Arc Flash Mitigation Case Study Jacob Bayer, PE AREGC Conference June 28, 2016 Definitions ► Arc Flash Hazard • A dangerous condition associated with the possible release of energy caused by an electric arc. ► Incident Energy • The amount of thermal energy impressed on a surface, a certain distance from the source, generated during an electrical arc event. Incident energy is typically expressed in calories per square centimeter (cal/cm2). 2 Incident 3 Arc Flash Facts ► As much as 80% of all electrical injuries are burns resulting from an arc-flash and ignition of flammable clothing. ► Arc temperature can reach 35,000°F - this is four times hotter than the surface of the sun. ► Fatal burns can occur at distances over 10 ft. ► As copper vaporizes, it undergoes an explosive volumetric increase of 67,000 to 1. ► An arc flash event can produce a force of 500 lbs. on an average human body. 4 Industry Standards and Regulations ► NFPA 70-2014 (NEC) • 240.87 Arc Energy Reduction. One of the following or approved equivalent means shall be provided: (1) Zone-selective interlocking (2) Differential relaying (3) Energy-reducing maintenance switching with local status indicator (4) Energy-reducing active arc flash mitigation system (5) An approved equivalent means 5 Industry Standards and Regulations ► NFPA 70E-2015 • 130.5 Arc Flash Risk Assessment. An arc flash risk assessment shall be performed… It shall be reviewed periodically, at intervals not to exceed 5 years. • 130.5 (D) Equipment Labeling. Electrical equipment...shall be field-marked with a label containing all the following information: (1) Nominal system voltage (2) Arc flash boundary (3) [Available incident energy and/or arc flash PPE category] 6 Industry Standards and Regulations ► 29 CFR 1910.269 (OSHA) Electric power generation, transmission, and distribution • (l) Working on or near exposed energized parts ► (8) Protection from flames and electric arcs (ii) For each employee exposed to hazards from electric arcs, the employer shall make a reasonable estimate of the incident heat energy to which the employee would be exposed. 7 Methods of Mitigating Arc Flash Incident Energy ► Protective Relay Coordination ► Fiber Detection ► Zone Selective Interlock (ZSI) ► Arc Resistant Gear ► Maintenance Mode ► Remote Control / Racking ► Differential Protection ► High Resistance Grounding 8 Protective Relay Coordination ► LV SWGR Tie ► LV SWGR Feeder ► LV MCC Feeder ► LV Loads 9 Protective Relay Coordination ► MV SWGR Feeder ► LV SWGR Main ► LV SWGR Tie ► LV SWGR Feeder ► LV MCC Feeder ► LV Loads 10 Zone Selective Interlock (ZSI) 11 Zone Selective Interlock (ZSI) 12 Zone Selective Interlock (ZSI) 13 Zone Selective Interlock (ZSI) 0.60 Seconds 14 Zone Selective Interlock (ZSI) 0.15 Seconds 15 Maintenance Mode ► MV SWGR Using Main Breaker MAINT MODE OFF ON LV SWGR PROTECTED ZONE 16 Maintenance Mode ► Using Upstream Breaker MV SWGR PROTECTED ZONE MAINT MODE OFF ON LV SWGR 17 Maintenance Mode ► MV SWGR Feeder • Normal Protection 18 Maintenance Mode ► MV SWGR Feeder • Maintenance Mode 19 Maintenance Mode ► MV SWGR Feeder • Maintenance Mode Δt 20 Bus Differential ► High Impedance: • Fast • Reliable • Requires Dedicated CTs 21 Bus Differential ► Low Impedance: • Fast • Reliable • More Complicated Relaying 22 Fiber Detection • Integral Light Sensors • Detects < 2.5ms • Possible to Retrofit 23 Arc Resistant Gear 24 Remote Control / Racking ► Open and Close Breakers from DCS ► Rack Breakers Remotely 25 High Resistance Ground ► Limit phase to ground fault current to less than 10 amps ► Often used on 480V systems ► Improves runtime 26 Arc Flash Analysis ► Energy Calculation (cal/cm2) • Current and Time ► Short Circuit Study (Current) ► Relay Coordination Study (Time) 27 Electrical Model 28 CURRENT IN AMPERES FGD PUS 101A FGD PUS101 TIE F60 FGD SST 102B F60 FGD SS XF 102B FGD PUS101 TIE F60 Open TCC Curves 1000 FGD PUS 101 TIE FGD PUS 101B 101B ISW FR 2B 10AB FU FR 2B 100 FGD SST 102B F60 1API024M001 FGD SS XF 102B P TIME IN SECONDS 10 FGD PUS101 TIE F60 - Phase 1 FGD SS XF 102B S FGD SST 102B GCT F60 FGD SUS102B MN FGD SUS102B FGD SST 102B F60 - Phase FGD SUS102 TIE 480V Tie1 FGD SUS102B MN - Phase FGD SUS102 TIE 0.10 FGD SUS102A Open MCC 102D FDR TX Inrush MCC 102B FDR - Phase MCC 102D CBL FGD MCC 102D Open RA 101 ME EXH 102 MCP RA 101 ME EXH 102 MCP PD-1028 RA 101 ME EXH 102 1ASW005S001&2 0.01 0.5 1 10 100 1K 10K FGD SST - Phase.tcc Ref. Voltage: 6900 Current in Amps x 1 RA 101 ME EXH 102 29 Arc Flash Study 30 Arc Flash Label 31 Minnesota Power Boswell Energy Center Unit 3 ► Electrical Upgrades • Case Study 32 Auxiliary Electrical System Assessment ► Short Circuit Study • Medium voltage short circuit current exceeded equipment ratings ► Arc Flash Assessment • Existing medium voltage buses all exceeded 40 cal/cm2 33 Auxiliary Electrical System ► Original Unit 3 One-Line Diagram 230kV 115kV Unit 3 GSU Xfmr Unit 3 Aux Xfmr Unit 3 Startup Xfmr G Aux Bus 3A Aux Bus 3B Startup Bus 3A Startup Bus 3B 34 Auxiliary Electrical System ► Final Unit 3 One-Line Diagram 230kV Unit 3 GSU Xfmr Unit 3 Aux Xfmr A Unit 3 Aux Xfmr B G Aux Bus 3A 15kV Bus 3A Aux Bus 3B VFD AQCS Bus 3C 15kV Bus 3B VFD AQCS Bus 3D M M ID Fan A 11,000HP ID Fan B 11,000HP 35 Auxiliary Electrical Equipment 36 Auxiliary Electrical System ► Medium Voltage Switchgear • Type 2BC Arc Resistant • Vented to Exterior • Included High Z Bus Differential Scheme • Arc Flash < 8 cal/cm2 37 Auxiliary Electrical System ► Low Voltage Switchgear • Standard Metal Enclosed 480V Switchgear • Arc Flash Mitigation Methods ► Optical Arc Sensing System ► Main Breaker Maintenance Mode ► Feeder Breaker Maintenance Mode ► High Resistance Grounded ► Insulated Bus 38 THANK YOU