This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. 1 Active Power Filter Control Strategy with Implicit Closed Loop Current Control and Resonant Controller Mauricio Angulo, Domingo Ruiz-Caballero, Jackson Lago, Student Member, IEEE, Marcelo L. Heldwein, Member, IEEE, and Samir A. Mussa, Member, IEEE Abstract—Novel simple indirect control concepts for an Active Power Filter (APF) application is proposed here. The concepts are exemplarily presented to control a modified APF structure. The main advantage over other control strategies is the achieved excellent simplicity to performance ratio. The proposed control strategies are based on the concept of virtual impedance emulation to provide high power factor in a system. To validate the operating principle a single-phase low power prototype has been built and experimentally tested. This prototype operates at a remarkably low switching frequency of 5 kHz and is digitally controlled by a Digital Signal Processor. is vs PCC iF Active Power Filter io vo Nonlinear loads Fig. 1. Active power filter connected in parallel with the loads — shunt-type APF. The filter current iF supplies the load harmonic current contents. Index Terms—Dc–ac converters, Active Power Filter, Sensorless Control techniques, Implicit control. I. I NTRODUCTION Nonlinear loads connected to electric energy distribution networks generate harmonic pollution. Such nonlinear loads drain currents with varying degree of harmonic contents. The harmonic current components do not represent useful active power due to the frequency mismatch with the grid voltage. However, the circulation of harmonic currents through feeders and protective network elements produces Joule losses and electromagnetic emissions that might interfere with other devices connected to the distribution network. This affects the electrical performance of control and communication systems involved with the protective elements. Several other harmful effects are observed as presented in [1], [2]. A remedy to the harmonic currents injection problem is to connect passive, active [3], [4] or hybrid [5] filters in parallel with the loads. This are named shunt active power filters (APF) [6], [7]. APFs are circuits based on switched power semiconductors (typically employing voltage source inverters) that inject opposed phase harmonic currents at the point of common coupling (PCC). This results in the whole nonlinear load plus APF system emulating a nearly resistive load behavior at the PCC terminals. Power transmission in the network is, thus, optimized and all nonlinear loads low c 2009 IEEE. Personal use of this material is permitted. Copyright However, permission to use this material for any other purposes must be obtained from the IEEE by sending a request to pubs-permissions@ieee.org J. Lago, S. A. Mussa and M. L. Heldwein are with the Power Electronics Institute (INEP), Federal University of Santa Catarina (UFSC), Florianópolis, SC, 88040-970, Brazil (e-mail: jacksonl@inep.ufsc.br; samir@inep.ufsc.br; heldwein@inep.ufsc.br). M. Angulo and D. Ruiz-Caballero are with the Power Electronics Laboratory (LEP), Pontificia Universidad Católica de Valparaı́so, Valparaı́so, Chile (e-mail: macswv07@live.cl; domingo.ruiz@ucv.cl). frequency harmonics electromagnetic compatibility issues are diminished. Two tasks are crucial to an APF to perform well its function, namely: the generation of appropriate current references, and the ability to rapidly follow the reference current signals. Thus, typical shunt APFs use the error signal generated by the comparison of measured currents with the references. The main control objective is to minimize such error. Finally, the employed controllers generate the modulation signals to the inverter power section. Generally, the error minimization is achieved through two different types of methods, the direct control methods or the indirect ones. In the direct control methods the required compensation inverter current reference is the one generated within the control algorithm. On the other hand, the indirect control methods generate the APF current reference indirectly, i.e., by causing that the APF plus nonlinear loads currents follow sinusoidal reference current signals in phase with the PCC voltages. Therefore, using the scheme shown in Fig. 1, Nh,max i∗F = i∗s − io = i∗s,non active − X io(h) , (1) h=1 where i∗F and i∗s are, respectively, the APF and the PCC reference currents, i∗s,non active is the non active current component of the mains current is and io(h) represents the load side current harmonics of order h. This condition guarantees that the correct inverter compensation current is injected even if the mains voltage presents harmonic distortion. The indirect control methods are typically easier to implement since only the input variables (currents and voltages) are measured. Whereas, the direct methods require sophisticated reference generation mechanisms. Fig. 2(a) shows a conventional APF system architecture Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org. This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. 2 where the smoothing inductor LF is series connected to the voltage source inverter. The compensation opposite phase load harmonic currents flow through the inductor generating the according harmonic voltages across the inductor in this architecture. Assuming a purely sinusoidal mains voltage vs results that the voltage drop across the inductor is generated by the inverter output voltage. Thus, the bandwidth of the modulation signal must be compatible with the voltage harmonics that are to be generated since the modulation signal is directly proportional to such voltage. In practice, considering that up to the 50th order harmonic component must be compensated in specifications such as given in standards IEEE 519 and the IEC 61000-3 series, i.e., 2.5 kHz in a 50 Hz network, leads to the need to employ high switching frequency fc . Carrier frequencies above fc > 25 kHz would be desirable and the local averaging method would provide proper results to model the system. A solution to this challenge is to consider the APF system architecture shown in Fig. 2(b) [8]–[11]. The smoothing inductor LF is now placed in series with the network and not with the inverter as usual. The dc-link capacitor CF requirements are approximately the same as in the standard APF configuration. The disadvantages of this architecture are that the inductor carries the full load current, except the harmonics, the PCC voltage vo is now switched (it requires an low-pass filter prior to the load), and the load voltage can be distorted due to load current harmonic components. Another aspect is that the presence of LF limits the rate of change of the load current. However, this APF structure implies an advantage from the APF control strategy viewpoint. The inductor current reference is now sinusoidal and in phase with the mains voltage as is the APF modulating signal m(t). Therefore, the inductor current becomes independent from the harmonic currents of the load. It follows that v̄o = v̄F = V̂ · sin(ω1 · t + ϕ), (2) where x̄ represents the local average value of x during a carrier period, V̂ is the peak value of the mains voltage, ω1 is the mains voltage angular frequency. In this context, the present work proposes novel indirect APF control methods to be applied in the modified shunt APF structure presented in Fig. 2(b). The proposed control strategy is much simpler to implement than conventional strategies, such as the ones listed in the following. Perhaps the most widespread method is the average current mode control [12], which presents an outer voltage control loop and an internal current control loop. Large control bandwidths are typically required with this approach. Hysteresis current control is also employed and demands a single outer voltage control loop to generate the current references. This scheme leads to very fast dynamics, but brings all disadvantages inherent to variable switching frequency. Examples of digital control strategies using intern model principles are: the adaptive [13] and the dead–beat control. One of the main control challenges faced in all these strategies is the generation of current references. Among the theories to compute the compensation reference current are: the p–q theory [14], [15], the synchronic reference frame [16], is vs (a) vC + CF io Sp Sp LF Sn vF iF vo Sn APF - Active Power Filter LF is vs (b) vC + CF Sp Sp Sn vF io iF vo Sn APF - Active Power Filter Fig. 2. (a) Typical single-phase APF system architecture; and, (b) the APF architecture used in this work. the discrete Fourier transform [17], adaptive neural networks [1], [13], Lyapunov based control [18], among others [6]. These techniques, while having an acceptable performance for achieving input unity power factor, are relatively complex to implement. In the case of digital programming, powerful digital signal processors (DSPs) are required in addition of analog to digital A/D converters, phase locked loops and other demanding software tasks. Novel APF control indirect strategies are proposed here as alternative to the cited techniques. These novel indirect methods are based on the concept of virtual impedance emulation through inverters to achieve unity input power factor. A key feature is that either mains-side current or voltage sensor is used, leading to sensorless strategies. The APF implicit current reference does not contain high order harmonic components to ensure unity power factor at the mains and, thus, the control function is greatly simplified leading to the control methods derived in section II. The system is theoretically analyzed in section III. The strategies can be implemented both with analog or digital electronics, demanding minimum hardware and data processing capabilities. The achieved performance is similar or superior to that attained with conventional strategies as shown through simulation and experimental results given in sections IV and V. The main contribution of this work lies on the use of very simple implicit current controllers to control an active power filter. II. APF I NDIRECT C ONTROL S TRATEGY C ONCEPTS A. Current Sensorless Strategy Applying Kirchhof’s second law to the circuit in Fig. 1 gives vs − LF · dis − (sp − sn ) ·vc = 0, dt | {z } (3) =sF where sp and sn are the switching functions for switches Sp and Sn , respectively. These are defined as +1 if a switch is closed and 0 when it is off. The resulting switching function Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org. This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. 3 for the filter comprehends both of these into sF = sp − sn . The switching signals are generated by a proper modulation scheme. For the case at hand phase-shifted pulse width modulation (PWM) is adopted. The high frequency (HF) harmonics are typically eliminated with filters and the following analysis considers only the low frequency behavior of the circuit. This is achieved with the definition of the local average value x̄ of the quantities within a switching period Ts . Applying this definition to APF switching function leads to _ vs dF k1 vm sF dt = dF , Fig. 3. (12). Rs dF k2 Sp´ where Re∗ is the desired resistance value. The APF dc-link voltage is controlled with a variable vm defined as k Vc∗ vm = , (7) Re∗ where k is a gain and Vc∗ is the dc-link voltage reference. Isolating Re∗ in (7) and using it in (5) gives d v̄s vm v̄s − LF − dF v̄c = 0. (8) dt kVc∗ Assuming a purely sinusoidal v̄s leads to Z d (v̄s ) = −ω 2 v̄s dt dt k1 = ω 2 LF k Vc∗ (9) (11) and replacing it in (9) results v̄s k1 dF = + v̄c v̄c Z (v̄s vm ) dt. Vc (12) The resulting control block diagram is presented in Fig. 3. This control strategy is simple and does not require complex computations for the generation of references. The phaseshifted PWM leads to the output of the inverter generating a voltage with twice the carrier frequency and with reduced current ripple. The procedure to determine the duty-cycle described above is input current sensorless and has the advantage of only measuring the input and the dc-link voltages to generate the control signal. * vc * 1 Sn 1 Sn´ _ vc Fig. 4. Block diagram for the voltage sensorless control based on (18). B. Voltage Sensorless Strategy Similarly to the input current sensorless strategy, an input voltage sensorless strategy is derived in the following. Replacing vs from (6) in (5) gives dīs − dF v̄c = 0. dt During sinusoidal steady state Z d 2 (īs ) = −ω īs dt. dt Re∗ īs − LF (13) (14) Defining the dc-link voltage control signal as vm = where ω is the sinus angular frequency. The control signal vm is assumed constant at steady state. Thus, (8) is rewritten as Z ω 2 LF v̄s + (v̄s vm ) dt − dF v̄c = 0. (10) k Vc∗ Defining Vc vm dīs − dF v̄c = 0. (5) dt Assuming that unity input power factor is to be achieved, the system should emulate a resistive behavior. Thus, v̄s īs = ∗ , (6) Re Sp _ t−T s v̄s − LF Sn´ Block diagram for the current sensorless control strategy based on (4) where dF is the resulting APF duty-cycle. This is to be generated by the control strategy. Applying (4) to (3), results 1 _ vc _ 1 s̄F = Ts 1 Sp´ Sn vc Vc * is Zt Sp _ Rs Vc∗ , Re∗ (15) where Rs is the current measurement gain, and substituting the above relations into (13) leads to Z īs Vc∗ Rs + ω 2 LF īs dt − dF v̄c = 0. (16) vm Defining gain k2 as k2 = LF ω 2 Rs Vc∗ (17) and dividing (16) by Vc∗ Rs , finally gives the duty-cycle Z k2 dF īs + īs dt. (18) = Rs Vc∗ vm v̄c v̄c The voltage sensorless control strategy based on (18) is implemented with the block diagram depicted in Fig. 4. The strategy is straightforward and similar from the practical implementation aspects to the current sensorless one. The advantage of this approach over the current sensorless is that overcurrent protection techniques are easier to implement with the current measurement. However, the semiconductor currents are not directly measured in neither approaches. Suitable current protection for IGBTs can be implemented through high performance gate drivers, low precision current sensors and the measurement of the dc-side current. Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org. This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. 4 III. T HEORETICAL ANALYSIS OF THE PROPOSED INDIRECT CONTROL SENSORLESS STRATEGIES This section presents theoretical analyses regarding the equivalent circuit observed from the mains and the equivalence between the proposed control technique and a control strategy that uses conventional feedback control theory with a resonant controller to obtain close to unity power factor. Furthermore, a general stability analysis is presented. Fig. 6. Block diagram for a control strategy based on the emulation of a virtual negative inductance to cancel the effects of LF and guarantee close to unity power factor. A. Equivalent Circuit Based Analysis Considering the low frequency behavior of the proposed APF configuration and a constant dc-link voltage vc = Vc∗ = Vc leads to dīs dis + sF vc ∼ + dF Vc . (19) vs = LF = LF dt dt Replacing the duty-cycle calculation function defined in (18) into (19) gives Z Rs Vc dīs + īs + ω 2 LF īs dt, (20) vs ∼ = LF | {z } |{z} dt vm | {z } =Leq =1/Ceq =Re where parameters Leq , Re and Ceq are equivalent circuit elements that model the controlled system. The equivalent circuit is presented in Fig. 5. This expression shows that the equivalent input impedance of the active filter with the proposed control strategy includes a series connection of a resistance Re and a capacitance Ceq . The resistance is responsible for the active power transference to the load, whereas the series capacitance compensates for the filter inductance LF . A frequency domain analysis is applied to the equivalent circuit. The first step is to define the reactive impedances √ jXL = jωLeq and −jXC = −j/(ωCeq ), with j = −1. Computing the total equivalent series impedance gives jω 2 LF = 0, (21) ω from where it is clear that the generated virtual capacitance does cancel the effects of the filter inductance regarding the low frequency behavior of the system. Therefore, theoretical unity power factor is achieved. The capability of bidirectional inverters to emulate virtual negative inductances have been proved in other applications [19], [20]. Therefore, another implementation possibility for the proposed APF control is to replace the virtual capacitance with a virtual negative inductance. This is derived from the idea given by the mains-side equivalent circuit analysis jXL − jXC = jωLF − producing a series capacitance. The according control diagram implementation is presented in Fig. 6, where k3 = −LF . Vc∗ Rs (22) Such a control method is equivalent in many aspects to the virtual capacitance method. However, since it employs a differentiation block, it tends to present faster dynamics and is more prone to electromagnetic noise interference. Furthermore, the stability aspects are different as presented in section III-C. The duty-cycle equation is then Rs Vc∗ Lf dīs . (23) īs − vm v̄c v̄c dt The generation of virtual impedances can be used to insert reactive power to the grid. This is done by deliberately changing parameters k1 , k2 or k3 at each of the control strategies. The effect is the emulation of a larger or smaller virtual impedance. dF = B. Equivalent Feedback Control Based Analysis The proposed control methods do not present a explicit current loop control. The current control is actually implicit in the control laws (12) and (18) and (23) that determine the APF duty cycle. This is understood in the following. A classic feedback control loop is seen in Fig. 7, where C(s) represents a current controller, G(s) is the system model, H(s) is the transfer function of the measurement chain. The derivation below shows the equivalence between the proposed control methods and a conventional feedback control loop assuming that both are in steady state with a constant dc-link voltage vc = Vc∗ . Finally, the large signal models are linearized around an operation point. Analyzing Fig. 7 results in the current controller being 1 C(s) = ˜∗ (24) Is − 1 · G(s) I˜ s Is∗ /I˜s and the transfer functions and G(s) must be found for the proposed APF control strategies. The loop equation of the circuit in Fig. 2 is dīs − RL īS = dF v̄C , dt where RL represents the inductor parasitic resistance. The current reference is given by vs i∗s = Re v̄s − LF Fig. 5. Equivalent circuit for the control strategy to emulate virtual capacitance Ceq . (25) (26) Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org. This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. 5 where Re is the actual emulated resistance. Assuming that vs is sinusoidal and considering that is is proportional to it, it follows that Z dīs 2 (27) = −ω1 īs dt. dt frequency w1 and the values of the circuit parameters Re and LF . Similar results are found for the equivalent input current sensorless case. To obtain a single equation that represents the control system, equations (25) and (26) are replaced in (25) neglecting RL and resulting in Z 2 (28) Re īs + LF ω1 īs dt = dF v̄C The proposed control strategies given by (18) and (23) can be combined to analyze both options simultaneously and, in an implementation to gain advantage from both sides. This strategy includes the integral (virtual capacitance) and derivative (virtual inductance) portions. This strategy gives Z 1 dīs īs dt, (35) + dF v̄c = īs Re + (Ls + Lv ) dt Cv Subtracting (25) from (28) gives v̄s − LF dīs = Re īs + LF ω12 dt Z īs dt. (29) Linearizing (29) produces ω 2 LF I˜s LF I˜s = R̃e Is,0 + Re,0 I˜s + 1 , (30) s where the ˜· represents the linearized variable and subscript 0 denotes the operating point. The linearization of (26) leads to Re,0 R̃e = −I˜s . Is,0 (31) Replacing (31) in (30) gives the linearized transfer function from the measured current to the reference current s2 + τse + ω1 I˜s∗ = , (32) s I˜s τ e with τe = LF /Re,0 . The next step is to find the plant function G(s). This is obtained with the linearization of (25). Thus, G(s) = I˜s 1 V∗ , = c ˜ RL 1 + τL s dF (33) with τL = LF /RL . Finally, substituting (32) and (33) in (24) gives the equivalent implicit current controller Cimplicit (s) transfer function Re s s + τ1 Cimplicit (s) = · 2 , (34) Vo s + ω12 which shows the transfer function of a resonant controller tuned at ω1 . Resonant controllers in current control give excellent results with purely sinusoidal references [21]. The high gain at the tuned frequencies guarantee the reference followup and the rejection of components in other frequencies. In the proposed methods the implicit resonant controller is implemented in a much simpler way than with the conventional control methods. Moreover, it follows from equation (34) that the bandwidth of the controller varies with the fundamental is* _ is,measured Fig. 7. where Cv and Lv are the emulated (virtual) capacitance and inductance, respectively. These are computed to result jXL − jXC = jω (LF − Lv ) − j 1 = 0. ωCv (36) Thus, guarantees zero mains current phase displacement. This system generates the equivalent circuit shown in Fig. 8, which is used in the following stability analysis. The transfer function from the mains voltage to the current in Fig. 8 is found as s I˜s (s) = 2 . s (LF + Lv ) + s Re + 1/Cv Ṽs (s) The poles from the system modeled with (37) are p −Re ± Re2 − 4 (LF + Lv ) /Cv psystem = . 2 (LF + Lv ) (37) (38) Assuming positive Re , i.e., power flow from the mains towards the load and positive Cv , i.e., a capacitance to cancel the effects of the APF inductance LF , the system poles are in the right half-plane if Leq = LF + Lv > 0. (39) Therefore, the first stability criteria is that the total series equivalent inductance is positive. This prevents the emulation of a pure negative inductance because if Lv = −LF the system is oscillatory. A practical implementation would require either a pure virtual capacitance or a combination with a negative inductance so that (39) is met. Still from (38) the system presents damped oscillatory responses if Re LF + Lv < , (40) 4 Cv where Re = Vs2 /Po depends on the load power. _ dF C(s) C. Stability Analysis G(s) is H(s) Current control closed loop. Fig. 8. Equivalent circuit for the control strategy to emulate both virtual capacitance Cv and negative inductance Lv . Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org. This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. 6 IV. S IMULATION RESULTS The power stage configuration used in the simulations based analysis of the proposed APF system is shown in Fig.9. A remarkably low APF switching frequency of fc = 5 kHz is used to highlight the performance of the proposed concepts. Other experimental parameters are: input ac voltage is set to Vs,rms = 110 V; mains frequency fs = 60 Hz; APF inductance LF = 12.83 mF; HF filter inductance L1 = 1.4 mH; HF filter resistance RL = 2 Ω; HF filter capacitance CL = 8 µF; and high frequency filter capacitance C1 = 0 µF (not used in this implementation). This setup parameters were chosen to approach the experimental setup in section V. The nonlinear load is a single-phase diode bridge rectifier with the following parameters: Ro = 40 Ω; Co = 940 µF; and L2 = 1 mH. Simulation results are shown in Fig. 10 for the voltage Fig. 9. Active power filter power stage setup used, both, in the simulations and in the experimental results. Fig. 10. Simulation results waveforms for the voltage sensorless indirect control strategy: (a) load-side PCC current io and rectifier current ir ; (b) APF filter capacitor voltage vC , APF output voltage vo and mains voltage vs ; (c) dc-link control variable vm ; (d) mains current is ; (e) APF control variable dF ; and (f) load voltage. Fig. 11. Simulation results waveforms for the current sensorless indirect control strategy: (a) load-side PCC current io and rectifier current ir ; (b) APF filter capacitor voltage vC , APF output voltage vo and mains voltage vs ; (c) dc-link control variable vm ; (d) mains current is ; (e) APF control variable dF ; and (f) load voltage. sensorless control strategy. Fig. 10(a) shows the nonlinear load currents at the PCC (io ) and after the HF filter (ir ). The currents are similar except from the high frequency harmonics and present a high THD even considering only the first 50 harmonic components. The APF filter capacitor voltage vC , the APF output voltage vo and the mains voltage vs are depicted in Fig. 10(b). The dc-link control variable vm seen in Fig. 10(c) is approximately constant as expected during steady state. The mains current is presented in Fig. 10(d) in phase with the mains voltage despite the large filter inductance of LF = 12.83 mH. Thus, proving the capability of the novel APF concept to emulate a resistive behavior when observed form the mains. Finally, Fig. 10(e) shows the APF duty-cycle. Similar results are found for the current sensorless control strategy as seen in the respective graphs presented in Fig. 11. Both, Fig. 10(f) and Fig. 11(f) show the load voltage at the terminals of the CL —RL branch with the respective THD values. It is seen that harmonic distortion appears as the load current causes a distorted voltage across inductors L1 , which is partially filtered with the parallel branch RL —CL . This effect should be analyzed on a case-based approach in order to evaluate the load voltage. Reducing inductor L1 , increasing CL and/or including capacitance C1 reduces the load voltage distortion as presented in the filter design guidelines provided at the Appendix. In order to compare the transient performance of the voltage sensorless control strategies a simulation with the same Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org. This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. 7 io [10 A/div] iF [10 A/div] is [10 A/div] Fig. 13. Experimental waveforms for the single-phase APF system shown in Fig.9. Currents: nonlinear load io , active filter inverter iF and mains is . Fig. 12. Simulation results waveforms for the current sensorless indirect control strategy: (a) local power factor value according to (41), (b) mains current is and (c) APF filter capacitor voltage vC during input voltage transient at t = 1.1 s from 100% to 120% of rated voltage and a load transient from 75% to 100% of rated power at t = 1.75 s for two voltage sensorless control strategies. The ratio from XLv to XCv is XLv /XCv = 4. conditions including an input voltage step at t = 1.1 s from 100% to 120% of rated voltage and a load step from 75% to 100% of rated power at t = 1.75 s was carried out. The results for the purely capacitive emulation (Cv + Re ) and the combination of both virtual capacitance and negative inductance (Cv + Lv + Re ) are shown in Fig. 12. As it is very difficult to observe the differences in the mains current a variable related to the power factor is used. This local power factor variable is defined as Rt 1 Tg t−Tg vo io dt q R hλiTg = q R , (41) t t 1 1 2 2 Tg t−Tg vs dt Tg t−Tg is dt where Tg is the mains fundamental period. It gives the correct power factor at steady state and an impression of the power deviations during transients. Fig. 12 shows that the combined method gives shorter transients and that both methods achieve close to unity power factor at steady state for all tested load conditions. Both control strategies have presented similar results regarding the mains side current is and APF dc-link voltage vC , which are exemplarily shown in Fig. 12. The settling time was below 1 s for the given simulation conditions and is mainly dictated by the APF dc-link voltage control loop. This is designed, as in a single-phase PFC rectifier, with low control bandwidth in order not to distort the mains-side current. V. E XPERIMENTAL R ESULTS A low power single-phase laboratory prototype of the proposed APF (cf. Fig.9) has been built in order to validate the theoretical analysis of the indirect control. The experimental setup employs the same configuration and parameters as the system used in the circuit simulations. vs [50 V/div] is [5 A/div] Fig. 14. Experimental waveforms for the single-phase APF system shown in Fig.9. Mains current is and voltage vs . The implementation of the modulation algorithm is performed in a fixed-point DSP , model T M S320F 2812 – Texas Instruments. The control software was implemented using “C“ language. Even though, the voltage sensorless strategies employing both capacitance and combined capacitance and negative inductance have been implemented and tested, the presented results are for the virtual capacitance control method because the achieved results are similar. Fig. 13 shows the waveforms of the mains is , load io and APF iF currents. The current drawn from the power grid is close to a sine wave. The presented distortion appears due to the distortion of the mains voltage. This verifies that the operation of the APF is appropriate, i.e., the load emulates a resistance from the viewpoint of the power grid. This is clearly seen in Fig.14, where mains current and voltage are in phase and presenting similar harmonic contents except from the switching noise observed at the voltage measurement due to noise coupled to the voltage probe. The effect of the emulation of a virtual capacitance in series with the APF filter inductor guarantees that the mains current phase displacement is close to zero even with the large value of the inductance LF . The APF synthesized current and dc-link voltage are shown in Fig. 15. The dc-link voltage is nearly constant at its set-point Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org. This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. 8 vC [50 V/div] iF [5 A/div] Fig. 15. Experimental waveforms for the single-phase APF system shown in Fig.9. Filter current iF and dc-link voltage vC . were able to guarantee close to unity power factor. Both, current and voltage sensorless versions were presented, where the voltage sensorless control was analyzed in details regarding its performance, equivalent circuits and stability. The main feature of the strategies is their extreme simplicity since no complex current reference computations are required. The implicit control loop is another inovative characteristic. In this sense, it was prooven that the proposed strategies are equivalent to explicit current control strategies employing resonant-type controller. This explains the excellent sinusoidal tracking performance. In addition to the resistive behavior, the APF emulates virtual capacitance and/or negative inductance. Thus, zero mains side current phase displacement is achieved. These characteristics were verified through circuit simulation and in an experimental setup including a nonlinear rectifier load, with the APF being switched at 5 kHz. This a very low swtiching and highlights the achievable performance. The concepts can be easily extended to the control of power factor correction rectifiers and three-phase systems. A PPENDIX The passive component parameters employed in the prototype were not optimized in any sense. Design guidelines are presented in the following to improve the filter overall performance. The first parameter to be chosen is the dc-link voltage. In the configuration shown in Fig. 9 the APF dc-link voltage vc must be higher than the mains maximum peak voltage (V̂s,max ) added to the maximum Lf inductor voltage drop (vLf ,max ) at any instant. In addition, there should be enough margin to guarantee that the APF dynamic is capable to handle transients. A 25% margin is suggested. Thus, Fig. 16. Experimentally obtained frequency spectra (peak values) for the mains current is and the load current io . The Total Harmonic Distortion for the currents are measured up to 3 kHz, i.e., h = 50th harmonic. Measured THDs: T HDvs = 6.85%; T HDis = 5.82% and T HDio = 79.02%. value around 300 V. Thus, proving a good voltage regulation across the dc bus. Frequency spectra of the mains is and load io currents are presented in Fig.16. The load has a very high total harmonic distortion of THDio ∼ = 79.02%, while the current supplied by the power grid presents a low harmonic distortion of THDis ∼ = 5.82% with a mains voltage THD of approximately THDvs ∼ = 6.85%. The main causes for the presented current distortion are, thus, the input voltage distortion and the overlock and delay times in the prototype. All harmonic components observed in Fig. 16(a) are clearly below the IEC 61000-3-2 standard limits for, both, Class A and Class D equipment. The harmonic components beyond 23 up to 50 present a maximum rms current value of 57 mA. Thus, the implemented prototype is able to fulfill the harmonic limits given in IEC 61000-3-2. This shows the effectiveness of the proposed control strategy. VI. C ONCLUSIONS Novel controls strategies for a modified shunt active power filter architecture were proposed here. The proposed strategies 5 (V̂s,max + vLf ,max ). (42) 4 The inductance value of Lf is designed to limit the HF current ripple towards the mains (∆Is ). This depends on the APF switching frequency and dc-link voltage leading to, Vc ≥ Lf ≥ Vc 4∆Is fc (43) Inductor L2 is typically part of the load and is not considered here as a part of the APF. The APF output filter must be design to attenuate the high frequency components of the voltage vo , which is switched, so to limit the output voltage (vl ) ripple. Considering the phase– shifted modulation used in this paper, the most significant of these high frequency components occur at 2fc ± f s. The function of this passive HF filter is to attenuate the HF harmonic components generated by the switching of the semiconductors. It is not a filter for low frequency current harmonics since these harmonics components are handled by the active filter. The inductance L1 must be as small as possible no to present a large impedance to the load current. This would generate voltage distortion in the presence of current harmonics. However, it must be large enough to limit the current ripple at io (∆Io ) similarly to the design of Lf . Thus, Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org. This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. 9 C1 = CL = 33 µF, L1 = 630 µH and RL = 6.8 Ω. The computed load voltage THD was T HDvl = 4.75% R EFERENCES Fig. 17. Simulation results waveforms for the voltage sensorless indirect control strategy: (a) load current ir and mains current is ; (b) load voltage vl and mains voltage vs . maximum and minimum values for L1 can be approximately computed with L1 ≥ Vc 4∆Io fs (44) v u X ∞ 1 T HDv V̂s2 u t , L1 < 2 πfs Pl n kn2 n=3,5,7,... (45) where, Pl is the load active power, T HDv is the maximum allowed THD at the load voltage generated by the load current and kn is the relative amplitude of the nth load current harmonic. The HF filter attenuation asymptote is mainly defined by L1 and C1 . Parameters RL and CL are used for passive damping and influence only around the resonance frequency. Thus, once L1 is determined, capacitance C1 is designed to provide the required attenuation for the voltage components at frequencies 2fc ± f s. It is suggested to set the natural frequency of this filter around 2fc /10 to achieve an attenuation around 40 dB. C1 = 1 4π 2 fo2 L1 (46) The RL – CL branch is designed to provide damping. Optimal value for these components to provide a minimal output impedance for the filter can chosen with [22], CL = mC1 s L1 (2 + m)(4 + 3m) RL = · , C1 2m2 (4 + m) (47) (48) where m must be imposed. Fig. 17 shows simulation results obtained from a new set of parameters for the HF filter to validate the design guidelines presented above. The load was the same as the used in Fig. 10. Load power is approximately Pl = 560 W been supplied with a sinusoidal voltage (110 V). The load current presents a crest factor of 2.4. The coefficients of the harmonic currents required to determine L1 can be obtained from a simulation of this load been supplied by a sinusoidal voltage supply. The coefficients used here are: k3 = 0.774, k5 = 0.438, k7 = 0.160, k9 = 0.0072, k11 = 0.0065. The T HDv desired was chosen as 4% and the m factor was imposed as 1. Applying the procedure and rounding the results of capacitances for commercial values, the filter parameters are: [1] M. Cirrincione, M. Pucci, G. Vitale, and A. Miraoui, “Current harmonic compensation by a single-phase shunt active power filter controlled by adaptive neural filtering,” IEEE Transactions on Industrial Electronics, vol. 56, no. 8, pp. 3128–3143, 2009. [2] P. Salmeron and S. Litran, “Improvement of the electric power quality using series active and shunt passive filters,” IEEE Transactions on Power Delivery, vol. 25, no. 2, pp. 1058–1067, 2010. [3] H. Akagi, A. Nabae, and S. Atoh, “Control strategy of active power filters using multiple voltage-source pwm converters,” IEEE Transactions on Industry Applications, no. 3, pp. 460–465, 1986. [4] Y. Tang, P. C. Loh, P. Wang, F. H. Choo, F. Gao, and F. Blaabjerg, “Generalized design of high performance shunt active power filter with output lcl filter,” Industrial Electronics, IEEE Transactions on, vol. 59, no. 3, pp. 1443 –1452, march 2012. [5] H. Akagi and K. Isozaki, “A hybrid active filter for a three-phase 12pulse diode rectifier used as the front end of a medium-voltage motor drive,” Power Electronics, IEEE Transactions on, vol. 27, no. 1, pp. 69 –77, jan. 2012. [6] M. Aredes, J. Hafner, and K. Heumann, “Three-phase four-wire shunt active filter control strategies,” IEEE Transactions on Power Electronics, vol. 12, no. 2, pp. 311–318, 1997. [7] S. Rahmani, N. Mendalek, and K. Al-Haddad, “Experimental design of a nonlinear control technique for three-phase shunt active power filter,” IEEE Transactions on Industrial Electronics, vol. 57, no. 10, pp. 3364 –3375, oct. 2010. [8] M. Routimo, M. Salo, and H. Tuusa, “Current sensorless control of a voltage-source active power filter,” in Applied Power Electronics Conference and Exposition, 2005. APEC 2005. Twentieth Annual IEEE, vol. 3, march 2005, pp. 1696 – 1702 Vol. 3. [9] M. Salo, “Ac current sensorless control of the current-source active power filter,” in Power Electronics Specialists Conference, 2005. PESC ’05. IEEE 36th, june 2005, pp. 2603 –2608. [10] D. Wojciechowski, “Sensorless predictive control of three-phase parallel active filter,” in AFRICON 2007, sept. 2007, pp. 1 –7. [11] G.-Y. Jeong, T.-J. Park, and B.-H. Kwon, “Line-voltage-sensorless active power filter for reactive power compensation,” Electric Power Applications, IEE Proceedings -, vol. 147, no. 5, pp. 385 –390, sep 2000. [12] L. Dixon, “Average current mode control of switching power supplies,” APPLICATION NOTE U-140,UNITRODE (Texas Instruments), pp. 3– 356 –3–369, Sep. 1999. [13] A. Bhattacharya and C. Chakraborty, “A shunt active power filter with enhanced performance using ann-based predictive and adaptive controllers,” IEEE Transactions on Industrial Electronics, vol. 58, no. 2, pp. 421–428, 2011. [14] H. Akagi and A. Nabae, “The p-q theory in three-phase systems under non-sinusoidal conditions,” European Transactions on Electrical Power, vol. 3, no. 1, pp. 27–31, 1993. [15] E. Watanabe, H. Akagi, and M. Aredes, “Instantaneous p-q power theory for compensating nonsinusoidal systems,” in Nonsinusoidal Currents and Compensation, 2008. ISNCC 2008. International School on, 2008, pp. 1 –10. [16] E. Watanabe and M. Aredes, “Power quality considerations on shunt/series current and voltage conditioners,” in Harmonics and Quality of Power, 2002. 10th International Conference on, vol. 2, 2002, pp. 595 – 600 vol.2. [17] M. Aredes and E. Watanabe, “New control algorithms for series and shunt three-phase four-wire active power filters,” IEEE Transactions on Power Delivery, vol. 10, no. 3, pp. 1649 –1656, Jul. 1995. [18] S. Rahmani, A. Hamadi, and K. Al-Haddad, “A lyapunov-functionbased control for a three-phase shunt hybrid active filter,” Industrial Electronics, IEEE Transactions on, vol. 59, no. 3, pp. 1418 –1429, march 2012. [19] A. Borre, R. Dias, A. de Lima, and E. Watanabe, “Synthesis of controlled reactances using vsc converters,” in Brazilian Power Electronics Conference (COBEP’09). IEEE, 2009, pp. 431–437. [20] A. Morsy, S. Ahmed, P. Enjeti, and A. Massoud, “An active damping technique for a current source inverter employing a virtual negative inductance,” in Twenty-Fifth Annual IEEE Applied Power Electronics Conference and Exposition (APEC). IEEE, 2010, pp. 63–67. Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org. This article has been accepted for publication in a future issue of this journal, but has not been fully edited. Content may change prior to final publication. 10 [21] F. Blaabjerg, R. Teodorescu, M. Liserre, and A. Timbus, “Overview of control and grid synchronization for distributed power generation systems,” IEEE Transactions on Industrial Electronics, vol. 53, no. 5, pp. 1398–1409, 2006. [22] M. L. Heldwein, “Emc filtering of three-phase pwm converters,” Ph.D. dissertation, ETH Zurich, 2008. Jackson Lago (S11) received the B.S. degrees in electrical engineering from the University Center of Jaragu do Sul (UNERJ), Jaragu do Sul, Brazil, in 2009, and the M.S. degree from the Federal University of Santa Catarina (UFSC), Florianpolis, Brazil, in 2011. He is currently working toward the Ph.D degree at the Power Electronics Institute (INEP), UFSC. Mauricio Angulo was born in Osorno, Chile, in 1973. He received the degree in Electrical Engineering from Universidad Tecnica Federico Santa Maria (UTFSM), Valparaiso, Chile. In 2006, he collaborated as research assistant in the Electronics Engineering department at UTFSM. His fields of interest include power converters control techniques, especially multilevel converter and active filters. Marcelo Lobo Heldwein (S99-M08) received the B.S. and M.S. degrees in electrical engineering from the Federal University of Santa Catarina (UFSC), Florianpolis, Brazil, in 1997 and 1999, respectively, and his Ph.D. degree from the Swiss Federal Institute of Technology (ETH Zurich), Zurich, Switzerland, in 2007. He is currently an Adjunct Professor with the Electrical Engineering Department at the UFSC. From 1999 to 2001, he was a Research Assistant with the Power Electronics Institute, Federal University of Santa Catarina. From 2001 to 2003, he was an Electrical Design Engineer with Emerson Energy Systems, in Brazil and Sweden. He was a Postdoctoral Fellow in the Power Electronics Institute (INEP) at the UFSC, under the PRODOC/CAPES program from 2008 to 2009. His research interests include power factor correction techniques, power conversion for energy distribution, multilevel converters and electromagnetic compatibility. Dr. Heldwein is a member of the Brazilian Power Electronic Society (SOBRAEP). Domingo A. Ruiz-Caballero was born in Santiago, Chile, in 1963. He received the degree in Electrical Engineering from Pontificia Universidad Catlica de Valparaiso, Valparaiso, Chile, in 1989, and M.Eng. in 1992 and Dr.Eng. in 1999 from Power Electronics Institute (INEP), Federal University of Santa Catarina, Florianpolis, Santa Catarina, Brazil. Since 2000, he has been with Department of Electrical Engineering, Pontificia Universidad Catlica de Valparaiso, where he is currently Adjunct Professor. His fields of interest include high-frequency switching converters, power quality, multilevel inverters and soft-switching techniques. He is currently a member of the Brazilian Power Electronics Society (SOBRAEP). Samir Ahmad Mussa (M06) was born in JaguariRS, Brazil, in 1964. He received the B.S. degree in electrical engineering from the Federal University of Santa Maria, Santa Maria, Brazil, in 1988, and a second degree in mathematics/physics. He received the M.Eng. and Ph.D. degrees in electrical engineering from the Federal University of Santa Catarina(UFSC), Florianpolis, Brazil, in 1994 and 2003, respectively. He is currently an Adjunct Professor with the Power Electronics Institute(INEP-UFSC), Florianpolis. His research interests include digital control applied to power electronics, power-factor- correction techniques and DSP/FPGA applications. Dr.Mussa is currently a member of the Brazilian Power Electronics Society (SOBRAEP). Copyright (c) 2011 IEEE. Personal use is permitted. For any other purposes, permission must be obtained from the IEEE by emailing pubs-permissions@ieee.org.