<= 16A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
20A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
G60
25A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
G100 & G25
32A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
DM100 &
40A
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
DME100
50A
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
B/C curve
63A
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Redline
80A
--
T
T
--
T
T
T
T
T
T
T
T
T
T
T
T
HTI
100A
--
--
T
--
T
T
T
--
T
T
T
T
T
T
T
T
C curve
125A
--
--
T
--
--
T
T
--
T
T
T
T
T
T
T
T
<= 25A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GPS1BS &
32A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GPS1MS
40A
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Downstream
Selectivity limit in kA*
In (A)
Redline
Surion
GPS2BS &
50A
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GPS2MS
63A
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Surion
<= 25A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GPS1BH &
32A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GPS1MH
40A
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GPS2BH &
50A
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
GPS2MH
63A
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Record Plus
<= 40A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
FD63/160E
50A
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
LTM/MO/GTM
63A
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
80A
--
--
T
--
T
T
T
T
T
T
T
T
T
T
T
T
100A
--
--
T
--
--
T
T
--
T
T
T
T
T
T
T
T
125A
--
--
--
--
--
T
T
--
--
T
T
T
T
T
T
T
160A
Record Plus
<= 40A
--
--
--
--
--
--
T
--
--
T
T
T
T
T
T
T
36kA
36kA
36kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
T
T
T
T
T
T
T
FD63/160S, N
50A
--
36kA
36kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
T
T
T
T
T
H&L
63A
--
36kA
36kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
T
T
T
T
T
T
LTMD/MO/GTM
80A
--
--
36kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
T
T
T
T
T
T
Record Plus
100A
--
--
36kA
--
42kA
42kA
42kA
--
50kA
50kA
T
T
T
T
T
T
125A
--
--
--
--
--
42kA
42kA
--
--
50kA
T
T
T
T
T
T
160A
--
--
--
--
--
--
42kA
--
--
50kA
T
T
T
T
T
T
36kA
36kA
36kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
T
T
T
T
T
T
<= 40A
FE160 N, H & L
50A
--
36kA
36kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
T
T
T
T
T
T
LTM/MO/GTM
63A
--
36kA
36kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
T
T
T
T
T
T
80A
--
36kA
36kA
42kA
42kA
42kA
42kA
50kA
50kA
50kA
T
T
T
T
T
T
100A
--
--
36kA
--
42kA
42kA
42kA
--
50kA
50kA
T
T
T
T
T
T
125A
--
--
--
--
--
42kA
42kA
--
--
50kA
T
T
T
T
T
T
160A
--
--
--
--
--
--
42kA
--
--
50kA
T
T
T
T
T
T
Record Plus
0.8kA
1.8kA
2.2kA
1.3kA
1.6kA
2.5kA
2.5kA
1.8kA
2.2kA
3.5kA
T
T
T
T
T
T
FE160 N, H & L
<= 40A
63A
--
1.8kA
2.2kA
1.3kA
1.6kA
2.5kA
2.5kA
1.8kA
2.2kA
3.5kA
T
T
T
T
T
T
LTMD/SMR1
80A
--
1.8kA
2.2kA
1.3kA
1.6kA
2.5kA
2.5kA
1.8kA
2.2kA
3.5kA
T
T
T
T
T
T
100A
--
--
2.2kA
--
1.6kA
2.5kA
2.5kA
--
2.2kA
3.5kA
T
T
T
T
T
T
125A
--
--
--
--
--
2.5kA
2.5kA
--
--
3.5kA
T
T
T
T
T
T
160A
--
--
--
--
--
--
2.5kA
--
--
3.5kA
T
T
T
T
T
T
Record Plus
125A
--
--
--
--
--
--
--
--
--
--
3.5kA
10kA
15kA
T
T
T
FE250 N, H & L
160A
--
--
--
--
--
--
--
--
--
--
3.5kA
10kA
15kA
T
T
T
LTMD/SMR1
200A
--
--
--
--
--
--
--
--
--
--
--
10kA
15kA
T
T
T
250A
--
--
--
--
--
--
--
--
--
--
--
10kA
15kA
T
T
T
Record Plus
FG400 N, H & L
250A
--
--
--
--
--
--
--
--
--
--
--
5kA
6kA
5kA
7kA
7kA
SMR1/SMR2
400A
--
--
--
--
--
--
--
--
--
--
--
--
--
--
--
7kA
TECHNICAL
*Where T is mentioned Selectivity is full up until the Icu of the downstream device.
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
513
DISCRIMINATION & SELECTIVITY
SELECTIVE TABLES
(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D4 ED. 2C)
Upstream
FK800N, H
FK1250N, H &
& L SMR1
L SMR1
800A
Downstream
1000A
FK1600N, H &
L SMR1
1250A
600A
Selectivity limit in kA*
In (A)
Redline
G60, G100, G25, DM60,
DME60, DM100 & DME100
B/C curve
ALL
T
T
T
T
T
ALL
T
T
T
T
T
Trip Units
ALL
T
T
T
T
T
Trip Units
ALL
T
T
T
T
T
Trip Units
ALL
T
T
T
T
T
Trip Units
ALL
T
T
T
T
T
Trip Units
400A
15kA
T
T
T
T
500A
15kA
T
T
T
T
630A
15kA
T
T
T
T
ALL
--
15kA
15kA
25kA
25kA
Surion
GPS1BS, GPS1MS, GPS2BS, GPS2MS
GPS1BH, GPS1MH, GPS2BH & GPS2MH
Record Plus
FD63/160E, S N & L types
LTM/LTMD/MO/GTM
Record Plus
FE160 N, H & L types
LTM/LTMD/MO/GTM/SMR1
Record Plus
FE250 V, N, H & L types
LTM/LTMD/MO/GTM/SMR1
Record Plus
FG400 N, H & L types
SMR1/SMR2
Record Plus
FG630 N, H & L types
SMR1/SMR2
Record Plus
FK800 N, H & L types
LTM/MO/SMR1e, s & g
Trip Units
Record Plus
FK1250 N, H & L types
LTM/MO/SMR1e, s & g
Trip Units 1000A
--
--
--
25kA
25kA
1250A
--
--
--
25kA
25kA
* Where T is mentioned Selectivity is full up untilthe Icu of the downstream device
IPD INDUSTRIAL PRODUCTS
514
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
DISCRIMINATION & SELECTIVITY
SELECTIVE TABLES
(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE D4 ED. 2C)
Upstream
Mpact + Frame 1
400A
630A
Mpact + Frame 2
800A 1000A 1250A 1600A 2000A 2500A
1000A 1250A 1600A
Mpact + Frame3
2000A
2500A
3200A
4000A
5000A
6300A
Downstream
Selectivity limit in kA*
In (A)
Redline
G60,G100,G25, DM60,
DME60, DM100 & DME100
B/C curve
ALL
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
ALL
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Trip Units
ALL
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Trip Units
ALL
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Trip Units
ALL
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Surion
GPS1BS, GPS1MS, GPS2BS, GPS2MS
GPS1BH, GPS1MH, GPS2BH & GPS2MH
Record Plus
FD63/160E, S N & L types
LTM/LTMD/MO/GTM
FE160 N, H & L types
LTM/LTMD/MO/GTM/SMR1
Record Plus
FE250 V, N, H & L types
LTM/LTMD/MO/GTM/SMR1
Record Plus
FG400 N, H & L types
SMR1/SMR2
Trip Units 250A
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
400A
--
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
Record Plus
FG630 N, H & L types
SMR1/SMR2
Trip Units 400A
--
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
500A
--
--
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630A
--
--
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
ALL
--
--
--
--
T
T
T
T
T
T
T
T
T
T
T
T
T
Trip Units 1000A
--
--
--
--
--
T
T
T
--
--
T
T
T
T
T
T
T
1250A
--
--
--
--
--
--
T
T
--
--
--
T
T
T
T
T
T
Record Plus
FK800 N, H & L types
LTM/MO/SMR1e, s & g
Trip Units
Record Plus
FK1250 N, H & L types
LTM/MO/SMR1e, s & g
Mpact Plus
Frame 1 & Frame 2
MPRO plus 17, 18, 30 & 40
Trip Units 400A
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
T
630A
--
--
--
T
T
T
T
T
T
T
T
T
T
T
T
T
T
800A
--
--
--
--
T
T
T
T
--
T
T
T
T
T
T
T
T
1000A
--
--
--
--
--
T
T
T
--
--
T
T
T
T
T
T
T
1600A
--
--
--
--
--
--
--
T
--
--
--
--
T
T
T
T
T
2000A
--
--
--
--
--
--
--
--
--
--
--
--
--
T
T
T
T
2500A
--
--
--
--
--
--
--
--
--
--
--
--
--
--
T
T
T
TECHNICAL
* Where T is mentioned Selectivity is full up until the Icu of the downstream device
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
515
DISCRIMINATION & SELECTIVITY
SELECTIVE PLUS TABLES
(RECORD PLUS MOULDED CASE CIRCUIT BREAKERS; TABLE DB1 ED. 2C)
Upstream
FDC 63/160 LTM
63A
Downstream
In (A)
Redline
G60 &GT10
B/C curve
Redline
G100
B/C curve
Redline
GT25
B/C curve
Surion
GPS1BS &
GPS1MS
Surion
GPS2BS &
GPS2MS
Surion
GPS1BH &
GPS1MH
GPS2BH &
GPS2MH
<= 16A
20A
25A
32A
40A
50A
63A
<= 16A
20A
25A
32A
40A
50A
63A
<= 20A
25A
32A
40A
50A
63A
<= 10A
12.5A
16/20A
25/32A
40A
50/63A
<= 10A
12.5A
16/20A
25/32A
40A
50/63A
<= 10A
12.5A
16/20A
25/32A
40A
50/63A
Upstream
6/18
3/18
-----6/18
3/18
------------------------------
80A
100A
125A
63A
160A
Selectivity limit in kA
6/18 10/18 18/18
6/22
6/18 8/18 18/18
3/22
6/18 6/18 18/18
-3/18 6/18 18/18
-3/18 4/18 18/18
--1.5/18 6/18
-----6/18 10/18 18/18
6/25
6/18 8/18 18/18
3/25
6/18 6/18 18/18
-3/18 6/18 18/18
-3/18 4/18 18/18
--1.5/18 6/18
---2/18
--------------------------------------------------------------------------------------------------
FDN 63/160 LTMD
63A
80A
100A
30/30
30/30
15/30
10/30
3.5/30
--36/36
36/36
15/36
10/36
3.5/36
--36/42
15/42
10/36
3.5/36
----42/42
42/42
---42/42
42/42
42/42
---------
30/30
30/30
15/30
10/30
10/30
3.5/30
-36/36
36/36
36/36
10/36
10/36
3.5/36
-36/42
15/42
10/36
10/36
3.5/36
---42/42
42/42
42/42
--42/42
42/42
42/42
42/42
--------
30/30
30/30
30/30
30/30
15/30
10/30
8/30
36/36
36/36
30/36
30/36
15/36
10/36
8/36
36/42
30/42
36/36
15/36
10/36
8/36
--42/42
42/42
42/42
42/42
-42/42
42/42
42/42
42/42
42/42
-------
Downstream
Redline
G60 &GT10
B/C curve
Redline
G100
B/C curve
Redline
GT25
B/C curve
Surion
GPS1BS &
GPS1MS
Surion
GPS2BS &
GPS2MS
Surion
GPS1BH &
GPS1MH
GPS2BH &
GPS2MH
In (A)
<= 16A
20A
25A
32A
40A
50A
63A
<= 16A
20A
25A
32A
40A
50A
63A
<= 20A
25A
32A
40A
50A
63A
<= 10A
12.5A
16/20A
25/32A
40A
50/63A
<= 10A
12.5A
16/20A
25/32A
40A
50/63A
<= 10A
12.5A
16/20A
25/32A
40A
50/63A
IPD INDUSTRIAL PRODUCTS
516
Product Catalogue 2013
FDE 63/160 LTM
80A
/ Icu of
6/22
6/22
6/22
3/22
3/22
--6/25
6/25
6/25
3/25
3/25
---------------------------
100A
125A
63A
160A
combination in kA at 400-415V AC
10/22 22/22
25/25
8/22
22/22
25/25
6/22
22/22
15/25
6/22
22/22
10/25
4/22
22/22
3.5/25
1.5/22
6/22
----10/25 25/25
30/30
8/25
25/25
30/30
6/25
25/25
15/30
6/25
25/25
10/30
4/25
25/25
3.5/30
-6/25
--2/25
---36/36
--15/36
--10/30
--3.5/30
--------------36/36
--36/36
-----------36/36
--36/36
--36/36
-------------------------
FDH 63/160 LTMD
125A
63A
80A
160A
Selectivity limit in kA / Icu of
30/30
36/36 36/36
30/30
36/36 36/36
30/30
15/36 15/36
30/30
10/36 10/36
25/30
3.5/36 10/36
22/30
-3.5/36
22/30
--36/36
36/42 36/42
36/36
36/42 36/42
30/36
15/42 36/42
30/36
10/42 10/42
25/36
3.5/42 10/42
22/36
-3.5/42
22/36
--36/42
36/50 36/50
30/42
15/50 15/50
30/36
10/42 10/42
25/36
3.5/42 10/42
22/36
-3.5/42
22/36
------80/80 80/80
42/42
50/50 50/50
42/42
50/50 50/50
42/42
-50/50
42/42
-----42/42
50/50 50/50
42/42
50/50 50/50
42/42
50/50 50/50
42/42
-50/50
42/42
---------80/80 80/80
-80/80 80/80
--80/80
----
Phone: 1300 556 601
FDS 63/160 LTMD
80A
100A
125A
160A
25/25
25/25
15/25
10/25
10/25
3.5/25
-30/30
30/30
30/30
10/30
10/30
3.5/30
-36/36
15/36
10/30
10/30
3.5/30
---36/36
36/36
36/36
--36/36
36/36
36/36
36/36
--------
25/25
25/25
25/25
25/25
15/25
10/25
8/25
30/30
30/30
30/30
30/30
15/30
10/30
8/30
36/36
30/36
36/30
15/30
10/30
8/30
--36/36
36/36
36/36
36/36
-36/36
36/36
36/36
36/36
36/36
-------
25/25
25/25
25/25
25/25
25/25
22/25
22/25
30/30
30/30
30/30
30/30
25/30
22/30
22/30
36/36
30/36
30/30
25/30
22/30
22/30
--36/36
36/36
36/36
36/36
-36/36
36/36
36/36
36/36
36/36
-------
FDL 63/160 LTMD
100A
125A
63A
80A
160A
combination in kA at 400-415V AC
36/36 36/36
36/42 36/42
36/36 36/36
36/42 36/42
30/36 30/36
15/42 15/42
36/36 30/36
10/42 10/42
15/36 25/36
3.5/42 10/42
10/36 22/36
-3.5/42
8/36
22/36
--36/42 36/42
36/50 36/50
36/42 36/42
36/50 36/50
30/42 30/42
15/50 15/50
30/42 30/42
10/50 10/50
15/42 25/42
3.5/50 10/50
10/42 22/42
-3.5/50
8/42
22/42
--36/50 36/50
36/65 36/65
30/50 30/50
15/65 15/65
36/42 30/42
10/50 10/50
15/42 25/42
3.5/50 10/50
10/42 22/42
-3.5/50
8/42
22/42
----150/150 150/150
80/80 80/80
150/150 150/150
50/50 50/50
65/65 65/65
50/50 50/50
65/65 65/65
50/50 50/50
-65/65
50/50 50/50
----150/150 150/150
50/50 50/50
65/65 65/65
50/50 50/50
65/65 65/65
50/50 50/50
65/65 65/65
50/50 50/50
-65/65
50/50 50/50
----150/150 150/150
--150/150 150/150
80/80 80/80
150/150 150/150
80/80 80/80
150/150 150/150
80/80 80/80
-150/150
80/80 80/80
---
www.ipdgroup.com.au
100A
125A
160A
36/42
36/42
30/42
36/42
15/42
10/42
8/42
36/50
36/50
30/50
30/50
15/50
10/50
8/50
36/65
30/65
36/50
15/50
10/50
8/50
150/150
150/150
65/65
65/65
65/65
65/65
150/150
65/65
65/65
65/65
65/65
65/65
150/150
150/150
150/150
150/150
150/150
150/150
36/42
36/42
30/42
30/42
25/42
22/42
22/42
36/50
36/50
30/50
30/50
25/50
22/50
22/50
36/65
30/65
30/50
25/50
22/50
22/50
150/150
150/150
65/65
65/65
65/65
65/65
150/150
65/65
65/65
65/65
65/65
65/65
150/150
150/150
150/150
150/150
150/150
150/150
DISCRIMINATION & SELECTIVITY
SELECTIVE PLUS
TABLE DB1A ED 2C
Upstream
FDC 63/160 LTM
63A
80A
100A
Downstream
63A
80A
100A
125A
160A
FDS 63/160 LTMD
63A
80A
100A
160A
125A
160A
Selectivity limit in kA / Icu of combination in kA at 240V AC
In (A)
Redline
125A
FDE 63/160 LTM
<= 16A
6/18
6/18
10/18
18/18
6/22
6/22
10/22
10/22
25/25
25/25
25/25
25/25
DME100
20A
3/18
6/18
8/18
18/18
3/22
6/22
8/22
10/22
25/25
25/25
25/25
25/25
B/C curve
25A
--
6/18
6/18
18/18
--
6/22
6/22
10/22
15/25
25/25
25/25
25/25
32A
--
3/18
6/18
18/18
--
3/22
6/22
10/22
10/25
10/25
25/25
25/25
40A
--
3/18
4/18
18/18
--
3/22
4/22
10/22
3.5/25
10/25
15/25
25/25
Upstream
FDN 63/160 LTMD
63A
80A
100A
Downstream
63A
80A
100A
125A
160A
In (A)
Redline
125A
FDH 63/160 LTMD
FDL 63/160 LTMD
63A
80A
100A
160A
125A
160A
Selectivity limit in kA / Icu of combination in kA at 240V AC
<= 16A
25/25
25/25 25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
DME100
20A
25/25
25/25 25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
25/25
B/C curve
25A
15/25
25/25 25/25
25/25
15/25
25/25
25/25
25/25
15/25
25/25
25/25
25/25
32A
10/25
10/25 25/25
25/25
10/25
10/25
25/25
25/25
10/25
10/25
25/25
25/25
40A
3.5/25
10/25 15/25 25/25
3.5/25
10/25
15/25
25/25
3.5/25
10/25
15/25
25/25
SELECTIVE PLUS
TABLE DB2A ED 2C
Upstream
FE160N-LTMD/SMR1
63A
100A
FE160H-LTMD/SMR1
125A
160A
63A
100A
125A
FE160L-LTMD/SMR1
160A
63A
100A
125A
160A
22/22
Downstream
Selectivity limit in kA / Icu of combination in kA at 240V AC
In (A)
Redline
<= 16A
22/22
22/22 22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
DME100
20A
22/22
22/22 22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
B/C curve
25A
22/22
22/22 22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
32A
22/22
22/22 22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
22/22
40A
--
22/22 22/22
22/22
--
22/22
22/22
22/22
--
22/22
22/22
22/22
Upstream
FE250N-LTMD/SMR1
125A
160A
FE250H-LTMD/SMR1
200A
250A
18/18
18/18
18/18
18/18
18/18
Selectivity limit in kA
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
125A
160A
200A
FE250L-LTMD/SMR1
125A
160A
200A
250A
combination in kA at 240V AC
18/18 18/18
18/18
18/18 18/18
18/18
18/18 18/18
18/18
18/18 18/18
18/18
18/18 18/18
18/18
250A
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
Downstream
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
18/18
/ Icu of
18/18
18/18
18/18
18/18
18/18
TECHNICAL
Redline
DME100
B/C curve
In (A)
<= 16A
20A
25A
32A
40A
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
517
DISCRIMINATION & SELECTIVITY
SELECTIVE PLUS
TABLE DB2 ED 2C
Upstream
FE160N-LTMD/SMR1
FE160H-LTMD/SMR1
63A
100A
125A
160A
63A
30/30
30/30
---36/36
36/36
---42/42
36/36
-----42/42
42/42
---42/42
42/42
42/42
---------
30/30
30/30
30/30
30/30
-36/36
36/36
36/36
36/36
-42/42
36/36
36/36
36/36
---42/42
42/42
42/42
--42/42
42/42
42/42
42/42
--------
30/30
30/30
30/30
30/30
30/30
36/36
36/36
36/36
36/36
36/36
42/42
36/36
36/36
36/36
36/36
--42/42
42/42
42/42
42/42
-42/42
42/42
42/42
42/42
42/42
-------
Selectivity limit in kA
30/30
36/36
30/30
36/36
30/30
-30/30
-30/30
-36/36
42/42
36/36
42/42
36/36
-36/36
-36/36
-42/42
50/50
36/36
42/42
36/36
-36/36
-36/36
----80/80
42/42
50/50
42/42
50/50
42/42
-42/42
---42/42
50/50
42/42
50/50
42/42
50/50
42/42
-42/42
------80/80
-80/80
-----
100A
125A
FE160L-LTMD/SMR1
160A
63A
100A
125A
160A
42/42
42/42
42/42
42/42
42/42
50/50
50/50
50/50
50/50
50/50
65/65
50/50
50/50
50/50
50/50
150/150
150/150
65/65
65/65
65/65
65/65
150/150
65/65
65/65
65/65
65/65
65/65
150/150
150/150
150/150
150/150
150/150
150/150
42/42
42/42
42/42
42/42
42/42
50/50
50/50
50/50
50/50
50/50
65/65
50/50
50/50
50/50
50/50
150/150
150/150
65/65
65/65
65/65
65/65
150/150
65/65
65/65
65/65
65/65
65/65
150/150
150/150
150/150
150/150
150/150
150/150
Downstream
In (A)
Redline
G60 &GT10
B/C curve
Redline
G100
B/C curve
Redline
GT25
B/C curve
Surion
GPS1BS &
GPS1MS
Surion
GPS2BS &
GPS2MS
Surion
GPS1BH &
GPS1MH
GPS2BH &
GPS2MH
<= 25A
32A
40A
50A
63A
<= 25A
32A
40A
50A
63A
<= 25A
32A
40A
50A
63A
<= 10A
12.5A
16/20A
25/32A
40A
50/63A
<= 10A
12.5A
16/20A
25/32A
40A
50/63A
<= 10A
12.5A
16/20A
25/32A
40A
50/63A
Upstream
FE250N-LTMD/SMR1
/ Icu of
36/36
36/36
36/36
36/36
-42/42
42/42
42/42
42/42
-50/50
42/42
42/42
42/42
--80/80
50/50
50/50
50/50
--50/50
50/50
50/50
50/50
---80/80
80/80
80/80
--
combination in kA at 400-415V AC
36/36 36/36
42/42 42/42
36/36 36/36
42/42 42/42
36/36 36/36
-42/42
36/36 36/36
-42/42
36/36 36/36
--42/42 42/42
50/50 50/50
42/42 42/42
50/50 50/50
42/42 42/42
-50/50
42/42 42/42
-50/50
42/42 42/42
--50/50 50/50
65/65 65/65
42/42 42/42
50/50 50/50
42/42 42/42
-50/50
42/42 42/42
-50/50
42/42 42/42
----150/150 150/150
80/80 80/80
150/150 150/150
50/50 50/50
65/65 65/65
50/50 50/50
65/65 65/65
50/50 50/50
-65/65
50/50 50/50
----150/150 150/150
50/50 50/50
65/65 65/65
50/50 50/50
65/65 65/65
50/50 50/50
65/65 65/65
50/50 50/50
-65/65
50/50 50/50
----150/150 150/150
--150/150 150/150
80/80 80/80
150/150 150/150
80/80 80/80
150/150 150/150
80/80 80/80
-150/150
80/80 80/80
---
FE250H-LTMD/SMR1
125A
160A
200A
250A
125A
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
36/36
36/36
36/36
30/30
30/30
--42/42
42/42
42/42
42/42
-42/42
42/42
42/42
42/42
42/42
-------
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
36/36
36/36
36/36
30/30
30/30
--42/42
42/42
42/42
42/42
-42/42
42/42
42/42
42/42
42/42
-------
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
30/30
36/36
36/36
36/36
30/30
30/30
--42/42
42/42
42/42
42/42
-42/42
42/42
42/42
42/42
42/42
-------
Selectivity limit in kA
30/30
36/36
30/30
36/36
30/30
36/36
30/30
36/36
30/30
36/36
30/30
36/36
30/30
36/36
30/30
36/36
30/30
36/36
30/30
36/36
36/36
42/42
36/36
42/42
36/36
42/42
30/30
36/36
30/30
36/36
---80/80
42/42
50/50
42/42
50/50
42/42
50/50
42/42
50/50
--42/42
50/50
42/42
50/50
42/42
50/50
42/42
-42/42
------80/80
-80/80
-80/80
-80/80
160A
200A
FE250L-LTMD/SMR1
250A
125A
160A
200A
250A
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
42/42
42/42
42/42
36/36
36/36
150/150
150/150
65/65
65/65
65/65
65/65
150/150
65/65
65/65
65/65
65/65
65/65
150/150
150/150
150/150
150/150
150/150
150/150
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
42/42
42/42
42/42
36/36
36/36
150/150
150/150
65/65
65/65
65/65
65/65
150/150
65/65
65/65
65/65
65/65
65/65
150/150
150/150
150/150
150/150
150/150
150/150
Downstream
Redline
G60 &GT10
B/C curve
Redline
G100
B/C curve
Redline
GT25
B/C curve
Surion
GPS1BS &
GPS1MS
Surion
GPS2BS &
GPS2MS
Surion
GPS1BH &
GPS1MH
GPS2BH &
GPS2MH
In (A)
<= 25A
32A
40A
50A
63A
<= 25A
32A
40A
50A
63A
<= 25A
32A
40A
50A
63A
<= 10A
12.5A
16/20A
25/32A
40A
50/63A
<= 10A
12.5A
16/20A
25/32A
40A
50/63A
<= 10A
12.5A
16/20A
25/32A
40A
50/63A
IPD INDUSTRIAL PRODUCTS
518
Product Catalogue 2013
/ Icu of
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
36/36
42/42
42/42
42/42
36/36
36/36
-80/80
50/50
50/50
50/50
50/50
-50/50
50/50
50/50
50/50
---80/80
80/80
80/80
80/80
combination in kA at 400-415V AC
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
42/42 42/42
42/42 42/42
42/42 42/42
42/42 42/42
42/42 42/42
42/42 42/42
36/36 36/36
36/36 36/36
36/36 36/36
36/36 36/36
--150/150 150/150
80/80 80/80
150/150 150/150
50/50 50/50
65/65 65/65
50/50 50/50
65/65 65/65
50/50 50/50
65/65 65/65
50/50 50/50
65/65 65/65
--150/150 150/150
50/50 50/50
65/65 65/65
50/50 50/50
65/65 65/65
50/50 50/50
65/65 65/65
50/50 50/50
-65/65
50/50 50/50
----150/150 150/150
--150/150 150/150
80/80 80/80
150/150 150/150
80/80 80/80
150/150 150/150
80/80 80/80
150/150 150/150
80/80 80/80
150/150 150/150
Phone: 1300 556 601
www.ipdgroup.com.au
DISCRIMINATION & SELECTIVITY
SELECTIVE PLUS
TABLE DB3 ED 2C
Upstream
In (A)
Type & In
Downstream
Record Plus
LTM. LTMD,
GTM & MO
Record Plus
LTM. LTMD,
GTM & MO
Record Plus
LTM. LTMD,
& GTM
Record Plus
LTM. LTMD,
& GTM
FE160N-LTMD
FDC160
FDE160
FDS160
FDN160
FDH160
FDC160
FDE160
FDS160
FDN160
FDH160
FDC160
FDE160
FDS160
FDN160
FDH160
FDC63
FDE63
FDS63
FDN63
FDH63
<= 100A
<= 100A
<= 100A
<= 100A
<= 100A
125A
125A
125A
125A
125A
160A
160A
160A
160A
160A
100A
30/30
30/36
30/42
30/50
-----------------
Upstream
Record Plus
LTM. LTMD,
GTM & MO
Record Plus
LTM. LTMD,
& GTM
Record Plus
LTM. LTMD,
& GTM
FDC160
FDE160
FDS160
FDN160
FDH160
FDC160
FDE160
FDS160
FDN160
FDH160
FDC160
FDE160
FDS160
FDN160
FDH160
160A
30/30
30/36
30/42
30/50
-----------------
Selectivity limit in kA / Icu of
30/30
30/36
30/36
30/42
30/42
30/50
30/50
30/80
-30/80
30/30
-30/36
-30/42
-30/50
------------------------
100A
FDC63
FDE63
FDS63
FDN63
FDH63
<= 100A
<= 100A
<= 100A
<= 100A
<= 100A
125A
125A
125A
125A
125A
160A
160A
160A
160A
160A
125A
30/30
36/36
42/42
42/50
-----------------
250A
125A
FE160L-LTMD
160A
100A
FE250H-LTMD
160A
200A
30/30
36/36
42/42
42/50
-30/30
36/36
42/42
42/50
------------
Selectivity limit in kA /
30/30
30/30
36/36
36/36
36/36
42/42
42/42
42/42
42/50
42/50
42/50
42/80
--42/80
30/30
30/30
-36/36
36/36
-42/42
42/42
-42/50
42/50
----30/30
30/30
-36/36
36/36
-42/42
42/42
-42/50
42/50
-----30/30
--36/36
--42/42
--42/50
-----
125A
160A
125A
combination in kA at 400 - 415V AC
30/36 30/36
30/42 30/42
30/42 30/42
30/50 30/50
30/50 30/50
30/65 30/65
30/80 30/80
30/150 30/150
30/80 30/80
30/150 30/150
-30/36
---30/42
---30/50
---30/80
---30/80
-------------------------------------------
160A
30/42
30/50
30/65
30/150
30/150
30/42
30/50
30/65
30/150
30/150
-----------
FE250L-LTMD
200A
Icu of combination
36/36
36/36
42/42
42/42
42/50
42/50
42/80
42/80
42/80
42/80
36/36
36/36
42/42
42/42
42/50
42/50
42/80
42/80
42/80
42/80
-36/36
-42/42
-42/50
-42/80
-42/80
-----------
250A
125A
160A
in kA at 400 - 415V AC
36/36
42/42
42/42
42/42
42/50
42/50
42/50
42/65
42/65
42/80
42/150 42/150
42/80
42/150 42/150
36/36
-42/42
42/42
-42/50
42/50
-42/65
42/80
-42/150
42/80
-42/150
36/36
--42/42
--42/50
--42/80
--42/80
--36/36
--42/42
--42/50
--42/80
--42/80
---
200A
250A
42/42
42/50
42/65
42/150
42/150
42/42
42/50
42/65
42/150
42/150
42/42
42/50
42/65
42/150
42/150
------
42/42
42/50
42/65
42/150
42/150
42/42
42/50
42/65
42/150
42/150
42/42
42/50
42/65
42/150
42/150
42/42
42/50
42/65
42/150
42/150
TECHNICAL
Record Plus
LTM. LTMD,
GTM & MO
125A
FE250N-LTMD
In (A)
Type & In
Downstream
FE160H-LTMD
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
519
DISCRIMINATION & SELECTIVITY
SELECTIVE PLUS
TABLE DB4 ED 2C
Upstream
FE160N-SMR1
In (A)
Downstream
FE160H-SMR1
63A
125A
160A
63A
125A
FE160L-SMR1
160A
63A
125A
160A
Type & In
Selectivity limit in kA / Icu of combination in kA at 400 - 415V AC
Record Plus
FDC63
--
30/30
30/30
--
30/36
30/36
--
36/42
36/42
LTM. LTMD,
FDE63
--
36/36
36/36
--
30/42
30/42
--
36/50
36/50
GTM & MO
FDS63
--
36/42
36/42
--
30/50
30/50
--
36/65
36/65
FDN63
--
36/50
36/50
--
30/80
30/80
--
36/150 36/150
36/150 36/150
FDH63
--
--
--
--
30/80
30/80
--
Record Plus
FDC160
<= 100A
--
--
30/30
--
--
30/36
--
--
36/42
LTM. LTMD,
FDE160
<= 100A
--
--
36/36
--
--
30/42
--
--
36/50
GTM & MO
FDS160
<= 100A
--
--
36/42
--
--
30/50
--
--
36/65
FDN160
<= 100A
--
--
36/50
--
--
30/80
--
--
36/150
FDH160
<= 100A
--
--
--
--
--
30/80
--
--
36/150
Record Plus
FDC160
125A
--
--
--
--
--
--
--
--
--
LTM. LTMD,
FDE160
125A
--
--
--
--
--
--
--
--
--
& GTM
FDS160
125A
--
--
--
--
--
--
--
--
--
FDN160
125A
--
--
--
--
--
--
--
--
--
FDH160
125A
--
--
--
--
--
--
--
--
---
Record Plus
FDC160
160A
--
--
--
--
--
--
--
--
LTM. LTMD,
FDE160
160A
--
--
--
--
--
--
--
--
--
& GTM
FDS160
160A
--
--
--
--
--
--
--
--
--
FDN160
160A
--
--
--
--
--
--
--
--
--
FDH160
160A
--
--
--
--
--
--
--
--
--
FE250N-SMR1
Upstream
In (A)
125A
160A
200A
FE250H-SMR1
250A
125A
160A
200A
FE250L-SMR1
250A
125A
160A
200A
250A
42/42
Type & In
Downstream
Selectivity limit in kA / Icu of combination in kA at 400 - 415V AC
Record Plus
FDC63
30/30
30/30
30/30
30/30
36/36
36/36
36/36
36/36
42/42
42/42
42/42
LTM. LTMD,
FDE63
36/36
36/36
36/36
36/36
42/42
42/42
42/42
42/42
50/50
50/50
50/50
50/50
GTM & MO
FDS63
42/42
42/42
42/42
42/42
50/50
50/50
50/50
50/50
50/65
50/65
50/65
50/65
FDN63
50/50
50/50
50/50
50/50
50/80
50/80
50/80
50/80
50/150
50/150
50/150
50/150
FDH63
--
--
--
--
50/80
50/80
50/80
50/80
50/150
50/150
50/150
50/150
Record Plus
FDC160
<= 100A
--
30/30
30/30
30/30
--
36/36
36/36
36/36
--
42/42
42/42
42/42
LTM. LTMD,
FDE160
<= 100A
--
36/36
36/36
36/36
--
42/42
42/42
42/42
--
50/50
50/50
50/50
GTM & MO
FDS160
<= 100A
--
42/42
42/42
42/42
--
50/50
50/50
50/50
--
50/65
50/65
50/65
FDN160
<= 100A
--
50/50
50/50
50/50
--
50/80
50/80
50/80
--
50/150
50/150
50/150
FDH160
<= 100A
--
--
--
--
--
50/80
50/80
50/80
--
50/150
50/150
50/150
Record Plus
FDC160
125A
--
--
30/30
30/30
--
--
36/36
36/36
--
--
42/42
42/42
LTM. LTMD,
FDE160
125A
--
--
36/36
36/36
--
--
42/42
42/42
--
--
50/50
50/50
& GTM
FDS160
125A
--
--
42/42
42/42
--
--
50/50
50/50
--
--
50/65
50/65
FDN160
125A
--
--
50/50
50/50
--
--
50/80
50/80
--
--
50/150
50/150
FDH160
125A
--
--
--
--
--
--
--
--
--
--
50/150
50/150
Record Plus
FDC160
160A
--
--
--
30/30
--
--
--
36/36
--
--
--
42/42
LTM. LTMD,
FDE160
160A
--
--
--
36/36
--
--
--
42/42
--
--
--
50/50
& GTM
FDS160
160A
--
--
--
42/42
--
--
--
50/50
--
--
--
50/65
FDN160
160A
--
--
--
50/50
--
--
--
50/80
--
--
--
50/150
FDH160
160A
--
--
--
--
--
--
--
50/80
--
--
--
50/150
IPD INDUSTRIAL PRODUCTS
520
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
DISCRIMINATION & SELECTIVITY
SELECTIVE PLUS
TABLE DB5 ED 2C
Upstream
In (A)
Downstream
FG400N-SMR1
250A
400A
FG400H-SMR1
250A
FG400L-SMR1
400A
250A
FG630N-SMR1
400A
400A
FG630H-SMR1
500A
Type & In
400A
FG630L-SMR1
500A
630A
400A
630A
500A
630A
Selectivity limit in kA / Icu of combination in kA at 400-415V AC
Record Plus
FDC63
30/30
30/30
36/36
36/36
42/42
42/42
30/30
30/30
36/36
36/36
42/42
42/42
LTM. LTMD,
FDE63
36/36
36/36
42/42
42/42
50/50
50/50
36/36
36/36
42/42
42/42
50/50
50/50
GTM & MO
FDS63
42/42
42/42
50/50
50/50
65/65
65/65
42/42
42/42
50/50
50/50
65/65
65/65
FDN63
50/50
50/50
80/80
80/80
150/150
150/150
50/50
50/50
80/80
80/80
150/150
150/150
FDH63
--
--
80/80
80/80
150/150
150/150
--
--
80/80
80/80
150/150
150/150
Record Plus
FDC160
30/30
30/30
36/36
36/36
42/42
42/42
30/30
30/30
36/36
36/36
42/42
42/42
LTM. LTMD,
FDE160
36/36
36/36
42/42
42/42
50/50
50/50
36/36
36/36
42/42
42/42
50/50
50/50
GTM & MO
FDS160
42/42
42/42
50/50
50/50
65/65
65/65
42/42
42/42
50/50
50/50
65/65
65/65
FDN160
50/50
50/50
80/80
80/80
150/150
150/150
50/50
50/50
80/80
80/80
150/150
150/150
Record Plus
FDH160
--
--
80/80
80/80
150/150
150/150
--
--
80/80
80/80
150/150
150/150
FEN160
50/50
50/50
80/80
80/80
150/150
150/150
50/50
50/50
80/80
80/80
150/150
150/150
LTM.LTMD,GTM
FEH160
--
--
80/80
80/80
150/150
150/150
--
--
80/80
80/80
150/150
150/150
MO & SMR1
FEN250
--
--
80/80
80/80
150/150
150/150
50/50
50/50
80/80
80/80
150/150
150/150
FEH250
--
--
80/80
80/80
150/150
150/150
--
--
80/80
80/80
150/150
150/150
SELECTIVE PLUS
TABLE DB6 ED 2C
Upstream
In (A)
Downstream
FK800N-SMR
FK800H-SMR
FK800L-SMR
800A
800A
800A
FK1250N-SMR
1000A
1250A
FK1250H-SMR
1000A
1250A
FK1250L-SMR
1000A
FK1600N-SMR
FK1600H-SMR
1250A
1600A
1600A
Type&In
Selectivity limit in kA / Icu of combination in kA at 400-415V AC
Record Plus
LTM. LTMD,
FDN63
50/50
80/80
100/100
50/50
50/50
80/80
80/80
100/100
100/100
50/50
80/80
GTM & MO
FDH63
50/50
80/80
100/100
50/50
50/50
80/80
80/80
100/100
100/100
50/50
80/80
Record Plus
FDN160
50/50
80/80
100/100
50/50
50/50
80/80
80/80
100/100
100/100
50/50
80/80
FDH160
50/50
80/80
100/100
50/50
50/50
80/80
80/80
100/100
100/100
50/50
80/80
Record Plus
FEN160
50/50
80/80
100/100
50/50
50/50
80/80
80/80
100/100
100/100
50/50
80/80
LTM. LTMD,
FEH160
50/50
80/80
100/100
50/50
50/50
80/80
80/80
100/100
100/100
50/50
80/80
GTM, MO
FEN250
50/50
80/80
100/100
50/50
50/50
80/80
80/80
100/100
100/100
50/50
80/80
& SMR1
FEH250
--
80/80
100/100
50/50
50/50
80/80
80/80
100/100
100/100
50/50
80/80
Record Plus
FGN400
50/50
80/80
100/100
50/50
50/50
80/80
80/80
100/100
100/100
50/50
80/80
SMR1 &
FGH400
50/50
80/80
100/100
50/50
50/50
80/80
80/80
100/100
100/100
50/50
80/80
SMR2
FGN630
15/50
15/80
15/100
50/50
50/50
80/80
80/80
100/100
100/100
50/50
80/80
FGH630
--
15/80
15/100
--
--
80/80
80/80
100/100
100/100
50/50
80/80
Record Plus
FKN800
--
--
--
15/50
15/50
15/80
15/80
15/100
15/100
25/50
25/80
SMR1
FKH800
--
--
--
--
--
15/80
15/80
15/100
15/100
25/50
25/80
FKN1250
--
--
--
--
--
--
--
--
--
25/50
25/80
TECHNICAL
LTM. LTMD,
GTM & MO
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
521
FUSE LINK TEMPERATURE DERATING
FUSE DE-RATING WITH HIGH ENCLOSURE TEMPERATURES
In accordance with the relevant Standards, the rated current of fuses is determined
by tests conducted at 35°C ambient air temperature. When fuses are installed within
enclosures, it is the temperature within the enclosure (fluid enviroment temperature)
which determines whether de-rating is necessary.
The effect of high enclosure temperatures on IPD Type T fuses is indicated by the
table below.
Fuse Nominal
Rating (A)
55°C
63 or less
80
100
125
160
200
250
315
355
400
450
500
560
630
670
710
750
800
1000
1250
De-rating not
necessary
475
540
600
650
700
725
760
950
1140
IPD INDUSTRIAL PRODUCTS
522
Product Catalogue 2013
Maximum Load Current (A)
Versus Fluid Environment
Temperature
60°C
65°C
70°C
300
350
390
425
450
520
570
615
665
710
720
900
1070
190
235
285
330
380
405
425
495
540
585
630
670
680
850
1020
Phone: 1300 556 601
75
95
120
145
180
225
270
315
360
380
400
465
510
550
595
630
640
800
960
75°C
70
90
110
135
170
210
255
295
340
360
380
440
480
520
560
590
600
750
900
www.ipdgroup.com.au
PROTECTION OF CABLES WITH FUSE LINKS
FUSE PROTECTION OF CABLES AGAINST TRANSIENT OVERCURRENTS
In some circuits such as the motors, significant transient overcurrents are produced during switching, and it is not
economical practice to match cable and fuse-link ratings. For these cases, the cable is chosen for the circuit load
condition and the fuse-links are chosen to withstand the transient overcurrent condition.
The fuse-links provide only short-circuit current protection to the motor, associated cables and other circuits
components. The necessary overload protection is provided by other means such as the motor starter’s thermal
overload relay.
The short-circuit protection of cables is covered by Section 5 of AS/NZS 3008.1.1:1998 and the Table below shows
how fuse-links relate to these requirements in protecting V75 rated PVC insulated copper conductors.
Maximum Current-Carrying
Capacity (A)
Maximum GEC,
GE or IPD
Fuse-Link
Rating (A)
Conductor
cross-sectional
area (mm2)
1
1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630
“Unenclosed” condition.
Ratings according to
Table 6, Column 6 of
AS/NZS 3008.1.1:1998
13
16
23
31
40
54
72
97
120
145
185
230
265
310
355
425
490
570
660
760
“Enclosed” condition.
Ratings according to
Table 6, Column 8 of
AS/NZS 3008.1.1:1998
11
14
20
26
34
47
62
87
100
125
155
185
220
250
285
340
390
455
530
620
Type T
‘gG’
DIN Type
‘gL’-’gG’
16
20
35
50
63
80
125
200
250
355
450
630
710
800
1000
1250
1250
1250
1250
1250
16
20
32
40
50
80
125
200
250
355
500
630
800
1000
1000
1000
1000
1000
1000
1000
Notes:
1. Selection of the above fuse-links is based on the formula I2t = K2S2 given in Clause 5.3 of AS/NZS
3008.1.1:1998 where:
I = Current which causes the fuse-link to operate in 5 seconds.
t = 5 seconds.
K = Constant of 111 for PVC insulated copper conductor, for the condition of initial.
temperature 75°C and final temperature 160°C (during overcurrent condition).
S = Cross-sectional area of the conductor in mm2.
TECHNICAL
2. For motor start fuse-links (i.e. those classified and marked ‘gM’) the larger of its dual current ratings is
applicable, e.g. 160A for TCP100M160 type.
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
523
GE CONTACTOR SELECTION - LIGHTING CIRCUITS
CONTACTORS FOR CONTROL LIGHTING CIRCUITS
The characteristics of the most usual lighting systems are as follows:
Incandescent lamps
The connection current in very high -of the order of 15 times- rated current. Although this is a very short duration, it is only taken into account in order for the contactor
connection current not to be exceeded. The power factor is always maintained at 1.
Fluorescent lamps
The connection current is slightly higher than rated current. The power factor is about 0.5. To improve up to 0.9, compensating capacitors can be used. In such cases,
the connection power of the capacitor must be taken into account, the effect of which is appreciably greater on the smaller contactors.
High pressure mercury vapour lamps
The connection current varies, depending on type, between 1.6 and 2 times the rated current and will hold for between 3 and 5 minutes.
The power factor is of the order of 0.6 and this can be improved up to approximately unit value by means of compensating capacitors. In such cases, the connection
power of the capacitor must be taken into account, the effect of which is appreciably greater on the smaller contactors.
High pressure sodium vapour lamps
The connection current values varies, depending on type, between 1.3 and 1.6 times the rated current and will hold between 3 and 5 minutes.
The power factor is of the order of 0.45 and this can be improved up to apporximately unit value by means of compensating capacitors. In such cases, the connection
power of the capacitor must be taken into account, the effect of which is appreciably greater on the smaller contactors.
SELECTION TABLE
Maximum number of lamps per phase at 230V
Types
Incandescent
Fluorescent
Single arrangement
Without compensation
Fluorescent
Single arrangement
With compensation
High pressure mercury
vapour
Without compensation
High pressure mercury
vapour
With compensation
High pressure sodium
vapour
Without compensation
High pressure sodium
vapour
With compensation
Metal iodide
Without compensation
Metal iodide
With compensation
W
A
60
100
200
300
500
1000
2000
15
20
40
65
100
15
20
40
65
100
250
400
700
1000
250
400
700
1000
250
400
1000
250
400
1000
250
400
700
1000
2000
250
400
700
1000
2000
0.27
0.45
0.91
1.36
2.27
4.5
9.1
0.23
0.37
0.44
0.7
1.5
0.23
0.25
0.3
0.45
0.7
2.13
3.25
5.4
7.5
1.3
2.1
3.6
5.3
3
4.4
10.3
1.45
2.5
5.5
2,17
3,48
6,09
8,7
17,39
1,4
2,0
3,6
5,3
10,6
μF
3.5
4.5
4.5
7
18
20
25
40
60
40
45
100
32
45
65
85
100
IPD INDUSTRIAL PRODUCTS
524
Product Catalogue 2013
MCR
MC0
MC1
MC2
RL
CL00
CL01
CL02
CL25
27
16
8
5
3
1
0
51
32
28
18
8
26
20
20
13
5
5
3
2
1
9
7
5
3
3
2
1
5
4
2
3
2
1
1
0
0
0
0
0
0
37
22
11
7
4
2
1
61
38
33
21
10
32
25
25
14
6
5
3
2
1
9
7
5
3
3
2
1
5
4
2
3
2
1
1
0
6
4
2
2
0
59
35
17
11
7
3
1
79
49
41
26
12
49
38
38
25
9
5
4
2
2
9
7
5
3
4
3
1
5
4
2
4
2
1
1
0
6
5
3
2
0
59
35
17
11
7
3
1
79
49
41
26
12
49
38
38
25
9
6
4
2
2
9
7
5
3
4
3
1
5
4
2
4
3
1
1
1
7
5
3
2
0
59
35
17
11
7
3
1
79
49
41
26
12
49
38
38
25
9
6
4
2
2
11
7
4
3
4
3
1
10
6
3
4
3
1
1
1
7
5
3
2
0
62
40
20
13
8
4
1
88
57
48
30
14
61
48
48
31
11
6
4
2
2
11
7
4
3
4
3
1
10
6
3
4
3
1
1
1
7
5
3
2
1
62
40
20
13
8
4
1
98
61
51
32
16
77
61
61
39
14
8
5
3
2
14
9
5
3
5
4
2
12
7
3
5
3
2
1
1
9
6
3
2
1
70
50
25
17
10
5
2
126
78
66
41
19
94
74
74
47
17
10
6
4
3
18
11
6
4
7
5
2
16
9
4
7
4
2
2
1
11
8
4
3
2
77
60
30
20
12
6
3
155
110
93
58
27
111
87
87
56
21
12
8
5
3
22
14
8
5
9
6
2
20
11
5
9
6
3
2
1
16
11
6
4
2
Phone: 1300 556 601
www.ipdgroup.com.au
GE CONTACTOR SELECTION - LIGHTING CIRCUITS
DIAGRAMS
Single-phase circuit
The total number of lamps will
be as shown in the table.
3-phase circuit,
lamps delta-connected
The total number of lamps will be
as shown in the table,
multiplied by 1.73 and distributed
in three equal quantities.
3-phase circuit,
lamps star-connected
The total number of lamps
will be as shown in the table,
multiplied by 3 and distributed
in three equal quantities.
Maximum number of lamps per phase at 230V
CL04
CL45
CL06
CL07
CL08
CL09
CL10
CK75C
CK08C
CK09
CK95
CK10
CK11
CK12
CK13
77
60
30
20
12
6
3
177
125
105
66
30
119
92
92
59
23
14
9
5
4
31
25
16
10
10
7
3
16
14
7
12
8
4
3
2
21
15
8
6
3
85
66
33
22
12
6
3
224
139
118
74
34
134
103
103
66
23
15
10
6
4
27
17
10
7
11
7
3
25
14
6
12
8
4
3
2
21
15
8
6
3
122
73
36
24
14
7
3
237
147
124
78
36
149
115
115
74
29
18
12
7
5
33
20
12
8
13
9
4
30
17
8
12
8
4
3
2
21
15
8
6
3
156
95
47
31
19
9
4
355
221
186
116
54
191
148
148
95
37
27
18
11
8
49
31
18
12
19
13
6
44
26
12
19
12
7
5
2
32
23
13
8
4
191
116
58
38
23
11
5
390
243
204
127
59
232
180
180
115
45
30
20
12
9
55
34
20
13
21
15
6
49
29
13
21
13
7
5
3
36
25
14
9
5
222
133
66
44
26
13
7
434
270
227
142
66
273
212
212
136
53
33
22
13
9
60
37
22
15
24
16
7
54
31
14
23
14
8
6
3
39
28
15
10
5
264
160
79
53
31
16
8
496
309
260
163
76
312
243
243
155
60
36
24
14
10
66
41
24
16
26
18
7
59
34
16
25
16
9
6
3
43
30
17
11
6
284
170
84
56
33
17
8
553
344
289
181
85
347
270
270
173
67
42
28
17
12
77
48
28
19
30
20
9
69
40
18
29
18
10
7
4
50
35
19
13
7
333
200
99
66
39
20
10
790
490
413
259
121
496
385
385
248
96
60
40
24
17
109
87
54
36
43
29
12
57
51
23
41
26
15
10
5
68
48
34
26
22
410
246
122
81
48
24
12
988
614
516
324
151
621
482
482
310
120
75
49
30
21
156
125
78
52
54
37
16
81
72
33
52
32
18
13
6
97
69
48
37
31
555
333
165
110
66
33
16
1245
774
650
409
190
786
610
610
393
152
95
62
38
27
156
125
78
52
68
46
20
81
72
33
65
41
23
16
8
97
69
48
37
31
820
490
240
165
95
50
25
1770
1090
920
570
270
900
700
700
440
170
136
89
54
39
171
137
86
57
96
66
28
90
80
36
93
58
33
23
12
107
76
53
40
34
1320
790
390
260
155
80
40
2340
1460
1220
770
360
1240
960
960
610
240
181
119
71
51
311
249
156
104
129
88
37
163
145
65
124
78
44
31
16
195
138
96
73
62
1550
930
460
300
185
90
45
2740
1700
1430
900
420
1450
1120
1120
720
280
211
138
83
60
311
249
156
104
150
102
44
163
145
65
145
91
52
36
18
195
138
96
73
62
1860
1120
550
370
220
110
55
3910
2430
2045
1280
600
1740
1350
1350
860
330
302
198
119
86
374
299
187
125
214
146
62
195
174
78
207
129
74
52
26
234
166
115
88
75
1860
1120
550
370
220
110
55
4890
3040
2550
1600
750
1740
1350
1350
860
330
377
247
149
107
467
374
234
156
268
183
78
244
217
98
259
162
92
65
32
292
208
144
110
93
TECHNICAL
CL03
IPD INDUSTRIAL PRODUCTS
Phone: 1300 556 601
15
www.ipdgroup.com.au
Product Catalogue 2013
525
RELAY EQUIVALENT SELECTION CHART
PANASONIC
(National)
FINDER
Compact Miniature Relay
RJ1S
G2R-1-SN
SJ1S-07L
P2RF-05-E
RJ2S
G2R-2-SN
SJ2S-07L
P2RF-08-E
AHN12
AHNA11P
AHN22
AHNA21P
46.61
97.01
46.52
97.02
RU Series
2 POLE Relay DPDT
Base
4 POLE Relay 4PDT
Base
Miniature Rely
RU2S
SY4S-05E1G2
RU4S
SY4S-05E1G2
HC2/HJ2
HC2/HJ2-SFD-K
HC4/HJ4
HC4/HJ4-SFD-K
55.32
94.02
55.34
94.04
RH Series
1 POLE Relay SPDT
Base
2 POLE Relay DPDT
Base
3 POLE Relay 3PDT
Base
4 POLE Relay 4PDT
Base
General Purpose Relay
RH1B
LY1
SH1B-05C
PTF08A-E
RH2B
LY2
SH2B-05C
PTF08A-E
RH3B
LY3
SH3B-05C
PTF11A
RH4B
LY4
SH4B-05C
PTF14A-E
HL1 / HC1
HL2-SFD-K / HC2-SFD-S
HL2 / HC2
HL2-SFD-K / HC2-SFD-S
HC3
HC3-SFD-K
HC4
HC4-TSF-K
56.32
96.02
62.33
92.03
56.34
96.04
RR2KP Series
2 POLE Relay DPDT
Base
Latching Relay
RR2KP
SR3P-05C
G2AK
PYF14A(-E)
-
-
RF1V Series
4 POLE Relay
Base
6 POLE Relay
Base
Safety Relay
RF1V
SF1V-4-07L
RF1V
SF1V-6-07L
-
SFS2 / SFS3
SFS4-SFD
SFS4 / SFS5 / SFS6
SFS6-SFD
-
RV8H Series
Interface Relay + Base
Slim-Line Relay
RV8H
G2RV
-
38.51
RELAY & BASE
IDEC (IPD)
RJ Series
1 POLE Relay SPDT
Base
2 POLE Relay DPDT
Base
OMRON
MY2
PYF08A-E
MY4
PYF14A-E
Note.
This is a guide only for relays that are similar in the market.
Consider physical size and detailed specification before making a final decision.
IPD INDUSTRIAL PRODUCTS
526
Product Catalogue 2013
Phone: 1300 556 601
www.ipdgroup.com.au
Download