SPDSG50-300 Spark Gap Class I Lightning Arrester (Single Phase, 1 Mode, 300vac, 50kA I imp, (10/350us ) SPECIFICATION AND INSTALLATION INSTRUCTIONS FEATURES • • • 1 mode protection (L-E or L-N) Compact solution for primary direct strike protection 2 wide Din 43880 form factor Applications • High risk, point of entry systems SPECIFICATIONS Model Technology Encapsulated Spark Gap Method of mounting 35mm Din rail Input voltage (Un) 230vac nominal Max Continuous Voltage (Mcov) 300vac Test classification IEC Class I Maximum rated surge current – (I imp) 10/350us Max rated surge current – (Imax) 8/20us 140kA Residual voltage (Vpl) <2.5KV 50kA Leakage current None Response time <100ns External disconnector max 160A gL Terminations Insulation resistance Enclosure material Enclosure rating Applicable standards. Dimensions Weight Environment Warranty FUNCTIONAL DESCRIPTION SPDSG50-300 35mm multi-strand > 103 M Ohm Thermo plastic. UL94-V0 IP20 IEC61643-1:2001 35mm (W) x 100mm (H) x 77mm (D) The SPDSG50-300 is designed to protect single phase power systems against damage from surges and spikes caused by lightning and other electrical sources. The unit is intended for high risk point-ofentry protection and is connected in parallel with the power system via HRC fuses if no other adequate over protection is present. Check that the model you have purchased is rated correctly for your power system. . WARRANTY Eaton warrants this unit against faulty parts and workmanship for a period of 5 years from the date of purchase. If this product fails to operate correctly, please contact your Eaton representative. This warranty doesn’t cover neglect or intentional misuse. As this product is intended for use in electrically harsh environments no claim is made of suitability for purpose. 200 grams -40c to +80c For installation details, see over page. 5 years Specification are subject to change without notice. Copyright 2010 Eaton Industries Pty Ltd Technical Specification –SPDSG50-300 Tvss Doc# 51xxxx Page 1 of 2 • INSTALLATION PROCEDURE: 1. CHECK • Always work safely – disconnect power before making connections. • All wiring must be carried out by suitably qualified personnel according to the applicable standards. • Check for correct operating voltage and power system. This model (SPDSG50-300) is designed for power systems in the range of 220-255vac. If your power system is a different voltage, this model is not suitable. Please contact your supplier. • Always use the correct size HRC fuses. • For services >160A, use 160A fuses maximum. For services <160A, fuse at a level lower than than the service size. • Always use Gg or Gl-rated fuses. Do not use delay types or ‘semiconductor’ fuses. 2. INSTALL • Locate a fuse position as close as possible to the Main Switch. • Install fuse holders or fuse-switch if required. • Locate a suitable position for the SPD, ensuring adequate space for cables. Do not install above heat-generating objects or in any position that is exposed to weather. 3. CONNECT • Connect wiring - refer to connection diagrams. If using stranded cable, always use wire ferrules for lowest resistance and to prevent damage to the wire. • Keep termination length as short as possible. Do not wire in extra loops or cable length. 4. Earth connections from the unit to earth link MUST be as short as possible. Failure to consider the above points can result in improper operation of the unit and possible damage to the installation. NOTES: • 160A fuses are rated such for maximum surge rating. On services below 160A, high-level surges may cause disconnection of the supply. • Wiring from fuse to SPD is carrying surge currents only, not load current. This means that smaller cables may be used than is normal for the current rating. • If using under-sized cables, some energy authorities require double insulation (i.e. sleeving) of the cables. • Unplug the alarm connector for termination. • Do not Megger test cabling with unit connected – unit may be damaged. EARTHING For proper operation, all surge diverters rely upon a good earth connection: • The main earth wire (from earth link on switchboard to ground rod or system) MUST be as short and direct as possible. Extra cable must not be looped. Specification are subject to change without notice. Copyright 2010 Eaton Industries Pty Ltd Technical Specification –SPDSG50-300 Tvss Doc# 51xxxx Page 2 of 2