ULTREX®, Technical

advertisement
®
ULTREX
PVC/Nylon and XLPE Insulated
Tray Cables
ULTREX®® Tray Cables
UL Type TC, 600 Volt
Power and Control Cables
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
ULTREX®® VN
PVC/Nylon Insulated, PVC Jacketed
Applications and Description . . .
18 AWG Unshielded . . . . . . . .
18 AWG Shielded . . . . . . . . . .
16 AWG Unshielded . . . . . . . .
16 AWG Shielded . . . . . . . . . .
14 AWG Unshielded . . . . . . . .
14 AWG Shielded . . . . . . . . . .
12 AWG Unshielded . . . . . . . .
12 AWG Shielded . . . . . . . . . .
10 AWG Unshielded . . . . . . . .
10 AWG Shielded . . . . . . . . . .
3 Conductors with Ground . . . .
4 Conductors with Ground . . . .
Dupont — Construction . . . . . . .
Dupont Composite Construction .
Dow Composite Construction. . .
Composite Cables . . . . . . . . . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.3
.4
.5
.6
.7
.8
.9
10
11
12
13
14
15
16
17
18
19
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
20
21
22
23
24
25
ULTREX®® XL - XLTC
XLP Insulated, PVC Jacketed
Applications and Description .
14 AWG Unshielded . . . . . .
12 AWG Unshielded . . . . . .
10 AWG Unshielded . . . . . .
3 Conductors with Ground . .
4 Conductors with Ground . .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Conductor or Phase Identification . . . . . . . . . . . . . . . . . . . . . . 26
Notices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
1-866-663-9267
1
Introduction
Nexans brings energy to life through an extensive range of cables and cabling solutions that deliver
impeccable performance for our customers worldwide. With more than a century of experience in cable
manufacturing, you can rely on the quality of Nexans’ products.
Our teams are committed to a partnership approach that supports customers in four main business
areas: Power transmission and distribution (Submarine and Land), Energy resources (Oil & Gas,
Mining and Renewables), Transportation (Road, Rail, Air, Sea) and Building (Commercial,
Residential, Industrial and Data Centers).
Nexans’ strategy is founded on continuous innovation in products, solutions and services, employee
development, customer training and the introduction of safe, low-environmental-impact industrial
processes. In 2013, Nexans became the first cable manufacturer to create a Foundation to introduce
sustained initiatives for access to energy for disadvantaged communities worldwide.
This catalog has been prepared for the convenience of those using electrical conductors in industrial
applications. The information included in the many tabulations will be of particular value to the
architect, engineer, electrician, and layperson alike. For your convenience, we have referenced
applicable Articles and Tables from the NEC.
All the cables in this catalog are LEAD FREE. This indicates that the Nexans cable components have less
than 300 ppm of lead, which is well below the 1000 ppm level indicated in RoHS (restriction of
hazardous substances) regulations and below the level requiring labeling by California Proposition
#65.
1-866-663-9267
2
ULTREX®®VN
PVC/Nylon Type TC or TC-ER 600 Volt
Power and Control Cable
°
/ wet rated
Temperature rating of 90°C dry
Applications
Nexans 600 V ULTREX® VN Tray Cables
are listed as type TC or TC-ER under UL
1277 Electrical Power and Control Cables.
These cables may be installed in wet or
dry locations; in cable trays, raceways and
open air; and are suitable for exposure
to weather, direct burial and for Class
I, Div. 2 (also Zone 2) and Class II, Div.
2 hazardous locations per NEC. Cables
with 3 or more conductors are UL listed
for exposed runs (ER) when installed in
accordance with NEC Article 336.10(7).
Construction
Conductor: bare, annealed copper
conforming to ASTM B3 and Class B
stranded in accordance to ASTM B8, from
18 AWG to 500 kcmil. Compressed
copper for 14 AWG through 500 kcmil.
Insulation: flame-retardant PVC/Nylon
type THHN/THWN-2 per UL 83 for sizes
14 AWG to 500 kcmil and type TFN per
UL 66 for 18 AWG and 16 AWG.
Assembly :
Non-shielded: cables with 3 or more
conductors are cabled in concentric layers
with interstices filled with suitable fillers,
as required. Two-conductor cables are
supplied in a flat/parallel configuration.
Ground wires are sized as required by UL
1277 (refer to the applicable product tables
for the standard sizes provided). Sizes
14 AWG to 6 AWG have an insulated
green ground wire. Sizes 4 AWG and
larger have a bare ground wire. Where
necessary, a binder tape of synthetic
material assembles the core in a tight
circular configuration.
Shielded : cabled in concentric layers with
interstices filled with suitable fillers as
required. A helically wrapped aluminum
tape, with synthetic backing, gives 100%
shielding. A tinned copper drain wire is
placed in contact with the aluminum side
of the tape, to lower the resistance and to
assist in the termination of the shield.
Jacket: UL listed sunlight and moisture
resistant, black, flame retardant polyvinyl
chloride (PVC) material meeting the
requirements of UL 1277. A Nylon ripcord
is included for ease of jacket removal.
Jacket surface is printed with required UL
/ NEC code information and sequential
footage markings.
Sample Print Legend: NEXANS-C
ULTREX-VN 600V TC-ER 3/C-12AWG
THHN/THWN-2 SUN RES DIR BUR (UL)
ROHS MFG DATE
Conductor Identification
(See page 26 of this catalog)
18 AWG to 10 AWG: Color coded
per Method #1-E2 per ICEA S-73-532
8 AWG to 500 kcmil: black with number
coding per Method 4 of ICEA S-73-532
Composite
Power:
Black with number coding per Method 4
of ICEA S-73-532
Control:
Color coded per Method #1-E2 per ICEA
S-73-532
Specifications
• Meets UL 1277: Power and Control Tray
Cables with Optional Fiber Members.
• Meets UL 83: Thermoplastic-Insulated Wires
and Cables for 14 AWG and larger.
• Meets UL 66: Fixture Wire for 18 AWG
and 16 AWG.
• Meets ICEA S-95-658, NEMA Publication
No. WC-70: Non-Shielded Power Cables
rated 2000 volts or Less for the Distribution
of Electrical Energy.
• Dupont constructions meet Dupont
Engineering Specification SE33.4B: “600-Volt
Multiconductor Type TC Cable; THWNTHHN or TFN Insulated and with Vinyl Jacket”
Product Features
• UL approved cables Type TC or TC-ER, 600 V.
• UL approved insulated conductors.
• Cables pass UL 1685 and IEEE 383 vertical
tray fire tests at 70,000 BTU/hr.
• Cables are UL listed to IEEE 1202 and FT4
70,000 BTU/hr flame test.
1-866-663-9267
3
• For use in power, lighting, control and signal
circuits.
• Can be used within industrial establishments
where serviced by qualified personnel and
not subject to physical damage.
• Can operate at continuous temperatures of
90°°C dry and wet.
• Cold bend of –25°C per UL 1277.
• Can be used In Class I Division 2 and Class
II Division 2 Hazardous Locations and
Intrinsically Safe applications as permitted
by NEC Articles 392, 501, 502, 503,
and 505.*
• As indicated in UL 1277: The overall jackets
of these cables are a “gas/vapor tight
continuous sheath” as discussed in NEC
Article 501.15(D) & (E).*
• For use in cable trays, raceways, conduits,
or for aerial applications where installed
with a messenger.
• For Direct Burial applications.
• Cables of 2 or more conductors (plus a
ground conductor) are UL listed for Exposed
Run (ER) per NEC Article 336.10(7):
1) Cables sized from 18 AWG to 6 AWG
have an insulated ground conductor.
2) Cables sized 4 AWG and larger have a
bare ground conductor.
• As permitted in NEC Article 725 for Class
1 circuits.
alarm
• As permitted for non-power-limited
circuits as defined in NEC Article 760.
• Lead free and RoHS compliant
• Sunlight and moisture resistant
Options
The following constructions can be provided on
special orders:
• Cables sized 4 AWG and larger with an
insulated ground conductor
• Dow Construction
• DuPont Construction
• Composite Cable Construction
• Insulated or bare ground wires
• Different conductor
methods
* Use in hazardous locations:
Please note that no investigation of these cables has
been performed regarding the transmission of gases
or vapors through the core. When these cables are
used in hazardous locations they should be sealed
properly as required by the NEC.
ULTREX®® VN
UL 1277
UL 66
ICEA S-73-532 (Conductor Identification Only)
Unshielded Tray Cable
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Multiconductor 18 AWG Type TFN
Insulation Thickness:
15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering
Part
# of
Number
Conduct ors
697151
697359
697169
627448
627273
627281
-------627901
669127
-------697367
--------------697177
697375
-------697383
-------626994
----------------------
2 Flat
3
4
5
6
7
8
9
10
11
12
13
14
15
19
20
25
30
37
40
45
50
Jacket
Diamet er
A pproximat e Net
Thickness
over Jacket
Cable Weight
mils
inches
lb/kft
amps
45
45
45
45
45
45
45
45
45
45
45
45
45
45
60
60
60
60
60
60
60
80
0.180 x0.270
0.288
0.311
0.337
0.364
0.364
0.392
0.421
0.448
0.454
0.468
0.476
0.491
0.504
0.574
0.590
0.658
0.701
0.754
0.782
0.867
0.898
35
45
54
66
76
82
92
108
117
122
131
139
148
184
210
217
272
308
380
397
442
516
6.0
6.0
4.8
4.8
4.8
4.2
4.2
4.2
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.7
2.7
2.4
2.4
2.1
2.1
A mpacit y
Mininum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation pull-in
.
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
• Ampacities are in accordance with NEC Article 336.80, and Table 402.5 “Allowable Ampacity for Fixture Wires” at an
° (with no load diversity). Ampacity for cables having more than three conductors have been derated
ambient temperature of 30°C
as stated in NEC Article 392.80(A), using the derating factors of NEC Table 310.15(B)(3)(a).
• For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
• Refer to NEC Article 240.4(D) for overcurrent protection requirements.
1-866-663-9267
4
ULTREX®® VN
UL 1277
UL 66
ICEA S-73-532 (Conductor Identification Only)
Shielded Tray Cable
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Multiconductor 18 AWG Type TFN
Insulation Thickness: 15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering
Drain Wire: 20 AWG (7w) Tinned Copper
Part
# of
Number
Conduc t ors
697409
697417
627059
-------627067
674689
627521
-------674697
-------697458
-----------------------------------675751
------------------------------------
2
3
4
5
6
7
8
9
10
11
12
13
14
15
19
20
25
30
37
40
45
50
Jac ket
Diamet er
A pproximat e Net
Thic kness
over Jac ket
Cable Weight
mils
inches
lb/kft
amps
45
45
45
45
45
45
45
45
45
45
45
45
45
45
60
60
60
60
60
60
80
80
0.280
0.294
0.317
0.343
0.370
0.370
0.404
0.433
0.460
0.466
0.480
0.488
0.503
0.516
0.586
0.602
0.670
0.713
0.766
0.794
0.879
0.910
38
49
58
73
82
87
98
112
127
130
136
144
153
165
215
272
280
318
390
407
452
526
6.0
6.0
4.8
4.8
4.8
4.2
4.2
4.2
3.0
3.0
3.0
3.0
3.0
3.0
3.0
3.0
2.7
2.7
2.4
2.4
2.1
2.1
A mpac it y
Mininum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during. installation pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
• Ampacities are in accordance with NEC Article 336.80, and Table 402.5 “Allowable Ampacity for Fixture Wires” at an
ambient temperature of 30°C
° (with no load diversity). Ampacity for cables having more than three conductors have been derated
as stated in NEC Article 392.80(A), using the derating factors of NEC Table 310.15(B)(3)(a).
• For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
• Refer to NEC Article 240.4(D) for overcurrent protection requirements.
1-866-663-9267
5
ULTREX® VN
UL 1277
UL 66
ICEA S-73-532 (Conductor Identification Only)
Unshielded Tray Cable
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Multiconductor 16 AWG Type TFN
Insulation Thickness:
15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering
Part
# of
Number
Conduct ors
697045
697052
631010
697342
697060
697078
697086
697094
697102
-------697110
--------------671784
697128
697136
627463
697144
697896
697664
--------------627471
2 Flat
3
4
5
6
7
8
9
10
11
12
13
14
15
16
19
20
25
30
37
40
45
50
Jacket
Diamet er
A pproximat e Net
Thickness
over Jacket
Cable Weight
mils
45
45
45
45
45
45
45
45
45
45
45
45
60
60
60
60
60
60
60
80
80
80
80
inches
0.190 x0.290
0.306
0.330
0.360
0.390
0.390
0.425
0.452
0.480
0.486
0.505
0.510
0.556
0.570
0.594
0.610
0.640
0.715
0.765
0.864
0.893
0.943
0.980
lb/kft
45
59
71
86
100
110
128
141
157
165
179
205
219
232
240
283
300
367
430
548
584
649
689
A mpacit y
amps
8.0
8.0
6.4
6.4
6.4
5.6
5.6
5.6
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
3.6
3.6
3.2
3.2
2.8
2.8
Mininum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation
.
pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
• Ampacities are in accordance with NEC Article 336.80, and Table 402.5 “Allowable Ampacity for Fixture Wires” at an
° (with no load diversity). Ampacity for cables having more than three conductors have been derated
ambient temperature of 30°C
as stated in NEC Article 392.80(A), using the derating factors of NEC Table 310.15(B)(3)(a).
• For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
• Refer to NEC Article 240.4(D) for overcurrent protection requirements.
1-866-663-9267
6
ULTREX®® VN
UL 1277
UL 66
ICEA S-73-532 (Conductor Identification Only)
Shielded Tray Cable
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Multiconductor 16 AWG Type TFN
Insulation Thickness:
15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering
Drain Wire: 18 AWG (7w) Tinned Copper
Part
# of
Number
Conduc t ors
697466
627091
627083
631127
687491
631135
----------------------------697441
---------------------627109
--------------------------------------------------
2
3
4
5
6
7
8
9
10
11
12
13
14
15
19
20
25
30
37
40
45
50
Jac ket
Diamet er
A pproximat e Net
Thic kness
over Jac ket
Cable Weight
mils
45
45
45
45
45
45
45
45
45
45
60
60
60
60
60
60
60
60
80
80
80
80
inches
0.298
0.314
0.339
0.368
0.398
0.398
0.435
0.467
0.497
0.504
0.549
0.558
0.575
0.589
0.634
0.652
0.727
0.775
0.885
0.905
0.955
0.989
lb/kft
51
67
80
96
111
120
136
149
165
173
187
213
229
242
301
310
377
440
568
604
669
743
A mpac it y
amps
8.0
8.0
6.4
6.4
6.4
5.6
5.6
5.6
4.0
4.0
4.0
4.0
4.0
4.0
4.0
4.0
3.6
3.6
3.2
3.2
2.8
2.8
Mininum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation
.
pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
• Ampacities are in accordance with NEC Article 336.80, and Table 402.5 “Allowable Ampacity for Fixture Wires” at an
° (with no load diversity). Ampacity for cables having more than three conductors have been derated
ambient temperature of 30°C
as stated in NEC Article 392.80(A), using the derating factors of NEC Table 310.15(B)(3)(a).
• For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
• Refer to NEC Article 240.4(D) for overcurrent protection requirements.
1-866-663-9267
7
ULTREX®® VN
UL 1277
UL 83
ICEA S-73-532 (Conductor Identification Only)
Unshielded Tray Cable
UL Type TC or TC-ER, 600 V, 90 °C dry / wet rated
Multiconductor 14 AWG Type THHN/THWN-2
Insulation Thickness:
15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering
Jac ket
Diamet er over
A pproximat e Net
Thic kness
Jac ket
Cable Weight
2 Flat
3
mils
45
45
inches
.205 x .315
0.336
lb/kft
58
77
amps
25.0
25.0
4
5
6
7
8
9
10
11
12
13
14
15
16
19
20
25
30
37
40
45
50
45
45
45
45
45
45
60
60
60
60
60
60
60
60
60
60
80
80
80
80
80
0.365
0.397
0.431
0.431
0.466
0.502
0.566
0.574
0.591
0.601
0.620
0.636
0.653
0.687
0.707
0.792
0.886
0.953
0.988
1.05
1.08
96
117
137
152
175
195
232
250
266
287
307
326
343
396
417
518
638
774
833
928
972
20.0/25.0(1)
20.0
20.0
17.5
17.5
17.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
11.3
11.3
10.0
10.0
8.8
8.8
Part
# of
Number
Conduc t ors
696815
696823
696831
696849
667055
696807
676700
696856
696864
-------696872
---------------------631002
696880
696898
696906
627299
696914
--------------697326
A mpac it y
Mininum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation
.
pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C
° rated conductors. Ampacities for cables having more than three conductors have been derated per NEC
temperature and 90°C
Table 310.15(B)(3)(a).
• For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310 .15(B)(16).
• NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG copper conducts after any
correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in
NEC Article 240.4(E) through (G).
(1)
Where the 4th conductor is the neutral of a balanced 3 phase system.
1-866-663-9267
8
ULTREX®® VN
UL 1277
UL 83
ICEA S-73-532 (Conductor Identification Only)
Shielded Tray Cable
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Multiconductor 14 AWG Type THHN/THWN-2
Insulation Thickness:
15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering
Drain Wire: 16 AWG (7w) Tinned Copper
Part
# of
Number
Conduc t ors
697698
627117
627794
631085
-------627125
----------------------------631101
----------------------------631119
--------------------------------------------------
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
19
20
25
30
37
40
45
50
Jac ket
Diamet er
A pproximat e Net
Thic kness
over Jac ket
Cable Weight
mils
inches
lb/kft
amps
45
45
45
45
45
45
45
60
60
60
60
60
60
60
60
60
60
60
80
80
80
80
80
0.324
0.342
0.371
0.403
0.437
0.437
0.478
0.514
0.578
0.586
0.603
0.613
0.632
0.648
0.665
0.699
0.719
0.804
0.898
0.965
1.00
1.06
1.10
69
86
107
128
148
163
186
206
243
261
283
298
318
337
358
413
432
529
653
789
848
943
1033
25.0
25.0
A mpac it y
20.0/25.0(1)
20.0
20.0
17.5
17.5
17.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
11.3
11.3
10.0
10.0
8.8
8.8
Mininum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation
.
pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C
° rated conductors. Ampacities for cables having more than three conductors have been derated per NEC
temperature and 90°C
Table 310.15(B)(3)(a).
• For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
• NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG copper conductors after any
correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in
NEC Article 240.4(E) through (G).
(1)
Where the 4th conductor is the neutral of a balanced 3 phase system.
1-866-663-9267
9
ULTREX®® VN
UL 1277
UL 83
ICEA S-73-532 (Conductor Identification Only)
Unshielded Tray Cable
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Multiconductor 12 AWG Type THHN/THWN-2
Insulation Thickness:
15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering
Part Number
696955
696963
696971
697292
------697300
------696989
696997
------697003
------------------697001
697318
697029
697037
688770
627455
-------------------
# of
Conduc t ors
2 Flat
3
4
5
6
7
8
9
10
11
12
13
14
15
16
19
20
25
30
37
40
45
50
Jac ket
Diamet er over
A pproximat e Net
Thic kness
Jac ket
Cable Weight
mils
inches
lb/kft
amps
45
45
45
45
45
45
45
60
60
60
60
60
60
60
60
60
60
80
80
80
80
80
80
.225 x .359
0.376
0.408
0.448
0.488
0.488
0.559
0.601
0.641
0.650
0.670
0.682
0.704
0.723
0.742
0.782
0.806
0.945
1.01
1.09
1.13
1.19
1.24
77
105
126
166
196
215
253
296
328
357
376
414
443
470
490
573
582
778
915
1107
1216
1358
1497
30.0
30.0
24.0/30.0(1)
24.0
24.0
21.0
21.0
21.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
13.5
13.5
12.0
12.0
10.5
10.5
A mpac it y
Mininum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation
.
pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C
° rated conductors. Ampacities for cables having more than three conductors have been derated per NEC
temperature and 90°C
Table 310.15(B)(3)(a).
• For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
• NEC Article 240.4(D) requires that overcurrent protection not exceed 20 amperes for 12 AWG copper conductors after any
correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in
NEC Article 240.4(E) through (G).
(1)
Where the 4th conductor is the neutral of a balanced 3 phase system.
1-866-663-9267
10
ULTREX®® VN
UL 1277
UL 83
ICEA S-73-532 (Conductor Identification Only)
Shielded Tray Cable
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Multiconductor 12 AWG Type THHN/THWN-2
Insulation Thickness:
15 mils / 0.38 mm PVC, 4 mils / 0.10 mm Nylon Covering
Drain Wire: 16 AWG (7w) Tinned Copper
Jac ket
Diamet er
A pproximat e Net
Thic kness
over Jac ket
Cable Weight
2
3
mils
45
45
inches
0.368
0.388
lb/kft
89
117
amps
30.0
30.0
4
5
6
7
8
9
10
11
12
13
14
15
16
19
20
25
30
37
40
45
50
45
45
45
45
60
60
60
60
60
60
60
60
60
60
60
80
80
80
80
80
80
0.423
0.460
0.500
0.500
0.572
0.614
0.654
0.663
0.683
0.695
0.717
0.736
0.755
0.795
0.819
0.958
1.02
1.10
1.14
1.21
1.25
147
183
208
227
265
316
345
369
400
426
455
482
502
585
627
790
927
1119
1228
1370
1509
24.0/30.0(1)
24.0
24.0
21.0
21.0
21.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
13.5
13.5
12.0
12.0
10.5
10.5
Part
# of
Number
Conduc t ors
631044
627539
631051
690032
------631069
------688929
------------631077
-------------------------------------------------------------------------
A mpac it y
Mininum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation
.
pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C
temperature and 90°C
° rated conductors. Ampacities for cables having more than three conductors have been derated per NEC
NEC Table 310.15(B)(3)(a).
• For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
• NEC Article 240.4(D) requires that overcurrent protection not exceed 20 amperes for 12 AWG copper conductors after any
correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in
NEC Article 240.4(E) through (G).
(1)
Where the 4th conductor is the neutral of a balanced 3 phase system.
1-866-663-9267
11
ULTREX®® VN
UL 1277
UL 83
ICEA S-73-532 (Conductor Identification Only)
Unshielded Tray Cable
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Multiconductor 10 AWG Type THHN/THWN-2
Insulation Thickness:
20 mils / 0.51 mm PVC, 4 mils / 0.10 mm Nylon Covering
Jac ket
Diamet er
A pproximat e Net
Thic kness
over Jac ket
Cable Weight
2 Flat
3
mils
45
45
inches
0.260 x 0.428
0.448
lb/kft
112
159
amps
40
40
4
5
6
7
8
9
10
11
12
13
14
15
16
19
20
25
30
37
40
45
50
45
60
60
60
60
60
60
60
60
80
80
80
80
80
80
80
80
80
80
80
80
0.490
0.568
0.617
0.617
0.668
0.721
0.770
0.782
0.807
0.862
0.890
0.913
0.938
0.987
1.02
1.14
1.22
1.32
1.37
1.45
1.51
200
263
324
346
397
459
488
530
572
646
735
780
795
914
954
1178
1394
1693
1824
2040
2253
32/40(1)
32
32
28
28
28
20
20
20
20
20
20
20
20
20
18
18
16
16
14
14
Part
# of
Number
Conduc t ors
696922
696930
697284
688309
------696948
------627646
------------627257
-------------------------------------------------------------------------
A mpac it y
Mininum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation
.
pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C
temperature and 90°C
° rated conductors. conductors. Ampacities for cables having more than three conductors have been derated
per NEC Table 310.15(B)(3)(a).
• For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
• NEC Article 240.4(D) requires that overcurrent protection not exceed 30 amperes for 10 AWG copper conductors after any
correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in
NEC Article 240.4(E) through (G).
(1)
Where the 4th conductor is the neutral of a balanced 3 phase system.
1-866-663-9267
12
ULTREX®® VN
UL 1277
UL 83
ICEA S-73-532 (Conductor Identification Only)
Shielded Tray Cable
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Multiconductor 10 AWG Type THHN/THWN-2
Insulation Thickness: 20 mils / 0.51 mm PVC, 4 mils / 0.10 mm Nylon Covering
Drain Wire: 16 AWG (7w) Tinned Copper
Jac ket
Diamet er
A pproximat e Net
Thic kness
over Jac ket
Cable Weight
2
3
mils
45
45
inches
0.428
0.454
lb/kft
127
169
amps
40
40
4
5
6
7
8
9
10
11
12
13
14
15
16
19
20
25
30
37
40
45
50
45
60
60
60
60
60
60
60
80
80
80
80
80
80
80
80
80
80
80
80
80
0.496
0.574
0.623
0.623
0.683
0.736
0.785
0.797
0.862
0.877
0.905
0.928
0.953
1.02
1.03
1.16
1.24
1.33
1.38
1.47
1.52
207
278
322
363
409
456
503
545
625
661
750
795
848
925
970
1190
1410
1710
1840
2055
2270
32/40(1)
32
32
28
28
28
20
20
20
20
20
20
20
20
20
18
18
16
16
14
14
Part
# of
Number
Conduc t ors
631028
------631036
690057
------------------------------------689679
-------------------------------------------------------------------------
A mpac it y
Mininum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation
.
pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C
° rated conductors. Ampacities for cables having more than three conductors have been derated per NEC
temperature and 90°C
Table 310.15(B)(3)(a).
• For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
• NEC Article 240.4(D) requires that overcurrent protection not exceed 30 amperes for 10 AWG copper conductors after any
correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in
NEC Article 240.4(E) through (G).
(1)
Where the 4th conductor is the neutral of a balanced 3 phase system.
1-866-663-9267
13
ULTREX®® VN
UL 1277
UL 83
ICEA S-95-658
ICEA S-73-532 (Conductor Identification Only)
Unshielded Tray Cable
UL Type TC-ER, 600 V, 90°C dry / wet rated
3 Conductors Type THHN/THWN-2 with Ground
Part
Conduct or
Ground Insulat ion Thickness
Jacket
Diamet er
Size
PV C/Nylon
AWG or kcmil
AWG
mils
mils
inches
lb/kft
amps
664995
14
14
15/4
45
0.350
90
25(1)
685578
12
12
15/4
45
0.368
126
30(1)
10
10
8
8
6
6
6
6
4
4
4
3
2
20/4
30/5
30/5
40/6
40/6
50/7
50/7
50/7
50/7
50/7
60/8
60/8
60/8
45
60
60
80
80
80
80
80
80
80
110
110
110
0.450
0.610
0.725
0.857
0.986
1.11
1.21
1.30
1.41
1.53
1.74
1.96
2.23
202
302
422
647
963
1156
1451
1738
2122
2576
3128
4347
5819
40(1)
55
75
95
130
150
170
195
225
260
290
350
430
665000
10
680747
8
680749
6
658948*
4
658955*
2
680752
1
658963*
1/0
665018
2/0
216341
3/0
665026
4/0
665034
250
665042
350
665059
500
* DOW construction cables.
Cable Weight
A mpacit y
Size
Number
Thickness over Jacket
A pproximat e Net
Mininum Bending Radius: 5 x overall diameter installed
Bend Radius :
7.5 x overall diameter during installation
.
pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C
° rated conductors.
temperature and 90°C
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
(1)
NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG,
and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors
have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G).
* DOW construction means:
• Control conductors are color coded – E2 (See chart page 26)
• Power conductors are black with numbers – M4 (See chart page 26)
• fillers where applicable
1-866-663-9267
14
ULTREX®® VN
Unshielded Tray Cable
UL Type TC-ER, 600 V, 90°C dry / wet rated
UL 1277
UL 83
ICEA S-95-658
ICEA S-73-532 (Conductor Identification Only)
4 Conductors Type THHN/THWN-2 with Ground
Part
Number
680748
680750
697581
680754
------680753
669143*
------669275
------669283*
669291*
Conductor
Ground
Insulation Thickness
Jacket
Diameter
Approximate Net
Size
Size
PVC/Nylon
Thickness
over Jacket
Cable Weight
AWG or kcmil
AWG
mils
mils
inches
lb/kft
amps
amps(1)
8
6
4
2
1
1/0
2/0
3/0
4/0
250
350
500
10
8
8
6
6
6
6
4
4
4
3
2
30/5
30/5
40/6
40/6
50/7
50/7
50/7
50/7
50/7
60/8
60/8
60/8
60
60
80
80
80
80
80
80
110
110
110
110
0.661
0.796
0.957
1.10
1.25
1.31
1.45
1.58
1.77
1.94
2.18
2.49
353
516
804
1108
1519
1811
2288
2756
3437
4046
5480
7574
44
60
76
104
120
136
156
180
208
232
280
344
55
75
95
130
150
170
195
225
260
290
350
430
Ampacity
* DOW construction cables
Mininum Bending Radius : 5 x overall diameter installed
7.5 x overall diameter during installation
.
pull-in
Notes:
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C
° rated conductors. Ampacities for cables having more than three conductors have been derated per NEC
temperature and 90°C
Table 310.15(B)(3)(a).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
(1)
Where the 4th conductor is the neutral of a balanced 3 phase system.
* DOW construction means:
• Control conductors are color coded – E2 (See chart page 26)
• Power conductors are black with numbers – M4 (See chart page 26)
•
where applicable
1-866-663-9267
15
ULTREX®® VN
Unshielded Tray Cable - DuPont Construction*
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Part
# of
Number
Conduc t ors
UL 1277
UL 83
ICEA S-95-658
ICEA S-73-532 (Conductor Identification Only)
Dupont SE33.4B
Jac ket
Diamet er
A pproximat e Net
Thic kness
over Jac ket
Cable Weight
mils
inches
lb/kft
A mpac it y
amps(2)
Multiconductor 14 A WG Type THHN/THWN-2
Insulation Thickne ss: 15 mils / 0. 38 mm PVC, 4 mils /0 . 10 mm Nylon Cove ring
697821
2
45
0.207x0.320
57
627505
3
45
0.370
79
631192
4
45
0.373
99
684738
5
45
0.395
119
697839
7
45
0.439
152
627653
9
45
0.510
200
631523
19
60
0.690
400
25.0
25.0
20/25(1)
20.0
17.5
17.5
12.5
Multiconductor 12 A WG Type THHN/THWN-2
Insulation Thickne ss: 15 mils / 0. 38 mm PVC, 4 mils /0 . 10 mm Nylon Cove ring
631168
2
45
0.225x0.355
77
631515
3
45
0.384
108
631176
4
45
0.419
137
684688
7
45
0.490
217
30.0
30.0
24/30(1)
21.0
Multiconductor 10 A WG Type THHN/THWN-2
Insulation Thickne ss: 20 mils / 0. 51 mm PVC, 4 mils / 0. 10 mm Nylon Cove ring
------2
45
0.261x0.428
112
627224
3
45
0.456
158
627232
4
45
0.498
202
627828
7
60
0.613
348
Multiconductor 8 A WG Type THHN/THWN-2
Insulation Thickne ss: 30 mils /0 . 76 mm PVC, 5 mils /0 . 13 mm Nylon Cove ring
627166
2
60
0.560
202
697870
3
60
0.588
254
697904
4
60
0.644
324
Multiconductor 6 A WG Type THHN/THWN-2
Insulation Thickne ss: 30 mils /0 . 76 mm PVC, 5 mils /0 . 13 mm Nylon Cove ring
627513
2
60
0.636
293
697862
3
60
0.680
363
627968
4
60
0.741
469
Multiconductor 4 A WG Type THHN/THWN-2
Insulation Thickne ss: 40 mils / 1. 02 mm PVC, 6 mils / 0. 15 mm Nylon Cove ring
627943
3
80
0.866
588
627950
4
80
0.950
757
Multiconductor 2 A WG Type THHN/THWN-2
Insulation Thickne ss: 40 mils / 1. 02 mm PVC, 6 mils /0 . 15 mm Nylon Cove ring
684837
3
80
0.982
889
684894
4
80
1.09
1114
1-866-663-9267
16
40.0
40.0
32/40(1)
28.0
55.0
55.0
55(1)
75.0
75.0
75(1)
95.0
95(1)
130.0
130(1)
ULTREX®® ULVN
1277
UL 83
ICEA S-95-658
ICEA S-73-532 (Conductor Identification Only)
Dupont SE33.4B
Unshielded Tray Cable - DuPont Construction* - (continued)
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Composite Conductors Type THHN/THWN-2 with Insulated Ground
Composite - 4 Control Conductors with 3 Power Conductors and 1 Insulated Ground
Part
Number
697813
697805
Control
Size
Insulation
Thickness
PVC/Nylon
Power
Size
Insulation
Thickness
PVC/Nylon
Ground
Jacket
Size
Thickness
Diameter Approximate
Over
Net Cable
Jacket
Weight
Control
Power
Ampacity Ampacity
AWG
mils
AWG
mils
AWG
mils
inches
lb/kft
amps
amps
14
14
45
45
12
10
45
45
12
10
60
60
0.515
0.575
220
288
17.5
17.5
21.0
28.0
Mininum Bending Radius : 5 x overall diameter installed
7.5 x overall diameter during installation
.
pull-in
Notes for DuPont Constructions:
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
(1)
Where the 4th conductor is the neutral of a balanced 3 phase system.
(2)
°
Conductor ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C
° rated conductors. Ampacities for cables having more
ambient temperature and 90°C
. than three conductors have been derated
per NEC Table 310.15(B)(3)(a).
• For correction factors for different ambient temperatures and ampacitities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
• NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG,
and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors
have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G).
*Dupont construction means:
• Conductor
black insulation with white print – numbered conductors (Method 4). See chart on page 26.
– where applicable
• Nylon
• Mylar tape around core
1-866-663-9267
17
ULTREX®® VN
UL 1277
UL 83
ICEA S-95-658
ICEA S-73-532 (Conductor Identification Only)
Unshielded Tray Cable - Dow Construction*
UL Type TC -ER, 600 V, 90°C dry / wet rated
Composite Conductors Type THHN/THWN-2 with Ground
Composite - 4 Control Conductors with 3 Power Conductors and 1 Ground
Part
Number
680759
658872
658880
658898
658906
658914
Control
Size
Insulation
Thickness
PVC/Nylon
Power
Size
Insulation
Thickness
PVC/Nylon
Ground
Jacket
Size
Thickness
Diameter Approximate
Over
Net Cable
Jacket
Weight
Control
Power
Ampacity Ampacity
AWG
mils
AWG
mils
AWG
mils
inches
lb/kft
amps
amps
14
14
14
14
14
14
15/4
15/4
15/4
15/4
15/4
15/4
12
10
8
6
4
2
15/4
15/4
30/4
30/4
40/6
40/6
12
10
10
8
8
6
60
60
60
60
80
80
0.515
0.575
0.675
0.750
0.905
1.01
205
286
380
502
727
1029
17.5
17.5
17.5
17.5
17.5
17.5
21.0
28.0
55.0
75.0
95.0
130.0
Mininum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation
.
pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C
temperature and 90°C
° rated conductors. Ampacities for cables having more than three conductors have been derated per NEC
Table 310.15(B)(16).
• For correction factors for different ambient temperatures and ampacitities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
• NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG,
and 30 amperes for 10 AWG copper conductors after any correction factors for ambient temperature and number of conductors
have been applied. Exceptions to this may be covered in NEC Article 240.4(E) through (G).
*DOW construction means:
• Control conductors are color coded – E2 (See chart page 26)
• Power conductors are black with numbers – M4 (See chart page 26)
• Fillers where applicable
1-866-663-9267
18
ULTREX®® VN
UL 1277
UL 83
ICEA S-95-658
ICEA S-73-532 (Conductor Identification Only)
Unshielded Tray Cable
UL Type TC -ER, 600 V, 90°C dry / wet rated
Composite Conductors Type THHN/THWN-2 with Ground
Composite - 4 Control Conductors with 3 Power Conductors and 1 Ground
Part
Number
684126
627042
627810
697680
682773
Control
Size
Insulation
Thickness
PVC/Nylon
Power
Size
Insulation
Thickness
PVC/Nylon
Ground
Jacket
Size
Thickness
Diameter Approximate
Over
Net Cable
Jacket
Weight
Control
Power
Ampacity Ampacity
AWG
mils
AWG
mils
AWG
mils
inches
lb/kft
amps
amps
12
12
12
12
12
15/4
15/4
15/4
15/4
15/4
10
8
6
4
2
20/4
30/5
30/5
40/6
40/6
10
10
8
6
6
60
60
60
80
80
0.585
0.675
0.720
0.890
1.02
320
405
530
760
1061
21
21
21
21
21
28
55
75
95
130
Mininum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
• Cables with different conductor counts and bare or insulated grounds are also available.
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C
° rated conductors. Ampacities for cables having more than three conductors have been derated per NEC
temperature and 90°C
Table 310.15(B)(3)(a).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
• NEC Article 240.4(D) requires that overcurrent protection not exceed 20 amperes for 12 AWG, and 30 amperes for 10 AWG
copper conductors after any correction factors for ambient temperature and number of conductors have been applied. Exceptions
to this may be covered in NEC Article 240.4(E) through (G).
Color codes:
• Power and Control conductors are black with number coding per Method 4 of ICEA S-73-532.
1-866-663-9267
19
ULTREX® XL
®
XLPE/PVC Type TC or TC-ER 600 Volt
Power and Control Cable
Temperature rating of 90°C dry / wet rated
Applications
Nexans 600 V ULTREX® XL Tray Cables
are listed as type TC or TC-ER under UL
1277 Electrical Power and Control Cables.
These cables may be installed in wet or
dry locations; in cable trays, raceways and
open air; and are suitable for exposure to
weather, direct burial and for Class I, Div. 2
(also Zone 2) and Class II, Div. 2 hazardous
locations per NEC. Cables with 3 or more
conductors are UL listed for exposed runs
(ER) when installed in accordance with
NEC Article 336.10(7).
Construction
Conductor: bare, annealed copper
conforming to ASTM B3 and Class B
stranded in accordance with ASTM B8, from
14 AWG to 500 kcmil.
Insulation: flame-retardant cross-linked
polyethylene meeting the requirements for
XHHW-2 per UL 44 and the requirements
of ICEA S-95-658 for XLPE insulation as
standard. Sizes 14 AWG to 8 AWG are
VW-1, and sizes 6 AWG and larger are not
VW-1.
Assembly: conductors are cabled in
concentric layers with interstices filled with
suitable fillers, as required. Ground wires
are sized as required by UL 1277 (refer
to the applicable product tables for the
standard sizes provided). Sizes 14 AWG
to 6 AWG have an insulated green ground
wire. Sizes 4 AWG and larger have a bare
ground wire. A binder tape of synthetic
material assembles the core in a tight circular
configuration.
Jacket: UL listed sunlight and moisture
resistant, sequentially length marked, black,
flame retardant polyvinyl chloride (PVC)
material meeting the requirements of UL
1277.
Sample Print Legend: (mon/year)
NEXANS ULTREX-XL 3/C 250 kcmil - 4
AWG GRD CU TYPE TC-ER XHHW-2 (UL)
E64956 F SUN RES DIR BUR 600V
Conductor Identification
(See page 26 of this catalog)
14 AWG to 10 AWG :
2–37 conductors:
Color coded per Method #1-E2 per ICEA
S-73-532
38 and More Conductors:
Black with number coding per Method 4
of ICEA S-73-532
8 AWG to 500 kcmil: black with number
coding per Method 4 of ICEA S-73-532
Specifications
• Meets UL 1277: Power and Control Tray
Cables with Optional Fiber Members.
• Meets UL 44: Thermoset-Insulated Wires
and Cables.
• Meets ICEA S-95-658, NEMA Publication
No. WC-70: Nonshielded Power
Cables Rated 2000 Volts or Less for the
Distribution of Electrical Energy.
Product features
• UL approved cables Type TC or TC-ER,
600 V.
• UL approved insulated conductors.
• Cables pass UL 1685 and IEEE 383
vertical tray fire tests at 70,000 BTU/hr.
• All cables pass IEEE 1202 and FT4
70,000 BTU/hr flame test.
• All cables pass ICEA T-29-520 210,000
BTU/hr flame test.
• For use in power, lighting, control and
signal circuits.
• Can be used within industrial
establishments where serviced by
qualified personnel and not subject to
physical damage.
• Continuous operation temperatures of
° dry and wet.
90°C
° per UL 1277
• Cold bend of –25°C
• Can be used In Class I Division 2 and
Class II Division 2 Hazardous Locations
and Intrinsically Safe applications as
permitted by NEC Articles 392, 501,
502, 503, and 505.*
1-866-663-9267
20
• As indicated in UL 1277: The overall
jackets of these cables are a “gas/vapor
tight continuous sheath” as discussed
in NEC Article 501.15(D) & (E).*
• For use in cable trays, raceways, conduits,
or for aerial applications where installed
with a messenger.
• For Direct Burial applications.
• Cables of 2 or more conductors (plus
a ground conductor) are UL listed for
Exposed Run (ER) per NEC Article
336.10(7):
1) Cables sized from 14 AWG to 6 AWG
have an insulated ground conductor.
2) Cables sized 4 AWG and larger have
a bare ground conductor.
• As permitted in NEC Articles 336.10 and
725 for Class 1 circuits.
• As permitted for non-power-limited
alarm circuits as defined in NEC Articles
336.10 and 760.27.
• Lead free and RoHS compliant
• Sunlight and moisture resistant
Options
The following constructions can be provided
on special orders:
• Cables sized 4 AWG and larger with an
insulated ground conductor
• Aluminum alloy conductors in sizes 12
AWG to 1000 kcmil
• Insulated or bare ground wires
• Different conductor
methods
• Shields of aluminum/mylar tape (with or
without a tinned copper drain wire)
• Composite constructions of different sized
conductors.
• 2000 volt rated cables with RHH/RHW-2
insulated conductors.
* Use in hazardous locations:
Please note that no investigation of these cables has
been performed regarding the transmission of gases
or vapors through the core. When these cables are
used in hazardous locations they should be sealed
properly as required by the NEC.
® ® XL
ULTREX
UL 1277
UL 44
ICEA S-73-532 (Conductor Identification Only)
Unshielded Tray Cable
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Multiconductor 14 AWG Type XHHW-2
Insulation Thickness:
30 mils / 0.76 mm
Part
# of
Number
Conduct ors
603092
603043
603118
602995
-----602862
-----602920
----------602888
----------620385
603126
-----603134
----------602953
----------------
2
3
4
5
6
7
8
9
10
11
12
13
14
15
19
20
25
30
35
37
40
45
50
Jacket
Diamet er
A pproximat e Net
Thickness
over Jacket
Cable Weight
mils
inches
lb/kft
amps
45
45
45
45
45
45
60
60
60
60
60
60
60
60
60
60
80
80
80
80
80
80
80
0.385
0.405
0.445
0.485
0.525
0.525
0.600
0.645
0.685
0.695
0.715
0.730
0.755
0.770
0.855
0.865
1.01
1.08
1.14
1.18
1.20
1.27
1.32
73
95
119
144
169
187
214
238
262
282
303
323
345
366
451
471
615
720
823
866
927
1031
1132
25.0
25.0
A mpacit y
20.0/25.0(1)
20.0
20.0
17.5
17.5
17.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
12.5
11.3
11.3
10.0
10.0
10.0
8.8
8.8
Mininum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation pull-in
Notes:
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in raceway or direct buried at 30°C
° rated conductors. Ampacities for cables having more than three conductors have been derated per NEC
temperature and 90°C
Table 310.15(B)(3)(a).
•For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature raitings see NEC
Table 310.15(B)(16).
• NEC Article 240.4(D) requires that overcurrent protection not exceed 15 amperes for 14 AWG copper conductors after any
correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in
NEC 2008 Article 240.4(E) through (G).
(1)
Where the 4th conductor is the neutral of a balanced 3 phase system.
1-866-663-9267
21
® ® XL
ULTREX
UL 1277
UL 44
ICEA S-73-532 (Conductor Identification Only)
Unshielded Tray Cable
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Multiconductor 12 AWG Type XHHW-2
Insulation Thickness:
30 mils / 0.76 mm
Part
# of
Number
Conduct ors
620377
602847
603050
603001
-----602870
-----603027
----------602896
----------620393
602938
-----603142
-------------------------------
2
3
4
5
6
7
8
9
10
11
12
13
14
15
19
20
25
30
35
37
40
45
50
Jacket
Diamet er
A pproximat e Net
Thickness
over Jacket
Cable Weight
mils
inches
lb/kft
amps
45
45
45
45
60
60
60
60
60
60
60
60
60
60
80
80
80
80
80
80
80
80
80
0.420
0.445
0.485
0.535
0.610
0.610
0.660
0.710
0.755
0.770
0.795
0.810
0.835
0.860
0.955
1.00
1.12
1.19
1.27
1.27
1.34
1.41
1.47
94
126
160
194
246
273
290
341
356
385
416
445
476
506
655
691
847
995
1142
1275
1289
1438
1582
30.0
30.0
A mpacit y
24.0/30.0(1)
24.0
24.0
21.0
21.0
21.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
15.0
13.5
13.5
12.0
12.0
12.0
10.5
10.5
Minimum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation
.
pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in raceway or direct buried at 30°C
° rated conductors. Ampacities for cables having more than three conductors have been derated per NEC
temperature and 90°C
Table 310.15(B)(3)(a).
• For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature raitings see NEC
Table 310.15(B)(16).
• NEC Article 240.4(D) requires that overcurrent protection not exceed 20 amperes for 12 AWG copper conductors after any
correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in
NEC Article 240.4(E) through (G).
1)
Where the 4th conductor is the neutral of a balanced 3 phase system.
1-866-663-9267
22
® ® XL
ULTREX
UL 1277
UL 44
ICEA S-73-532 (Conductor Identification Only)
Unshielded Tray Cable
UL Type TC or TC-ER, 600 V, 90°C dry / wet rated
Multiconductor 10 AWG Type XHHW-2
Insulation Thickness:
30 mils / 0.76 mm
Part
# of
Number
Conduct ors
603159
603167
603076
603175
-----603183
-----603191
------------------------------------------------------------------
2
3
4
5
6
7
8
9
10
11
12
13
14
15
20
25
30
35
40
45
50
Jacket
Diamet er
A pproximat e Net
Thickness
over Jacket
Cable Weight
mils
inches
lb/kft
amps
45
45
45
60
60
60
60
60
60
80
80
80
80
80
80
80
80
80
80
80
80
0.470
0.495
0.545
0.630
0.685
0.685
0.740
0.800
0.855
0.910
0.935
0.950
0.980
1.01
1.13
1.26
1.35
1.43
1.51
1.61
1.67
128
174
223
290
341
382
408
479
505
581
626
670
715
760
983
1209
1427
1644
1861
2082
2296
40
40
A mpacit y
32/40(1)
32
32
28
28
28
20
20
20
20
20
20
20
18
18
16
16
14
14
Minimum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation
.
pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables with 3 or more conductors are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in raceway or direct buried at 30°C
° rated conductors. Ampacities for cables having more than three conductors have been derated per NEC
temperature and 90°C
Table 310.15(B)(3)(a) .
• For load diversity of 50%, refer to NEC Table B.310.15(B)(2)(11).
• For correction factors for different ambient temperatures and ampacities at different conductor temperature raitings see NEC
Table 310.15(B)(16).
• NEC Article 240.4(D) requires that overcurrent protection not exceed 30 amperes for 10 AWG copper after any correction
factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in NEC
Article 240.4(E) through (G).
(1)
Where the 4th conductor is the neutral of a balanced 3 phase system.
1-866-663-9267
23
ULTREX® XL
®
UL 1277
UL 44
ICEA S-95-658
ICEA S-73-532 (Conductor Identification Only)
Unshielded Tray Cable
UL Type TC-ER, 600 V, 90°C dry / wet rated
3 Conductors Type XHHW-2 with Ground
Part
Number
611517
295196
306829
306845
306860
-----306886
-----306894
306910
-----306928
619114
-----619338
-----619148
Conduc t or
Ground Insulat ion Thic kness
Jac ket
Diamet er
Thic kness over Jac ket
A pproximat e Net
Cable Weight
A mpac it y
Size
Size
PV C/Nylon
AWG or kcmil
AWG
mils
mils
inches
lb/kft
amps
12
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
12
10
10
8
8
6
6
6
6
6
4
4
4
3
3
3
2
30
30
45
45
45
45
45
55
55
55
55
55
65
65
65
65
65
45
45
60
60
60
80
80
80
80
80
80
80
80
110
110
110
110
1.14
1.14
1.52
1.52
1.52
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.03
2.79
2.79
2.79
2.79
145
205
323
451
595
824
922
1200
1358
1663
2156
2506
2941
3394
4103
4818
5670
30(1)
45(1)
55
75
95
110
130
150
170
195
225
260
290
320
350
380
430
Minimum Bending Radius: 5 x overall diameter installed
7.5 x overall diameter during installation pull-in
Notes :
• Dimensions and weights shown are nominal values. They are subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in a raceway or direct buried at 30°C
° rated conductors.
temperature and 90°C
• For correction factors for different ambient temperatures and ampacities at different conductor temperature ratings see NEC
Table 310.15(B)(16).
(1)
NEC Article 240.4(D) requires that overcurrent protection not exceed 20 amperes for 12 AWG, and 30 amperes for 10 AWG
copper conductors after any correction factors for ambient temperature and number of conductors have been applied.
Exceptions to this may be covered in NEC Article 240240.4(E) through (G).
1-866-663-9267
24
ULTREX® XL
®
UL 1277
UL 44
ICEA S-95-658
ICEA S-73-532 (Conductor Identification Only)
Unshielded Tray Cable
UL Type TC-ER, 600 V, 90°C dry / wet rated
4 Conductors Type XHHW-2 with Ground
Part
Number
619403
306837
306852
659334
-----603209
---------------------------------------------------
Conduct or
Ground Insulat ion Thickness
Jacket
Diamet er
Thickness over Jacket
A pproximat e Net
Cable Weight
A mpacit y
Size
Size
PV C/Nylon
AWG or kcmil
AWG
mils
mils
inches
lb/kft
amps
10
8
6
4
3
2
1
1/0
2/0
3/0
4/0
250
300
350
400
500
10
10
8
8
6
6
6
6
6
4
4
4
3
3
3
2
30
45
45
45
45
45
55
55
55
55
55
65
65
65
65
65
60
60
80
80
80
80
80
80
80
80
80
110
110
110
110
110
0.604
0.734
0.890
0.950
1.04
1.09
1.22
1.31
1.42
1.54
1.66
1.88
2.01
2.12
2.23
2.43
269
392
595
792
1023
1176
1470
1772
2151
2667
3243
3928
4639
5300
6003
7391
40(1)
55
75
95
110
130
150
170
195
225
260
290
320
350
380
430
Minimum Bending Radius: 5 x overall diameter installed
.
7.5 x overall diameter during installation
pull-in
Notes :
• Dimensions and weights shown are nominal values, subject to standard manufacturing tolerances.
• Cables with different conductor counts and bare or insulated grounds are also available.
• Cables are UL listed for exposed runs (ER) when installed in accordance with NEC Article 336.10(7).
° ambient
• Ampacities are in accordance with NEC Table 310.15(B)(16) for conductors in raceway or direct buried at 30°C
° rated conductors, where the fourth conductor is the neutral of a balanced 3 phase, 4 wire system.
temperature and 90°C
• For correction factors for different ambient temperature ratings and ampacities at different conductor temperatures see NEC
Table 310.15(B)(16).
(1)
NEC Article 240.4(D) requires that overcurrent protection not exceed 30 amperes for 10 AWG copper conductors after any
correction factors for ambient temperature and number of conductors have been applied. Exceptions to this may be covered in
NEC Article 240.4(E) through (G).
1-866-663-9267
25
Conductor or Phase
Identification
Per ICEA S-73-532-E3.4 Method 4
Number Code
Conductor
Printing Details
Conductor
Printing Details
1st
“1-ONE-1”
4th
“4-FOUR-4”
2nd
“2-TWO-2”
5th
“5-FIVE-5”
3rd
“3-THREE-3”
6th
“6-SIX-6”
Per ICEA S-73-532-E3.1 Method 1 and Table E2 (formerly K2)
Colored Insulation with/without Colored Stripe
Conductor
Insulation
Stripe
Conductor
Insulation
Stripe
1st
BLACK
—
19th
ORANGE
Blue
2nd
RED
—
20th
YELLOW
Blue
3rd
BLUE
—
21st
BROWN
Blue
4th
ORANGE
—
22nd
BLACK
Orange
5th
YELLOW
—
23rd
RED
Orange
6th
BROWN
—
24th
BLUE
Orange
7th
RED
Black
25th
YELLOW
Orange
8th
BLUE
Black
26th
BROWN
Orange
9th
ORANGE
Black
27th
BLACK
Yellow
10th
YELLOW
Black
28th
RED
Yellow
11th
BROWN
Black
29th
BLUE
Yellow
12th
BLACK
Red
30th
ORANGE
Yellow
13th
BLUE
Red
31st
BROWN
Yellow
14th
ORANGE
Red
32nd
BLACK
Brown
15th
YELLOW
Red
33rd
RED
Brown
16th
BROWN
Red
34th
BLUE
Brown
17th
BLACK
Blue
35th
ORANGE
Brown
18th
RED
Blue
36th
YELLOW
Brown
Note : The color code repeats at #1 “BLACK” as the 37th conductor (for cables with more than 36 conductors) for ULTREX-VN.
1-866-663-9267
26
WARNING
NOTICE
FLAMMABLE
Non-metallic covering of electrical
cables will burn and under certain
conditions may transmit fire when
ignited.
Nexans has endeavored to ensure the
accuracy of the data in this publication,
however we cannot be liable for the
consequences of errors or omissions.
All data is subject to change without
notice. The installer and/or user assumes
all liability for the consequences of
the installation and/or use of any of
our products in contravention of any
applicable law, regulation or code.
TOXIC
Burning non-metallic coverings may
emit acid gases, which are highly toxic,
and may generate dense smoke.
CORROSIVE
Emission of acid gases may corrode
metal in the vicinity, such as sensitive
instruments and reinforcing rod in
concrete.
1-866-663-9267
27
wire and cable
A t
t h e
c o r e
o f
1-866-663-9267
28
p e r f o r m a n c e
09/2016