Application Guide M-0359 Syncrocloser® Check Plus SYNCROCLOSER ® Syncrocloser® Check Plus M-0359 • Enhances system stability when applied to transmission and primary distribution reclosing schemes • Detects a static phase angle across an open breaker in 0.5 second to assure a fast permissive for reclosure • Simultaneously measures voltage magnitudes to ensure that they are within upper, lower and difference limits • Includes dead line/dead bus closing features • Remote command widens the phase angle setpoint to respond to system emergencies or to narrow the setpoint when the two systems are isolated to close the breaker very close to 0° • Transducer analog outputs are SCADA compatible Industry Leader Since 1969 Made in the USA M-0359 Syncrocloser® Check Plus INPUTS 1. 2. 3. Power is derived from either the Line or Bus input, whichever is greater. Below 65 V, the low voltage detection circuitry will shut down the M-0359. Line voltage, nominal 120 V ac, 145 V ac maximum continuous. Will withstand 240 V ac for 1 sec. Bus voltage, nominal 120 V ac, 145 V ac maximum continuous. Will withstand 240 V ac for 1 sec. ■ NOTE: Line and Bus voltage inputs are transformer-isolated, allowing complete freedom in applications. 4. 5. Select Dead Bus Close (by closing contact)*. Select Dead Line Close (by closing contact)*. *■ ■ NOTE: One input must be greater than 100 V ac to ensure output relay closure. 6. 7. Shift PHASE ANGLE LIMIT setpoint. An external contact closure will reduce the setpoint by a specified ratio. This can also be used as a widening function by operating with the external terminals normally closed. Enable Sync-Check. BURDEN Whichever input voltage is high, 11 VA; other input, 1 VA. CONTROLS UPPER VOLTAGE LIMIT: 110 to 140 V ac either input, dial calibration accuracy ±2% of full scale. LOWER VOLTAGE LIMIT: 90 to 120 V ac either input, dial calibration accuracy ±2% of full scale. DELTA V LIMIT: 1 to 5 V, dial calibration accuracy ±5% of full scale. Other ranges available. DEAD LINE LIMIT: 10 to 60 V, dial calibration accuracy ±7% of full scale. DEAD BUS LIMIT: 10 to 60 V, dial calibration accuracy ±7% of full scale. PHASE ANGLE LIMIT: 0 to ±30°, dial calibration accuracy ±5% of full scale. Other ranges available. DELTA F LIMIT: 0.01 to 0.5 Hz, dial calibration accuracy ±5% of full scale. ■ NOTE: Controls are independent of each other and do not require additional instrumentation for field setting. LED INDICATORS All LEDs are lit when conditions are met to close the breaker. BUS UPPER VOLTAGE LIMIT OK LINE UPPER VOLTAGE LIMIT OK BUS LOWER VOLTAGE LIMIT OK LINE LOWER VOLTAGE LIMIT OK DELTA V OK LINE HOT BUS HOT ANGLE OK DELTA F OK –2– M-0359 Syncrocloser® Check Plus BREAKER CLOSE RELAY Dry output contacts rated to make and carry 20 A at 250 V dc, and interrupt 0.9 A at 120 V dc or 0.4 A at up to 250 V dc inductive load. Open contacts will withstand 1500 V ac for 1 min. Contacts to ground will withstand 1500 V ac for 1 min. RESPONSE TIME When the Line and Bus inputs are first applied to the unit, the voltage magnitude circuits require approximately 0.5 sec. to sense the correct voltage. The unit will simultaneously measure phase angle and close the breaker with proper phase angle after this initial delay. In closing on dead line or dead bus, the phase condition is ignored so that the unit will close upon a voltage below the set threshold in approximately 0.5 sec. STATUS RELAY CONTACTS Voltage Status Relay: Closed when Voltage conditions are within limits. Phase Angle Status Relay: Closed when Phase Angle is within limits. Delta Frequency Status Relay: Form C contact provided. These are light duty contacts intended primarily for status interrogation by supervisory. They can be used to light local lights with the following restrictions: 1/2 A at 125 V dc resistive; 1 A at 120 V ac, 250 V dc across open contacts ANALOG OUTPUTS Various dc analog outputs are provided for Bus Voltage, Line Voltage, Delta V, Phase Angle, and Delta F. These analog outputs can interface with most SCADA systems. RELIABILITY The M-0359 Syncrocloser® Check Plus relay is assembled on three glass-epoxy printed circuit boards. All semiconductor components are hermetically sealed, and of the highest and most reliable quality available. Highly stable, instrument-grade capacitors and resistors are used in critical measurement circuits to minimize the possibility of error. TRANSIENT PROTECTION Input and output circuits are protected against system transients. The M-0359 will pass all requirements of ANSI/IEEE C37.90.1-1989, which defines oscillatory and fast transient surge withstand capability. All inputs and outputs will withstand 1500 V ac to chassis or instrument ground for one minute. Voltage inputs are electrically isolated from each other, from other circuits, and from ground. ENVIRONMENTAL Temperature Range: Units will operate properly over a temperature range of –40° to +80°C. Humidity: Stated accuracies are maintained at up to 95% relative humidity (non-condensing). Fungus Resistance: A conformal printed circuit board coating inhibits fungus growth. –3– PHYSICAL Size: 19" wide x 3-1/2" high x 13" deep (48.3 cm x 8.9 cm x 33.0 cm). Requires two rack units space in a standard 19" rack. May also be panel mounted horizontally or vertically. Approximate Weight: 15 lb (6.8 kg). Approximate Shipping Weight: 20 lb (9.1 kg). SYNCROCLOSER® COVER KIT M-0217 The M-0217 may be ordered that includes a transparent cover and mounting bracket to cover the controls and prevent accidental resetting. PATENT The M-0359 Syncrocloser Check Plus relay is covered by U.S. Patent 4,218,625. WARRANTY The M-0359 Syncrocloser Check Plus relay is covered by a five year warranty from date of shipment. Specification is subject to change without notice. BECKWITH ELECTRIC CO., INC. 6190 - 118th Avenue North • Largo, Florida 33773-3724 U.S.A. PHONE (727) 544-2326 • FAX (727) 546-0121 marketing@beckwithelectric.com www.beckwithelectric.com ISO 9001:2008 © Beckwith Electric Co. All Rights Reserved. Printed in U.S.A 800-0359-SP-MC4 01/13 WARNING DANGEROUS VOLTAGES, capable of causing death or serious injury, are present on the external terminals and inside the equipment. Use extreme caution and follow all safety rules when handling, testing or adjusting the equipment. However, these internal voltage levels are no greater than the voltages applied to the external terminals. DANGER! HIGH VOLTAGE – This sign warns that the area is connected to a dangerous high voltage, and you must never touch it. PERSONNEL SAFETY PRECAUTIONS The following general rules and other specific warnings throughout the manual must be followed during application, test or repair of this equipment. Failure to do so will violate standards for safety in the design, manufacture, and intended use of the product. Qualified personnel should be the only ones who operate and maintain this equipment. Beckwith Electric Co., Inc. assumes no liability for the customer’s failure to comply with these requirements. – This sign means that you should refer to the corresponding section of the operation manual for important information before proceeding. Always Ground the Equipment To avoid possible shock hazard, the chassis must be connected to an electrical ground. When servicing equipment in a test area, the Protective Earth Terminal must be attached to a separate ground securely by use of a tool, since it is not grounded by external connectors. Do NOT operate in an explosive environment Do not operate this equipment in the presence of flammable or explosive gases or fumes. To do so would risk a possible fire or explosion. Keep away from live circuits Operating personnel must not remove the cover or expose the printed circuit board while power is applied. In no case may components be replaced with power applied. In some instances, dangerous voltages may exist even when power is disconnected. To avoid electrical shock, always disconnect power and discharge circuits before working on the unit. Exercise care during installation, operation, & maintenance procedures The equipment described in this manual contains voltages high enough to cause serious injury or death. Only qualified personnel should install, operate, test, and maintain this equipment. Be sure that all personnel safety procedures are carefully followed. Exercise due care when operating or servicing alone. Do not modify equipment Do not perform any unauthorized modifications on this instrument. Return of the unit to a Beckwith Electric repair facility is preferred. If authorized modifications are to be attempted, be sure to follow replacement procedures carefully to assure that safety features are maintained. PRODUCT CAUTIONS Before attempting any test, calibration, or maintenance procedure, personnel must be completely familiar with the particular circuitry of this unit, and have an adequate understanding of field effect devices. If a component is found to be defective, always follow replacement procedures carefully to that assure safety features are maintained. Always replace components with those of equal or better quality as shown in the Parts List of the Instruction Book. Avoid static charge This unit contains MOS circuitry, which can be damaged by improper test or rework procedures. Care should be taken to avoid static charge on work surfaces and service personnel. Use caution when measuring resistances Any attempt to measure resistances between points on the printed circuit board, unless otherwise noted in the Instruction Book, is likely to cause damage to the unit. TABLE OF CONTENTS M-0359 Syncrocloser® Check Plus Application Guide Introduction ................................................................................................................ 1 The Syncrocloser Line ................................................................................................. 1 The M-0359 Syncrocloser Check Plus Relay ............................................................. 1 Figure 1 System Restoration Application ................................................................. 2 Application .................................................................................................................. 3 Features ....................................................................................................................... 3 Figure 2 External Connections .................................................................................. 4 Analog Outputs ............................................................................................................ 5 Figure 3 Voltage Analog Output ............................................................................... 7 Figure 4 Current Analog Output ................................................................................ 7 Table 1 Scale Factors ............................................................................................... 8 Mounting ..................................................................................................................... 9 Figure 5 Outline Dimensions for all Syncrocloser Equipment Chassis .................. 9 Figure 6 Hole Drill and Cutout Dimensions ............................................................ 10 Adjustment ................................................................................................................ 11 Maintenance .............................................................................................................. 12 Patent, Warranty, and Indemnification ..................................................................... 13 © Beckwith Electric Co. All Rights Reserved. Printed in U.S.A. 800-0359-AG-MC5 01/13 This Page Left Intentionally Blank INTRODUCTION ® THE SYNCROCLOSER LINE This product line is directed towards the problem of when to close a circuit breaker. In most cases, it is expected that the products will be used with a transmission rather than a distribution breaker. They may be used with either generator breakers, line breakers, or breakers selectively used for either purpose. The units are available with various features, giving a flexibility of application to a wide variety of conditions. Solid-state technology gives all units the following important advantages: 1. Each unit mounts in a standard 19" rack, thereby conserving valuable panel space for meters and frequently used controls. Each unit requires only 3-1/2" of vertical rack space. 2. The units are capable of meeting extreme shock, vibration and seismic requirements. THE M–0359 SYNCROCLOSER CHECK PLUS RELAY The M–0359 is a replacement for the familiar electromechanical “sync-check” relay, with the added features of DELTA F LIMIT, DEAD LINE LIMIT and DEAD BUS LIMIT front panel settings. The unit is intended for use in closing a circuit breaker when slip frequency, phase angle and voltage magnitudes fall within adjustable windows. USE OF MODERN PRECISION SOLID-STATE TECHNOLOGY YIELDS THE FOLLOWING FEATURES: 1. 2. 3. 4. Phase Angle and Frequency Difference windows, each of which is easily adjustable using calibrated controls that have no interdependence with each other. Highly stable Undervoltage, Overvoltage, Voltage Difference, Dead Line and Bus Limit functions with thresholds set by accurately calibrated controls. Phase angle, line voltage, bus voltage, delta voltage and delta frequency analog information is available on the rear terminal block for telemetry purposes, instrument interrogation or SCADA interface. Phase angle, line/bus voltage, and delta frequency status contacts are available on the rear terminal block. THIS UNIT IS INTENDED FOR THREE GENERAL CLASSES OF APPLICATION 1. 2. 3. For supervising the closing of a substation tie line breaker where either a rotating or static phase angle is expected. As a backup device for an operator. Status outputs can be used to tell why the M–0359 did not close the breaker so that the operator can change system parameters as needed. As a backup device for an automatic synchronizer such as the M–0193 Syncrocloser Unit, either at a generating plant or at a system tie breaker. The interconnections for this application are shown in Figure 1. Refer to the M–0193 Application Guide for further information. –1– ■ NOTE: The M–0193 closes on a rotating phase angle (isolated systems). The M–0359 closes on a static phase angle (network interties) or black line/bus, as enabled. The M–0359 also provides analog data for SCADA input. FIGURE 1 System Restoration Application –2– APPLICATION The M–0359 can be used, either alone or as a permissive relay in series with an operator or automatic synchronizer, to close or reclose a line circuit breaker where there could be a difference in frequency across the open breaker. The maximum allowable frequency difference for breaker closing is set on the front panel DELTA F LIMIT control. In some instances, a difference in frequency can exist with two “islands” of generation separated by the breaker under consideration. The M–0359 will close with either a rotating or static phase angle, provided the parameters are within the setpoint limits. Unlike other sync-check relays, the M–0359 has SCADA-compatible analog outputs that represent the phase angle, difference frequency, voltage magnitudes and voltage difference across the open breaker. This can be essential to system operators since it allows them to determine when it is safe to close a certain breaker and can also serve as the criteria for correction. Various logic inputs enable or inhibit the different modes of M–0359 breaker closing, as shown in Figure 2. It is suggested that these be used so that the M–0359 contact directly closes the breaker or a 25X sync auxiliary relay. This eliminates reliance on a number of inherently less reliable electromechanical contacts in the close circuit. ■ NOTE: All functions operate simultaneously, depending on the inhibit/enable inputs. FEATURES UPPER AND LOWER VOLTAGE LIMIT The UPPER and LOWER VOLTAGE LIMIT settings permit checking the voltage conditions prior to closing and are used to supervise the closing of a line breaker. DELTA V LIMIT The Voltage Difference (DELTA V LIMIT) is used to ensure that the difference in voltage magnitude between the Bus and Line voltages is not excessive. Using the DELTA V LIMIT allows the UPPER VOLTAGE and LOWER VOLTAGE LIMIT controls to be set for a wide range of acceptable voltage, while requiring a close voltage match within the acceptable voltage range. DEAD LINE/BUS CLOSING The Dead Line/Bus Closing will be used if system conditions and operating practices require the function. Note that either Dead Line Closing and/or Dead Bus Closing can be enabled by terminal block connections. This can be done by permanent terminal block jumpers, if one or the other or both functions are required. The connections may also be made by operator switches if operating conditions sometimes require the functions and other times do not. ■ NOTE: Enabling of Dead Line and Dead Bus permits either mode of operation; the system will not operate with a simultaneous Dead Line and Dead Bus condition. –3– ■ NOTES: 1. 2. 3. External connections are shown for voltage output and current output in Figures 3 and 4. Close the external circuit to enable the function. These inputs should not be permanently jumpered, since an inadvertent close command can take place if a voltage transformer or it’s associated circuit fails open. Close the external circuit to enable the function. If a function is required at all times, permanent enable jumpers may be added. FIGURE 2 External Connections –4– PHASE ANGLE LIMIT The Phase Angle Limit Detector measures the phase angle between the line and bus voltages, and compares the angle to the PHASE ANGLE LIMIT control setting. When the angle is less than the limit setting, the PHASE OK LED will light and, assuming that voltage and frequency difference conditions are within their setpoints, the M–0359 will close the permissive output relay for breaker closing. PHASE ANGLE LIMIT SHIFT An external contact can be connected between terminals TB1-15 and TB1-21, as shown in Figure 2. The contact can be closed by supervisory control to reduce the PHASE ANGLE LIMIT setting by a fixed ratio, while permitting the M–0359 to continue to monitor all parameters. The ratio is selected when the M–0359 is ordered, but can be changed by the user. There are two typical applications of the Phase Angle Limit Shift function. One would be when a rotating angle could exist across a breaker due to an islanding condition. For example, assume that normal conditions require a PHASE ANGLE LIMIT setting of 15°, but islanded conditions require closing a breaker at 3°. In this case, the M–0359 would be ordered with a 1/5 ratio reduction, and the PHASE ANGLE LIMIT control would be set at 15°. For normal operations, the external contact would be open, and the M–0359 would operate within a 15° limit setting. When required to operate with a 3° limit, supervisory would close the external contact across TB115 to TB1-21. The second instance would be when a static phase angle could exist across the breaker, and abnormal system conditions would require breaker closing with a greater than normal angle. For example, assume that normal conditions require a PHASE ANGLE LIMIT setting of 15°, but abnormal conditions require closing the breaker at 30°. In this case, the M–0359 would be ordered with a 1/2 ratio reduction, and the PHASE ANGLE LIMIT control would be set at 30°. For normal operations, the contact would be closed, and the M–0359 would operate within a 15° limit setting. When required to operate with a 30° limit, supervisory would open the external contact across TB1-15 to TB1-21. DELTA F LIMIT The Delta F Limit Detector portion of the M–0359 measures the frequency of the line and bus input voltages, and compares the difference between them (the slip value) with the DELTA F LIMIT control setting. When the frequency difference measurement is less than or equal to the DELTA F LIMIT setting, the DELTA F OK LED will light and, assuming that voltage and phase angle conditions are within their setpoints, the M–0359 will close the permissive output relay contact for breaker closing. A status relay contact is provided that will indicate when the frequency difference has fallen below the DELTA F LIMIT setting. STATUS RELAYS The Voltage Status, Frequency Status and the Phase Angle Status Relays permit interrogation of the M–0359 by supervisory control to indicate whether a breaker can be closed, and if not, whether the problem is with phase angle, frequency or voltage conditions. Alternatively, the status contacts can be used for local indicator lights. ANALOG OUTPUTS The Analog Outputs provided on the M–0359 can be used as transducer outputs or for interrogation of the relay while in operation. Voltage analog outputs (Option 1 for Bus Voltage, Line Voltage, Delta Voltage, Phase –5– Angle, and Delta Frequency) can be modeled as in Figure 3. Should a current output (Option 2 for each) be desired rather than voltage, the circuit connection of Figure 4 should be used. As shown in these figures, diodes D1 through D4 provide protection to operational amplifier U1. Since all outputs are monopolar voltages, the diodes never conduct except if a voltage is inadvertently applied to the analog output terminals. Scale factors for either option are shown in Table 1. Should scale factors other than those provided by the M– 0359 be desired, the voltage analog outputs may be resistively divided, or an additional external amplifier may be used for gain. The current output scale factor may be changed by selecting a different value for R3. The value of R3 should be selected to provide the desired scale factor. The maximum current “I” available is 5 mA. In addition, the maximum voltage output from U1 is limited to 12 V dc. For proper operation, the circuit must stay within the voltage and current limitations. The maximum voltage output from U1 can be calculated as shown in Equation 1 below. Vmax = Imax(R1 + RS + R3) (1) For a current output, the correct value of R3 in Ký can be calculated from the following equations. Phase: 1V R3 = ————————— x 103 Imax(mA) at 180° (2) 1V R3 = ————————— x 103 Imax(mA) at 150 V (3) 1V R3 = ————————— x 103 Imax(mA) at 20 V* (4) Line and Bus Voltage: Delta V: * ■ NOTE: Imax at the maximum voltage of the range selected when above 20 V. –6– FIGURE 3 Voltage Analog Output FIGURE 4 Current Analog Output –7– Delta F: 1V R3 = ————————— x 103 Imax(mA) at 0.5 Hz FUNCTION (5) TERMINAL SCALE FACTOR VOLTAGE SCALE FACTOR CURRENT R3 = 1.00 K TB1, 11-12 0.0556 V/Deg, 10 V dc = ±180°* 0.00556 mA/Deg, 1 mA dc = ±180°* V Bus TB1, 5-6 0.05 V/V ac, 7.5 V dc = 150 V rms 0.00667 mA/V rms, 1 mA dc = 150 V rms V Line TB1, 7-8 0.05 V/V ac, 7.5 V dc = 150 V rms 0.00667 mA/V rms, 1 mA dc = 150 V rms Delta V TB1, 9-10 0.5 V/V ac, 10 V dc = 20 V rms** 0.05 mA/V rms, 1 mA dc = 20 V rms Delta F TB3, C-D 20 V/Hz 10 V dc = 0.5 Hz 2 mA/Hz 1 mA dc = 0.5 Hz Phase Angle 0 to ±180° ■ NOTES: * Output voltage or current is the absolute value of phase angle. ** For ranges up to and including 20 V rms. Please consult factory for other ranges. TABLE 1 Scale Factors –8– MOUNTING Figure 5 shows outline dimensions for all of the units in the Syncrocloser® Line. Each unit fits a standard 19" rack mount and requires two rack units of height. Figure 6 shows the cutout required for panel mounting. The units can be mounted horizontally or vertically. The M–0217 Cover Kit option is a transparent cover and mounting bracket set that covers the knobs and prevents accidental resetting. FIGURE 5 Outline Dimensions for all Syncrocloser® Equipment Chassis –9– FIGURE 6 Hole Drill and Cutout Dimensions –10– ADJUSTMENT Controls should be set as follows: 1. Adjust the UPPER VOLTAGE LIMIT control to the limit voltage which both the line and bus voltages must not exceed, if breaker closing is to be permitted. 2. Adjust the LOWER VOLTAGE LIMIT control to the limit voltage which both the line and bus voltages must not fall below, if breaker closing is to be permitted. 3. Adjust the DELTA V LIMIT control to the difference in voltage which, if exceeded, will block breaker closing. 4. Adjust the DEAD LINE LIMIT control to the voltage limit which, if the line voltage falls below it, will result in immediate breaker closing when programmed regardless of the PHASE ANGLE LIMIT or DELTA F LIMIT control settings. 5. Adjust the DEAD BUS LIMIT control to the voltage limit which, if the bus voltage falls below it, will result in immediate breaker closing when programmed regardless of the PHASE ANGLE LIMIT or DELTA F LIMIT control settings. 6. Adjust the PHASE ANGLE LIMIT control to an angle window on either side of 0° which, if the phase angle falls within it, will allow breaker closing. The phase angle before a breaker is closed is a measure of the power that will flow after closing. The maximum allowable phase angle must be calculated such that damage or tripping of protective relays will not result from the power which flows immediately after closing. 7. Adjust the DELTA F control to the frequency difference that must not be exceeded to allow breaker closing after the phase angle comes within limits. The various LEDs will light when the conditions indicated are within limits for breaker closing. –11– MAINTENANCE Due to the extremely sophisticated nature of the circuitry in the M–0359 circuitry, field repair is not recommended. All units are fully calibrated at the factory prior to shipment; there is no need to re-calibrate a unit prior to initial installation. Calibration is only required after a component is replaced. In the event that a unit does not operate properly, it should be established that the problem is caused by malfunction of a Beckwith Electric unit and not caused by an external fault or wiring error. Once this is assured, the entire unit should be returned to Beckwith Electric. Pack the unit carefully (in the original carton if possible), assuring that there is adequate packing material to protect the contents. ■ NOTE: Any equipment returned for repair must be sent with transportation charges prepaid. The equipment must remain the property of the user. The warranty is void if the value of the unit is invoiced to Beckwith Electric at the time of return or if the unit is returned with transportation charges collect. If under warranty, units will be repaired rapidly and returned at no cost and with return transportation paid if the fault is found to be due to workmanship or failure of material. If a unit is under warranty and express shipment for return of the repaired unit is requested, shipping charges will be billed at the current rate. If the fault is due to abuse or misuse, or if the unit is out of warranty, a modest charge will be made. Repair can normally be expected to take two weeks, plus shipping time. If faster service is required, it should be requested at the time of return. ■ NOTE: Units returned with only a blown fuse are not covered by warranty and a nominal repair charge will be made for replacement of the fuse. Please check the fuses before returning the M–0359 for repair in order to avoid unnecessary repair charges. To help in analyzing the problem, a complete description of the malfunction and conditions leading to the failure should be included with the unit. However, if you choose to repair the unit, it is necessary to be completely familiar with the circuitry involved, and have an adequate understanding of field effect devices. Be sure to carefully read the WARNING page at the beginning of this manual. ▲ CAUTION: This unit contains sensitive MOS circuitry that can be damaged by improper repair procedures. Work stations used for repair should be static-free and procedures for handling MOS circuitry should be followed. In addition, any attempt to measure resistances between points on the printed circuit board may cause damage to the unit. It is suggested that first a visual inspection be made for any component that does not appear normal or appears to have overheated. Analysis of the circuit will then often lead to the cause of the failure and components that need to be replaced. If no obvious problems exist, it is suggested that the TEST and CALIBRATION PROCEDURES in the Instruction Book be followed until a portion of a circuit is detected which does not perform as expected or until a calibration point is found which will not meet requirements. These procedures should lead to a determination of the defective component. –12– PATENT The units described in this manual are protected by U.S. Patent 4,218,625. Buyer shall hold harmless and indemnify the Seller, its directors, officers, agents, and employees from any and all costs and expense, damage or loss, resulting from any alleged infringement of United States Letters Patent or rights accruing therefrom or trademarks whether federal, state, or common law, arising from the Seller’s compliance with Buyer’s designs, specifications, or instructions. WARRANTY Seller hereby warrants that the goods which are the subject matter of this contract will be manufactured in a good workmanlike manner and all materials used therein will be new and reasonably suitable for the equipment. Seller warrants that if, during a period of two years from date of shipment of the equipment, the equipment rendered shall be found by the Buyer to be faulty or shall fail to perform in accordance with Seller’s specifications of the product, Seller shall at his expense correct the same, provided however that Buyer shall ship the equipment prepaid to Seller’s facility. The Seller’s responsibility hereunder shall be limited to the replacement value of the equipment furnished under this contract. The foregoing shall constitute the exclusive remedy of the Buyer and the sole liability of the seller and is in lieu of all other warranties, whether written, oral, implied or statutory, except as to the title of the Seller to the equipment furnished. No implied statutory warranty of merchantability or of fitness for a particular purpose shall apply. Seller does not warrant any product or services of others which Buyer has designated. SELLER MAKES NO WARRANTIES EXPRESSED OR IMPLIED OTHER THAN THOSE SET OUT ABOVE. SELLER SPECIFICALLY EXCLUDES THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. THERE ARE NO WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION CONTAINED HEREIN. IN NO EVENT SHALL SELLER BE LIABLE FOR CONSEQUENTIAL, EXEMPLARY, OR PUNITIVE DAMAGES OF WHATEVER NATURE. Any equipment returned for repair must be sent with transportation charges prepaid. The equipment must remain the property of the Buyer. The aforementioned warranties are void if the value of the unit is invoiced to the Seller at the time of return. INDEMNIFICATION The Seller shall not be liable for any property damages whatsoever or claims of any kind whether based on contract, warranty, tort including negligence or otherwise, or for any loss or damage arising out of, connected with, or resulting from this contract, or from the performance or breach thereof, or from all services covered by or furnished under this contract. In no event shall the Seller be liable for special, incidental, exemplary or consequential damages including, but not limited to loss of profits or revenue, loss of use of the equipment or any associated equipment, cost of capital, cost of purchased power, cost of substitute equipment, facilities or services, downtime costs, or claims or damages of customers or employees of the Buyer for such damages, regardless of whether said claim or damages is based on contract, warranty, tort including negligence or otherwise. Under no circumstances shall the Seller be liable for any personal injury whatsoever. It is agreed that when the equipment furnished hereunder or any services furnished hereunder are to be used or performed in connection with any nuclear installation, facility, or activity, Seller shall have no liability for any nuclear damage, personal injury, property damage, or nuclear contamination to any property located at or near the site of the nuclear facility. Buyer agrees to indemnify and hold harmless the Seller against any and all liability associated therewith whatsoever whether based on contract, tort, or otherwise. Nuclear installation or facility means any nuclear reactor and includes the site on which any of the foregoing is located, all operations conducted on such site and all premises used for such operations. It is the intention of the parties that this is a complete indemnification and hold harmless agreement in regard to all claims arising from nuclear operations of Buyer. –13– Legal Information Patent The units described in this manual are covered by U.S. Patent 4,218,625. Buyer shall hold harmless and indemnify the Seller, its directors, officers, agents, and employees from any and all costs and expense, damage or loss, resulting from any alleged infringementof United States Letters Patent or rights accruing thereform or trademarks, whether federal, state, or common law, arising from the Seller’s compliance with Buyer’s designs, specifications, or instructions. Warranty Seller hereby warrants that the goods which are the subject matter of this contract will be manufactured in a good workmanlike manner and all materials used herein will be new and reasonably suitable for the equipment. Seller warrants that if, during a period of five years from date of shipment of the equipment, the equipment rendered shall be found by the Buyer to be faulty or shall fail to peform in accordance with Seller’s specifications of the product, Seller shall at his expense correct the same, provided, however, that Buyers shall ship the equipment prepaid to Seller’s facility. The Seller’s responsibility hereunder shall be limited to replacement value of the equipment furnished under this contract. Seller makes no warranties expressed or implied other than those set out above. Seller specifically excludes the implied warranties of merchantibility and fitness for a particular purpose. There are no warranties which extend beyond the description contained herein. In no event shall Seller be liable for consequential, exemplary, or punitive damages of whatever nature. Any equipment returned for repair must be sent with transportation charges prepaid. The equipment must remain the property of the Buyer. The aforementioned warranties are void if the value of the unit is invoiced to the Seller at the time of return. Indemnification The Seller shall not be liable for any property damages whatsoever or for any loss or damage arising out of, connected with, or resulting from this contract, or from the performance or breach thereof, or from all services covered by or furnished under this contract. In no event shall the Seller be liable for special, incidental, exemplary, or consequential damages, including but not limited to, loss of profits or revenue, loss of use of the equipment or any associated equipment, cost of capital, cost of purchased power, cost of substitute equipment, facilities or services, downtime costs, or claims or damages of customers or employees of the Buyer for such damages, regardless of whether said claim or damages is based on contract, warranty, tort including negligence, or otherwise. Under no circumstances shall the Seller be liable for any personal injury whatsoever. It is agreed that when the equipment furnished hereunder are to be used or performed in connection with any nuclear installation, facility, or activity, Seller shall have no liability for any nuclear damage, personal injury, property damage, or nuclear contamination to any property located at or near the site of the nuclear facility. Buyer agrees to indemnify and hold harmless the Seller against any and all liability associated therewith whatsoever whether based on contract, tort, or otherwise. Nuclear installation or facility means any nuclear reactor and includes the site on which any of the foregoing is located, all operations conducted on such site, and all premises used for such operations. Notice: Any illustrations and descriptions by Beckwith Electric Co., Inc. are for the sole purpose of identification. The drawings and/or specifications enclosed herein are the proprietary property of Beckwith Electric Co., Inc., and are issued in strict confidence; therefore, shall not be used as a basis of reproduction of the apparatus described therein without written permission of Beckwith Electric Co., Inc. No illustration or description contained herein shall be construed as an express warranty of affirmation, promise, description, or sample, and any and all such express warranties are specifically excluded nor shall such illustration or description imply a warranty that the product is merchantable or fit for a particular purpose. There shall be no warranties which extend beyond those contained in the Beckwith Electric Co., Inc. terms of sale. All rights reserved by Beckwith Electric Co., Inc. No reproduction may be made without prior written approval of the Company. BECKWITH ELECTRIC CO., INC. 6190 - 118th Avenue North • Largo, Florida 33773-3724 U.S.A. PHONE (727) 544-2326 • FAX (727) 546-0121 marketing@beckwithelectric.com www.beckwithelectric.com ISO 9001:2008 © Beckwith Electric Co. All Rights Reserved. Printed in USA 800-0359-AG-MC5 01/13