Certificate

advertisement

1151 Boston Providence Turnpike

P.O. Box 9102 Norwood, MA 02062 USA

T: 781 762 4300 F: 781-762-9375 www.fmapprovals.com

&(57,),&$7(2)&203/,$1&(

+$=$5'286&/$66,),('/2&$7,21(/(&75,&$/(48,30(17

This certificate is issued for the following equipment:

I. VEGADIF IS Version

VEGADIF DF 6a.bFcdefghij, Level Measuring Equipment.

IS/I,II,III/1/ABCDEFG/T**; 42225; Entity; FISCO; Type 4X/*6P; IP66

I/0/AEx ia/IIC/T**; 42225; Entity; FISCO; Type 4X/*6P; IP66

Reference Control Drawing No. 42225 for Entity Parameter values

Reference Control Drawing No. 42225 for FISCO Parameter values a = Configuration: 5 b = Agency Approval: U c = Process Connection/Fitting: Two digit alphanumeric variable for connections, which represents a

ASME, DIN, G, LA, NPT or TRI-CLAMP industry type process connection/flange, with pressure ratings and any type which comply with an international or national standard d = Material Diaphragm: 1, 2, 3, 5 or 6 e = Seal: 1, 2, 3, A, C, F, H, K, W, Y or Z f = Measuring Range/PN: 7B, 7C, 7D, 7F, 7H, 7L, 7M, 8F, 8H, 8L or 8M g = Electronics: F, H, P or Z; (FISCO certification available only with option F or P) h = Housing Type: 2, 3, 5, 8, 9, A, C, D, H, K, P, Q, R, V, W, X or Y i = Cable Entry: M, N, or any single digit alphanumeric variable representing NRTL certified connection or cable gland suitable for the application j = Indicator Control Module (PLICSCOM): A, B or X

** T6-T1 is based on maximum process temperature identified in Safety Instructions Document No.

42225

Special Conditions of Use:

1. For Division 1, Division 2, Zone 0, Zone 1, and Zone 2 Approvals, the process probes are suitable for connections to Class I, II & III, Division 1, Groups A, B, C, D, E, F & G and Class I, Zone 0, Groups

IIC hazardous (classified) locations.

2. Process temperature no greater than +120 ºC.

3. Maximum working pressure 2320 psi (160 bar) or 6091 psi (420 bar).

4. * Enclosure Type 6P rating is available only for Housing option type “8”, type “K” and type “V”.

To assure that this Approval is still valid, please refer to www.approvalguide.com

FM Approvals HLC 5/13 3044382

Page 1 of 7

5. Potential Electrostatic Charging Hazard – The enclosure is constructed from plastic. To prevent the risk of electrostatic sparking the plastic surface should only be cleaned with a damp cloth.

6. Enclosures containing aluminum constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction.

7. The maximum permitted ambient temperature of the vibrating level switch is +70 ºC. To avoid the effects of process temperatures and other thermal effects, care shall be taken to ensure the surrounding ambient temperature and the ambient temperature inside the equipment enclosure does not exceed +70 ºC. Adherence to the manufacturer’s installation manual must be followed for fulfillment of this requirement.

To assure that this Approval is still valid, please refer to www.approvalguide.com

FM Approvals HLC 5/13 3044382

Page 2 of 7

II. VEGADIF XP-AIS Version

VEGADIF DF 6a.bGcdefghij, Level Measuring Equipment.

XP-AIS/I/1/ABCD/T**; 42226; Entity; Type 4X; IP66; Dual Seal***

I/1/AEx d [ia]/IIC/T**; 42226; Entity; Type 4X; IP66; Dual Seal***

DIP-AIS/II,III/1/EFG/T**; 42226; Entity; Type 4X; IP66; Dual Seal***

Reference Control Drawing No. 42226 for Entity Parameter values a = Configuration: 5 b = Agency Approval: U c = Process Connection/Fitting: Two digit alphanumeric variable for connections, which represents a

ASME, DIN, G, LA, NPT or TRI-CLAMP industry type process connection/flange, with pressure ratings and any type which comply with an international or national standard d = Material Diaphragm: 1, 2, 3, 5 or 6 e = Seal: 1, 2, 3, A, C, F, H, K, W, Y or Z f = Measuring Range/PN: 7B, 7C, 7D, 7F, 7H, 7L, 7M, 8F, 8H, 8L or 8M g = Electronics: F, H, P or Z h = Housing Type: D, Q, W or Y i = Cable Entry: M, N, or any single digit alphanumeric variable representing NRTL certified connection or cable gland suitable for the application j = Indicator Control Module (PLICSCOM): A or X

** T6-T1 is based on maximum process temperature identified in Safety Instructions Document No.

42226

Special Conditions of Use:

1. For Division 1, Division 2, Zone 1, and Zone 2 Approvals, the process probes are suitable for connections to Class I, II & III, Division 1, Groups A, B, C, D, E, F & G and Class I, Zone 0, Groups

IIC hazardous (classified) locations.

2. Process temperature no greater than +120 ºC.

3. Maximum working pressure 2320 psi (160 bar) or 6091 psi (420 bar).

4. *** Dual Seal for Housing option type “D” and type “W” only.

5. Enclosures containing aluminum constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction.

6. The maximum permitted ambient temperature of the vibrating level switch is +70 ºC. To avoid the effects of process temperatures and other thermal effects, care shall be taken to ensure the surrounding ambient temperature and the ambient temperature inside the equipment enclosure does not exceed +70 ºC. Adherence to the manufacturer’s installation manual must be followed for fulfillment of this requirement.

To assure that this Approval is still valid, please refer to www.approvalguide.com

FM Approvals HLC 5/13 3044382

Page 3 of 7

III. VEGADIF DIP-AIS Version

VEGADIF DF 6a.bRcdefghij, Level Measuring Equipment.

DIP-AIS/II,III/1/EFG/T**; 42228; Entity; Type 4X/*6P; IP66

Reference Control Drawing No. 42228 for Entity Parameter values a = Configuration: 5 b = Agency Approval: U c = Process Connection/Fitting: Two digit alphanumeric variable for connections, which represents a

ASME, DIN, G, LA, NPT or TRI-CLAMP industry type process connection/flange, with pressure ratings and any type which comply with an international or national standard d = Material Diaphragm: 1, 2, 3, 5 or 6 e = Seal: 1, 2, 3, A, C, F, H, K, W, Y or Z f = Measuring Range/PN: 7B, 7C, 7D, 7F, 7H, 7L, 7M, 8F, 8H, 8L or 8M g = Electronics: F, H, P or Z h = Housing Type: 3, 5, 8, A, C, D, H, V or W i = Cable Entry: M, N, or any single digit alphanumeric variable representing NRTL certified connection or cable gland suitable for the application j = Indicator Control Module (PLICSCOM): A, B or X

** T6-T1 is based on maximum process temperature identified in Safety Instructions Document No.

42228

Special Conditions of Use:

1. For Division 1, and Division 2 Approvals, the process probes are suitable for connections to Class I, II

& III, Division 1, Groups A, B, C, D, E, F & G hazardous (classified) locations.

2. Process temperature no greater than +120 ºC.

3. Maximum working pressure 2320 psi (160 bar) or 6091 psi (420 bar).

4. * Enclosure Type 6P rating is available only for Housing option type “8” and type “V”.

5. Potential Electrostatic Charging Hazard – The enclosure is constructed from plastic. To prevent the risk of electrostatic sparking the plastic surface should only be cleaned with a damp cloth.

6. Enclosures containing aluminum constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction.

7. The maximum permitted ambient temperature of the vibrating level switch is +70 ºC. To avoid the effects of process temperatures and other thermal effects, care shall be taken to ensure the surrounding ambient temperature and the ambient temperature inside the equipment enclosure does not exceed +70 ºC. Adherence to the manufacturer’s installation manual must be followed for fulfillment of this requirement.

To assure that this Approval is still valid, please refer to www.approvalguide.com

FM Approvals HLC 5/13 3044382

Page 4 of 7

IV. VEGADIF NI Version

VEGADIF DF 6a.bXcdefghij, Level Measuring Equipment.

NI/I,II,III/2/ABCDFG/T**; Type 4X/*6P; IP66 a = Configuration: 5 b = Agency Approval: U c = Process Connection/Fitting: Two digit alphanumeric variable for connections, which represents a

ASME, DIN, G, LA, NPT or TRI-CLAMP industry type process connection/flange, with pressure ratings and any type which comply with an international or national standard d = Material Diaphragm: 1, 2, 3, 5 or 6 e = Seal: 1, 2, 3, A, C, F, H, K, W, Y or Z f = Measuring Range/PN: 7B, 7C, 7D, 7F, 7H, 7L, 7M, 8F, 8H, 8L or 8M g = Electronics: F, H, P or Z h = Housing Type: 2, 3, 5, 8, 9, A, C, D, H, Q, V, W or Y i = Cable Entry: M, N, or any single digit alphanumeric variable representing NRTL certified connection or cable gland suitable for the application j = Indicator Control Module (PLICSCOM): A, B or X

** T6-T1 is based on maximum process temperature identified in Safety Instructions Document No.

42227

Special Conditions of Use:

1. Process temperature no greater than +120 ºC.

2. Maximum working pressure 2320 psi (160 bar) or 6091 psi (420 bar).

3. * Enclosure Type 6P rating is available only for Housing option type “8” and type “V”.

4. Potential Electrostatic Charging Hazard – The enclosure is constructed from plastic. To prevent the risk of electrostatic sparking the plastic surface should only be cleaned with a damp cloth.

5. Enclosures containing aluminum constitute a potential risk of ignition by impact or friction. Care must be taken into account during installation and use to prevent impact or friction.

6. The maximum permitted ambient temperature of the vibrating level switch is +80 ºC. To avoid the effects of process temperatures and other thermal effects, care shall be taken to ensure the surrounding ambient temperature and the ambient temperature inside the equipment enclosure does not exceed +80 ºC. Adherence to the manufacturer’s installation manual must be followed for fulfillment of this requirement.

To assure that this Approval is still valid, please refer to www.approvalguide.com

FM Approvals HLC 5/13 3044382

Page 5 of 7

Equipment Ratings:

I. IS (Div. 1) Version

Intrinsically Safe Apparatus for use in Class I, Division 1 or 2, Groups A, B, C & D, Class II, Division 1 or

2, Group E, F & G, Class III, Division 1 or 2, in accordance with manufacturer’s Control Drawing;

Intrinsically Safe Apparatus with Fieldbus Intrinsically Safe Concept Wiring for use in Class I, Division 1 or

2, Groups A, B, C & D, Class II, Division 1 or 2, Groups E, F & G, Class III, Division 1 or 2, in accordance with manufacturer’s Control Drawing; Equipment protection by Intrinsic Safety AEx ia for use in Class I,

Zone 0, Zone 1, or Zone 2, Group IIC, in accordance with manufacturer’s Control Drawing; Equipment protection by Intrinsic Safety AEx ia with Fieldbus Intrinsically Safe Concept Wiring for use in Class I,

Zone 0, Zone 1, or Zone 2, Group IIC, in accordance with manufacturer’s Control Drawing, hazardous

(classified) locations, Type 4X/6P and IP66

II. XP-AIS (Div. 1) Version

Explosionproof Equipment with Intrinsically Safe Connections for use in Class I, Division 1 or 2, Groups A,

B, C & D, in accordance with manufacturer’s Control Drawing; Equipment protection by Flameproof

Enclosure AEx d for use in Class I, Zone 1 or Zone 2, Group IIC with Intrinsically Safe Connections [ia] for use in Class I, Zone 0, Zone 1 or Zone 2, Group IIC, in accordance with manufacturer’s Control Drawing;

Dust Ignitionproof Equipment with Intrinsically Safe Connections for use in Class II, Division 1 or 2,

Groups E, F & G, Class III, Division 1 or 2, in accordance with manufacturer’s Control Drawing, hazardous (classified) locations, Type 4X and IP66, Dual Seal

III. DIP-AIS (Div. 1) Version

Dust Ignitionproof Equipment with Intrinsically Safe Connections for use in Class II, Division 1 or 2,

Groups E, F & G, Class III, Division 1 or 2, in accordance with manufacturer’s Control Drawing, hazardous (classified) locations, Type 4X/6P and IP66

IV. NI (Div. 2) Version

Nonincendive Equipment for use in Class I, Division 2, Groups A, B, C & D, Class II, Division 2, Groups F

& G, Class III, Division 1 or 2 hazardous (classified) locations, Type 4X/6P and IP66

FM Approved for:

VEGA Grieshaber KG

Am Hohenstein 113

D-77761 Schiltach

Germany

To assure that this Approval is still valid, please refer to www.approvalguide.com

FM Approvals HLC 5/13 3044382

Page 6 of 7

This certifies that the equipment described has been found to comply with the following

Approval Standards and other documents:

2011

2010

Class 3615

Class 3810

ANSI/IEC 60529

ANSI/ISA-12.27.01

ANSI/ISA-60079-0

ANSI/ISA-60079-1

2004

2006

2005

2004

2003

2009

2009

ANSI/ISA-60079-11

ANSI/ISA-60079-27

ANSI/ISA-61010-1

NEMA 250

2009

2006

2004

2003

Original Project ID:

3044382

Approval Granted:

October 26, 2015

Subsequent Revision Reports / Date Approval Amended

Report Number / Date

RR203075

Report Number / Date

November 13, 2015

FM Approvals LLC

Report Number / Date

J.E. Marquedant

Manager, Electrical Systems

13 November 2015

Date

To assure that this Approval is still valid, please refer to www.approvalguide.com

FM Approvals HLC 5/13 3044382

Page 7 of 7

52217-EN-151113